Electrical data Nominal voltage AC/DC 24 V Nominal voltage frequency

Similar documents
Electrical data Nominal voltage AC/DC 24 V Nominal voltage frequency

Electrical data Nominal voltage AC/DC 24 V Nominal voltage frequency

Electrical data Nominal voltage AC/DC 24 V Nominal voltage frequency

Electrical data Nominal voltage AC/DC 24 V Nominal voltage frequency

21 VA (l max 20 5 ms) Connection Cable 1 m, 4 x 0.75 mm 2 Functional data Factory settings Variable Setting Torque Inhibiting torque

Electrical data Nominal voltage AC/DC 24 V Nominal voltage frequency

Electrical data Nominal voltage AC/DC 24 V Nominal voltage frequency

Electrical data Nominal voltage AC/DC 24 V Nominal voltage frequency

Electrical data Nominal voltage AC/DC 24 V Nominal voltage frequency

Power consumption In operation At rest For wire sizing. 150 s / C Sound power level Motor. Emergency setting function 61 db (A)

Manual triggering of the adaption by pressing the «Adaption» button or with the PC-Tool

Overview of types. Technical data

Electrical data Nominal voltage AC/DC 24 V Nominal voltage frequency

Functional data Factory settings Variable Settings

11 VA Connection Cable 1 m, 4 x 0.75 mm 2 Functional data Factory settings Variable Setting Torque (nominal torque) Motor Spring return

Electrical data Nominal voltage AC 230 V Nominal voltage frequency

Manual triggering of the adaption by pressing the «Adaption» button or with the PC-Tool

Electrical data Nominal voltage AC/DC 24 V Nominal voltage frequency

Electrical data Nominal voltage AC/DC 24 V Nominal voltage frequency

Technical data V phase cut, input impedance 8.2 k Position feedback (measuring voltage U) DC V, max. 0.5 ma Start point DC

[ ] kvs theor.: Theoretical kvs value for pressure drop calculation. Electrical data Nominal voltage AC/DC 24 V Nominal voltage frequency

Electrical data Nominal voltage AC/DC 24 V Nominal voltage frequency

Technical data. Parameterisable damper actuator in the

AC/DC 24 V, 50/60 Hz. Functional data Variable Settings. DC V, max. 0.5 ma. End point DC V... 4 ma ma Non-variable

Power consumption In operation At rest For wire sizing

Power consumption In operation At rest For wire sizing

Power consumption In operation At rest For wire sizing. Auxiliary switch NRF24A-SR-S2 NRF24A-SR-S2-O

Technical data. T2-SM230ASR en v Subject to changes / 3. Electrical data Nominal voltage AC

Power consumption In operation At rest For wire sizing

DN [ ] kvs theor.: Theoretical kvs value for pressure drop calculation. Electrical data Nominal voltage AC/DC 24 V Nominal voltage frequency

Brief description. Type overview

Electrical data Nominal voltage AC 24 V, 50/60 Hz DC 24 V. Power consumption In operation At rest For wire sizing

Technical data. Safety notes. T3-LR24A-SR en v Subject to changes 1 / 2

Technical data sheet. Technical data. Safety notes

Power consumption In operation At rest For wire sizing. 1.5 W at nominal torque 0.4 W 4 VA Connection Cable 1 m, 3 x 0.75 mm 2

Overview of types. Technical data. T5-NRDVX24-SR-T-.. en v Subject to changes 1 / 3

Technical data. Safety notes. Power consumption In operation At rest For wire sizing

[ ] kvs theor.: Theoretical kvs value for pressure drop calculation Vmax low-n: Vmax for low-noise operation

Technical data. Safety notes

Technical data. Safety notes. T5-HT24-SR-T en v Subject to changes 1 / 3

Brief description. VAV-Compact MP en-gb Changes reserved 1. Application. Pressure measurement. Actuator

Power consumption Operation At rest Wire sizing

[ ] kvs theor.: Theoretical kvs value for pressure drop calculation. Electrical data Nominal voltage AC/DC 24 V Nominal voltage frequency

Rp [ ] [ ] kvs theor.: Theoretical kvs value for pressure drop calculation. Electrical data Nominal voltage AC/DC 24 V Nominal voltage frequency

Type overview. Technical data

kvs theor.: Theoretical kvs value for pressure drop calculation Electrical data Nominal voltage AC/DC 24 V Nominal voltage frequency

Extension for ground plate Z-SMA. Shaft extension AV8-25. Reversible spindle clamp K-SA. Damper crank arm KH8. Extension from SM.. or AM.. to SM..A..

kvs theor.: Theoretical kvs value for pressure drop calculation Electrical data Nominal voltage AC/DC 24 V Nominal voltage frequency

Servomotor for butterfly valves VF, VFH. delta-elektrogas.com EE157-01/16

EY-EM 527: Remote I/O module, ecolink527

Installation of VAV-Compact Retrofit with ZDMS-..

Image. Installation VAV-Universal Retrofit-Set. General Information. Safety notes

Spring Return DuraDrive Proportional Actuator

Electromotoric actuators

SAT.. Electromotoric actuators for valves ACVATIX. with a 5.5 mm stroke and 300 N positioning force

Adaptive control system for duct and room pressure applications. Table of Contents

Air damper actuators. OpenAir GDB..1E. Electronic motor driven actuators for open-close, three-position and modulating control

Electrical data Nominal voltage AC/DC 24 V Nominal voltage frequency

Electromotoric actuators for stroke valves

COMMERCIAL. GA Series - Actuator Operating Instructions. GA Non-Spring Return Actuator - (GA24-562) 04/08 /15

Electrical data Nominal voltage AC/DC 24 V Nominal voltage frequency

SAX..P. Electromotoric actuators for valves ACVATIX. with a 20 mm stroke

Type 3374 Electric Actuator

AC 01.2 HART Technical data Actuator controls

Modulating controlled actuators AME 10, AME 20, AME 30 AME 13, AME 23, AME 33 - with DIN EN certified safety function (spring down)

GLB...9. Ball Valve actuators. Building Technologies HVAC Products. for valves VAI61... AC 24 V / AC 230 V

SAL.. ACVATIX Electromotoric rotary actuators for butterfly or slipper valves. with 90 rotary angle

AC 01.2 Modbus TCP/IP

SAY..P.. A6V ACVATIX Electromotoric actuators for valves. with a 15 mm stroke

SAX.. Electromotoric actuators for valves ACVATIX. with a 20 mm stroke

1-phase AC current Voltages/frequencies Volt Volt 110, 115, , 230, 240 Hz Hz 60 50

VFSC9 ELECTRONIC SPEED CONTROLLER. Mounting and operating instructions

Configured air damper actuators 6FU11xx-xDxxx-xxxx

EY-EM 522, 523: Remote I/O module, ecolink522, 523

Operating Instruction

Rotary actuators for ball valves

1-phase AC current voltages/frequencies Volt Volt

SAX.. ACVATIX Electromotoric actuators for valves. with a 20 mm stroke

Specification GRUNER YSP 227C

Rotary actuators for ball valves

Installation / Monitoring Technique

Non-Spring Return DuraDrive Modulating Actuator

SAY..P.. A6V ACVATIX Electromotoric actuators for VPI46. with a 15 mm stroke

Air damper actuators. OpenAir GSD...1A. Electric motor-driven rotary actuators for open-close, three-position and modulating control

Actuators for modulating control AME 85, AME 86

Non-Spring Return EconoDrive Proportional Actuator

Electrical data Nominal voltage AC/DC 24 V Nominal voltage frequency

1-phase AC current Voltages/frequencies Volt Volt 110, 115, , 230, 240 Hz Hz 60 50

SAX.. ACVATIX Electromotoric actuators for valves. with a 20 mm stroke

Rotary actuators for ball valves

GM24-MFT US. Proportional damper actuator, non-spring return, Multi-Function Technology

Output Signal Active Temperature. Electrical data Power Supply DC V, ±10%, 0.5 W

Electric thrust actuator. Electric thrust actuator ARI-PREMIO -Plus 2G. 2,2-5 kn. Electric thrust actuator. ARI-PREMIO -Plus 2G kn.

Technical Instructions Document No EA GQD October 25, OpenAir GQD Series

GMU24. Technical data. Dimensions [mm] For operation of air control dampers in HVAC system Torque: 40Nm Nominal voltage: AC/DC 24V Control: Open/Close

Actuators for modulating control AME 55, AME 56

Technote. Actuator Frese OPTIMA. Application. Features actuator DN15-DN32. Features actuator DN40-DN50. Approval.

Function. Adjustment. Extra functions included. Modes. Housing

LM Series Direct Coupled Actuator

TORKEL 900-series Battery Load Unit

Transcription:

echnical data sheet SVK24A--PC Communicative globe valve actuator with emergency control function for 2-way and 3-way globe valves Actuating force 1500 N Nominal voltage AC/DC 24 V Control modulating, communicative DC (0)2...10 V Variable Nominal stroke 20 mm Conversion of sensor signals Design life SuperCaps: 15 years Communication via Belimo -Bus echnical data Electrical data Nominal voltage AC/DC 24 V Nominal voltage frequency 50/60 Hz Nominal voltage range AC 19.2...28.8 V / DC 21.6...28.8 V Power consumption in operation 2.5 W Power consumption in rest position 1.5 W Power consumption for wire sizing 6 VA Connection supply / control erminals with cable 1 m, 4 x 0.75 mm² (erminal 4 mm²) Parallel operation es (note the performance data) Functional data Actuating force motor 1500 N Positioning signal DC 0...10 V Positioning signal note Input impedance 100 kω Control signal variable Open/Close 3-point (AC only) Modulating (DC 0...32 V) Operating range DC 2...10 V Operating range variable Start point DC...30 V End point DC 2.5...32 V Position feedback DC 2...10 V Position feedback note Max. ma Position feedback variable Start point DC...8 V End point DC 2.5...10 V Setting emergency setting position (POP) Actuator spindle 0...100%, adjustable (POP rotary button) Bridging time (PF) variable 1...10 s Position accuracy 5% absolute Manual override Gear disengagement with push-button Nominal stroke 20 mm Actuating time motor 150 s / 20 mm Actuating time variable 90...150 s / 20 mm Actuating time emergency control 35 s / 20 mm function Adaption setting range manual (automatic on first power-up) Adaption setting range variable No action Adaption when switched on Adaption after pushing the gear disengagement button Override control MAX (maximum position) = 100% MIN (minimum position) = 0% ZS (intermediate position, AC only) = 50% Override control variable MAX = (MIN + 33%)...100% MIN = 0%...(MAX 33%) ZS = MIN...MAX Sound power level motor 45 db(a) Sound power level emergency control 60 db(a) position Position indication Mechanically, 5...20 mm stroke Safety Protection class IEC/EN III Safety extra-low voltage Protection class L L Class 2 Supply www.belimo.com SVK24A--PC en-gb 2016-04-01 subject to changes 1

SVK24A--PC echnical data Safety Degree of protection IEC/EN IP54 Degree of protection NEMA/L NEMA 2, L Enclosure ype 2 EMC CE according to 2014/30/E Certification IEC/EN IEC/EN 60730-1 and IEC/EN 60730-2-14 Certification L clus according to L 60730-1A, L 60730-2- 14 and CAN/CSA E60730-1:02 Mode of operation ype 1.AA Rated impulse voltage supply / control 0.8 kv Control pollution degree 3 Ambient temperature range 0...50 C Non-operating temperature -40...80 C Ambient humidity 95% r.h., non-condensing Maintenance Maintenance-free Weight Weight 1.7 kg erms Abbreviations POP = Power off position / emergency setting position CPO = Controlled power off / controlled emergency control function PF = Power fail delay time / bridging time Safety notes! his device has been designed for use in stationary heating, ventilation and air conditioning systems and must not be used outside the specified field of application, especially in aircraft or in any other airborne means of transport. Only authorised specialists may carry out installation. All applicable legal or institutional installation regulations must be complied during installation. he switch for changing the direction of motion and so the closing point may be adjusted only by authorised specialists. he direction of motion is critical, particularly in connection with frost protection circuits. he device may only be opened at the manufacturer s site. It does not contain any parts that can be replaced or repaired by the user. he device contains electrical and electronic components and must not be disposed of as household refuse. All locally valid regulations and requirements must be observed. Product features Mode of operation Conventional operation: he actuator is connected with a standard modulating signal of DC 0...10 V and moves to the position defined by the positioning signal at the same time as the integrated capacitors are loaded. Interrupting the supply voltage causes the valve to be moved to the selected emergency setting position (POP) by means of stored electrical energy. Operation on the -Bus: he actuator receives its digital positioning signal from the higher level controller via the -Bus and drives to the position defined. Connection serves as communication interface and does not supply an analogue measuring voltage. 2 SVK24A--PC en-gb 2016-04-01 subject to changes www.belimo.com

SVK24A--PC Product features Pre-charging time (start up) he capacitor actuators require a pre-charging time. his time is used for charging the capacitors up to a usable voltage level. his ensures that, in the event of an electricity interruption, the actuator can move at any time from its current position into the preset emergency setting position (POP). he duration of the pre-charging time depends mainly on following factors: Duration of the electricity interruption PF delay time (bridging time) ypical pre-charging time 30 [s] 25 PF [s] 10 s 30 [s] 25 20 5s 2s 0s 20 15 15 10 10 5 5 0 0 0 2 4 6 8 10 [d] 12 [d] = Electricity interruption in days [s] = Pre-charging time in seconds PF[s] = Bridging time Calculation example: Given an electricity interruption of 3 days and a bridging time (PF) set at 5 s, the actuator requires a pre-charging time of 14 s after the electricity has been reconnected (see graphic). Delivery condition (capacitors) Converter for sensors Parameterisable actuators Simple direct mounting Manual override High functional reliability Combination valve/actuator Position indication Home position PF [s] [d] 0 1 2 7 10 0 5 8 10 15 19 2 6 9 11 16 20 5 8 11 13 18 22 10 12 15 17 22 26 [s] he actuator is completely discharged after delivery from the factory, which is why the actuator requires approximately 20 s pre-charging time before initial commissioning in order to bring the capacitors up to the required voltage level. Connection option for a sensor (passive or active sensor or switching contact). he actuator serves as an analogue/digital converter for the transmission of the sensor signal via -Bus to the higher level system. he factory settings cover the most common applications. Single parameters can be modified with the Belimo Service ools MF-P or ZH AP. Simple direct mounting on the globe valve by means of form-fit hollow clamping jaws. he actuator can be rotated by 360 on the valve neck. Manual control with push-button possible - temporary. he gear is disengaged and the actuator decoupled for as long as the button is pressed. he stroke can be adjusted by using a hexagon socket screw key (4 mm), which is inserted into the top of the actuator. he stroke spindle extends when the key is rotated clockwise. he actuator is overload protected, requires no limit switches and automatically stops when the end stop is reached. Refer to the valve documentation for suitable valves, their permitted medium temperatures and closing pressures. he stroke is indicated mechanically on the bracket with tabs. he stroke range adjusts itself automatically during operation. Factory setting: Actuator spindle is retracted. When valve-actuator combinations are shipped, the direction of motion is set in accordance with the closing point of the valve. he first time the supply voltage is switched on, i.e. at the time of commissioning, the actuator carries out an adaption, which is when the operating range and position feedback adjust themselves to the mechanical setting range. he actuator then moves into the position defined by the positioning signal. www.belimo.com SVK24A--PC en-gb 2016-04-01 subject to changes 3

SVK24A--PC Product features Direction of stroke switch Adaption and synchronisation Emergency setting position (POP) rotary knob When actuated, the direction of stroke switch changes the running direction in normal operation. he direction of stroke switch has no influence on the emergency setting position (POP) which has been set. An adaption can be triggered manually by pressing the Adaption button or with the PC-ool. Both mechanical end stops are detected during the adaption (entire setting range). Automatic synchronisation after pressing the gearbox disengagement button is configured. he synchronisation is in the home position (0%). he actuator then moves into the position defined by the positioning signal. A range of settings can be adapted using the PC-ool (see MF-P documentation) he rotary knob «Emergency setting position» can be used to adjust the desired emergency setting position (POP) between 0 and 100% in 10% increments. he rotary knob refers to the adapted or programmed height of stroke. In the event of an electricity interruption, the actuator will move into the selected emergency setting position (POP), taking into account the bridging time (PF) of 2 s which was set exworks. Settings: he rotary knob must be set to the «ool» position for retroactive settings of the emergency setting position (POP) with the Belimo service tool MF-P. Once the rotary knob is set back to the range 0 100%, the manually set value will have positioning authority. Bridging time Electricity interruptions can be bridged up to a maximum of 10 s. In the event of an electricity interruption, the actuator will remain stationary in accordance with the set bridging time. If the electricity interruption is greater than the set bridging time, then the actuator will move into the selected emergency setting position (POP). he bridging time set ex-works is 2 s. his can be modified on site in operation with the use of the Belimo service tool MF-P. Settings: he rotary knob must not be set to the «ool» position! Only the values need to be entered for retroactive adjustments of the bridging time with the Belimo service tool MF-P. Accessories Description ype Gateways Gateway for BACnet MS/P, AC/DC 24 V K24BAC Gateway to Modbus R, AC/DC 24 V K24MOD Gateway to LonWorks, AC/DC 24 V, LonMark certified K24LON Gateway to KNX, AC/DC 24 V, EIBA certified K24EIB Description ype Electrical accessories Connecting cable 5 m, A+B: RJ12 6/6, o ZH/ZIP-SB- ZK1-GEN Connection cable 5 m, A: RJ11 6/4, B: Free wire end, o ZH/ZIP- ZK2-GEN SB- -Bus power supply for actuators, AC 230/24V for local power ZN230-24 supply Connecting board bus suitable for wiring boxes EX-WR-FP..- ZFP2- Auxiliary switch, 2 x SPD, add-on, grey S2A-H Service ools Description Service ool, for MF//Modbus/LonWorks actuators and VAV- Controller Belimo PC-ool, software for adjustments and diagnostics Adapter to Service ool ZH ype ZH AP MF-P MF-C 4 SVK24A--PC en-gb 2016-04-01 subject to changes www.belimo.com

SVK24A--PC Electrical installation! Wiring diagrams AC/DC 24 V, modulating Notes Connection via safety isolating transformer. Parallel connection of other actuators possible. Observe the performance data. Direction of stroke switch factory setting: Actuator spindle retracted. Operation on the -Bus DC (0)2 10 V DC 2 10 V Sensor Cable colours: 1 = black 2 = red 3 = white 5 = orange Cable colours: 1 = black 2 = red 3 = white 5 = orange Functions Functions when operated on -Bus Connection on the -Bus Network topology + A) Connection of active sensors A) more actuators and sensors (max.8) Connection of external switching contact here are no restrictions for the network topology (star, ring, tree or mixed forms are permitted). Supply and communication in one and the same 3-wire cable no shielding or twisting necessary no terminating resistors required + p + A) A) A) more actuators and sensors (max.8) Supply AC/DC 24 V Output signal DC 0...10 V (max. DC 0...32 V) (Resolution 30 mv A) more actuators and sensors (max.8) Switching current 16 ma @ 24 V Start point of the operating range must be parameterised on the actuator as V Connection of passive sensors + A) Ni1000 28...+98 C 850...1600 Ω 2) P1000 35...+155 C 850...1600 Ω 2) NC 10...+160 C 1) 200 Ω...60 kω 2) A) more actuators and sensors (max.8) 1) Depending on the type 2) Resolution 1 Ohm www.belimo.com SVK24A--PC en-gb 2016-04-01 subject to changes 5

SVK24A--PC Functions Functions with basic values (conventional mode) Override control with AC 24 V with relay contacts Override control with AC 24 V with rotary switch a b c (DC 0...10 V) 0% ZS 50% 100% (DC 0...10 V) 0% ZS 50% a b c 100% Remote control 0...100% with positioner SG.. Minimum limit with positioner SG.. Z 1 2 3 4 SGA24 SGF24 SGE24 Z 1 2 3 4 SGA24 SGF24 SGE24 10 [V] (DC 0...10 V) min 0 [%] 0 100 Follow-up control (position-dependent) Control with 4...20 ma via external resistor DC (0)2 10 V DC 2 10 V 500 Ω ( ) (+) 4 20 ma DC 2 10 V Functional check Caution: he operating range must be set to DC 2...10 V. he 500 Ω resistor converts the 4...20 ma current signal to a voltage signal DC 2...10 V Procedure 1. Apply 24 V to connection 1 and 2 2. Disconnect connection 3: - with upwards direction of motion: closing point at top - with downwards direction of motion: closing point at bottom 3. Short circuit connections 2 and 3: - Actuator runs in the opposite direction 6 SVK24A--PC en-gb 2016-04-01 subject to changes www.belimo.com

SVK24A--PC Functions Functions for actuators with specific parameters (Parametrisation with PC-ool necessary) Override control and limiting with AC 24 V with relay contacts Override control and limiting with AC 24 V with rotary switch a b c d e (DC 0...10 V) Close 1) MIN ZS MAX Open (DC 0...10 V) Close 1) MIN ZS MAX Open a b c d e 1) Caution: his function is only guaranteed if the start point of the operating range is defined as min. V. Control Open/Close Control 3-point a b a b www.belimo.com SVK24A--PC en-gb 2016-04-01 subject to changes 7

SVK24A--PC Operating controls and indicators 1 Direction of stroke switch Switch over: Direction of stroke changes 2 Cover, POP button 3 POP button 4 Scale for manual adjustment 5 Position for adjustment with tool 10 6 Service plug For connecting the parameterisation and service tools 7 Gear disengagement button Press button: Gear disengaged, motor stops, manual override possible Release button: Gear engaged, standard mode 7 2 5 1 POP 3 4 ool 8 Status Address Adaption Power 9 LED displays 8 yellow 9 green Meaning / function Off On Operation OK Off Flashing POP function active On Off Pre-charging time SuperCap, Fault SuperCap or wiring error in supply Off Off Not in operation On On Adaptation process active Flickering On Communication active 6 8 Push-button (LED yellow) Press button: Confirmation of addressing 9 Push-button (LED green) Press button riggers stroke adaptation, followed by standard mode 10 Manual override Clockwise: Counterclockwise: Actuator spindle extends Actuator spindle retracts Setting emergency setting position (POP) OOL OOL OOL OOL POP % 0...100 POP > PC-ool 8 SVK24A--PC en-gb 2016-04-01 subject to changes www.belimo.com

SVK24A--PC Service! Notes he actuator can be parameterised by PC-ool and ZH AP via the service socket. Service ools connection ZH AP connection AC 24 V DC 24 V SB i esc OK PC-ool connection AC 24 V DC 24 V SB i esc OK BELIMO PC-ool SB Dimensions [mm] Dimensional drawings 45 244 98 177 167 www.belimo.com SVK24A--PC en-gb 2016-04-01 subject to changes 9