NRT 105: Electronic fan-coil controller, equiflex

Similar documents
NRT 300: Electronic air-conditioning controller, heating/cooling, equiflex

NRT 107: Room- and supply-temperature controller, equiflex

43.019/1. NRT 300: Electronic controller for air-conditioning (heating/cooling) Sauter Components

43.030/1. NRT 101: Electronic room-temperature controller with time program. Sauter Components

Sauter Components

EY-EM 527: Remote I/O module, ecolink527

Room Temperature Controllers. for heating and cooling systems

Room Temperature Controllers. for heating and cooling systems

Room Temperature Controllers. for heating and cooling systems

Room Temperature Controllers. for heating and cooling systems

EY-EM 522, 523: Remote I/O module, ecolink522, 523

Room Temperature Controllers. for heating and cooling systems

Control solutions Biofloor

EQJW145. Content: 1 General. 2. Indicators and operating controls 3. Putting into service (by a technician) 4. How to operate (user)

Use of the application program. Contents. 1. Functional description General. GAMMA instabus Application program description.

Use of the application program. Contents. 1. Functional description General. GAMMA instabus Application program description.

Electrical data Nominal voltage AC/DC 24 V Nominal voltage frequency

theben Fan Coil Actuator FCA 1 Fan Coil Actuator FCA 1 FCA Version: Jan-08 (Subject to change) Page 1 of 77

TLC3-BCR-U Series Thermostat

Fan Coil Actuator FCA 2

Functional data Factory settings Variable Settings

Use of the application program. Contents. instabus EIB Application program description. September S2 Room temperature controller

STR-LCF. Security Advice Caution. Notes on Disposal. Electronic Fan Coil Thermostat (Flush mounting) Datasheet. Application

Self-learning Room Temperature Controller Receiver

Intelligent Compact Controller

Overview of types. Technical data

Thermostat P. Thermostats Electronic room thermostat with clock for thermal actuators

Electrical data Nominal voltage AC/DC 24 V Nominal voltage frequency

Radiocontrol F. Floor Heating Controller Radio control system for floor heating

Technical data. Safety notes. T3-LR24A-SR en v Subject to changes 1 / 2

Electrical data Nominal voltage AC 24 V, 50/60 Hz DC 24 V. Power consumption In operation At rest For wire sizing

Power consumption In operation At rest For wire sizing. 1.5 W at nominal torque 0.4 W 4 VA Connection Cable 1 m, 3 x 0.75 mm 2

Overview of types. Technical data. T5-NRDVX24-SR-T-.. en v Subject to changes 1 / 3

SRC-110 Series Zone Controllers with Modbus RTU

11 VA Connection Cable 1 m, 4 x 0.75 mm 2 Functional data Factory settings Variable Setting Torque (nominal torque) Motor Spring return

Fan-coil intelligent unitary controller

Brief description. Type overview

SERVICE-MANUAL ROOM TEMPERATURE CONTROLLER NEA 230V / 24V. Construction Automotive Industry

Technical data. Safety notes

Room Temperature Controller with Built-in Room Sensor 1 Feb 2002

AC/DC 24 V, 50/60 Hz. Functional data Variable Settings. DC V, max. 0.5 ma. End point DC V... 4 ma ma Non-variable

21 VA (l max 20 5 ms) Connection Cable 1 m, 4 x 0.75 mm 2 Functional data Factory settings Variable Setting Torque Inhibiting torque

Manual triggering of the adaption by pressing the «Adaption» button or with the PC-Tool

PRODUCT CATALOGUE TEMPERATURE CONTROL Grässlin products for individual control of temperature

By means of C-Bus connection DTT 318 can be inserted in a telemanagement system.

Manual triggering of the adaption by pressing the «Adaption» button or with the PC-Tool

AHC-XP. Dewpoint-guided Power Controller for Glass and Handrail Heaters. Front view. Characteristics

Universal Controller

Technical data V phase cut, input impedance 8.2 k Position feedback (measuring voltage U) DC V, max. 0.5 ma Start point DC

Technical data. Safety notes. T5-HT24-SR-T en v Subject to changes 1 / 3

KNX Room temperature controller

[ ] kvs theor.: Theoretical kvs value for pressure drop calculation Vmax low-n: Vmax for low-noise operation

Technical data. T2-SM230ASR en v Subject to changes / 3. Electrical data Nominal voltage AC

Room sensors. In ventilating and air conditioning plants to acquire relative humidity and temperature in rooms. Humidity measuring range

Power consumption In operation At rest For wire sizing. Auxiliary switch NRF24A-SR-S2 NRF24A-SR-S2-O

RAM 712 KNX room thermostat for surface-mounted and flush-mounted installation

Viconics VT76x7 Series Rooftop Unit Controllers Engineering Guide Specification

KNX TH65-AP. Thermo-Hygrometer. Installation and Adjustment. Item number 70184

Power consumption In operation At rest For wire sizing

B 520 ELECTRONIC AMBIENT TEMPERATURE CONTROLLERS. RTB C2 Eng. COSTER BUS. B RTB C2 Eng MC REV 01

Application Sheet Fan coil unit with staged fan, heating/cooling coil (2 pipe) on triac output and electric reheater

EYL225: nova225, Compact automation station

Application Sheet Fan coil unit with variable fan, heating/cooling coil (2 pipe) on triac output and electric reheater

Power consumption In operation At rest For wire sizing

Electrical data Nominal voltage AC/DC 24 V Nominal voltage frequency

Electrical data Nominal voltage AC/DC 24 V Nominal voltage frequency

Room thermostat solo, FM Type: 6124-xx

INSTAT 868 Radio Frequency Single-Room Controls

MODEL: MRP5. Final Control Elements. [2] TERMINAL BOX T: With

Technical data sheet. Technical data. Safety notes

QFM21... Duct sensors. Symaro. for relative humidity and temperature

Wireless multizone receiver RDE-MZ6

Technical manual GS 4x.00 knx application description air quality sensor

SAX..P. Electromotoric actuators for valves ACVATIX. with a 20 mm stroke

Electrical data Nominal voltage AC 230 V Nominal voltage frequency

PRODUCT MANUAL. ABB i-bus KNX VC/S 4.x.1 Valve Drive Controller

MODEL: MRP6. Final Control Elements

Installation Guide. ECL Comfort 310, application A Table of Contents

Electrical data Nominal voltage AC/DC 24 V Nominal voltage frequency

Power consumption In operation At rest For wire sizing

R7426A. MicroniK 200 TEMPERATURE CONTROLLER WITH AND WITHOUT REAL-TIME CLOCK

Intelligent Installation Systems. ABB i-bus KNX Room Thermostat Fan Coil with Display 6138/11-xx-500 Product Manual

UNICONT. PMG-400 Universal controller and display unit USER'S AND PROGRAMMING MANUAL 1. pmg4111a0600p_01 1 / 24. ST edition

Power consumption In operation At rest For wire sizing. 150 s / C Sound power level Motor. Emergency setting function 61 db (A)

Technical data. Safety notes. Power consumption In operation At rest For wire sizing

CONTROL Room. Room product for Swegon s WISE system for demand-controlled ventilation. Quick facts Room control against temperature, CO 2

SAY..P.. A6V ACVATIX Electromotoric actuators for VPI46. with a 15 mm stroke

SAY..P.. A6V ACVATIX Electromotoric actuators for valves. with a 15 mm stroke

Electrical data Nominal voltage AC/DC 24 V Nominal voltage frequency

Communicative heating controller

Analogue temperature controllers

LK Wireless Room Control Cq

Electronic Air / Fuel Ratio Control System

CR24-.. Single room controllers

SINEAX U 553 Transducer for AC Voltage

ECB-103 BACnet B-ASC 10-Point Programmable Controllers

1 Digital input (24Vac or dry contact) Inputs

Electrical data Nominal voltage AC/DC 24 V Nominal voltage frequency

Room Temperature Controller

Electro Controls. Input-Output Modules WattsIndustries.co.uk

Transcription:

Product data sheet 4.04 R 105: Electronic fan-coil controller, equiflex How energy efficiency is improved ECO Meter for displaying the current energy consumption and digital input for the change-over between presence and absence Features Individual single room, apartment and zone temperature control in 2- and 4-pipe systems for heating, cooling or heating/cooling Automatic activation of the valves (heating/cooling) P controller with pulse-pause or analogue output (0...10 V) Measurement of room temperature by either integrated or external temperature sensor Input for C/O signal Easy to use with frontal keys and large LCD -speed fan control with configurable on/off switching points for each level Frost-protection/anti-overheating functions Hours-run meter R105F0*1 R105F011 echnical data Power supply Power supply 110...20 V~/24 V~ olerance in power supply ±15%, 50...60 Hz Power consumption < 1 VA Max. switching capacity of internal sensor (C) 2(1.6) A, 250 V~ Max. switching capacity of external sensor (i1000) 5() A, 250 V~ Setting range1) 8...7 C R105F061 Parameters emperature sensor, internal Additional data for R105F011 Proportional band 1...20 K Operating modes ormal, reduced (/R) Dead zone (/R) 0...10 K/0...12 K ime constant 22 min Dead time 2 min Frost-protection temperature 8 C (when heating OFF) hermal overload temperature 8 C (when cooling OFF) Switching interval 4...0 min Control factor indicated in ten levels Min. pulse 0 s Admissible ambient temperature 0...50 C Admissible ambient humidity 5...95% rh, no condensation Display range, actual temperature 8...50 C Ambient conditions Indicators, display, operation Construction Weight 0.27 kg Housing material fire-retardant thermoplastic Housing pure white (RAL 9010) Fitting wall fitting/recessed junction box Screw terminals for wires of up to 2.5 mm² Cable feed at rear ype of protection IP 0 (E 60529) Protection class II (IEC 6070) Standards and directives 1) Depends on the setting parameters P05, P08 Right of amendment reserved 2015 Fr. Sauter AG 6.1 1/7

Energy class I = 1 % acc. EU 811/201, 2010/0/EU, 2009/125/EG Software class A E 6070 CE conformity as per EMC directive 2004/108/EC E 61000-6-1, E 61000-6-2 E 61000-6-, E 61000-6-4 Low-voltage directive 2006/95/EC E 6070-1 Overview of types ype R105F011 R105F061 Control characteristics P, quasi-continuous P, continuous, 0...10 V Power supply ype of installation Outputs for fan 110...20 V~ 2-, 4-pipe Relay, stages Relay Valve outputs 24 V~ 4-pipe Relay, stages 0...10 V, load > 4 kω, max. 2.5 ma Accessories ype AX2** AXM*** EG*** Description hermal valve actuators (see product data sheet) Motorised valve actuator (see product data sheet) External temperature sensor i1000 (see product data sheet) 00124000 Recessed junction box Description of operation he room temperature is measured by a precision temperature sensor and compared with the current setpoint. Depending on the control offset and the control characteristic, the heating/cooling in the room is increased or decreased and the required room temperature is kept constant. Optimal comfort is ensured by the fully-automatic controlling. For individual temperature requirements, the time-limited and time-unlimited manual operating modes are available for using the absence and presence functions. he operating status of the system is shown on the display (LCD) with visual symbols and a numerical field. Service mode is available for adapting the device to the installation etc. he following can be parameterised: the control behaviour, the switching points of the blower levels, the frost-protection and anti-overheating functions, the anti-jamming function for valves, the setpoint limiting, etc. Intended use his product is only suitable for the purpose intended by the manufacturer, as described in the Description of operation section. All related product regulations must also be adhered to. Changing or converting the product is not admissible. Engineering and fitting notes he device must be supplied with power all year round due to the frost-protection, anti-overheating and valve anti-jamming functions. he unit should be fitted approx. 1.5 m above the floor, and protected from direct sunlight, draughts and sources of heat and cold. Additional technical data emperature setpoint 2 C (factory setting) ime-limited changing of operating mode SERV parameters emperature measurement Input for ext. temperature sensor Zero-point correction, e.g. influence of wall Granularity for setpoints 2...9 hours, with the remaining time displayed on-volatile EEPROM C sensor (internal) i1000; selectable internally/externally (closes dew-point switch and switches off c/o input respectively) ±6 K 0.5 K 2/7 6.1 Right of amendment reserved 2015 Fr. Sauter AG

Granularity for display of actual value 0.1 K Measuring accuracy 0. K at 20 C Setting limit for setpoint Universal input PROG Limitable minimum and maximum setpoints via SERV ( min, max ), factory setting not limited Suitable for one of the following functions: For external potential-free gold-plated contacts. Multiple controllers can be connected in parallel to one contact, but connecting more than 20 is not recommended. Cross-section of cable 0.5 mm 2 Cu and distance for contact controller 100 m. Absence Presence Window contact Energy-saving operation with reduced temperature level ormal temperature level () Reduced temperature level (R) External clock Extended dead zone (temperature level reduced, R) Remote control Malfunction (e.g. filter contamination) Keyboard locking (key switch) EMP input for external potential-free gold-plated contacts Dew point Changeover (C/O) Anti-jamming function for valve Frost-protection and anti-overheating functions Child protection Valve output Ventilator control Stand-by/normal mode Display with warning symbol Display with symbol Cooling off (closes ext. temperature sensor and C/O off) For 2-pipe system, only F011 (closes ext. temperature sensor and temperature detector off) After a week, the valve outputs are activated for 0...15 minutes if none of the valves has been activated previously (adjustable) Selectable via SERV, without display of setpoint Locked and unlocked using key sequence; display with symbol With indication of switching status Automatic level 0, 1, 2,. Manual override with level 1, 2,, with indication of switching status; heating without fan possible; however, the priority of manual fan control remains for ventilation purposes. Minimum fan speed level 0 or 1 selectable (for channel controller) Mode of operation in accordance with E 6070 Hours-run meter for fan Relay switching frequency, mechanical ype 1C, normally-open contacts, partially with power applied - see connection diagrams Can be queried via SERV 0...9990 h; non-deletable > 5 million. SERV parameters with factory settings (setting range) P01:000 EMP input 0 = external temperature 1 = dew point 2 = C/O (only F011) P02:000 ype of sensor 0 = C See table below 2) 1 = i1000 ) P0:000 C influence of wall (-60...60 = ±6 K) P04:000 i1000 influence of wall (-60...60 = ±6 K) P05:020 2 K proportional band X p heating and cooling valves (010...200) P06:004 4 min. period t p heating and cooling valves (004...00) P07:008 0.8 K dead zone normal X tn (002...98) P08:100 10.0 K dead zone extended X tr (004...120) X tr > X tn P09:00 0 % cut-in point for 1st fan level G1 in % of P band (005...040) P10:090 90 % cut-in point for 2nd fan level G2 in % of P band (020...120) P11:120 120 % cut-in point for rd fan level G in % of P band (040...160); G1 G2 G P12:015 15 % switching difference for fan X SdG in % of P band (005...040) P1:002 2 min. fan follow-up t G (000...010) when fan switched off automatically 2) Dew point sensor or c/o input and i1000 sensor are mutually exclusive ) Dew point sensor or c/o input and i1000 sensor are mutually exclusive Right of amendment reserved 2015 Fr. Sauter AG 6.1 /7

P14:000 Fan function for heating and cooling = 0 Only for cooling = 1 P15:000 Minimum fan speed level G1 0 = inactive P16:000 Contact input PROG: See table below 1 = active 4) P17:000 Frost-protection and anti-overheating functions 0 = active graphic 8 C 1 = active graphic 8 C 2 = active graphic and graphic = inactive P18:000 Anti-jamming function for valve (0 = inactive, 1...15 = active minutes) P19:014 Minimum limitation setting range for temperature setpoint min (009...05) 5) P20:02 Maximum limitation setting range for temperature setpoint max (011...07) 6) P21:000 Hours-run meter for fan in units of 10 hours. on-deletable P22:10 Input functions Software version Input functions Possible mode when Activated by contacts are closed 000 Absence PROG R R Absence sensor Symbols when contacts are closed 001 Presence PROG R Occupancy detector 002 Window contacts PROG R R Window contacts P16 00 External time-switch PROG R R External timer 004 Remote control PROG elephone 005 Fault indicator PROG Fault contacts P01 006 Keys disabled PROG Key-operated sw. 1) 001 Dew point EMP OFF Dew-point monitor 1) 2) 002 Change-over EMP c / o SERV = normal temperature setpoint (normal comfort and energy requirement) R = reduced temperature setpoint (reduced comfort and energy requirement) 1) If the dew point is exceeded, the cooling valve is closed; control mode no longer possible; display of actual value: --- 2) Only F011 Disposal When disposing of the product, observe the currently applicable local laws. More information on materials can be found in the Declaration on materials and the environment for this product. 4) Apart from P17:00, and P16:004 with contacts input closed (stand-by mode) 5) Depends on P band and dead zone 6) Depends on P band and dead zone 4/7 6.1 Right of amendment reserved 2015 Fr. Sauter AG

Connection diagrams R 105 F011 / F901 < 7 A L 110...20 V~ 1 2 Rel C Rel 4 P-controller pulse/ pause PROG EMP Rel 0 Rel 1 Rel 2 4 5 6 7 8 9 10 11 I II III i1000 4 5 6 7 8 9 10 11 I II III c/o R 105 F061 24 V~ 1 2 P-controller C Rel 0 Rel 1 PROG Rel 2 EMP M 4 5 6 7 8 9 10 11 I II III M L i1000 8 9 10 11 L III 125 III II 100 % II F011 F061 F061 F011 75 50 I I 25 XsdG - -2-1 Xs +1 +2 +? Xtn Xp Right of amendment reserved 2015 Fr. Sauter AG 6.1 5/7

Dimension drawing Accessories 6/7 6.1 Right of amendment reserved 2015 Fr. Sauter AG

Example applications - + - + P 2P F011 - + - c/o P 2P F011 Fr. Sauter AG Im Surinam 55 CH-4016 Basel el. +41 61-695 55 55 www.sauter-controls.com Right of amendment reserved 2015 Fr. Sauter AG 6.1 7/7