GE Multilin 369 LV & MV Mtr Management Relay Specificatins The mtr management relay shall prvide primary prtectin and management t medium vltage mtrs. The relay shall be equipped with the fllwing prtectin functins. Mtr Thermal Overlad Mdel (49) Include 15 standard verlad curves, a custm curve feature, and a curve specifically designed fr the starting f high inertia lads, when the acceleratin time exceeds the safe stall time The statr prtective thermal mdel shall cmbine inputs frm phase and unbalance currents, and RTD winding feedback. This will then cause the mdel t becme dynamic in nature in rder t fllw the lading and temperature f the mtr Mtr cling time cnstants Rtr prtectin during stall and acceleratin. T achieve this a speed switch input shall be available The relay shall detect grund faults r earth leakage currents as lw as 0.25 A using a 50:0.025 Grund CT Use phase and unbalance current heating t calculate mtr thermal capacity during starting and running states Settable mtr stpped and mtr running cling time cnstants Phase and residual vercurrent elements (50P/50G) Unbalance / single phase biasing (46) Lad-lss (undercurrent) (37) Mechanical jam (48) Mtr stall prtectin Re-start blcking timer t be used as a start permissive t ensure the mtr had slwed t a safe speed r t a cmplete stp, befre it can be re-started again
Antibackspin prtectin ensuring that the mtr can nly be re-started when it has slwed t within acceptable limits. A backspin detectin vltage input shall be prvided t measure frequency. If the measured frequency is belw a prgrammed minimum threshld, the backspin start inhibit shall be remved Starts-per-hur (66) Minimum-time-between-starts The relay shall prvide an ptin fr vltage transfrmer inputs, which shall be used t prvide vervltage (59), undervltage (27), vltage phase reversal (47), verfrequency (81O) and underfrequency (81U) functins The relay shall be equipped with an Undervltage Aut-restart functin that will restart the mtr after an undervltage trip caused by a mmentary lss f pwer 12 RTD inputs with assciated ver-temperature prtectin functins including alarm and trip settings, with crrespnding settable time delays, and assciated utputs. The fllwing additinal functinality shall be prvided, assciated t RTDs: Able t cnfigure each f the twelve RTDs as Nne r any ne f fur applicatin types: Statr, Bearing, Ambient, r Other RTD type shall be selectable between fur different RTD types: 100 Ohm Platinum, 120 Ohm Nickel, 100 Ohm Nickel, r 10 Ohm Cpper The mtr relay shall incrprate the RTD inputs t supprt the fllwing: Thermal verlad mdel biasing Temperature alarms and trips (49/38) RTD pen- r shrt-circuit alarm The mtr relay shall include trip vting fr extra reliability in the event f RTD malfunctin. If enabled, a secnd RTD must als exceed the trip temperature f the RTD being checked befre a trip is issued Prvisins shall be included t allw the RTDs t be identified by name The relay shall be able t mnitr up t fur remte RTD mdules, each with 12 RTD inputs, with assciated ver-temperature prtectin functins including alarm and trip settings, settable time delays, and assciated utputs. Additinal functinality shall be identical t that prvided by the n bard RTDs as describer abve
Prtectin functins assciated t Pwer, which include alarm and trip settings, with crrespnding settable time delays, and assciated utputs: Pwer Factr (55) Reactive Pwer Under Pwer (37) Reverse Pwer The relay shall perate with either wye-cnnected (fur wire) r pen -delta-cnnected (three wire) ptential transfrmers, and three phase, fur wire cnnected current transfrmers. The relay shall include prvisins t allw its use in cnjunctin with variable frequency drives. All f the elements shall functin prperly with the exceptins f vltage and pwer elements. The mtr prtectin relay shall have five (5) utput relay s, and six (6) digital inputs. The utput relays shall be as fllws: Trip Relay, Alarm Relay, tw auxiliary relays, and a service relay. Five f the six digital inputs shall have the fllwing pre-assigned default functins: Access Switch t allw changing f any setpint values frm the face plate Differential Switch t accept inputs frm an external differential prtectin relay Emergency Restart t allw a ht mtr t be restarted External Reset, t allw resetting trips r latched alarms Speed Switch t accept a trip signal frm a speed mnitring device Althugh assigned default functins, these five inputs, alng with the ne remaining spare input, can be user prgrammable t alternate functins. The functin that the input is used fr may be chsen frm the fllwing list f functins: Starter Status cnfigured fr either an 'a' r 'b' auxiliary cntact, Wavefrm Capture, Digital Cunter, DeviceNet Cntrl, and General Switch functins in which an alarm and/r trip may then be cnfigured fr that input. The relay shall be able t mnitr the digital inputs f up t fur remte RTD mdules. The relay shall allw mtr starting and stpping via any f the cmmunicatin prts. When a Stp cmmand is sent the TRIP relay shall be activated fr 1 secnd t cmplete stp sequence. When a Start cmmand is issued, an utput relay shall be assigned fr starting cntrl, which shall be activated fr 1 secnd t cmplete the start sequence. The Serial Cmmunicatin Cntrl functin shall als be used t reset the relay and activate a wavefrm capture.
The relay shall be capable f prtecting the mtr during the entire starting prcess in Reduce Vltage starting applicatins. The relay shall prvide cmplete mnitring and metering functins. These shall include: Current: Phasrs, RMS Values f per Phase, Average, Mtr Lad, Current Unbalance, Unbalance Biased Mtr Lad, Grund, Differential Currents Vltage: Phasrs, RMS Values f Phase-Phase and Phase-Neutral, Average Vltage Frequency Temperature f each RTD Inputs Mtr Speed (RPM) Pwer: Pwer Factr, Three phase Real (kw, hp), Reactive (kvar), Apparent (kva) Pwer Energy: Watt-hurs, Var-hurs Demand: Rlling Demand methd, time interval, prgrammed t 5 t 90 min in steps f 1 minute An event recrder with a recrd f the last 512 events, time tagged with a reslutin f 10 ms The wavefrm capture feature is similar t a transient/fault recrder. The relay shall strage f up t 16 cycles f data, captured fr Phase A, B, and C currents (Ia, Ib, and Ic), Grund currents (Ig), Phase A-N, B-N, and C-N vltages (Van, Vbn, and Vcn) fr wye cnnectins, Phase A-B and B-C (Vab and Vbc) fr pen-delta cnnectins The relay shall be able t prvide data in the frm f trending r data lgger, sampling and recrding up t eight actual values at an interval defined by the user. Several parameters shall be trended and graphed at sampling perids ranging frm 1 secnd up t 1 hur. The parameters which can be trended by the Setup sftware shall be: Phase Currents A, B, and C, and Average Phase Current, Mtr Lad, Current Unbalance, Grund Current, System Frequency, Vltages Vab, Vbc, Vca Van, Vbn & Vcn, Pwer Factr, Real (kw r hp) Reactive (kvar), and Apparent (kva) Pwer, Psitive Watt-hurs, Psitive and Negative Var-hurs, Httest Statr RTD, Thermal Capacity Used, RTDs 1 thrugh 12 temperature, Remte RTDs 1 thrugh 12 The relay shall include fur transducer utputs with a settable DC utput range f 0 t 20 ma, 4 t 20 ma r 0 t 1 ma, which may be assigned t any measured parameter. The range f these utputs shall be scalable The relay shall be able t mnitr up t fur remte RTD mdules, each with fur Analgue Outputs, with settable DC utput range and functinality identical t the n bard Analgue Outputs. The remte RTD Mdule Analgue Outputs shall be assigned t any temperature measured by the mdule RTDs
Latest trip reprt cntaining date and time, cause, phase, grund, mtr lad, current unbalance, Line-Line and Line-grund vltages, httest statr RTD, system frequency, real, reactive and apparent pwer, and pwer factr Alarm status infrmatin reflecting Alarm Name as prgrammed and status Start blck timer status including verlad lckut, start inhibit, starts per hur, time between starts, and restart blck The relay shall prvide cmprehensive statistical data and learned infrmatin, as fllws: The Mtr Learned Data must capture up t 250 sets f mtr starting values, averaged ver up t five mtr starts. The mtr learned data must be graphically represented thrugh a PDF reprt. The fllwing is the learned data captured and stred and can als be printed and filed: Learned Acceleratin Time Learned Starting Time Learned Starting Capacity Learned Running and Cl Time Cnstant Learned Stpped Cl Time Cnstant Learned Unbalance K Factr Learned Average Mtr Lad Learned Run Time After Start Date f last learned Date average calculatin r last recrd The relay must prvide a high-speed data lgger t capture analg signals during mtr starting cnditins. A ttal f six individual lgs (1 baseline and rlling buffer f last 5 starts), each 30 secnds lng are available t recrd key analg quantities at a sampling rate f 200 millisecnds The fllwing infrmatin must be captured: True RMS Phase A, B and C Currents Phase Current Unbalance True RMS Grund Current True Phase t Phase r Phase t Grund Vltages Thermal Capacity Accumulated (%) System Frequency Breaker / Cntactr Status
Preventive Maintenance Infrmatin: The relay shall keep cunt f number f trips by type Number f mtr starts r start attempts Number f Emergency Restarts Mtr running hurs Autrestart start attempts Time t autrestart Digital input cunters The relay shall have starter failure detectin feature which shall prduce an alarm in the event that the mtr relay des nt detect a starter/breaker pen cnditin after a trip is initiated The relay shall have the capability t display up t 5 user prgrammable text messages Under nrmal cnditins, if n frnt panel activity is detected within a settable time, the screen shall sequentially display up t 30 default messages. Any actual value r setpint message shall be selectable fr default display Security / Change Histry Reprt The relay must cmply with NERC CIP security reprting requirements and prvide traceability. The relay must maintain a histry f the last changes made t the cnfiguratin, including mdificatins t settings and firmware upgrades. A summary histry f the last ten sessins and a list the last 100 specific setting changes made must be recrded and stred in nn-vlatile memry. The reprt must be available t be saved and printed in PDF frmat. Security Setting Reprts must the fllwing infrmatin: Dates and times f security setting changes MAC address f user making setting changes Listing f mdified changes Hw setting changes were made Keypad, Frnt serial prt, Ethernet User interfaces shall include: A 40 character LCD display, and navigatin keys Indicatr LEDs n the frnt panel which shall prvide a quick visual indicatin f status
A frnt panel RS232 serial prt that shall prvide easy cmputer access. The cmmunicatins prtcl shall be Mdbus RTU Tw rear RS485 prts. The cmmunicatins prtcl shall be Mdbus RTU An RS485 cmmunicatins prt shall be prvided specifically designed t cmmunicate t Remte RTD mdules. The relay shall be capable f cmmunicating with up t fur Remte RTD mdules. Access t the remte RTD mdules fr setpints and actual values shall be achieved thrugh the mtr relay via any f the available cmmunicatin prts. The remte RTD cmmunicatin prt standard media shall be a three terminal prt. Optinal media shall be fiber ptic, with a maximum baud rate f 19.2 kbs, fiber sizes 50/125, 62.5/125, 100/140, and 200 µm, and emitter fiber type 820 nm LED, multimde An ptinal RJ45 Ethernet prt shall be prvided t allw 10BaseT Ethernet cnnectivity t Lcal r Wide Area Netwrks. The cmmunicatins prtcl shall be Mdbus TCP An ptinal terminal prt shall be prvided t allw DeviceNet r Prfibus cnnectivity t Lcal DeviceNet r Prfibus Netwrks The relay shall be capable f being set by Windws-based, Easy t use, Setup graphical terminal interface T make the data acquisitin mre efficient, the mtr relay shall prvide a User Definable Memry Map, which shall allw a remte cmputer t read up t 125 nncnsecutive data registers by using ne Mdbus packet. The User Definable Memry Map shall be prgrammed t jin any memry map address t ne in the blck f cnsecutive User Map lcatins, s that they can be accessed by means f these cnsecutive lcatins. The User Definable area shall have tw sectins: A Register Index area cntaining 125 Actual Values r Setpints registers A Register area cntaining the data lcated at the addresses in the Register Index A testing feature shall be included t allw testing analgue utputs and relays, withut the need fr external vltage and current inputs. The relay must be capable f being prgrammed thrugh a windws based sftware prgram that is capable f the fllwing:
1. The sftware prgram will perate in the fllwing fashin: a. Request system and mtr nameplate data frm user thrugh display screens b. Generate cautinary ntes based n inputted infrmatin c. Generate settings file d. Review settings with user with the ptin t disable any cnfigured settings that are nt required e. Prvide PDF reprt utlining the settings that have been generated, as well as any cautinary ntes required f. Reprt and Settings file t be saved in user-selectable lcatin 2. The fllwing system and prtectin settings will be generated based n inputted infrmatin: a. All CT, VT and Pwer System settings b. All Thermal Mdel settings including i. Shrt Circuit ii. Mechanical Jam iii. Unbalance iv. Undercurrent v. Grund Fault c. All Mtr Start / Inhibit prtectins d. Lcal RTD cnfiguratin, alarming and tripping e. Under / Over Vltage f. Under / Over frequency g. Phase Reversal h. Lcal Digital input fr 52A / B cntact i. All ther settings will have default values 3. Include Typical Wiring Diagram based n CT / VT type 4. Prvide a summary f all enabled settings in a PDF frmat that can be saved r printed Mtr Health Reprt The Mtr Health Reprt included with the relay will prvide a detailed histry f the peratin and perfrmance f the assciated mtr in bth graphical and data frmat. The fllwing infrmatin will be prvided in the Mtr Health Reprt. The reprt can either be saved t a lcatin in a sft cpy r be printed in PDF frmat.
The reprt shall be divided int seven categries and prvide the fllwing infrmatin: Device Summary Requested Perid Reprt Created By Mtr Name Prtectin Device Firmware Versin Mtr FLA Rated Vltage Phase Rtatin System Frequency Mtr Running Time Status Overview Prvide histrical learned date f the fllwing Acceleratin Time Starting Current Starting Capacity Mtr Lad Run Time After Start Trip Summary Overlad / Thermal Current Vltage / Frequency / Pwer Miscellaneus Infrmatin shall be represented bth graphically and numerically Mtr Operating Histry The Mtr Operating Histry will prvide infrmatin extracted frm the Events Recrd Mtr Start / Running Manual Stp Cmmand Trip Cmmand Lckut Alarm Cnditins Emergency Restarts Infrmatin shall be represented bth graphically and numerically
Mtr Starting Learned Infrmatin Learned Data will be captured fr every mtr start 250 Learned Data Recrds will be stred in the relay Learned Acceleratin Time Learned Starting Current Learned Starting Capacity Learned Average Mtr Lad Learned Average Run Time After Start Infrmatin shall be represented bth graphically and numerically Mtr Start Data Lgger The Mtr Start Data Lgger cnsists f Baseline Recrd and 5 additinal recrds Each recrd shall cntain 6 channels f infrmatin Each channel shall cntain 150 samples, sampled at 200ms intervals fr a ttal f 30 secnds Infrmatin t be included in the Mtr Start Data Lgger: Average Current Average Current Unbalance in Percent Grund Current Average Vltage Thermal Capacity Used Frequency Breaker Status Infrmatin shall be represented bth graphically and numerically Mtr Stpping / Tripping Events that are related t the stpping r tripping f the mtr Overlad Trip Mechanical Jam Shrt Circuit Under Pwer Current Unbalance RTD Temperature Grund Fault Under/Over Vltage Under/Over Frequency Manual/Remte Stp Infrmatin shall be represented bth graphically and numerically
T help extend prduct life, and t prtect the mtr prtectin relay frm hstile and harsh envirnments including misture, temperature variatins, salt spray, rganic attack (fungus), and aggressive chemicals and vaprs, the prduct manufacturer shall prvide ptinal harsh envirnment cnfrmal cating. The fllwing specificatins shall be met: Military specificatins MIL-I-46058-C, type AR, ER and UR UL recgnized accrding t specificatin UL746C/94 fr indr and utdr applicatins IEC68-2-60 Part 2, Methd 3, 1995 Mixed Flwing Gas Testing