NOVEL METHOD FOR ON-SITE TESTING AND DIAGNOSIS OF TRANSMISSION CABELS UP TO 250KV

Similar documents
INSULATION DIAGNOSIS OF HIGH VOLTAGE POWER CABLES

Aspects of PD interpretation in HV power cables. by Edward Gulski, Piotr Cichecki, Rogier Jongen

Long lengths transmission power cables on-site testing up to 500 kv by damped AC voltages

USING DAMPED AC VOLTAGES

SENSITIVITY ASPECTS OF ON-LINE PD DIAGNOSIS OF MV POWER CABLES

Testing and PD Diagnosis of MV Cable Systems with DAC Voltage Educational Session May St Pete Beach, Fl

Practical aspects of PD localization for long length Power Cables

Investigations on a Combined Resonance/VLF HV Test System Partial Discharge (PD) characteristics at VLF and DAC voltages

OFFLINE PD DIAGNOSTICS USING SEVERAL EXCITATION VOLTAGES

Statistical Characteristics of Partial Discharge Caused by Typical Defects in Cable Joint under Oscillating Voltage

OPTIMIZATION OF ON-SITE PD MEASUREMENTS AND EVALUATION OF DIAGNOSTIC PARAMETERS FOR ASSESSING CONDITION OF DISTRIBUTION CABLE SYSTEM ELPIS J SINAMBELA

Kurzfassung. Abstract. 1 Introduction

Partial discharge diagnostics on very long and branched cable circuits

Partial Discharge Measurement and Monitoring on High Voltage XLPE Cables

HV AC TESTING OF SUPER-LONG CABLES

The University of New South Wales. School of Electrical Engineering and Telecommunications. High Voltage Systems ELEC9712. Appendix Partial Discharge

IN HOUSE CALIBRATION OF PD DETECTOR SYSTEM FOR FIELD TEST RESULT RELIABILITY

High Voltage Diagnostics Sarl 4, Rue de Lac CH 1897 Le Bouveret Switzerland

PD Testing Considerations for MV Plant Cables

Why partial discharge testing makes good sense

EFFECT OF INTEGRATION ERROR ON PARTIAL DISCHARGE MEASUREMENTS ON CAST RESIN TRANSFORMERS. C. Ceretta, R. Gobbo, G. Pesavento

NEW MV CABLE ACCESSORY WITH EMBEDDED SENSOR TO CHECK PARTIAL DISCHARGE ACTIVITY

OMICRON Seminar on Partial Discharge Diagnostics on HV Assets. January 30, 2018 Beirut, Lebanon

BEST PRACTICES FOR OFFLINE DIAGNOSIS OF MV CABLES

Condition Assessment of High Voltage Insulation in Power System Equipment. R.E. James and Q. Su. The Institution of Engineering and Technology

Advanced Test Equipment Rentals ATEC (2832) CP RC. Resonance circuit for GIS testing

International Journal of Advance Engineering and Research Development. Comparison of Partial Discharge Detection Techniques of Transformer

Reprint E Two Years of Experience with a Mobile Resonant Test System for Testing of Installed Medium- and High Voltage Power Cables

CVVOZE Power Laboratories (CVVOZEPowerLab)

Africa Utility Week Focus Day Substation Condition Monitoring Benefits of Ultrasound

INVESTIGATION ON THE TECHNOLOGIES FOR DEFECT LOCALIZATION AND CHARACTERIZATION ON MEDIUM VOLTAGE UNDERGROUND LINES

Simultaneous Partial Discharge and Tan Delta Measurements: New Technology in Cable Diagnostics

Testing 320 kv HVDC XLPE Cable System

MEDIUM & HIGH VOLTAGE

Basics of Partial Discharge. Prepared for 2015 Phenix RSM Meeting January 2015

Cable testing and diagnostics

Abstract. 1 Introduction

Partial Discharge Patterns in High Voltage Insulation

Investigation of PD Detection on XLPE Cables

Partial Discharge Measurements on 110kV Current Transformers. Case Study. Results

Coherence and time-frequency analysis of impulse voltage and current measurements

Modeling insulation in high-voltage substations

PHG 70 TD PD / PHG 80 TD PD

VLF. DAC tandelta. Partial Discharge. Experience the world of Megger electrical testing

Online Localisation of Partial Discharge Using Pulse Propagation Parameters in Medium Voltage Cable Network

ON-LINE PARTIAL DISCHARGE DETECTION ON TRANSFORMERS

IMPORTANCE OF ACCURATE MEASUREMENTS DURING THE LIFE CYCLE OF UTILITIES

Electric Stresses on Surge Arrester Insulation under Standard and

Diagnostic testing of cast resin transformers

PERMANENT ON-LINE MONITORING OF MV POWER CABLES BASED ON PARTIAL DISCHARGE DETECTION AND LOCALISATION AN UPDATE

IEEE (2016) (2016). IEEE.,

Field Experiences. Partial Discharge Diagnosis on MV Cables. Philipp Legler. XVI. Szigetelésdiagnosztikai Konferencia (

GENERATOR TESTING APPLICATION GUIDE. reliable. precision.

Dielectric response and partial discharge measurements on stator insulation at varied low frequency. Nathaniel Taylor

THE POWER OF LIFE. WinTech Partial Discharge based Predictive Intelligence of insulation system to eliminate power failure risk.

The Application of Partial Discharge Measurement and Location on CGIS

SMART CABLE GUARD A TOOL FOR ON-LINE MONITORING AND LOCATION OF PD S AND FAULTS IN MV CABLES ITS APPLICATION AND BUSINESS CASE

Cable fault location in power cables. Systematics for cable testing, diagnosis and cable fault location

INFLUENCE OF VOLTAGE WAVEFORMS ON PARTIAL DISCHARGES DEVELOPED IN POWER CABLE INSULATION

Doble Solutions for Partial Discharge. Greg Topjian Solutions Manager

On-Site Partial Discharge Monitoring using the differential LEMKE PROBE LDP-5 and its accessories

Specialists in HV and MV test and diagnostics. Testing in Substations

Design and Construction of a150kv/300a/1µs Blumlein Pulser

For the electronic measurement of current: DC, AC, pulsed..., with galvanic separation between the primary and the secondary circuit.

For the electronic measurement of current: DC, AC, pulsed..., with galvanic separation between the primary and the secondary circuit.

For the electronic measurement of current: DC, AC, pulsed..., with galvanic separation between the primary and the secondary circuit.

A6.6 9 th International Conference on Insulated Power Cables A6.6

The importance of partial discharge testing throughout the development and operation of power transformers

On-line Partial Discharge Assessment and Monitoring of MV to EHV Cables

CITY SERIES. Compact, fully equipped cable fault location, test and diagnostic systems

Estimating the Impact of VLF Frequency on Effectiveness of VLF Withstand Diagnostics

H V T E S T S O L U T I O N S PA RT N E RS F O R H V & E M C

PD Diagnostic Applications and TechImp solutions

For the electronic measurement of current: DC, AC, pulsed..., with galvanic separation between the primary and the secondary circuit.

Electrical Power Engineering Group, School of Electronics and Computer Science, University of Southampton, Highfield, Southampton, SO17 1BJ, UK 2

Ref: HO 50-S/SP33, HO 100-S/SP33, HO 150-S/SP33, HO 200-S/SP33, HO 250-S/SP33

700 Series AC Dielectric Test Sets

TECHIMP Technologies & Services for Diagnostics and Monitoring of High Voltage Assets

For the electronic measurement of current: DC, AC, pulsed..., with galvanic separation between the primary circuit and the secondary circuit.

Transient Data Acquisition System, TAS 4-40 Potential-free measurement of fast rise pulses:

PARTIAL DISCHARGE LOCATION Selected Topics

EI HIGH VOLTAGE INSULATION TESTING POLICY

Sources of transient electromagnetic disturbance in medium voltage switchgear

= 1000 V. Voltage transducer DVC 1000-P V P N

IRIS POWER TGA-B. Periodic Online Partial Discharge Monitoring Instrument for Turbine Generators and Motors

Measurement and Analysis for Switchmode Power Design

ECP HV INSULATION TESTING

Partial Discharge Inception and Propagation Characteristics of Magnet Wire for Inverter-fed Motor under Surge Voltage Application

IRIS POWER PDTracII. Continuous On-line Partial Discharge Monitoring for Motors, Generators, Dry Type Transformers, and Air-Insulated Switchgear.

PD Monitoring of MV/HV Power Cables December 2016

700 Series AC Dielectric Test Sets

ECP HV INSULATION TESTING

NEW. The new Centrix 2.0 sets the standard for testing, diagnosis and fault location of power cables.

Insulation Test System

Fixed Series Compensation

BY JASON SOUCHAK, Megger

Test systems made by SebaKMT. Don t stress over tests! SebaKMT has the right answers: reliability, speed, economy.

High-Voltage Test and

PRODUCT PORTFOLIO TEST AND MEASURING SYSTEMS

For the electronic measurement of current: DC, AC, pulsed..., with galvanic separation between the primary and the secondary circuit.

Transcription:

NOVEL METHOD FOR ON-SITE TESTING AND DIAGNOSIS OF TRANSMISSION CABELS UP TO 250KV Paul P. SEITZ, Seitz Instruments AG, (Switzerland), pps@seitz-instruments.ch Ben QUAK, Seitz Instruments AG, (Switzerland), bq@seitz-instruments.ch Edward GULSKI, Delft University of Technology, (The Netherlands), e.gulski@tudelft.nl Johan J SMIT, Delft University of Technology, (The Netherlands), j.j.smit@tudelft.nl Piotr CICHECKI, Delft University of Technology, (The Netherlands), p.cichecki@tudelft.nl Frank de VRIES, NUON Tecno, (The Netherlands), frank.de.vries@nuon.com Frank PETZOLD, SebaKMT, (Germany), petzold.f@sebadyn.de ABSTRACT For complete on-site diagnosis of transmission power cables up to 220kV by partial discharge detection and dielectric losses measurement it is necessary to energize the disconnected cable system. One of the methods available for this purpose is based on applying damped AC voltages up to 250kV. In this paper, the use of modern technological solutions in power electronics and signal processing as well as in technical design and production methods will be discussed on the basis of ultra light system (300kg) which is able to test cables up to 20km lengths. KEYWORDS HV power cables, on-site energizing, DAC, partial discharges, dielectric losses INTRODUCTION Condition assessment of HV cables is one of the issues of asset management in power utility business. In particular, due to the importance of HV cables in the transmission network is the knowledge about the initial condition during after-laying as well as the actual condition of HV power cable sections during operation after several years of service of great importance. With regard to partial discharge (PD) processes and dielectric degradation processes in transmission power cables there is still a need for advanced, sensitive and economical attractive tools suitable for non-destructive PD diagnosis on-site: the after-laying testing as well as the service diagnosis [1, 2]. For complete on-site diagnosis of transmission power cables by PD detection and dielectric losses measurement it is necessary to energize the disconnected cable system. In order to decrease the capacitive power demands for energizing cables as compared to 50Hz test voltages, different energizing methods have been developed in the past. One of the methods available for this purpose is based on applying damped AC voltages [3, 4]. In particular, in the last 8 years [5, 6] the worldwide acceptance of this method has already demonstrated that in the case of power cables up to 40kV by means of advanced PD diagnosis the identification of highrisk cable circuits in the network can be achieved and implemented in utility asset management decision processes. In this contribution, based on 4 years [7] of utility experiences and laboratory investigations a novel method Figure 1: Examples of on-site testing and diagnosis of HV power cables: a) OWTS HV150 system testing at 23Hz damped AC voltage frequency a 12.4km long 66kV oil-filled cable, b) OWTS 250 system testing at 71Hz damped AC voltage frequency a 2km long oil-filled 150kV cable for diagnosis of PD and dielectric losses of transmission power cables using damped AC voltages up to 250kV will be presented. To generate on-site damped AC voltages up to

150kV peak respectively 250kV peak and to perform advanced diagnosis by meaningful PD parameters modular hardware/software solution has been developed (figure 1). In particular, by use of - modern solid-state technology and laser-control techniques (HV Solid-State Switch), Table 1: Maximum OWTS HV series Test voltage levels Network voltage OWTS HV 150 OWTS HV 250 [kv] x U 0 x U 0 50 3.6-66 2.7-110 1.6 2.7 132 1.4 2.3 150 1.2 2.0 220 0.8 1.4 240-1.2 330-0.9 - power electronics, digital signal processing (HV Solid- State Switch, HV source), - digital signal processing and filtering (PD detector), - wireless communication and embedded computer system (PD detector, Control unit, PD analyzer) novel system OWTS HV -series type 150 type 250 have been developed for on-site PD diagnosis of HV power cables up to 330kV (table 1). HV Power Cable 150kV HV Divider and PD analyser Unit 150 kv HV solidstate switch 150kV Inductor Unit L=7.1 H energizing methods using specific voltage shaped and frequencies have been introduced for PD diagnostics nowadays [4, 8, 9]. As shown in [9-11] due to several important characteristics such as 1. AC voltage type equivalence in PD inception processes for solid insulating materials, HV Source HV Solid- State Switch S Process Control Unit Data Storage PD Analysis Dielectric losses estimation Inductor L Test Object: Power Cable HV Divider PD Coupling Capacitor PD detector Figure 3: Schematic view of the damped AC circuit inclusive the partial discharge and dielectric losses measuring system. 2. non-destructiveness of voltage stress during the diagnosis, 3. real-time advanced analysis of diagnostic data, 4. sufficient immunity for on-site interferences and low level of system background noise, 5. IEC, IEEE standards conformity [2, 3, 4, 12, 13], 6. test cost efficiency based on investment and maintenance costs, transportability and operation of the method in different field circumstances, the use of partial discharges and dielectric losses diagnosis at damped AC voltages (DAC) has become important solution for on-site testing and diagnosis of HV power cables (figures 1-3). C c Process Control Unit Data Storage PD Analysis Dielectric losses estimation 150 kv HV Voltage Source Figure 2: Schematic structure of OWTSHV150 an on-site system for partial discharges and dielectric losses diagnosis for transmission power cables up to 150 kv; (weight 300kg) t[s] 10 1 150kV 120kV 90kV 60kV 30kV ON-SITE ENERGIZING OF HV POWER CABLES For the on-site detection of PD related defects in power cables, it is necessary to energize the disconnected cable sample for the ignition of the PD sources. The detection and measuring equipment is therefore directly connected to the cable conductors (or through the switchgear). In this way, the different phases of the cable circuit can be energized and the PD pulses can be coupled out. The capacitive power P = 2π f C cable U 2 test needed to stress on-site the cable insulation is determined by the test frequency f, the cable capacitance C cable and the test voltage U test. In order to decrease the capacitive power demands for energizing cables as compared to 50Hz test voltages, different 0.1 0 0.5 1 1.5 2 2.5 3 3.5 4 4.5 5 5.5 6 6.5 7 Figure 4: Charging time in function of power cable capacitance for different voltage levels. DAMPED AC VOLTAGE GENERATION For the generation of damped AC (DAC) voltages, the power demand is low due to the charging the cable capacitance (figure 4) with a current of 10mA and a continuously increasing DC voltage, after which the cable capacitance (represented as a capacitance C c ) is switched by S in series with large inductance L, resulting in an sinusoidal damped AC voltage form with a frequency between 20Hz and few

hundreds of Hz (figure 5). In particular, the cable sample is linearly charged with continuously increasing HV voltage, directly followed by a switching process and period of several sinusoidal AC cycles (figure 6). As a result, during Due to the low loss factor and design of the air-core, the resonant frequency is close to the range of power frequency of the service voltage: 20Hz to 300Hz. The quality factor Q C of the resonant circuit, which is damped AC frequency f 180 160 140 120 80 60 40 20 0 0 1 2 3 4 5 6 7 8 9 10 11 12 13 HV power cable capacitance [μf] (a) damped AC frequency f 200 180 160 140 120 80 60 40 20 0 0 0.2 0.4 0.6 0.8 1 1.2 1.4 1.6 1.8 2 HV power cable capacitance [μf] (b) Figure 5: Dependence of the frequency of damped AC test voltage on the power cable capacitance. the charging time no steady state DC conditions occur in the cable insulation [14]. As soon as the cable is charged, the HV supply is disconnected and a specially designed HV solid-state switch (150kV type or 250kV type) connects the cable sample C c to an air-core inductor L =7.1H in a closure time of less than 1μs. In this way, and LC loop is created and an oscillating voltage wave is applied to test the sample. The test frequency of the oscillating voltage wave is approximately the resonant frequency of the circuit: 1 f = 2π L C This means that the test frequency of the applied DAC voltage is dependent on the cable capacitance, see figure 5. The HV power cable capacitance varies due to parameters like the cross-section of the conductor and the thickness and the type of the insulation. In table 2 examples Table 2: Examples of the typical damped AC voltage frequencies in for different lengths of two typical 150kV power cables Length XLPE (C=154pF/m) Oil filled (C=373pF/m) [km] 0.25 300 194 0.5 213 137 1 151 97 2 107 69 4 76 49 8 53 34 16 38 24 20 34 22 are shown for different types of HV cables and cable length and the damped AC frequencies to be generated using system as shown in figure 2). Figure 6: Example of sinusoidal damped AC voltages as generated to energize at kv a capacitive load of 0.5μF and the measured PD pattern: a) full AC wave of 86Hz b) single AC cycle of 12ms 00 0 10 1 10 30 50 70 90 110 130 150 Damped AC Voltage [kv] Figure 7: Maximum power cable capacitance in function of the applied damped AC test voltage for max current of 300A. responsible for the attenuation of the oscillations, can be expressed by: Q C = (L / ( C * R 2 A ) Here is R A the equivalent circuit resistance. The quality factor Q of the resonant circuit remains high depending upon cable (30 to more than ), as a result of the relative low dissipation factor of power cables. A slowly decaying sinusoidal waveform (decay time up to 0.3 second) is applied as test voltage to energies the cable sample. The maximum power cable capacitance which can be tested at DAC stresses using OWTS HV system can be calculated in dependence of maximum voltage applied and the AC current in the resonant circuit. (figure 7): 300A

Cmax = I V 2 L - Due to the fact that the maximum short-duration current as specified for the solid-state switch is in the range of 10 ka the accepted max current in the test circuit is determined by the system earthing of the test circuit and set to hundreds of Amp s (figure 6). It follows from this figure that at 150kV test voltages e.g. by circuit current of 300A the max capacitive load will be in the range of 28μF, which theoretically may represent a HV cable length of 76km of oil filled cable with e.g. capacitance per unit length 373pF/m). HARDWARE SYSTEM Based on the OWSTHV150 system the hardware and software solutions will be discussed below (figure 8). With regard to OWTS 250 kv system the technical information is given in [7]. In the table 3 the basic parameters are given. Table 3: Technical parameters of OWTSHV150 system Max. DAC output voltage 150 kv eff / 106kV peak DAC frequency range 20 Hz 500 Hz Test object capacitance range 0,025 µf... 13 µf HV charging current 10 ma PD measuring range 1 pc... nc PD detection acc. to IEC 60270 Bandwidth for PD-localization 150 khz... 45 MHz Dissipation factor 0,1 %... 10 % Power supply 115/230 V 50 / 60 Hz Weight app. 300 kg 150 kv HV Source: to load the power cable capacitance 150kV HVDC voltage supply is used with a circuit effective load current of 10mA. During charging the test object the linear and continuously increasing HV voltage is controlled by the computer. In figure 4 the charging time in function of the load capacities is shown. The switching discharge current of the power supply are limited by 15kΏ series resistor to max. 16A. 150 kv HV solid-state switch: The function of the 150kV switch is to establish a series resonance circuit between charge HV power cable capacitance and the air inductor L. As a result sinusoidal damped AC voltages may occur in the cable sample. The switch is permanently installed on the HV power supply. 150kV Inductor Unit: the system inductor consists of three in series connected air coils with a total inductance of 7.1H. To make it sure that the damping of the voltage waves is mainly depending on the test object losses the inductor is air core type. Also the epoxy insulation of the windings provides PD freedom of this part. HV Divider / PD coupling capacitor: to measure the damped AC voltages and to couple PD signals a PD free AC/DC divider C= 1nF/R= 800 MΏ is integrated in the unit costing the PD detection system. PD detection system: to detect PD signals a coupling device is connected to a PD-free coupling capacitor 1nF. The signals as detected in this way are process by digital PD detector. In particular this embedded system controlled by the PD Analyser Control Unit consists of IEC60270 conform Figure 8: OWTS HV 150 System for on-site diagnosis of HV power cable circuits. signal processing and display in [pc] and to provide HF signals for localisation purposes wideband signal amplification and processing is used. PD Analyser Control Unit: Using special User interface software installed on a laptop the HV generation process, data measurement process, data storage and analysis are possible. Moreover, this unit communicates with PD detection system by wireless or optical link. SOFTWARE SYSTEM The operation of the hardware system as described in previous section is supported by software concept as shown in figure 9. It follows from this figure that the whole on-site process of testing and diagnostic data gathering is divided into four steps. Cable System Definition: for practical reasons, a cable section may be constructed from multiple parts of cable, which are connected to each other with cable joints. Moreover such relevant information as the voltage ratting, insulation type, type and the position of the accessories are used to identify particular test, figure 10. Test Circuit Calibration: PD calibration of a measuring circuit means the reading adjustment of the PD detector. This calibration consists of a process where two calibrations procedures are automatically performed: - Calibration of the PD reading; in accordance to IEC60270 recommendation a PD pulse calibrator as defined in the IEC 60270 has to be used. - Calibration of the PD pulse propagation velocity reading: for this purpose the same as in 1 mentioned PD pulse calibrator can be used. If possible in particular cases, on the basis of additional reflections as observed on the calibration signals the location of individual joints can be done (figure 11). On-site Diagnosis of Power Cable: during application of HV voltage to the test object diagnostic parameters are measured (figure 12). The test voltage level selection and correct selected PD measuring range are important

(A) Cable System Definition 1) Input of cable section parameters: cables type, voltage rating, installation year, substation locations, cable length, type and position of accessories 2) Inspection information Date, time Inspector Comments (B) Test Circuit Calibration 1) PD measurement calibration: PD reading according to IEC 60270, PD pulse propagation parameters e.g. velocity, attenuation 2) Calibration data storage 3) Joint location detection On-site (C) On-site Diagnosis of Power Cable System 1) On-site test of a cable section Voltage application, e.g.. damped AC voltages (50Hz 500Hz) Measurement of PD levels and PD patterns in accordance to IEC 60270, Measurement of VHF PD pulses, dielectric losses measurement 2) Data storage On-site (D) Data Analysis and Report Generation 1) Analysis of measuring data e.g. comparison of PD inception voltages to U 0, PD-behavior in function of voltage up to 2xU 0, TDR analysis of VHF signals, Generation of PD mapping showing the PD locations in the cable section 2) Preparing of Diagnosis report Generation of standard headers/parameters Selection of graphs/data relevant for the test information Selection of diagnostic key parameters e.g. PDIV, PD@PDIV, PD@2U 0 for database protocol Figure 9: Integral concept of on-site testing and data gathering of HV power cables. parameters in obtaining correct measuring data. In particular, real-time registration of PD inception voltage (PDIV), PD extinction voltage (PDEV), PD-patterns is crucial for the execution of the on-site tests. For instance, during increase of the test voltage a sudden increase of PD activity may be used to identify and real-time localize serious discharging defects. Data Analysis; after during an on-site test diagnostic data have been collected analysis of data can be done. In particular with regard to PD data the location of discharge sites can be determined on the basis of VHF records. As a result, PD mapping can be obtained shown on the power cable the PD levels and PD concentration in function of the applied test voltages (figure 13). This information and all other data [15] can be used to asses the condition status of a particular HV cable system. CONCLUSIONS In this contribution novel solution for on-site testing and diagnosis of HV power cables up to 250kV is presented. In particular the following can be concluded. 1. Applying modern solid-states materials, power electronics technology and advanced signal processing allows developing compact system to generate on-site damped AC voltages up to 250kV. 2. PD and dielectric losses diagnosis at damped AC voltages can be used for non-destructive on-site testing of new and service aged HV power cables. 3. Due to digital signal processing and filtering as well as due to the fact that during application of damped AC voltages no active voltage sources are switched on, sensitive on-site PD detection (few pc s) can be achieved. 4. The complete solution for on-site testing and diagnosis complies with international standards and recommendations [2-4, 12, 13]. 5. Testing, measuring, analyzing and reporting processes are supported by embedded hardware/software solutions as well signal processing tolls like wavelets and digital filters. 6. Such characteristics like - AC sinusoidal and non-destructive stresses, Figure 10: Example of cable system definition.

- the available testing power (cables with length up to more than 20km) and voltages (up to 250kV), - efficiency in transportation (300kg 400kg), setting up and on-site test execution (1/2 hrs/phase), - diagnostic information as generated for HV power cables: PD detection localization, dielectric losses [15], may make to transmission and service companies as well as cable manufacturer this novel method as an very attractive option for on-site tests and diagnosis of new and service aged power cables. PD numeric display Actual DAC test voltage curve Actual PD pattern DAC test frequency Test object capacitance Dielectric losses numeric display DAC voltage display mode Default PD range Selected DAC test voltage Actual DAC test voltage V peak [kv] Power cable length Calibration status indicator Pulse markers REFERENCES User functions Power cable phase selection e.g. L1, L2, L3, All User functions System status Figure 12: Example of the user main screen during on-site testing. Calibration pulse display Figure 11: Example of test circuit PD calibration. [1] CIGRE WG 21.05, Diagnostic Methods for HV Paper Cables and Accessories, Electra No. 176, February 1998 [2] IEC 60840, Power Cables with extruded insulation and their accessories for ratted voltages above 30kV- Test methods and requirements [3] IEC 60060-3 High Voltage test techniques Part 3: Definitions and requirements for on-site testing [4] IEEE 400.3 Guide for PD Testing of Shielded Power Cable Systems in a Field Environment [5] Gulski E, J J Smit, P.N. Seitz, R.F.F. Koning, M. Turner; On-site partial discharge diagnostics of medium voltage power cables. Proceedings Jicable '99. 5th Figure 13: Example of PD mapping (PD activity versus cable length) as obtained during on-site tests using OWTSHV 150 system up to 2xU 0 for three phases (red, yellow, and blue) for a 6.4km long 50kV mass-insulated HV power cable. The X- axis represents the length of the power cable including the position of the individual joints (black dots) International Conference on Insulated Power Cables, France, Versailles, June 1999, p. 283-290 [6] Wester F.J., E Gulski, J J Smit; Electrical and acoustical PD on-site diagnostics of service aged medium voltage power cables. Proceedings Jicable '99. 5th International Conference on Insulated Power Cables, France, Versailles, June 1999 p. 896-901 [7] Gulski, E, Wester, FJ, Smit, JJ, Groot, ERS, Wester, Ph, Seitz, PN. Transmission power cables partial discharge detection at damped AC voltages. Proceedings JICABLE'03; 6 th International Conference on Insulated Power Cables France, Versailles, June 2003, p. 235-240 [8] Gulski, E, Lemke, E, Gamlin, M, Gockenbach, E, Hauschild, W, Pultrum, E. Experiences in partial discharge detection of distribution power cable systems. Cigre Electra, 2003, p 34-43. [9] F.J. Wester, Condition Assessment of Power Cables Using PD Diagnosis at Damped AC Voltages, ISBN 90-8559-019-1, 2004 [10] E. Gulski, F.J. Wester, J.J. Smit, P.N. Seitz and M. Turner, Advanced PD diagnostic of MV power cable system using oscillating wave test system, IEEE Electrical Insulation Magazine, 16, 2, 2000, p. 17-25 [11] E. Gulski, S. Meijer, J.J. Smit, F. de Vries, H. Geene, E.R.S. Groot, M. Boone, A. Bun, Condition assessment and AM decision support for transmission network components, Proceedings CIGRE 2006, Session, paper D1-109 [12] IEC 60270, Partial Discharges Measurements [13] IEC 885-3 Test methods for Partial Discharges measurements on lengths of extruded power cable [14] F.H. Kreuger, Industrial High DC Voltage, Delft University Press, 1995 [15] E. Gulski, J.J. Smit, P. Cichecki, P.P. Seitz, B. Quak, F. de Vries, F. Petzold, Insulation Diagnosis of HV Power Cables, Proceedings Jicable '07. 7th International Conference on Insulated Power Cables, France, Versailles, June 2007, paper 51