COMMERCIAL. GA Series - Actuator Operating Instructions. GA Non-Spring Return Actuator - (GA24-562) 04/08 /15

Similar documents
Non-Spring Return EconoDrive Proportional Actuator

Spring Return DuraDrive Proportional Actuator

Non-Spring Return DuraDrive Modulating Actuator

FA-3300 Heavy Duty Electric Actuator. Features and Benefits. FA-3300 Actuator with VG8000 valve. Constant running time. Fixed close-off force.

Manual triggering of the adaption by pressing the «Adaption» button or with the PC-Tool

SAX..P. Electromotoric actuators for valves ACVATIX. with a 20 mm stroke

MODEL: M2SES SEN TRONIC AG [3] OUTPUT

MODEL: W2DYS SEN TRONIC AG. Mini-MW Series

VA-9070 Series Electric Rotary Actuators for Two-Position and Modulating Service

MODEL: M2DYS SEN TRONIC AG

Provides line voltage capable single Pole Double-Throw (SPDT) switch and 140Ω, 1KΩ, 2KΩ or 10KΩ feedback potentiometric.

Technical Instructions Document No EA GQD June 23, OpenAir

SAT.. Electromotoric actuators for valves ACVATIX. with a 5.5 mm stroke and 300 N positioning force

Electrical data Nominal voltage AC/DC 24 V Nominal voltage frequency

Power consumption In operation At rest For wire sizing

Modulating controlled actuators AME 10, AME 20, AME 30 AME 13, AME 23, AME 33 - with DIN EN certified safety function (spring down)

Electrical data Nominal voltage AC/DC 24 V Nominal voltage frequency

Technical Instructions Document No EA GQD October 25, OpenAir GQD Series

SAX.. ACVATIX Electromotoric actuators for valves. with a 20 mm stroke

AC/DC 24 V, 50/60 Hz. Functional data Variable Settings. DC V, max. 0.5 ma. End point DC V... 4 ma ma Non-variable

SAX.. ACVATIX Electromotoric actuators for valves. with a 20 mm stroke

SAX.. Electromotoric actuators for valves ACVATIX. with a 20 mm stroke

Technical data. Parameterisable damper actuator in the

Electrical data Nominal voltage AC/DC 24 V Nominal voltage frequency

Overview of types. Technical data

DATA SHEET Selectable AC transducer TAS-311DG

11 VA Connection Cable 1 m, 4 x 0.75 mm 2 Functional data Factory settings Variable Setting Torque (nominal torque) Motor Spring return

Technical data sheet. Technical data. Safety notes

Technical data V phase cut, input impedance 8.2 k Position feedback (measuring voltage U) DC V, max. 0.5 ma Start point DC

SALES SERVICE +358 (0)

Functional data Factory settings Variable Settings

Power consumption Operation At rest Wire sizing

MODEL: M2MNV MODEL: M2MNV-[1][2]-[3][4]

SAY..P.. A6V ACVATIX Electromotoric actuators for valves. with a 15 mm stroke

Technical data. T2-SM230ASR en v Subject to changes / 3. Electrical data Nominal voltage AC

Electrical data Nominal voltage AC/DC 24 V Nominal voltage frequency

Electrical data Nominal voltage AC/DC 24 V Nominal voltage frequency

Electrical data Nominal voltage AC/DC 24 V Nominal voltage frequency

Manual triggering of the adaption by pressing the «Adaption» button or with the PC-Tool

SAY..P.. A6V ACVATIX Electromotoric actuators for VPI46. with a 15 mm stroke

Technical data. Safety notes

21 VA (l max 20 5 ms) Connection Cable 1 m, 4 x 0.75 mm 2 Functional data Factory settings Variable Setting Torque Inhibiting torque

Power consumption In operation At rest For wire sizing. Auxiliary switch NRF24A-SR-S2 NRF24A-SR-S2-O

Power consumption In operation At rest For wire sizing

Electrical data Nominal voltage AC/DC 24 V Nominal voltage frequency

Power consumption In operation At rest For wire sizing

MODEL: W2TS. Mini-MW Series

AC 01.2 HART Technical data Actuator controls

Technical data. Safety notes. Power consumption In operation At rest For wire sizing

Technical data. Safety notes. T3-LR24A-SR en v Subject to changes 1 / 2

Theta 60R. Technical Data Sheet. Special Features. Fig. 2 Theta R, 2 channel version, in housing S17 hole mounting brackets pulled out.

600T Series Transmitters Model 653L Electronic temperature transmitter (PC programmable for RTD and resistance) Specification Sheet

Electrical data Nominal voltage AC 24 V, 50/60 Hz DC 24 V. Power consumption In operation At rest For wire sizing

MODEL: M2VF MODEL: M2VF [1][2] [3][4]

Electromotoric actuators for stroke valves

Series 70 24V and 120V Actuator 600 to 18,000 lb.-in.

MODEL: MRP6. Final Control Elements

Electrical data Nominal voltage AC/DC 24 V Nominal voltage frequency

Three models available: Relay output with 24 VDC power input Relay output with 85 to 250 VAC power input Solid-state output with 24 VDC power input

MODEL: M2MNV MODEL: M2MNV-[1][2]-[3][4]

Electromotoric actuators

Extension for ground plate Z-SMA. Shaft extension AV8-25. Reversible spindle clamp K-SA. Damper crank arm KH8. Extension from SM.. or AM.. to SM..A..

Rotary gear motor series AG8...

SAV.. ACVATIX Electromotoric actuators for valves. with a 20/40 mm stroke

OpenAir Electric Damper Actuators GDE/GLB Series Non-spring Return Rotary 24 Vac - Modulating Control 0 to 10 Vdc

Actuator for modulating control AME 435

Technical Information itemp TMT180

Technical data. Safety notes. T5-HT24-SR-T en v Subject to changes 1 / 3

MODEL: MRP5. Final Control Elements. [2] TERMINAL BOX T: With

DCS-62 Series Spring Return Electronic Actuator Product Bulletin

Digital flow transmitter for continuous flow measurement

Valve Series V2001 Globe Valve Type 3321 with Pneumatic or Electric Actuator

Overview of types. Technical data. T5-NRDVX24-SR-T-.. en v Subject to changes 1 / 3

High-quality digital indicator for panel mounting Model DI35-M, with multi-function input Model DI35-D, with two inputs for standard signals

TS-9100 Electronic Sensors and Transducers. Features and Benefits. G Wide range of enclosures and signal outputs

MODEL AT-10 ANALOG TRANSMITTER

Power consumption In operation At rest For wire sizing. 1.5 W at nominal torque 0.4 W 4 VA Connection Cable 1 m, 3 x 0.75 mm 2

Any installation position possible. 1K5, but C. < 2 % of the control range. < 0,2 % / 0,1 bar, type 824.P < 0,1 % / 0,1 bar. Approx.

Type 3374 Electric Actuator

Type Overview. Technical Data. Outdoor Humidity, Temperature Sensor

High-quality digital indicator for panel mounting Model DI35-M, with multi-function input Model DI35-D, with two inputs for standard signals

ELECTRONIC ROTARY GEAR MOTOR SERIES SED (AR2...SE )

Electrical data Nominal voltage AC/DC 24 V Nominal voltage frequency

Output Signal Active Note. Output Signal Temperature 22UTH-51 DC V, DC V

Phase-sequence Phase-loss Relay

Actuators for modulating control AME 85, AME 86

Glass-fibre-reinforced polycarbonate. Dead zone Adaptive or fixed from % 1.5 s adjustable. 20 ms. 60 ms. 60 ms. Approx. 1.

RA / /6. Replaces: Table of contents RA /06.98

SAL.. ACVATIX Electromotoric rotary actuators for butterfly or slipper valves. with 90 rotary angle

Electromagnetic flowmeters and switches DWM 1000/2000

MODEL: M2XPA3. [2] EXCITATION 2: 4 V DC / 20 ma 3: 8 V DC / 20 ma 4: 12 V DC / 20 ma Configurator software is used to change the excitation value.

Power consumption In operation At rest For wire sizing. 150 s / C Sound power level Motor. Emergency setting function 61 db (A)

EMD-FL-3V-400. Electronic monitoring relay for voltage monitoring in three-phase networks. INTERFACE Data sheet _en_03. 1 Description.

600T Series Transmitters. Specification Sheet. Model 653T Electronic temperature transmitter (PC programmable)

Position switches FM series

Servomotor for butterfly valves VF, VFH. delta-elektrogas.com EE157-01/16

PART # mA Positioner

Echotel Model 910 Ultrasonic Level Switch

DEIF A/S. TAS-311DG Selectable AC transducer J (UK) Installation and start up instructions

Safety switches with slotted hole lever

Transcription:

COMMERCIAL Bray Controls Commercial Diision 13788 West Road, Suite 200A Houston, Texas 77041 BCDSales@Bray.com Phone: 1-888-412-2729 Fax: 1-888-412-2720 www.braycommercialdiision.com GA Series - Actuator Operating Instructions 04/08 /15 GA Non-Spring Return Actuator - (GA24-562) 24 V, /, Floating and Modulating Automatic adaptation to ale, precision control and high energy efficiency with minimal operating noise. Features Extending or retracting force of minimum 562 lb. (2500 N) Stepping motor with electronic control unit and electronic load-dependent cut-off Automatic detection of control signal applied (modulating or floating), display ia 2 LEDs The type of characteristic cure (linear, quadratic or equal percentage) can be adjusted in the drie Independent adaptation to ale stroke between 0.31 in.(8 mm) and 1.57 in.(40 mm), captie een if the power is turned off Direction of trael can be selected ia screw terminals when making electrical connection or remotely Hand crank for external manual adjustment with motor cut-off and as trip for re-calibration Easy assembly with ale, spindle connection takes place automatically after application of control oltage Many adaptors kits allow assembly on third-party ales Technical Description Two-part housing made of self-extinguishing red plastic and sealing to IP66 (equialent to NEMA 4) protection class Maintenance-free gearbox in sintered steel, gearbox base-plate in steel Patented drie-ale coupling Mounting column made of Stainless Steel and mounting bracket for fitting ale made of cast light alloy Electrical connections 13 AWG (max. 2.5 mm²) with screw terminals Three knock-out cable entries for M20 x 1.5 (2x) and M16 x1.5 Installation position: ertical to horizontal, but not upside down Accessories Auxillary Switches 0372333 001 Continuously adjustable, min. 100 ma and 12 V, additional load 6(2) A 0372333 002 Gold-plated contacts, from 1 ma and up to 30 V, further range 3(1) A Adaptor kits for Industrial Globe Vales GA-MTG-01 DG250-x and DG3-x GA-MTG-02 DG4-x, DG5-x and DG6-x Fittings 0386263 001 Screwed cable fitting M16 X 1.5 0386263 002 Screwed cable fitting M20 X 1.5 High Media Temperature Kit 0372336 240 Adaptor required for medium temperatures between 266 F (130 C) and 464 F (240 C) Operation Depending on the type of connection (see the connection diagram), the deice may be used as a modulating drie (0...10 V and/or 4...20 ma), as a / (2-point) drie (extend/retract) or as a Floating (3-point) drie (extend/stop/retract) with an intermediate position. The run time of the drie can be set according to the specific requirements, using switches S1 and S2. Switches S3 and S4 are used to configure the characteristic cure (equal percentage, linear or quadratic) The external hand crank allows you to adjust the position manually. When the hand crank is folded out, the motor is switched off. After the hand crank is folded back, the set point position is adopted again. If the hand crank is unfolded, the drie stays in this position. Calibration and feedback signal When used as a modulating drie, the deice calibrates itself automatically. As soon as oltage is applied to either terminal 2a or 2b for the first time, it moes to the lower limit stop on the ale, thus enabling automatic connection with the ale spindle. Then it moes to the upper limit stop and the alue is recorded and saed with the help of a path measurement system. The control signal and the feedback signal are adjusted to this effectie stroke. There is no re-calibration if the oltage is interrupted or if the oltage supply is remoed. The alues remain saed. Calibration must be performed in order to utilize the feedback signal when / (2-point) or Floating (3-point) control is required. Terminal 44 is 0-10VDC feedback. The feedback signal always increases as the shaft extends. 1

Re-Calibration To re-calibrate, oltage needs to be applied to either terminal 2a or 2b and the oltage signal input circuit needs to be completed by installing a jumper between terminals 3u and1. To trigger re-calibration, fold the hand crank out and back in again twice within 4 seconds. Each time the hand crank is folded out rotate it slightly in either direction until a clicking sound is heard. Both the LEDs will then flash red. During re-calibration, the feedback signal is inactie, or it corresponds to a alue of "0". Re-calibration uses the shortest run time. The re-calibration is only alid once the entire procedure has been completed. Folding the hand crank out again will interrupt the procedure. If the ale drie detects a blockage, it will report this by setting the feedback signal to 0 V after approx. 90 s. Howeer, the drie will try to oercome the blockage during this time. If it is possible to oercome the blockage, the normal control function is actiated again and the feedback signal is restored. Connection as a / (2-point) Actuator This actiation can take place ia two cables. Voltage is applied to terminal 2a. Applying the oltage to terminal 2b extends the actuator shaft. After this oltage has been switched off from 2b, the drie moes to the opposite end position. The electronic motor switch-off responds in the end positions (ale limit stop, or when maximum stroke is reached) or in case of oerload (no limit switches). The coding switch can be used to set the run times. The characteristic cure cannot be selected in this case (resulting in the characteristic cure for the ale). The feedback signal is actie as long as calibration was performed and a jumper is installed between terminals 3u and 1.Terminal 3i must not be connected. Connection as a Floating (3-point) Actuator Applying oltage to terminal 2a or 2b makes it possible to moe the ale to any desired position. If oltage is applied to terminal 2b, the actuator shaft extends. The shaft retracts when oltage is applied to terminal 2a. In the end positions (at the ale stop, or when the maximum stroke is reached) or in case of an oer- load, the electronic motor switch-off responds (no limit switches). The direction of the stroke can be changed by transposing the connections. The coding switch is used to set the run times. In this case, the characteristic cure cannot be selected (resulting in the characteristic cure for the ale). The feedback signal is actie as long as calibration was performed and a jumper is installed between terminals 3u and 1.Terminal 3i must not be connected. Modulating Actuator (0...10 V and/or 4...20 ma) The built-in positioner controls the drie depending on the controller input signal y. The input signal used is a oltage signal (0...10 V ) at terminal 3u, or a current signal at terminal 3i. If an input signal is present at both terminals (3u (0...10 V) and 3i (4...20 ma)) simultaneously, the input with the higher alue takes priority. Mode of action 1 (apply oltage to internal connection 2a): As the input signal increases, the ale shaft extends. Mode of action 2 (apply oltage to internal connection 2b): As the input signal increases, the ale shaft retracts. The starting point and the control span are fixed. After the oltage supply is applied and after calibration, the drie moes to each ale stroke between 0% and 100%, depending on the input signal. The electronics and the path measurement system ensure that no stroke is lost, and the drie does not require re-calibration at interals. When the end positions are reached, the position is checked, corrected as necessary and stored again. This ensures parallel running of seeral dries of the same type. Feedback signal y0 = 0...10 V corresponds to the effectie ale extention of 0 to 100%. The coding switch can be used to set the characteristic for the ale. Equal-percentage and square characteristics can only be produced if the deice is used as a proportional-action drie. Further switches can be used to select the run-times (can be used for the / (2-point), Floating (3-point) or proportional functions). 2

LED Display The display consists of two dual-color LEDs (red / green). Both LEDs flashing red: Calibration procedure Upper LED lit red: Upper limit stop or "shaft fully retracted" position reached Lower LED lit red: Lower limit stop or "shaft fully extended" position reached Upper LED flashing green: Drie running, "shaft retracting" Upper LED lit green: Drie stationary, last direction of running "is shaft retracting" Lower LED flashing green: Drie running, moing towards "fully extended" position Lower LED lit green: Drie stationary, last direction of running "is shaft extending" No LED lit: No oltage supply (terminal 2a or 2b) Both LEDs are flashing red and green: Drie is in manual mode Engineering and Installation Notes Penetration of condensate or dripping water, etc. along the ale spindle into the drie should be aoi- ded. The ale is plugged directly onto the drie and is fixed with screws (no further settings are needed). The drie is automatically connected to the ale spindle. When the deice is deliered, the drie spindle is in the middle position. The housing contains three breakthrough-type cable lead-throughs which are broken open automatically when the cable lead-through is screwed in. The stepping motor/electronics concept guarantees parallel running of seeral ale dries of the same type. The crosssection of the connecting cable should be selected according to the line length and the number of dries. With fie dries connected in parallel and a line length of 50 m, we recommend using a cable cross-section of 1,5 mm2 (power consumption of the drie 5). Fitting Outdoors If the deices are fitted outdoors, we recommend that additional measures be taken to protect them against the effects of the weather. Additional Technical Information The red housing (consisting of the front and back sections and the connecting lid) only seres the purpose of a coer. The DC motor, the control electronics, the load-bearing parts and the maintenance- free gear unit are accommodated in the housing. The drie shaft and column are made of rustproof materials. The interior plates and the gear unit are made of steel. The ale axle guide way and the ale collar connection are made of die-cast aluminum. Warnings If the temperature of the medium in the ale is high, the drie columns and the shaft may also reach high temperatures. If a failure of the final control element could cause damage, additional protectie precautions must be taken. CE Conformity EMC Directie 2004/108/EC Machinery Directie 98/37/EEC/I/B Low Voltage Directie 2006/95/EC EN 61000-6-1 DIN EN 150 14121 EN 60730-1 EN 61000-6-2 EN 60730-2-14 EN 61000-6-3 Oer-oltage category III EN 61000-6-4 Degree of pollution III 3

GA - Cure Characteristic Switch Settings Desired Character. Cure Switch Coding Characteristic Cure for Vale Characteristic Cure for Drie Effectie on Vale Equal percentage = % Quadratic x 2 Linear lin Equal percentage = % Linear lin = factory setting GA - Run Time Switch Settings Run Time per in.(mm) 51 (2) Seconds Switch coding Run time for 0.55 in.(14 mm) stroke Run time for 0.79 in.(20 mm) stroke Run time for 1.58 in.(40 mm) stroke 28s ± 1 40s ± 1 80s ± 2 102 (4) Seconds 56s ± 2 80s ± 2 160s ± 4 153 (6) Seconds 84s ± 4 120s ± 4 240s ± 8 = factory setting 4

GA - Dimensions 0.73 in. (18.5mm) 2.24 in. (57mm) 2.36 in. (60mm) Non-Spring Return 9.06 in.(230mm) B Adaptor for media temperatures between 266 F (130 C) and 464 F (240 C) C B A A 3.54 in.(90mm) Description A B C GA Series 2.52 in. (64mm) 11.38 in. (289mm) 1.73 in. (44mm) Part Number A B 0372336 240 4.31 in. (109.4mm) 3.94 in. (100mm) GA - Wiring Modulating _ 24 V~/= / (2 Point) 24 V~/= + + + y=0 10V y=4 20mA yo=0 10V S1 1 2a 2b 3u 3i 44 S2 S3 S4 S1; S2 = Runtime S3; S4 = Characteristic 100% 2a µc M 2b 0 0 10V 1 2a 2b 3u 3i 44 Floating (3 Point) 24 V~/= 1 2a 2b 3u 3i 44 Options 0372333 001 0372333 002 (Auxillary Switches) 4 5 6 7 8 9 Y = modulating signal 3u = 0.. 10 V, in case of control by oltage 3i = 4.. 20 ma, in case of control by current 44 = 0.. 10 V Feedback, independent from the use of 3u or 3i = Extra Low Voltage 5

GA - Specifications Technical Specifications Non-Spring Return Power Requirements Positioner 1 Action GA24-562 /, Floating and Modulating Control 1 Control 2 Position Feedback /, Floating and Modulating 24 VAC (±20%) at 50/60 Hz or 24 VDC (±15%) 0 to 10 V, Ri> 100 kω 4 to 20 ma, Ri = 50Ω 0 to 10 V, Load 2.5 kω Direct or Reerse Acting Switching Range 300 m Power Consumption 2 Non-Spring Return 10W, 18VA Force Non-Spring Return 562 lbs. (2,500 N) Max. Temperature of Medium 3 Ambient Conditions Temperature Humidity 0.31" to 1.57" (8 mm to 40 mm) 266 F (130 C) 14 F to 131 F (-10 to 55 C) 0 to 95% RH without condensation Leel of Protection Equialent to NEMA 4 (IP 66) Protection Class III to IEC 60730 Enclosure Self-extinguishing plastic sealing equialent to NEMA 4 Electrical Connection Motor Run Time sec. per in. (mm) Response Time - 3-Point 13 AWG (2.5 mm²) with screw terminals. Three knock-out cable entries for M20 1.5 (2 ) and M16 1.5 51 (2), 102 (4), 153 (6), Dip Switch Adjustable 200 ms Weight Non-Spring Return 9.1 lbs. (4.1 kg) UL Listed Temperature-Indicating and Regulating Equipment, XAPX, XAPX7. File E366456 1 Also for / (2-point) or Floating (3 point) depending on the connection for 24V~ 2 Design the transformers for this alue, otherwise functional faults may occur. 3 An intermediate piece is required for medium temperatures between 266 F (130 C) and 464 F (240 C) 4 The return time corresponds to a stroke of 0.55 in. (14 mm) to 1.58 in. (40 mm) and does not depend on the set run time. Disclaimer - The performance specifications are nominal and conform to acceptable industry standards. For application at conditions beyond these specifications, consult the local Bray office. Bray, Inc. shall not be liable for damages resulting from misapplication or misuse of its products. 6