X International Symposium on Lightning Protection

Similar documents
SURGES TRANSFERRED TO THE LOW-VOLTAGE NETWORK VIA TRANSFORMER THE INFLUENCE OF THE LOAD CONNECTED TO THE SECONDARY

EVALUATION OF LIGHTNING-INDUCED VOLTAGES ON LOW-VOLTAGE DISTRIBUTION NETWORKS

Simulation and Analysis of Lightning on 345-kV Arrester Platform Ground-Leading Line Models

The relationship between operating maintenance and lightning overvoltage in distribution networks based on PSCAD/EMTDC

Lightning Performance Improvement of 115 kv and 24 kv Circuits by External Ground in MEA s Distribution System

High voltage engineering

PREVENTING FLASHOVER NEAR A SUBSTATION BY INSTALLING LINE SURGE ARRESTERS

Lightning current waves measured at short instrumented towers: The influence of sensor position

Simplified Approach to Calculate the Back Flashover Voltage of Shielded H.V. Transmission Line Towers

LIGHTNING OVERVOLTAGES AND THE QUALITY OF SUPPLY: A CASE STUDY OF A SUBSTATION

Effect of High Frequency Cable Attenuation on Lightning-Induced Overvoltages at Transformers

Lightning transient analysis in wind turbine blades

Modeling for the Calculation of Overvoltages Stressing the Electronic Equipment of High Voltage Substations due to Lightning

ABSTRACTS of SESSION 6

OVERVOLTAGE PROTECTION OF POLE MOUNTED DISTRIBUTION TRANSFORMERS

ARTICLE IN PRESS. Lightning effects in the vicinity of elevated structures. F.H. Silveira, S. Visacro

Utility System Lightning Protection

The impact of recent advances on lightning measurement and detection on the protection of transmission and distribution lines

Analysis of lightning performance of 132KV transmission line by application of surge arresters

EMC Philosophy applied to Design the Grounding Systems for Gas Insulation Switchgear (GIS) Indoor Substation

A Study on Lightning Overvoltage Characteristics of Grounding Systems in Underground Distribution Power Cables

A Contribution to the Direct Measurement of Lightning Currents by Means of Resistive Transducers

Parameters Affecting the Back Flashover across the Overhead Transmission Line Insulator Caused by Lightning

IMPROVEMENTS OF THE FACILITIES FOR LIGHTNING RESEARCH AT MORRO DO CACHIMBO STATION

Protection against unacceptable voltages in railway systems

Maximum Lightning Overvoltage along a Cable due to Shielding Failure

ATP SIMULATION OF FARADAY CAGE FOR THE ANALYSIS OF LIGHTNING SURGES

Effect of Shielded Distribution Cables on Lightning-Induced Overvoltages in a Distribution System

Analysis of MOV Surge Arrester Models by using Alternative Transient Program ATP/EMTP

Session Four: Practical Insulation Co-ordination for Lightning Induced Overvoltages

Lightning Flashover Rate of an Overhead Transmission Line Protected by Surge Arresters

Modeling of overhead transmission lines with line surge arresters for lightning overvoltages. Poland

Power Quality and Reliablity Centre

When surge arres t ers are installed close to a power transformer, overvoltage TRANSFORMER IN GRID ABSTRACT KEYWORDS

Simulation Study on Transient Performance of Lightning Over-voltage of Transmission Lines

Lightning Overvoltages on Low Voltage Circuit Caused by Ground Potential Rise

Lightning Protection of Distribution Substations by Using Metal Oxide Gapless Surge Arresters Connected in Parallel

Modeling insulation in high-voltage substations

Effective Elimination Factors to the Generated Lightning Flashover in High Voltage Transmission Network

INFLUENCE FACTORS ON THE TRANSMITTED OVERVOLTAGES FROM HIGH VOLTAGE TO LOW VOLTAGE NETWORKS

2000 Mathematics Subject Classification: 68Uxx/Subject Classification for Computer Science. 281, 242.2

Investigation on the Performance of Different Lightning Protection System Designs

University of Zagreb Faculty of Electrical Engineering and Computing

Lightning current field measurement on a transmission line, comparison with electromagnetic transient calculations

The Effect of Lightning Parameters on Induced Voltages Caused by Nearby Lightning on Overhead Distribution Conducting Line.

Cable Protection against Earth Potential Rise due to Lightning on a Nearby Tall Object

Fig.1. Railway signal system

TRIGGERED by energy transition towards sustainability,

Effect of Surge Arrester on Overhead Transmission Lines as Shield against Over Voltage

Lightning overvoltage and protection of power substations

Transmission of Electrical Energy

EXPERIMENTAL ISSUES OF OVERVOLTAGE COORDINATION

Analysis of current distribution among long-flashover arresters for 10 kv overhead line protection against direct lightning strikes

Simulation of Short Circuit and Lightning Transients on 110 kv Overhead and Cable Transmission Lines Using ATP-EMTP

Tab 2 Voltage Stresses Switching Transients

Simulation of Lightning Transients on 110 kv overhead-cable transmission line using ATP-EMTP

Lightning Risk Analysis of a Power Microgrid

10. DISTURBANCE VOLTAGE WITHSTAND CAPABILITY

Influence Of Lightning Strike Location On The Induced Voltage On a Nearby Overhead Line

ABSTRACT 1.0 INTRODUCTION LIST OF SYMBOLS

Lightning performance of a HV/MV substation

In order to minimise distribution (11 and 22 kv) feeder breaker

APPLICATION OF LONG FLASHOVER ARRESTERS FOR IMPROVEMENT OF LIGHTNING PROTECTION AND OPERATING VOLTAGE RELIABILITY OF DISTRIBUTION LINES

MODIFICATION OF THE ARRESTER ARRANGEMENT WHEN CONVERTING THE METHOD OF NEUTRAL TREATMENT

EXPERIMENTAL INVESTIGATION OF A TRANSIENT INDUCED VOLTAGE TO AN OVERHEAD CONTROL CABLE FROM A GROUNDING CIRCUIT

Evaluation of Distribution Line Spacers Located Near the Coast

ABSTRACT 1 INTRODUCTION

Study of Tower Grounding Resistance Effected Back Flashover to 500 kv Transmission Line in Thailand by using ATP/EMTP

Key-Words: - capacitive divider, high voltage, PSPICE, switching transients, high voltage measurements, atmospheric impulse voltages

CHOICE OF MV FEEDER BIL TO MAXIMIZE QOS AND MINIMIZE EQUIPMENT FAILURE

MARCEL A. ARAÚJO, ROGÉRIO A. FLAUZINO, OURESTE E. BATISTA, LUCAS A. MORAES

7P Series - Surge Protection Device (SPD) Features 7P P P

Energy Division. Bowthorpe LV/MV Surge Arresters

Lightning Overvoltage Performance of 110 kv Air-Insulated Substation

Calculation of Transient Overvoltages by using EMTP software in a 2-Phase 132KV GIS

HIGH VOLTAGE Insulation Coordination

Evaluation of Distribution Line Spacers through the Leakage Current Monitoring

OVERVOLTAGE MEASUREMENTS RELATED TO LIGHTNING- DETECTION SYSTEMS IN NORWAY

Towards an Accurate Modeling of Frequency-dependent Wind Farm Components under Transient Conditions

The Simulation Experiments on Impulse Characteristics of Tower Grounding Devices in Layered Soil

The line-lightning performance and mitigation studies of shielded steelstructure

Computation of Lightning Impulse Backflashover Outages Rates on High Voltage Transmission Lines

Electromagnetic Shielding Analysis of Buildings Under Power Lines Hit by Lightning

SCIENCE & TECHNOLOGY

Measurements for validation of high voltage underground cable modelling

Lightning Performance of Transmission Lines with Tall Sections

Accuracy of Lightning Surge Analysis of Tower Surge Response

EVALUATION OF DIFFERENT SOLUTIONS OF FAULTED PHASE EARTHING TECHNIQUE FOR AN EARTH FAULT CURRENT LIMITATION

The impact of distributed generation to the lightning protection of modern distribution lines

G. KOEPPL Koeppl Power Experts Switzerland

Pre location: Impulse-Current-Method (ICE)

Software Development for Direct Lightning Stroke Shielding of Substations

Neutral Reactor Optimization in order to Reduce Arc Extinction Time during Three-Phase Tripping

GIS Disconnector Switching Operation VFTO Study

Grounding Strategies for Solar PV Panels

Computer Based Model for Design Selection of Lightning Arrester for 132/33kV Substation

Triggered-Lightning Testing of the Protective System of a Residential Building: 2004 and 2005 Results

The Many Uses of Transmission Line Arresters

The Role of the Grounding System in Electronics Lightning Protection

Electric Stresses on Surge Arrester Insulation under Standard and

Transcription:

X International Symposium on Lightning Protection 9 th -13 th November, 2009 Curitiba, Brazil LIGHTNING SURGES TRANSFERRED TO THE SECONDARY OF DISTRIBUTION TRANSFORMERS DUE TO DIRECT STRIKES ON MV LINES, CONSIDERING DIFFERENT LV LINE CONFIGURATIONS Paulo F. Obase 1, Fabio Romero 1, Jorge M. Janiszewski 2, Alexandre Piantini 1, Acácio Silva Neto 1, Thais O. Carvalho 1, Alberto Araújo Filho 3 1 Institute of Electrotechnics and Energy / University of São Paulo, Brazil pfobase@iee.usp.br, fromero@iee.usp.br, piantini@iee.usp.br, acacio@iee.usp.br, thais@iee.usp.br 2 Polytechnic School / University of São Paulo, Brazil jorge@lcs.poli.usp.br 3 Electrical Distribution Company of State of Tocantins, Brazil alberto.araujo@redenergia.com Abstract - This paper aims at analyzing the behaviour of lightning surges transferred to low-voltage lines due to direct strikes on medium voltage networks considering two cases: open wire and twisted conductor low-voltage lines. The analysis considers the influences of parameters such as stroke current front time (t f), ground resistance (R g) and ground resistivity (ρ g) on the overvoltages transferred to low-voltage lines. The overvoltages are calculated employing the Alternative Transients Program (ATP) and the simulations refer to a typical rural distribution network of the Electrical Distribution Company of the State of Tocantins (CELTINS), Brazil. To evaluate the surges transferred to the low-voltage line, a high frequency model was developed for the distribution transformer. The results show that the use of twisted conductors configuration for the secondary circuit can reduce the magnitudes of the surges transferred through the distribution transformers. 1 INTRODUCTION Lightning discharges are responsible for a significant amount of unscheduled supply interruptions in electrical overhead lines, usually causing permanent damages to equipment such as distribution transformers. There are various ways by which lightning can disturb medium (MV) and low-voltage (LV) lines. Transients may be caused by direct strokes to the MV or LV line conductors, by lightning induced overvoltages, and by surges transferred through the distribution transformer. In recent years, several studies have been developed concerning transferred surges to LV networks [1-3]. In this work, the characteristics of surges transferred from the primary to the secondary side of distribution transformers due to direct strikes on MV lines are evaluated considering open wire and twisted conductor LV line configurations. In the simulations a typical rural distribution network of the feeder Nova Olinda Arapoema, of CELTINS, is adopted. CELTINS is the company responsible for electricity distribution in the State of Tocantins, in the North of Brazil. The feeder Nova Olinda Arapoema supplies power to a great number of consumers and was selected as the most critical with relation to transformer damages caused by lightning in the period 2006-2008. The rural distribution networks of CELTINS are located in regions characterized mainly by pastures with stunted vegetation so that the MV line conductors correspond, in general, to the highest points in these regions. Thus, the typical rural distribution network adopted in the simulations is highly exposed to lightning and the overvoltages in the primary and secondary circuits may be caused by direct and indirect strokes. However, a significant number of transient events in LV lines also can be due to surges transferred to the secondary circuit through distribution transformers [4, 5]. 2 SYSTEM DESCRIPTION AND MODELING For the calculations, initially a high frequency model of a single-phase transformer (15 kva, 20.25 kv / 440 V - 220 V) was developed according to the procedure described in [6]. The model gives good results for simulations considering the transformer both in the noload condition and for resistive and inductive loads. To illustrate the results obtained with the model, Fig. 1a presents a comparison between measured and calculated transferred voltage waveforms for the experimental set up depicted in Fig. 1b. The transformer model is presented in Fig. 2, which shows a good agreement between the two waveforms.

Simulations were then performed with the ATP (Alternative Transients Program) considering direct strokes to the MV line, and the surges transferred to the low-voltage line were calculated. The simulations refer to the Nova Olinda Arapoema line, whose schematic circuit is shown in Fig. 3 Fig. 2 High frequency distribution transformer (15 kva, single-phase) model. (a) Fig. 3 Nova Olinda Arapoema distribution line configuration. For the LV line, two configurations were taken into account: open wire and twisted conductors. (b) Fig. 1 Impulse response of the distribution (15 kva, single-phase) transformer with inductive load. a) measured and calculated waveforms b) experimental set up The lightning current was assumed to have triangular waveform with amplitude I = 45 ka, front time t f = 5.6 s, and time to zero of 150 s [7]. The MV line is matched at one end, whereas at the other end a singlephase transformer (T1), protected by surge arresters, is connected. The distance between the lightning strike point (identified as point A in Fig. 3) and the transformer T1 was assumed as 300 m and the LV line has a total length of 600 m. It is considered, also, that a consumer is connected to each pole of the LV line through a 30 m long service drop. Consumers were represented by 30 H inductances [8] connected between the phase conductors and the neutral. Line conductors were characterized by the following parameters:

MV line (Single Wire Earth Return Distribution System, SWER): diameter = 0.636 cm and lowfrequency resistance R DC = 1.3548 /km; LV line with open wire configuration: diameter = 0.741 cm and R DC = 0.8535 /km; LV line with twisted conductors configuration: diameter = 0.676 cm and R DC = 1.0 /km; 30 m long service drop (twisted conductors configuration): 2 conductor and neutral with diameter = 0.3568 cm and R DC = 3.08 /km. Fig. 4 shows the MV and LV conductor configurations adopted in the simulations, in which N is the neutral and Sa and Sb are LV phase conductors. Insulators were represented by switches that close when their CFO (critical impulse flashover voltage) is reached. Table 1 gives the CFO values adopted in the simulations. Insulator CFO (kv) MV line 156 LV line and neutral 20 Unless otherwise indicated, the ground resistance R g was assumed to be 60 (mean value obtained from measurements made in the area near the feeder) for poles that are grounded (transformer T1 and points P1 and P2, as indicated in Fig. 3). For poles without grounding, it is assumed that in the case of an insulator flashover (of either the MV or LV lines), the surge current will flow to ground through a resistance that has a value twice that of a grounded pole, according to [9]. The value of the ground resistance at the consumers entrance is R g = 60 Ω and the ground lead is 1 m long. The soil is assumed homogeneous, with resistivity ρ g = 2300.m (mean value obtained from measurements made in the area near the feeder). The inductance of all connection wires and accessories was assumed to be 1 H/m. Ionization effects of the soil were considered as described in [10]. In the simulations is assumed a typical VxI characteristic curve of the surge arresters connected at the distribution transformer HV terminals. 3 RESULTS AND DISCUSSION The overvoltages transferred to the secondary circuit resulting from direct strokes to the MV line were studied at the transformer (T1) LV terminals, taking into account the variations of some parameters. (a) Initially, a comparison can be made between the surges transferred through the transformer to the secondary line, in the cases of open wire and twisted conductor configurations. In the simulations, the lightning current was assumed to have a triangular waveform with the parameters shown in Fig. 3. The strike point A (Fig. 3) is 300 m from transformer T1. Fig. 5 presents the transferred surges at the LV transformer terminals (conductors Sa and Sb ) for both the twisted conductors and the open wire configurations shown in Fig. 4b. (b) Fig. 4 - MV and LV line configurations adopted in the simulations. a) MV line (b) LV line Table 1: CFO values adopted in the simulations. It can be observed that the voltage waveforms have a significantly smaller amplitude for the configuration with twisted conductors. This is due to the cable geometry, in which the phase and neutral conductors are closely assembled. This proximity of conductors results in a stronger electromagnetic coupling, causing a reduction in the voltage amplitudes. Owing to the effect of the transformer, the voltages on phases Sa and Sb present, at the very beginning, opposite polarities. Then, the current injected into the neutral (transformer terminal

X0) due to the operation of the primary arrester tends to equalize the phase-to-neutral voltages at the transformer terminals. This behaviour can be observed for both LV line configurations, but it is particularly evident in the case of the line with twisted conductors. In the following items, the influences of the stroke current front time, ground resistance, and ground resistivity upon the overvoltages in the transformer LV terminals are evaluated, taking into account both the twisted conductors and the open wire configurations. In order to evaluate the influence of the neutral ground resistance (R g ) on the transferred voltages, simulations were performed considering the values of 60 Ω (Fig. 5) and 20 Ω (Fig. 7). The difference between the magnitudes of the phase-to-neutral transferred voltages for the two line configurations increases with the ground resistance. The influence of the ground resistance on the transferred voltages is more significant in the case of the open wire line. In general, the greater the ground resistance, the greater the absolute value of the transferred voltage magnitude. For instance, the voltage peak values in the case of the open wire configuration are 5.05 kv and 10.8 kv for ground resistances of 20 Ω and 60 Ω, respectively. Fig. 5 Transferred voltages (phase-to-neutral) at the LV transformer terminals (twisted conductors and open wire configurations) - t f = 5.6 µs; Rg = 60 Ω; ρ g = 2300 Ω.m. 3.1 Stroke current front time Regarding the influence of the stroke current front time, the values of t f = 2.8 µs, t f = 5.6 µs were considered, with the remaining parameters unaltered. In general, the greater the current steepness, the greater the magnitude of the transferred voltage. Fig. 6 Transferred voltages (phase-to-neutral) at the transformer LV terminal Sa for twisted conductors and open wire configurations t f = 2.8 µs; Rg = 60 Ω; ρ g = 2300 Ω.m. Fig. 6 presents the overvoltages at the Sa" terminal of the transformer LV side for t f = 2.8 µs, considering the open wire and twisted conductors configurations. The influence of the current front time upon the transferred voltages can be observed by comparing Fig. 5 (t f = 5.6 µs) with Fig. 6 (t f = 2.8 µs). It can be seen that, for both current front times, the transferred voltages present lower magnitudes in the case of the line with twisted conductors. 3.2 Ground resistance

the first situation, while Fig. 9 presents the transferred voltages for the latter case. Fig. 7 Transferred voltages at the transformer LV terminal Sa for twisted conductors and open wire configurations t f = 5.6 µs; Rg = 20 Ω; ρ g = 2300 Ω.m. Fig. 8 shows the phase-to-ground and neutral-to-ground transferred voltages at the LV terminal Sa for the open wire configuration, and it can be clearly seen that both voltages increase substantially as the ground resistance increases. The phase-to-neutral voltages, in general, have the same behaviour, but the variation is less significant. Fig. 9 Transferred voltages at the transformer LV terminal Sa for twisted conductors and open wire configurations t f = 5.6 µs; Rg = 20 Ω; ρ g = 100 Ω.m. The larger the ground losses are, the lower the magnitudes of the voltages at the primary side of the distribution transformer will be. As a result, a high value for the ground resistivity results in a transferred voltage with lower magnitude. This influence, however, is usually not significant, mainly in the case of the line with twisted conductors. For the open wire configuration the effect is more visible. 4 CONCLUSIONS Fig. 8 Phase-to-ground and neutral-to-ground transferred voltages at the transformer LV terminal Sa for open wire configuration - t f = 5.6 µs; Rg = 20 Ω; ρ g = 2300 Ω.m. 3.3 Ground resistivity Two situations were considered regarding the ground resistivity (ρ g ): 2300 Ω.m and 100 Ω.m. Fig. 5 refers to In this paper, some features of the voltages transferred to the secondary of a distribution transformer in the case of direct strikes to the MV line were presented and discussed. The calculations were performed with the ATP considering, for the LV line, the twisted conductors and the open wire configurations. A high frequency transformer model, validated by comparisons of measured and calculated transferred voltages considering the transformer both under no-load condition and with different resistive and inductive loads connected to the secondary, was used. Examples of surges transferred to the secondary, considering a typical rural distribution network, were presented. The influences of the lightning current front time, ground resistance and ground resistivity were analysed for the two LV line configurations. For all situations, the obtained results showed that the voltage surges transferred to the secondary in the case of a line

with twisted conductors have significantly smaller magnitudes than those associated with the open wire configuration. 5 REFERENCES [1] Task Force Report, Secondary (low-side) surges in distribution transformers, IEEE Transactions on Power Delivery, vol. 7, n. 2, pp. 746-756, Apr. 1992. [2] W. Bassi, J. M. Janiszewski, A. Piantini and N. M. Matsuo, Surges in low-voltage networks due to direct lightning strikes in MV lines. Proceedings of the V International Symposium on Lightning Protection, pp. 206-210, São Paulo, May 1999. [3] P. F. Obase; A. Piantini, and A. G. Kanashiro Overvoltages transferred to low voltage networks due to direct strokes on the primary Proceedings of the VIII International Symposium on Lightning Protection, pp. 489-494, São Paulo, Nov. 2005. [4] A. Piantini, A. G. Kanashiro and P. F. Obase, Lightning surges transferred to the low-voltage network, Proceedings of the VII International Symposium on Lightning Protection, pp. 216-221, Curitiba, Nov. 2003. [5] A. Borghetti, A. Morched, F. Napolitano, C. A. Nucci, and M. Paolone, Lightning-induced overvoltages transferred through distribution power transformers, IEEE Transactions on Power Delivery, vol. 24, n. 1, pp. 360-372, Jan. 2009. [6] A. G. Kanashiro, A. Piantini and G. F. Burani, A methodology for transformer modelling concerning high frequency surges. Proceedings of the VI International Symposium on Lightning Protection, pp. 75-280, Santos, Nov. 2001. [7] S. Visacro, A. Soares Jr., M. A. O. Schroeder, L. C. L. Cherchiglia and V. J. de Sousa, Statistical analysis of lightning current parameters: Measurements at Morro do Cachimbo Station, Journal of Geophysical Research, vol. 19, pp. 1-11, Jan. 2004. [8] H. K. Høidalen, Lightning-induced voltages in low-voltage systems and its dependency on overhead line terminations, Proceedings of the 24 th International Conference on Lightning Protection, pp. 287-292, Birmingham, Sep. 1998. [9] S. Sekioka, K. Yamamoto, and S. Yokoyama, Measurements of a concrete pole impedance with an impulse currents source, Proceedings of the International Conference on Power Systems Transients, pp. 457-462, Lisbon, Sep. 1995. [10] IEEE Guide for Improving the Lightning Performance of Electric Power Overhead Distribution Lines, IEEE Standard 1410, 2004.