Enhanced PID for Air Compressors F7 Drive Software Technical Manual

Similar documents
VS-616G5 Series (Revision F) Programming Manual. Constant Torque Inverter with Adaptive Vector Control (AVC )

HPVFP High Performance Full Function Vector Frequency Inverter

CHAPTER AC DRIVE PARAMETERS. In This Chapter...

GS1 Parameter Summary Detailed Parameter Listings...4 9

MA7200 PLUS INVERTER SERIES PID Quick Start Manual For Fan and Pump Applications

INDEX. i 1. B Braking Resistor Dimensions: A 24 Braking Resistors: A 20 Braking Units: A 20. DURAPULSE AC Drive User Manual

CHAPTER 8 PARAMETER SUMMARY

CHAPTER KEYPAD OPERATION AND QUICKSTART. In This Chapter... The GS2 Digital Keypad GS2 Quickstart...3 6

TECO F510 Inverter. Quick Start Guide. Step 1. Supply & Motor connection

SJ100 Series Inverter Quick Reference Guide. Single-phase Input 200V Class Three-phase Input 200V Class Three-phase Input 400V Class

vacon 100 flow ac drives application manual

GB QUICK GUIDE FOR THE CONFIGURATION OF VARIABLE SPEED DRIVES

HITACHI. L100-M Series Inverter Quick Reference Guide. Hitachi Industrial Equipment Systems Co., Ltd. Single-phase Input 100V Class

NX Series Inverters. HVAC Pocket Programming Guide

1-2 VOLTS PER HERTZ CHARACTERISTICS EXERCISE OBJECTIVE

Multi-function, Compact Inverters. 3G3MV Series

Optidrive Applications Support Library

6.9 Jump frequency - Avoiding frequency resonance

Advanced user guide. Commander SX. IP66/Nema 4X AC Variable Speed Drive en / a. Part Number :

vacon 100 flow ac drives application manual

CHAPTER 8 SUMMARY OF PARAMETER SETTINGS

Configuring Drive Parameters

160 Series C Custom Firmware

TOSVERT TM VF-nC3 Parameter List

The MFT B-Series Flow Controller.

BACnet- MS/TP COMMUNICATION V

Custom Software Supplement

TOSVERT VF-AS1 PID control Instruction Manual

OPC-E1-PG3 Specifications

Copyright 2014 YASKAWA ELECTRIC CORPORATION All rights reserved. No part of this publication may be reproduced, stored in a retrieval system, or

ROLL TO ROLL FUNCTION MANUAL FR-A (0.4K)-04750(90K)-R2R FR-A (0.4K)-06830(280K)-R2R FR-A (315K)-12120(500K)-R2R

PID Software Kit. Part No. SK-PID1-L503. For GPD 503 Adjustable Frequency Drives CT: 1-30HP, 230V; 1-60HP, 460V VT: 1-40HP, 230V; 1-75HP, 460V

THYFREC-VT210S 400V System 37 to 315kW (C/T) 400V System 45 to 370kW (V/T) QUICK START GUIDE

INSTRUCTIONS YASKAWA. Upon receipt of the product and prior to initial operation, read these instructions thoroughly, and retain for future reference.

Instruction Manual D

Appendix F: PID Control...F 1 PID Control...F 2

NX series Constant and variable torque Variable Speed Drives for induction motors

Installation, Programming Operation, & Maintenance Manual V

QUICK GUIDE PUMP CONTROL. High performance Compact Inverter. Date Version 22/09/

FUJI Inverter. Standard Specifications

Compact & Powerful Inverter STARVERT ig5a 0.4~1.5kW 1phase 200~230Volts 0.4~22kW 3Phase 200~230Volts 0.4~22kW 3Phase 380~480Volts

1000 Hz High Frequency Custom Software

E3 Adjustable Speed Drive Engineering Specification

vacon nx all in one application manual ac drives Phone: Fax: Web: -

MicroManager. Velocity Mode PID Dancer/Loadcell Control. Instruction Manual MM3000-PID

3. Be aware of the ambient temperature. Use the unit within the specified ambient temperature only.

Application Note CTAN #287

Quick Reference Guide. DF5-... Frequency Inverters 02/02 AWB GB

The GS1 Digital Keypad LED Display Function Keys Displaying the Status of the GS1 AC Drive Programming the GS1 AC Drive...

Servo Indexer Reference Guide

Series Valve Temperature Controller. Instruction Sheet

QUICK GUIDE PUMP CONTROL. Frequency inverter for pump control and HVAC applications. Date Version 22/09/

Max. sp Min. spe Negativ speed s Synchro out speed refere selection Menu 13. g t x (-1) UMV 4301

PL.P7.06.TransitionP5. Product Transition Guide GPD 506/P5 to P7

Control chain diagrams

ig5a 0.4~1.5kW (0.5~2HP) 1phase 200~230Volts 0.4~22kW (0.5~30HP) 3Phase 200~230Volts 0.4~22kW (0.5~30HP) 3Phase 380~480Volts Compact & Powerful Drive

ADJUSTABLE SPEED DRIVES. AS1 Drive

Continental Hydraulics Installation Manual CEM-PA-A

QUICK GUIDE PUMP CONTROL. Frequency inverter for pump control and HVAC applications. Date Version 24/10/

[ 4 ] Using pulse train input (F01 = 12)

Index 2. G Gain settings 4 31 Glossary of terms A 2 Grommets 2 13

MD310 Quick Start Manual. General-Purpose AC Drive

user's manual nx frequency converters beam pump application asfiff13

S11 Adjustable Speed Drive Engineering Specification

Quick Reference Guide. DF5-... Frequency Inverters 02/02 AWB GB. For Immediate Delivery call KMParts.com at (866)

VFD - D700 Series Specifications. The latest low-cost variable speed control solution for centrifugal pumps.

Tech Note #3: Setting up a Servo Axis For Closed Loop Position Control Application note by Tim McIntosh September 10, 2001

ig5a Compact AC Drive 0.4~1.5kW(0.5~2HP) 1-phase 200~230Volts 0.4~22kW(0.5~30HP) 3-Phase 200~230Volts 0.4~22kW(0.5~30HP) 3-Phase 380~480Volts

Inverter Drive /Vector Drive Motors & Controls

INTERNATIONAL SERVICE BULLETIN - I #2-319 Liberty - Delta M+ VFD parameter list. A VFD parameter list is required when replacing a DELTA M+ VFD.

ADTECH Solar inverter

CHAPTER 5 DESCRIPTION OF PARAMETER SETTINGS

VF-nC1 Adjustable Speed Drive Engineering Specification

ABB machinery drives. Supplement to Users Manual ACS355 Low ambient start (+N828)

ControlMaster CM10, CM30, CM50 Universal process controllers, 1 /8, 1 /4 and 1 /2 DIN

Series 70 Servo NXT - Modulating Controller Installation, Operation and Maintenance Manual

The new Yaskawa Varispeed G7 Inverter

vacon nx ac drives all in one application manual

CHAPTER 5 DESCRIPTION OF PARAMETER SETTINGS

PumpSmart Commissioning Process

6 Parameterizing steps

AV-300i Specifications. Saftronics Inc. VG10 Product Specifications VG10. Dynamic Vector Drive

VSD Series II Variable Speed Micro Drives (VSM II) FS1 FS5

safety Doc: DPD00714C, Released: vacon 1 ONLY A COMPETENT ELECTRICIAN IS ALLOWED TO CARRY OUT THE ELECTRICAL INSTALLATION! 1.

Rev.8 03/08 SSRMAN-1P SERIES USERS MANUAL SSR INTELLIGENT PHASE ANGLE CONTROL MODULE COPYRIGHT 2008 NUWAVE TECHNOLOGIES, INC.

1. Institute of Electrical and Electronic Engineers (IEEE) a. Standard , IEEE Guide for Harmonic Content and Control.

CT435. PC Board Mount Temperature Controller

Please enter the identity code of your device here!

AQUAVAR CPC. Modbus Communications (Software Version 204 and later)* INSTRUCTION MANUAL ADAQCPC R1

Before you operate the inverter, the parameters that you must first program are the basic parameters.

1336 PLUS II Custom Firmware

SAFETY INSTRUCTIONS WARNING

TECHNICAL DOCUMENT EPC SERVO AMPLIFIER MODULE Part Number L xx EPC. 100 Series (1xx) User Manual

NXL HVAC APPLICATION MANUAL Programming manual for NXL HVAC drives

MicroManager. Torque Mode CTCW/Loadcell Control. Instruction Manual MM3000-CTCW

P-SERIES VFD 1-40HP (200~230VAC), 1-400HP (380~480VAC),3Ø Dual Rated for Constant & Variable Torque Integrated PID Control

Programming Guide. VLT Micro Drive FC 51

(Supplement to Instruction Manual)

Invertek Optidrive E3 Frequency Inverter (IP20, 3ph output) Easy Start Guide

YASKAWA AC Drive. P7 to P1000 Product Transition Guide

Transcription:

Software Number: VSF11020X, Drive Models: CIMR-F7UXXXXXX-096 Document Number: TM.F7SW.096, Date: 08/01/05, Rev: 05-08 Enhanced PID for Air Compressors F7 Drive Software Technical Manual

This document is intended to provide proper installation and use of the Yaskawa drive with custom software. This document is a supplement to the standard drive technical manual. It describes the effects on the drive parameters and functions with the software installed. Read and understand this document and the standard drive technical manuals before attempting to install, adjust, operate, inspect or maintain the drive. Observe all cautions and warnings in this document and the standard drive technical manuals. Custom software is written to add functionality to a standard AC drive to enhance or enable use in a specific application. The software is loaded to the flash ROM area of the control board, and replaces the standard drive software. Custom software can add new functions, modify standard functions, or even inhibit standard functions. It can be used to modify display text or parameter names. Custom software is usually loaded to the drive before delivery. The control board and drive nameplate are assigned unique part numbers and the software is registered, archived, and retrievable. When seeking support for a drive with custom software, it is imperative to provide the unique part number shown on the drive nameplate. The software has been flashed to the control board memory and the operation of parameters, functions, and monitors are different than the standard drive software, as described herein. 1.0 Overview The drive s standard PID algorithm and display has been modified to provide optimum control of nonreciprocating rotary screw air compressors. The PID features are designed to expand the functionality and correct some deficiencies of the drive s standard PID algorithm. The enhanced PID function utilizes the parameters of the standard software PID function (B5 group) as well as many new P group parameters. Date: 08/01/05, Rev: 05-08 Page 2 of 17 TM.F7SW.096

1.1 Simplified Block Diagram of Enhanced PID: 2 Input (B5-01 = 1 or 2) 1.2 Simplified Block Diagram of Enhanced PID: 3 Input (B5-01 = 3 or 4) (PID setpoint is independent of frequency reference) 1.3 Simplified Block Diagram of Enhanced PID: 2 Input (B5-01 = 3 or 4) (PID setpoint is same as the frequency reference) Date: 08/01/05, Rev: 05-08 Page 3 of 17 TM.F7SW.096

2.0 Changes from Standard Product 2.1 Enhanced PID versus Standard Software Feature Enhanced Standard PID Software Full Range PID (2-input) PID + Reference Capable (3-input) PID x Reference Capable (3-input) PID Setpoint Offset Parameter PID + Trim is Accomplished Algebraically, Regardless of Commanded Direction Reference as PID Setpoint Parameter B5-19 PID Setpoint can be changed during running Independent Digital PID Setpoint Independent Digital PID Setpoint (changeable during run) Multiple PID Setpoint Sources (digital preset, analog, pulse input, Modbus RTU, option card) Setpoint Ramp (when PID setpoint is from frequency reference) Setpoint Ramp (all PID setpoints, regardless of source) Multiple PID Feedback Sources (analog, pulse input) Feedback Detection (high, low, on-delay, off-delay, digital output, alarm, fault, during run, always detected) PID Monitors with User Units (scaled using parameter O1-03) Detailed PID Monitors (proportional, integral, derivative) Integral Hold Digital Input Positive Integral Hold Digital Input (integrator can only decrease) Negative Integral Hold Digital Input (integrator can only increase) Integral term is lower-limited to PID minimum output Integral term is held during sleep and the sleep minimum off time PID Output Limit Independent + / - PID Output Limits (B5-06 PID limit now functions only as a PID upper limit) PID Output Gain can be proportional to the frequency reference PID Output Gain (0.01 Resolution, instead of 0.1) Independent Sleep Delay and Wake-up Delay parameters Increased range for sleep mode timers (0.0 600.0 sec) Minimum sleep time parameter Parameters O1-01 and O1-02 have been removed. Parameters P2-09 and P2-10 have taken their place Parameter O1-03 controls the units & scaling for U1-01, D1-XX, and U1-90 thru U1-96 Parameter P2-10 controls the units & scaling for U1-02, U1-05, U1-20, and U1-46 Parameter P2-09 controls the displayed keypad custom units for D1-XX, U1-01, U1-02, U1-05, U1-20, U1-46, and U1-90 thru U1-96 Keypad monitors are now displayed in a different order: U1-01 -> U1-90 -> U1-02 -> U1-03 ->.. U1-96 -> U1-01 PID Setpoint (U1-01), PID Feedback (U1-90), and Output (U1-02) are displayed at power-up and return to drive mode Multi-function digital output for controlling the Blowdown valve. When the Blowdown valve is energized, the air compressor can make air. Controlled by PID feedback level, drive run status, and delay timers. 3. Limitations None. Date: 08/01/05, Rev: 05-08 Page 4 of 17 TM.F7SW.096

4. Related Parameters and Functions 4.1 Parameters Parameter Number Modbus Address Parameter Name Digital Operator Display Description Range Default Change During Run Access Level For All Control Modes *1 B1-01 180H Reference Selection Reference Source Selects the frequency reference source. 0: Operator 1: Control Terminal Strip 2: Modbus RTU (Terminals R+, R-, S+, S-) 3: Option Card 4: Pulse Input (Terminal RP) 0 4 1 No Q B5-16 1B4H PID Sleep Delay Time PID Sleep Time Sets the sleep function delay time in terms of seconds. The wake-up time delay is controlled by P2-06. This parameter selects the characteristics of the PID feedback detection function. 0.0 600.0 sec 0.0 No A P1-01 600H Feedback Detection Mode Selection Fb Det Mode Sel 0: Output/AlwaysDet Feedback high & low multi-function digital outputs are enabled (if programmed); detection is always active. 1: Output/DuringRUN Feedback high & low multi-function digital outputs are enabled (if programmed); detection is active only during run. 2: Alarm/AlwaysDet Feedback range alarms (FRH, FRL) and feedback high & low multi-function digital outputs are enabled (if programmed); detection is always active 3: Alarm/DuringRUN Feedback range alarms (FRH, FRL) and feedback high & low multi-function digital outputs are enabled (if programmed); detection is active only during run 4: Fault/AlwaysDet Feedback range faults (FRH, FRL) and feedback high & low multi-function digital outputs are enabled (if programmed); detection is always active. Drive coasts to a stop and activates the fault contacts. 5: Fault/DuringRUN Feedback range faults (FRH, FRL) and feedback high & low digital outputs are enabled (if programmed); detection is active only during run. Drive coasts to a stop and activates the fault contacts. *1: Access Level (A1-01): Q = Quick Start, A = Advanced, F = Factory. 0 5 0 No A Date: 08/01/05, Rev: 05-08 Page 5 of 17 TM.F7SW.096

4.1 Parameters (continued) Parameter Number Modbus Address Parameter Name Digital Operator Display Description Range Default Change During Run Access Level For All Control Modes *1 P1-02 601H Feedback Detection Level (High) Fb Det Lvl High This parameter sets the detection level for PID feedback (high) detection function. -100.0 +100.0 % 100.0 No A P1-03 602H Feedback On- Delay Time (High) Fb High On-Delay This parameter sets the on-delay time for the PID feedback detection (high) function. 0.0 100.0 sec 0.0 No A P1-04 603H Feedback Off-Delay Time (High) Fb HighOff-Delay This parameter sets the off-delay time for the PID feedback (high) detection function. 0.0 100.0 sec 0.0 No A P1-05 604H Feedback Detection Level (Low) Fb Det Lvl Low This parameter sets the detection level for PID feedback (low) detection function. -100.0 +100.0 % 0.0 No A P1-06 605H Feedback On-Delay Time (Low) Fb Low On-Delay This parameter sets the on-delay time for the PID feedback detection (low) function. 0.0 100.0 sec 0.0 No A P1-07 606H Feedback Off-Delay Time (Low) Fb Low Off-Delay This parameter sets the off-delay time for the PID feedback (low) detection function. 0.0 100.0 sec 0.0 No A P1-08 607H Feedback Detection Hysteresis FbDet Hysteresis This parameter sets the hysteresis level for the PID feedback detection function (high & low). 0.0 10.0 % 10.0 No A P2-01 60AH PID Lower Limit PID Lower Limit This parameter sets the PID lower limit as a percentage of the maximum output frequency. Works in conjunction with the PID Limit (B5-06), which sets the upper limit. Note: If P2-01 is set greater than B5-06, an OPE12 error will be displayed. *1: Access Level (A1-01): Q = Quick Start, A = Advanced, F = Factory. -100.0 100.0 % -100.0 Yes A Date: 08/01/05, Rev: 05-08 Page 6 of 17 TM.F7SW.096

4.1 Parameters (continued) Parameter Number Modbus Address Parameter Name Digital Operator Display Description Range Default Change During Run Access Level For All Control Modes *1 P2-02 60BH PID Output Gain 2 Output Gain 2 This parameter sets the gain at the output of the PID. Functions the same as PID Output Gain (B5-10), but with finer resolution (0.01 versus 0.1). The total output gain is determined by B5-10 x P2-02. 0.00 25.00 1.00 No A P2-03 60CH PID Setpoint Offset Setpoint Offset This parameter sums with the PID setpoint (analog input, pulse input, network communication, or parameter) to provide an offset. -100.0 +100.0 % 0.0 No A P2-04 60DH PID Trim Mode Selection PID Trm Mode Sel This parameter selects how the PID output will trim the frequency reference. Active only when b5-01 = 3 or 4. 0: Constant The PID output trim is independent of the frequency reference. 1: Freq Ref Prop The PID output trim is proportional to the frequency reference. 0 1 0 No A P2-05 60EH Reference Proportional Trim Lower Limit FrefProp Low Lim This parameter sets the lower limit of the PID output trim of the frequency reference when P2-01 = 1 (trim is proportional to the frequency reference). Active only when b5-01 = 3 or 4 and P2-04 = 1. 0.00 100.00 % 10.00 Yes A P2-06 60FH Wake-Up Delay Timer Wake Up Delay This parameter determines the time delay after the frequency reference exceeds the sleep level, that the drive will resume running. 0.0 600.0 sec 1.0 No A P2-07 610H Minimum Off-Time during sleep operation Min Off Time This parameter determines the minimum amount of time the drive will be off during sleep mode to allow the pressure in the sump to dissipate. 0.0 6000.0 sec 30.0 No A P2-08 611H Blowdown Valve Delay Time Blowdown Delay This parameter determines (after the drive is started or re-started after a sleep cycle) how long the drive has to run for before closing the multi-function digital output blowdown valve. 0.0 120.0 sec 3.0 No A *1: Access Level (A1-01): Q = Quick Start, A = Advanced, F = Factory. Date: 08/01/05, Rev: 05-08 Page 7 of 17 TM.F7SW.096

4.1 Parameters (continued) Parameter Number Modbus Address Parameter Name Digital Operator Display Description Range Default Change During Run Access Level For All Control Modes *1 This parameter determines what custom units are displayed for U1-01, D1-XX, and U1-90 thru U1-96. P2-09 612H Custom Units Display Selection Custom Units 0: No units displayed 1: PSI 2: kpa 3: o F 0 3 1 No A P2-10 612H Output Monitor Units Note: Only applicable when O1-03 40 (custom units). Selects the units & scaling for the following keypad monitors: U1-02, U1-05, U1-20, and U1-46. Works in the same fashion as parameter O1-03. 0: Hz Output Mon Units 1: % 2 38: RPM (Set motor poles) 40 39999: Custom *1: Access Level (A1-01): Q = Quick Start, A = Advanced, F = Factory. 0 39999 0 No A Date: 08/01/05, Rev: 05-08 Page 8 of 17 TM.F7SW.096

4.2 Monitors (U1-XX) Monitor Number Modbus Address Monitor Name Digital Operator Display Description Scaling for Multifunction Analog Outputs Terminals FM and AM (H4-01, H4-04) Unit V/f Control Mode *1 V/f w/ PG Open Loop Vector Flux Vector U1-01 040H U1-02 041H U1-05 044H U1-20 053H U1-46 06DH U1-90 720H U1-91 721H U1-92 722H U1-93 723H Reference Ref Output Output Freq Motor Speed Motor Speed Soft Starter Output SFS Output Feed-Forward Speed FF Estimate SPD PID Feedback PID Feedback PID Input PID Input PID Output PID Output PID Proportional Output Displays the frequency reference. Displays the output frequency. Displays the encoder feedback speed or estimated motor speed. Displays the frequency reference after the Accel, Decel, and S-curve ramps. Displays the estimated feedforward speed (Flux Vector only). Displays the PID feedback as a percentage of the maximum output frequency. Displays the PID input value as a percentage of the maximum output frequency. Displays the PID output value as a percentage of the maximum output frequency. Displays the PID proportional value as a percentage of the maximum 0.01 Hz *2 0.01 Hz *3 0.01 Hz *3 0.01 Hz *3 0.01 Hz *3 0.1% *2 0.1% *2 0.1% *2 0.1% *2 - Q Q Q - - - F PID P Output frequency. *1: Access Level (A1-01): Q = Quick Start, A = Advanced, F = Factory. *2: Unit and scaling based on O1-03 (Display Scaling) setting. When O1-03 40 (custom units), the displayed units on the keypad are determined by parameter P2-09. *3: Unit and scaling based on P2-10 (Output Monitor Units) setting. Parameter P2-10 operates exactly the same way as O1-03. When P2-10 40 (custom units), the displayed units on the keypad are determined by parameter P2-09. Date: 08/01/05, Rev: 05-08 Page 9 of 17 TM.F7SW.096

4.2 Monitors (U1-XX) (continued) Monitor Number Modbus Address Monitor Name Digital Operator Display Description Scaling for Multifunction Analog Outputs Terminals FM and AM (H4-01, H4-04) Unit V/f Control Mode *1 V/f w/ PG Open Loop Vector Flux Vector U1-94 724H U1-95 725H U1-96 726H PID Integral Output PID I Output PID Derivative Output PID D Output PID Setpoint PID Setpoint Displays the PID integral value as a percentage of maximum output frequency. Displays the PID derivative value as a percentage of the maximum output frequency. Displays the PID setpoint as a percentage of the maximum output frequency. 0.1% *2 0.1% *2 0.1% *2 *1: Access Level (A1-01): Q = Quick Start, A = Advanced, F = Factory. *2: Unit and scaling based on O1-03 (Display Scaling) setting. When O1-03 40 (custom units), the displayed units on the keypad are determined by parameter P2-09. *3: Unit and scaling based on P2-10 (Output Monitor Units) setting. Parameter P2-10 operates exactly the same way as O1-03. When P2-10 40 (custom units), the displayed units on the keypad are determined by parameter P2-09. 4.3 Multi-function Digital Input Settings (H1-0X) Setting Display Description 80 Positive Integral Hold 81 Negative Integral Hold : Available. 4.4 Multi-function Digital Output Settings (H2-0X) Closed: Integral is permitted to decrease, but not increase. Closed: Integral is permitted to increase, but not decrease. Setting Display Description 40 Feedback High 41 Feedback Low 42 : Available. Blowdown Valve Closed: PID feedback has exceeded P1-02 level for the time set in P1-03. Closed: PID feedback has fallen below the P1-05 level for the time set in P1-06. Closed: Drive has received a run command, the P2-08 delay timer has expired, and the PID feedback high detection function is not on (level set in P1-02). Opens immediately after the run command is removed or the PID feedback high detection function is satisfied. Available For All Control Modes Available For All Control Modes Date: 08/01/05, Rev: 05-08 Page 10 of 17 TM.F7SW.096

4.5 Modbus Registers Modbus Monitor Address Name Description Unit 024H Output Output frequency monitor 0.01Hz *4 *4: Scaling based on P2-10 (Output Monitor Units) setting. Parameter P2-10 programs and functions exactly like standard parameter O1-03. 4.6 Faults Fault Display Description Cause Countermeasures FRH Feedback Range High FRL Feedback Range Low PID feedback out of range (high). Motor will coast to a stop. PID feedback out of range (low). Motor will coast to a stop. P1-01 = 4 or 5 and the PID feedback has exceeded the P1-02 level for the time set in P1-03. P1-01 = 4 or 5 and the PID feedback has fallen below the P1-05 level for the time set in P1-06. Correct the cause of the high feedback signal. Correct the cause of the low feedback signal. 4.7 Alarms Alarm Display Description Cause Countermeasures FRH Feedback Range High FRL Feedback Range Low PID feedback out of range (high) PID feedback out of range (low) P1-01 = 2 or 3 and the PID feedback has exceeded the P1-02 level for the time set in P1-03. P1-01 = 2 or 3 and the PID feedback has fallen below the P1-05 level for the time set in P1-06. Correct the cause of the high feedback signal. Correct the cause of the low feedback signal. 5.0 Function Description 5.1 Enhanced PID The Enhanced PID feature includes many enhancements over the drive s standard PID function. The PID algorithm is programmed using the existing B5 group of parameters as well as the P group of parameters. See Section 2.0 for details. Enhanced features include: The ramp in the PID setpoint behaves differently depending upon the PID mode and the reference source. In most cases, the PID setpoint ramp affects only the PID setpoint. When the PID + Trim feature is enabled (B5-01 = 3 or 4) and there is no independent PID setpoint, the PID ramp affects both the PID setpoint and the frequency reference. The PID output is now algebraically summed with the frequency reference. Motor rotation will be forward if: a forward run is commanded and there is a positive PID + trim, or if a reverse run is commanded and there is a negative PID + trim. Motor rotation will be reverse if: a reverse run is commanded and there is a positive PID + trim, or if a forward run is commanded and there is a negative PID + trim. The integral time is lower-limited to the to the PID minimum output limit (P2-01). The integrator is also held during the sleep mode, and the sleep minimum off time. These changes were done to prevent integrator windup and insure smooth starts with a minimum of pressure overshoot. Date: 08/01/05, Rev: 05-08 Page 11 of 17 TM.F7SW.096

5.2 Modified PID Sleep Function In standard software, parameter B5-16 controls both the sleep delay, and the wake-up delay. In this software, parameter B5-16 controls the sleep delay, and P2-06 controls the wake-up delay. The maximum settable range of B5-16 is increased from 25.5 seconds to 600.0 seconds. An additional timer has been added (P2-07) to the sleep function to insure that when the drive does go into the sleep mode, it remains in sleep mode even if the PID is calling for the drive to run. This is to insure that the pressure in the sump of the air compressor can dissipate before it restarts. This prevents foaming of the oil. 5.3 Blowdown Valve Digital Output This digital output can be used to control the blowdown or loading valve for the air compressor. When this output is energized, the blowdown valve is active, and the compressor is allowed to make air. If this output is de-energized, the air compressor won t produce any air, even if it is turning. This output should normally be energized when the drive is running, but only after a delay after startup (determined by parameter number P2-08). This allows the motor, drive, and compressor to start under less load. The output will also de-energize if the PID feedback (air pressure) goes too high. The level, time delays, and hysteresis share the same parameters as the PID feedback high detection alarm and fault. (P1-02, P1-03, P1-04, and P1-08). See Section 6.5 for a detailed block diagram. 5.4 Customized Display of Keypad Monitors When first powered up (or returning to the drive mode), the digital operator display will show pressure setpoint (U1-01), pressure feedback (U1-90), and output frequency (U1-02). All PID setpoints (U1-01, D1-XX) and PID monitors (U1-9X) have user selectable scaling (O1-03) and keypad display units (P2-09). User selectable units will only be displayed when O1-03 40 (custom units). Unit selections are PSI, kpa, and o F. Other parameters that are normally scaled using O1-03, which include U1-02, U1-05, U1-20, and U1-46, are scaled by parameter P2-10. Parameter P2-10 will work in exactly the same manner as O1-03 does. When the setting is 0, the units and scaling will be in 0.01Hz. When the setting is 1, the units and scaling will be in 0.01%. When the setting is 2 38, the scaling will be in RPM, with the setting of P2-10 acting as the number of motor poles for the calculation. When the P2-10 40 (custom scaling), the keypad display units are determined by parameter P2-09. Unit selections are PSI, kpa, and o F. 6.0 Block Diagrams The following pages give detailed flowcharts of the following software functions: 6.1 PID with 2 Inputs (B5-01 = 1 or 2) 6.2 PID with 2 Inputs (B5-01 = 3 or 4) 6.3 PID with 3 Inputs (B5-01 = 3 or 4) 6.4 PID Feedback Detection 6.5 PID Sleep function and Blowdown Valve Digital Output U1-01 U1-90 U1-02 U1-03... U1-91 U1-92 U1-93 U1-94 U1-95 U1-96 Date: 08/01/05, Rev: 05-08 Page 12 of 17 TM.F7SW.096

6.1 Enhanced PID with 2 Inputs (B5-01 = 1 or 2) Date: 08/01/05, Rev: 05-08 Page 13 of 17 TM.F7SW.096

6.2 Enhanced PID with 2 Inputs (B5-01 = 3 or 4) Date: 08/01/05, Rev: 05-08 Page 14 of 17 TM.F7SW.096

6.3 Enhanced PID with 3 Inputs (B5-01 = 3 or 4) Date: 08/01/05, Rev: 05-08 Page 15 of 17 TM.F7SW.096

6.4 Enhanced PID Feedback Detection Date: 08/01/05, Rev: 05-08 Page 16 of 17 TM.F7SW.096

6.5 PID Sleep Function and Blowdown Valve Digital Output Date: 08/01/05, Rev: 05-08 Page 17 of 17 TM.F7SW.096