FUZZY LOGIC BASED OVERCURRENT PROTECTION FOR MV NETWORKS

Similar documents
Keywords: Transformer, differential protection, fuzzy rules, inrush current. 1. Conventional Protection Scheme For Power Transformer

Analysis of Modern Digital Differential Protection for Power Transformer

A Novel Fuzzy Neural Network Based Distance Relaying Scheme

POWER TRANSFORMER PROTECTION USING ANN, FUZZY SYSTEM AND CLARKE S TRANSFORM

Improved power transformer protection using numerical relays

A NEW METHOD FOR ISLANDING DETECTION IN DISTRIBUTED GENERATION

Electrical Protection System Design and Operation

Data. Dr Murari Mohan Saha ABB AB. KTH/EH2740 Lecture 3. Data Acquisition Block. Logic. Measurement. S/H and A/D Converter. signal conditioner

Z. Kuran Institute of Power Engineering Mory 8, Warszawa (Poland)

LIMITING THE DANGER OF ELECTRIC CURRENT SHOCK IN RELATION TO THE MEAN OF NEUTRAL POINT EARTHING IN THE MV NETWORKS

METHOD OF TESTING AND CORRECTING SIGNAL AMPLIFIERS TRANSFER FUNCTION USING PRONY ANALYSIS

ANFIS Approach for Locating Faults in Underground Cables

Ferroresonance Experience in UK: Simulations and Measurements

A NEW DIFFERENTIAL PROTECTION ALGORITHM BASED ON RISING RATE VARIATION OF SECOND HARMONIC CURRENT *

Busbars and lines are important elements

[Nayak, 3(2): February, 2014] ISSN: Impact Factor: 1.852

Proceedings of the 5th WSEAS Int. Conf. on SIMULATION, MODELING AND OPTIMIZATION, Corfu, Greece, August 17-19, 2005 (pp )

Ferroresonance in MV Voltage Transformers: Pragmatic experimental approach towards investigation of risk and mitigating strategy

A Tutorial on the Application and Setting of Collector Feeder Overcurrent Relays at Wind Electric Plants

SAFETY ASPECTS AND NOVEL TECHNICAL SOLUTIONS FOR EARTH FAULT MANAGEMENT IN MV ELECTRICITY DISTRIBUTION NETWORKS

Reducing the Effects of Short Circuit Faults on Sensitive Loads in Distribution Systems

2015 Relay School Bus Protection Mike Kockott March, 2015

DC Motor Speed Control: A Case between PID Controller and Fuzzy Logic Controller

Decriminition between Magnetising Inrush from Interturn Fault Current in Transformer: Hilbert Transform Approach

Application of Fuzzy Logic Controller in Shunt Active Power Filter

Design of an Intelligent Pressure Control System Based on the Fuzzy Self-tuning PID Controller

Abstract: PWM Inverters need an internal current feedback loop to maintain desired

Voltage Sags Evaluating Methods, Power Quality and Voltage Sags Assessment regarding Voltage Dip Immunity of Equipment

Negative-Sequence Based Scheme For Fault Protection in Twin Power Transformer

Sequence Networks p. 26 Sequence Network Connections and Voltages p. 27 Network Connections for Fault and General Unbalances p. 28 Sequence Network

VALIDATION THROUGH REAL TIME SIMULATION OF A CONTROL AND PROTECTION SYSTEM APPLIED TO A RESONANT EARTHED NEUTRAL NETWORK

Symmetrical Components in Analysis of Switching Event and Fault Condition for Overcurrent Protection in Electrical Machines

IDENTIFICATION OF POWER QUALITY PROBLEMS IN IEEE BUS SYSTEM BY USING NEURAL NETWORKS

Improving Transmission Line Performance using Transient Based Adaptive SPAR

Course No: 1 13 (3 Days) FAULT CURRENT CALCULATION & RELAY SETTING & RELAY CO-ORDINATION. Course Content

PRC Generator Relay Loadability. Guidelines and Technical Basis Draft 5: (August 2, 2013) Page 1 of 76

Transformer Protection

RAIDK, RAIDG, RAPDK and RACIK Phase overcurrent and earth-fault protection assemblies based on single phase measuring elements

Shortcomings of the Low impedance Restricted Earth Fault function as applied to an Auto Transformer. Anura Perera, Paul Keller

PRC Generator Relay Loadability. Guidelines and Technical Basis Draft 4: (June 10, 2013) Page 1 of 75

Commissioning Process and Acceptance Test of a Sub-harmonic Protection Relay

PSV3St _ Phase-Sequence Voltage Protection Stage1 (PSV3St1) Stage2 (PSV3St2)

Harmonic Distortion Levels Measured at The Enmax Substations

Protection Basics Presented by John S. Levine, P.E. Levine Lectronics and Lectric, Inc GE Consumer & Industrial Multilin

p. 1 p. 6 p. 22 p. 46 p. 58

Wavelet Based Fault Detection, Classification in Transmission System with TCSC Controllers

Earth Fault Protection

Phase earthing system - method for faulty phase selection with phase-to-earth faults. Ari Nikander Tampere University of Technology

DESIGNING POWER SYSTEM STABILIZER FOR MULTIMACHINE POWER SYSTEM USING NEURO-FUZZY ALGORITHM

DG TRANSFER CONNECTION SCHEME IN ACTIVE DISTRIBUTION NETWORKS

Improvement of Power Quality Using a Hybrid Interline UPQC

Differential Protection Optimal differential protection for phase shifter transformers and special transformers

Neutral Reactor Optimization in order to Reduce Arc Extinction Time during Three-Phase Tripping

Impact of transient saturation of Current Transformer during cyclic operations Analysis and Diagnosis

Discrimination between Inrush and Fault Current in Power Transformer by using Fuzzy Logic

Power System Protection Manual

Distance Relay Response to Transformer Energization: Problems and Solutions

Detection and classification of faults on 220 KV transmission line using wavelet transform and neural network

CHAPTER 3 REVIEW OF POWER TRANSFORMER PROTECTION SCHEMES

EVALUATION OF DIFFERENT SOLUTIONS OF FAULTED PHASE EARTHING TECHNIQUE FOR AN EARTH FAULT CURRENT LIMITATION

NERC Protection Coordination Webinar Series June 16, Phil Tatro Jon Gardell

Keywords: Wavelet packet transform (WPT), Differential Protection, Inrush current, CT saturation.

Unit Protection Differential Relays

UProtection Requirements. Ufor a Large scale Wind Park. Shyam Musunuri Siemens Energy

International Journal of Digital Application & Contemporary research Website: (Volume 2, Issue 10, May 2014)

ISSN: Page 298

An Adaptive Protection Scheme for Optimal Overcurrent Relay Coordination in Interconnected Power Systems

Single-Core Symmetrical Phase Shifting Transformer Protection Using Multi-Resolution Analysis

Protection of Electrical Networks. Christophe Prévé

Transformer Fault Categories

Operation Analysis of Current Transformer with Transient Performance Analysis Using EMTP Software

FERRORESONANCE SIMULATION STUDIES USING EMTP

A Novel Method in Differential Protection of Power Transformer Using Wavelet Transform and Correlation Factor Analysis

Application Of Artificial Neural Network In Fault Detection Of Hvdc Converter

Simulation Analysis of Control System in an Innovative Magnetically-Saturated Controllable Reactor

Feature Extraction of Magnetizing Inrush Currents in Transformers by Discrete Wavelet Transform

CHAPTER 1 INTRODUCTION

Modern transformer relays include a comprehensive set of protective elements to protect transformers from faults and abnormal operating conditions

Capacitive Voltage Substations Ferroresonance Prevention Using Power Electronic Devices

DETECTION AND CLASSIFICATION OF POWER QUALITY DISTURBANCES

Modeling Ferroresonance Phenomena on Voltage Transformer (VT)

Discrimination of Fault from Non-Fault Event in Transformer Using Concept of Symmetrical Component

A FUZZY EXPERT SYSTEM FOR QUANTIFYING VOLTAGE QUALITY IN ELECTRICAL DISTRIBUTION SYSTEMS

Solutions to Common Distribution Protection Challenges

Simulation of Synchronous Machine in Stability Study for Power System: Garri Station as a Case Study

RESEARCH ON CLASSIFICATION OF VOLTAGE SAG SOURCES BASED ON RECORDED EVENTS

This webinar brought to you by The Relion Product Family Next Generation Protection and Control IEDs from ABB

Automatic bearing fault classification combining statistical classification and fuzzy logic

ENHANCED DISTANCE PROTECTION FOR SERIES COMPENSATED TRANSMISSION LINES

R10. IV B.Tech I Semester Regular/Supplementary Examinations, Nov/Dec SWITCH GEAR AND PROTECTION. (Electrical and Electronics Engineering)

II. DIFFERENTIAL PROTECTION

Study of Centralized Anti-Islanding Method on Large-Scale Photovoltaic Power Plants

PHYSICAL PHENOMENA EXISTING IN THE TURBOGENERATOR DURING FAULTY SYNCHRONIZATION WITH INVERSE PHASE SEQUENCE*

Identification of network models parameters for simulating transients

Artificial Neural Networks approach to the voltage sag classification

A New Subsynchronous Oscillation (SSO) Relay for Renewable Generation and Series Compensated Transmission Systems

Online Automatic Gauge Controller Tuning Method by using Neuro-Fuzzy Model in a Hot Rolling Plant

Switch-on-to-Fault Schemes in the Context of Line Relay Loadability

Harmonic Distortion Impact On Electro-Mechanical And Digital Protection Relays

1

Transcription:

FUZZY LOGIC BASED OVERCURRENT PROTECTION FOR MV NETWORKS Waldemar Rebizant, Daniel Bejmert, Janusz Szafran Wroclaw University of Technology Wroclaw, Poland waldemar.rebizant@pwr.wroc.pl, daniel.bejmert@pwr.wroc.pl, janusz.szafran@pwr.wroc.pl Abstract In the paper a novel approach to overcurrent protection stabilisation based on Fuzzy Logic technique is presented. The scheme is intended for MV overhead lines for which the autoreclosure function is applied to enhance reliability of supply in case of intermediate (vanishing faults. Protection stabilisation is required for the feeders supplying a part of network with numerous loaded MV/LV transformers that may face inrush conditions after reenergising the line. Traditional harmonic restraint approach as for single transformer may not be effective for line overcurrent protection because of different current spectrum as measured at the MV busbars. The new FL protection developed takes both current and voltage signals for further processing and final decision is issued as a result of aggregation of partial decision support coefficients. Application of signal fuzzification and fuzzy settings enables obtaining a relay with increased sensitivity, reliability and much faster than commonly available solutions. The developed fuzzy protection scheme has been tested with EMTP signals and compared with other standard protection approaches. Keywords: overcurrent protection, fuzzy logic, transformer inrush, relay stabilisation INTRODUCTION Overcurrent (OC principle belongs to the oldest and widely used criteria in power system protection. It is often applied as primary protection for distribution lines, small transformers and motors as well as a backup protection of transmission lines, transformers, generators and motors. The idea of the method is simple, however, it has also numerous drawbacks. Overcurrents are characteristic for phase and ground faults, but can also occur during normal operation, e.g. when energising power transformers, induction motors etc. The overcurrent criterion can thus be used for detecting faults, providing overcurrents of the kind mentioned above either cannot occur in the particular system or are prevented from causing tripping by functions included in the protection (e.g. time delay, blocking by harmonic detectors, discrimination by pick-up setting etc.. Distribution networks in Poland are mainly of the radial structure. The overhead lines, cables and transformers in such MV networks are usually protected with use of timeovercurrent protection relays. In case of such OC protection short peaks of current, which are higher than the pickup setting but shorter than the time delay (fixed or depending on the current level cannot cause tripping of the circuit breaker. Since the majority of faults in MV networks are of transient (arcing nature, i.e. they disappear either spontaneously or as a result of tripping the faulty feeder, the autoreclosure (ARC relays usually supplement the main OC protection. Excluding persistent fault cases, the ARC schemes enable fast re-establishing of the normal state of the power system, thus restoring power supply to the customers. Reenergising the feeder after defined dead time may be successful after single shot or, sometimes, after two or more attempts. In case of MV feeders supplying a part of network with numerous MV/LV transformers certain problems with OC relay setting may be faced due to inrush phenomena in loaded transformers after successful ARC cycle. Restoring the power supply may result in temporarily increased currents measured at the relay location, which can be interpreted as overcurrent and consequently lead to feeder tripping (Fig.. a Phase currents, i [A] Current amplitudes, I [A] 5 5-5 - 6 5 4 3 2 i L i L2-5.25.3.35.4. 45.5.55.6 Time, t [s] b 8 I L 7 I L2 Pick-up current level.25.3.35.4. 45.5.55.6 Time, t [s] Figure : Phase currents for a successful ARC case: a instantaneous signals, b measured amplitudes. 5th PSCC, Liege, 22-26 August 25 Session 9, Paper 2, Page

In the paper the OC protection operation in distribution networks is studied, with particular consideration of mentioned above effects of ARC on line-transformer feeders. EMTP-ATP model of a fragment of typical Polish MV network as well as the simulation results of a few of ARC-cleared fault cases are described. Furthermore, a new algorithm of the OC relay stabilisation with application of Fuzzy Logic is described and its performance is compared to traditional stabilisation versions with harmonic blocking (second, or second, third and fifth harmonics. The FL reasoning unit developed takes advantage of parallel fuzzy processing of numerous criteria (current fundamental component amplitude, harmonic content, etc. and their fuzzy aggregation, leading to final protection decision. The proposed fuzzy OC protection scheme has been tested with the signals generated with use of EMTP- ATP programme as well as field recordings. The designed protection proved to be reliable and much more sensitive than the traditionally used OC relays, assuring sufficient stabilisation for the cases of transformer inrush currents evoked by autoreclosure operation. In the next sections the structure and algorithms of Fuzzy Logic based relay is described (section 2. Its testing and comparison with chosen standard versions of OC protection is presented (section 3. Concluding remarks (section 4 close the paper. 2 FUZZY LOGIC BASED PROTECTION 2. Fuzzy Systems in power system protection The fuzzy signal processing and fuzzy reasoning techniques (belonging to the family of Artificial Intelligence have gained remarkable attention for at least 5 years and numerous studies have been performed in world-leading research centres with regard to their application also for power system protection and control tasks. Fuzzy Logic systems (FL are well suited for solving various decision-making problems, especially when the precise analytical model of the process/object to be tracked is not known or is very complicated (e.g. non-linear [2]. Analysis of power system faults and other abnormal phenomena belongs to the family of tasks that can be quite well carried out with use of FLbased decision modules or classifiers. Fuzzy Inference Systems (FIS employ the theory of fuzzy sets and fuzzy if-then rules to derive an output. Various types of FIS are often used either for fuzzy modelling or fuzzy classification purposes. Typically a FIS scheme performs its action in several steps including (Fig. 2: fuzzification (comparing the input values with membership functions to obtain membership values of each linguistic term, fuzzy reasoning (firing the rules and generating their fuzzy or crisp consequents, defuzzification (aggregating rule consequents to produce a crisp output. Input signals Fuzzy signals Fuzzyfication Decision making Defuzzyfication Fuzzy settings Output signals Figure 2: Basic structure of a fuzzy reasoning system. The theory of fuzzy sets has met considerable approval for the sake of ability to describe quantitatively the uncertainties appearing during the operation of a protective relay. Implementation of fuzzy criteria signals together with fuzzy settings brings antidotes to uncertainties caused by dynamic measurement errors and may constitute a remedy against problems related with sharp boundaries in the universe of criteria signals between areas of faulty and failure-free operation of protected plant. Sample applications of this approach to power system protection include fault type identification [3] and multi-criteria protection of power transformers [4]. An idea of FL-based generator protection against out-of-step conditions was developed by the authors of this paper and published at the IEEE PES Summer Meeting in Vancouver in 2 [5]. In the literature one can find also protection or control schemes employing a fuzzy processing module supplemented with other techniques, e.g. neural networks, wavelet transformation, etc. The resulting hybrid structures combine the strengths and eliminate weaknesses of particular techniques, which brings about increased efficiency and reliability of the scheme. Applications of fuzzy hybrid solutions are e.g. fuzzywavelet scheme for fault classification [6] and location [7] as well as fuzzy-neural distance protection [8]. 2.2 Fuzzy Logic overcurrent protection developed In this paper a fuzzy approach to overcurrent protection of MV feeders is studied. The protection solution developed (Fig. 3 takes advantage of fuzzy signal processing and fuzzy comparison to issue trip decision. Analogue filters u(t Trip i(t δ (U N,δ (I δ ( Decision making A D i(n u(n Comparison with fuzzy settings Digital filters & criterion values measurement µ (U N, µ(i µ( U N(n I (n (n Fuzzification block Figure 3: Block scheme of the FL-based OC protection. 5th PSCC, Liege, 22-26 August 25 Session 9, Paper 2, Page 2

The first three blocks in Fig. 3, i.e. analogue filters, A/D converters and digital signal processing unit, are typically applied in contemporary digital protection relays. At the output of this path certain criterion values are issued, basing on which the protection decision is to be worked out, usually by their comparison with pre-set thresholds or characteristics. Here, additional signal processing is performed to obtain fuzzified criterion Current amplitude, I [A] 3 25 2 5 µ(ι µ(ι Ι I min I m I max 3 3 2 3 4 5 6 7 8 9 Time, t [ms] Figure 4: Sample current amplitude signal with respective fuzzy values (for two selected time intervals. µ S (I µ S ( I R µ S (U N I U R min U N max Figure 5: Membership functions of fuzzy settings of the signals I, U N,. a b.6.4.2.8.6.4.2.8.6.4.2.8.6.4.2 3 4 5 6 7 8 9 t [ms] Figure 6: Illustration of membership function adjusting on basis of simulation data for the cases with: a unsuccessful ARC, b successful ARC. Ι µ B ( µ T ( signals (Fig. 4. Signal fuzzification is made according to the following formulae: X X X m N / 4 ( n = X N / 4 + k= max ( k,..., N / 4 ( n k, ( n = min { X ( n k}, (2 = min ( k,..., N / 4 n = min { X ( n k}. (3 = which can be interpreted as finding minimum, maximum and average values of the criterion signal X over a time period corresponding to a quarter of fundamental frequency cycle, with N being number of samples within 2 ms. The criterion signals taken into account were: amplitude of fundamental frequency phase current I, relative level of second to fundamental harmonic (a ratio of amplitudes I 2 /I and line-to-line voltage amplitude U N. All the amplitudes were calculated with application of full cycle Fourier algorithm (sine-cosine filters plus determination of complex vector norm. The latter two variables are intended to serve as protection stabilisation criteria. High values of coefficient indicate temporary increase of second harmonic current I 2, which may take place either due to MV/LV transformers inrush phenomenon after successful ARC cycle or as an effect of current transformer saturation during switching the feeder on a persistent fault (unsuccessful ARC. To discriminate between the two cases the voltage amplitude is additionally measured, with decreased values indicating a persistent fault on the line. The criterion signals mentioned are fuzzified in order to obtain a relative measure of their membership to given group of cases. The fuzzy criterion signals are compared with fuzzy settings that have been set as shown in Fig. 5. The fuzzy setting µ S for current amplitude I and voltage amplitude U N are crisp (sudden change from to or from to after exceeding certain threshold value, while the function µ S ( is a kind of saturable curve, changing gradually from to. Its shape and parameters have been found after analysis of the level of I 2 for numerous cases of faults with successful and unsuccessful ARC (Fig. 6. The result of fuzzy comparison (see Fig. 7, here for variable is defined as a ratio of the area F under both setting and signal membership functions and the area F under criterion signal membership function: µ µ( F µ S( δ(h = F F 2 F Figure 7: Comparison of fuzzy signal with fuzzy setting. 5th PSCC, Liege, 22-26 August 25 Session 9, Paper 2, Page 3

Input parameters: δ(i,δ(, δ(u N δ = δ(i *(- δ( N δ(u N >,5 Y δ = δ(i High values of the resulting support coefficient δ are observed for the cases of persistent line-to-line faults with or without current transformer saturation, which indubitably should lead to line tripping. Other cases, including magnetising inrush situations, would imply relay stabilisation and further uninterrupted supplying of electrical energy to customers in the network. δ > Y Trip the line Figure 8: Block scheme of the decision making. min[ µ ( X, µ S ( X ] dx F δ ( X = =. (4 µ ( X dx F As a result of fuzzy comparison the non-fuzzy coefficients δ(i, δ(u N, δ( are determined. The calculated values of δ specify the degree of satisfying of given criterion (degree of confidence of exceeding the fuzzy threshold and may amount between and. The calculated variables are interpreted as follows: if δ(i = & δ ( = a clear indication on a persistent fault is issued, which implies necessity of immediate line tripping; 2 if δ (I = & δ ( = & δ (U N = a situation of magnetising inrush in MV/LV transformers in the depth of network (supplied from the feeder to be protected is confirmed, i.e. the feeder should not be tripped; 3 if δ (I = & δ ( = & δ (U N = the second harmonic current I 2 is evoked due to saturation of current transformers, which, simultaneously with full support for exceeding of fundamental frequency current threshold I, gives a reliable indication on line-to-line fault, i.e. the feeder should be tripped. The situations listed above encompass only the most extreme and unquestionable cases. The space inbetween the cases to 3 includes, of course, all uncertain situations which are also expected to be well handled by the scheme. Thanks to introduced fuzzy features the borders between the classes of events to be discriminated become fuzzy and the decision, even for doubtful cases, may be taken with higher confidence. The block scheme of reasoning with fuzzy variables is shown in Fig. 8. Depending on the value of voltage related support coefficient δ(u N, the final decision is met on the basis of either single-handed current support coefficient δ(i for δ(u N greater than.5, or a combined fundamental/second harmonic current support coefficient δ(i ( δ( for δ(u N <.5. N 3 RELAY TESTING AND COMPARATIVE ANALYSIS 3. MV network structure and testing signals The new fuzzy logic based protection has been verified with use of signals generated with EMTP-ATP software. To obtain data for scheme testing a model of typical Polish radial MV network has been prepared (Fig. 9. The network under study (voltage level 2 kv was operated with neutral point grounded via Petersen coil, i.e. with compensation of capacitive currents, connected through Zy grounding transformer. The feeders outgoing from MV busbars were of mixed type, i.e. overhead lines, cable sections or both. The MV lines were distributing power to numerous domestic and industrial loads connected to the network through dedicated 2/.4 kv transformers, rated power from 63 kva to.2 MVA. Some of the feeders were supplying power to 3 or even more MV/LV transformers. The ATP model of power transformer applied included details related to parameters of transformer windings, active and reactive power losses as well as non-linear magnetising characteristics with full hysteresis loop (ATP inductor model type 96. The simulation results obtained from the model prepared were of good conformity with the signals registered in a real MV network of similar structure []. It was also confirmed that the network model was sufficiently good for accurate rendering of phenomena related to faults and autoreclosure induced transients. Z l kv R w T T pw 2 kv L L 2 L 3 L n.4 kv 2/.4 kv/kv 2/.4 kv/kv Figure 9: Structure of the MV network under study. Various line-to-ground and line-to-line fault cases were simulated at the beginning and at the end of selected feeders in the network. The faults were of both transient and persistent type, with three-phase autoreclosure initiated for overhead lines. The protection has 5th PSCC, Liege, 22-26 August 25 Session 9, Paper 2, Page 4

been tested with current signals from the cases with both successful and unsuccessful ARC. Such model parameters as feeder switching on angle (after ARC pause, degree of MV/LV transformer loadings, load type, etc. were being changed to obtain a wide variety of fault conditions. Feeder currents as well as MV busbar voltages were registered in ATP output files for further processing. 3.2 FL protection testing The algorithms and logic of proposed fuzzy overcurrent protection have been implemented in MATLAB programming code. Numerous testing attempts have been performed with the aim to optimise the relay fuzzy settings, threshold values and fuzzification window lengths. The optimisation goal was to obtain a protection solution characterised by possibly shortest operating time for persistent faults, yet being absolutely stable for transformer inrush cases after successful ARC cycle, at the same time. Operation of proposed fuzzy overcurrent protection for MV lines has been compared with other versions of available OC relays: A classical OC scheme without stabilisation, B as A, supplemented with second harmonic restraint (set low or high [9], C OC scheme wit nd, 3 rd and 5 th harmonic stabilisation, as described in []. The scheme B, with second harmonic restraint, was modelled on simple stabilisation idea typically applied e.g. in transformer protection. A flag for exceeding certain amount of 2 nd harmonic content was used for relay blocking purpose. The problems with proper setting of such a restraint will be shown below, which confirm impossibility of ideal solving of the sensitivity vs. stability dilemma with single crisp relay setting. The solution C is based on correcting of OC relay input current by subtracting a current term related to transient components evoked by switching on the line after ARC pause, according to: I( n k I( n I s ( n = k s ( k2hh2 + k3h h3+ k5hh5 (5 I N where: k s stabilisation coefficient, I(n, I(n k current samples before correction, I N nominal current of the protected overhead line, k 2h, k 3h, k 5h coefficients of stabilisation for the 2 nd, 3 rd and 5 th harmonic, respectively, h2, h3, h5 percentage content of 2 nd, 3 rd and 5 th harmonic currents. The corrected current value was further compared with typically set OC threshold. Below two cases of ARC attempts for single-phase intermediate fault (relay blocking required, Fig. and line-to-line persistent fault (fast tripping necessary, Fig. are shown. Operation of overcurrent protection solutions A and B is compared with the new FL based relay developed. Direct comparison with version C was not possible here due to lack of all required parameters and relay settings. a 5 i [A] 5-5 - -5.2.3.4.5.6.7.8 b c d e.565.57.575.58.585.59.595.6.565.57.575.58.585.59.595.6.565.57.575.58.585.59.595.6.565.57.575.58.585.59.595.6 t [s] Figure : Operation of MV line protection for a case with successful ARC: a phase current from the healthy phase, b trip signal of the classic OC protection, c trip signal of the OC protection wit nd harmonic stabilisation set low, d as above set high, e trip signal of the FL based relay. a i [A] b c e 2 - -2.2.3.4.5.6.7.8.55.56.57.58.59.6.565.57.575.58.585.59.595.6.565.57.575.58.585.59.595.6.565.57.575.58.585.59.595.6 t [s] Figure : Operation of MV line protection for a case with unsuccessful ARC (line-to-line persistent fault: a phase current observed, b trip signal of the classic OC protection, c trip signal of the OC protection wit nd harmonic stabilisation set low, d as above set high, e trip signal of the FL based relay. 5th PSCC, Liege, 22-26 August 25 Session 9, Paper 2, Page 5

It is seen (Fig. b that the classical OC scheme without stabilisation version A responded falsely to situation of healthy line switching on (overfunction. Numerous simulation runs have shown, as anticipated, that avoiding unselective trippings for magnetising inrush conditions after successful ARC is possible at a cost of increased trip delay (not less than ms for most cases or significant raising of relay pick-up setting (decreased sensitivity. Application of relay blocking in dependence on the second harmonic level (OC version B enables considerable increase of resulting relay selectivity (Fig. c. Nevertheless, choosing the restraint threshold should be made with care, since too small values may imply elongated operation time for persistent line-to-line faults (Fig. c, without complete elimination of possible unselective trippings for transformer inrush cases. It is obvious that along with increase of the 2 nd harmonic threshold faster relay operation is expected for persistent faults (Fig. d, yet by considerable deterioration of relay selectivity (Fig. d. Comparison of the FL based scheme with the stabilisation algorithm with temporary current correction (version C was performed indirectly, i.e. by using the result statistics given in paper []. The tests have shown that stable and selective operation of the relay C was obtainable with ca. 3 ms internal time delay. It should be stated, however, that such operation parameters could be reached with introduction of numerous coefficients and threshold values, which may unfavourably influence universalness of the scheme and cause problems by relay setting. The new FL-based scheme turned out to be even faster than relay C, being able to respond to all cases with time delay less than 2 ms. Such a high operation speed was obtained despite of the fact that for calculation of criterion values (amplitudes of I, I 2 and U N an algorithm with full cycle filtering was used. The relay C was a bit slower, although it employed much faster wavelet transformation for signal processing. 4 CONCLUSIONS In the paper a new Fuzzy Logic based overcurrent protection for MV overhead lines is proposed. The scheme designed is well suited for interaction with standard autoreclosure relays. Its main feature is the improved stabilisation for transients evoked by switching on the feeder after successful ARC cycle due to possible inrush currents of supplied MV/LV transformers. The FL-based OC protection scheme has been thoroughly tested with ATP-generated power system signals. The new relay was able to classify properly all the considered simulated fault/arc cases. No unselective answers for transients due to transformer inrush have been observed. With FL algorithm the decisions were taken earlier and much more reliable than with use of other OC protection systems. Wide robustness features of the scheme with respect to changes of both network configuration and fault parameters have also been confirmed. REFERENCES [] H. Ungrad, W. Winkler and A. Wiszniewski, Protection Techniques in Electrical Energy Systems, Marcel Dekker, Inc., New York, 995 [2] J. M. Mendel, Fuzzy Logic Systems for Engineering: A Tutorial, Proc. of the IEEE, vol. 83,No. 3, pp. 345-377, 995 [3] A. Ferrero, S. Sangiovanni, E. Zappitelli, A fuzzyset approach to fault type identification in digital relaying, IEEE Trans. On Power Delivery, vol. 3, no. 4,pp. 69-75, 995 [4] M.-S. Shin, C.-W. Park, J.-H. Kim, Fuzzy Logic- Based Relaying for Large Power Transformer Protection, IEEE Trans. On Power Delivery, vol. 8, no. 3, pp. 78-724, 23 [5] W. Rebizant and K. Feser, Fuzzy logic application to out-of-step protection of generators, Proceedings of the 2 IEEE PES Summer Meeting, 5-9 July 2, Vancouver, Canada, paper SM6 [6] A. K. Pradhan, A. Routray, S. Pati, D. K. Pradhan, Wavelet Fuzzy Combined Approach for Fault Classification of a Series-Compensated Transmission Line, IEEE Tran. On Power Delivery, vol. 9, No. 4, pp. 62-68, 24 [7] J. Moshtagh, R. K. Aggarwal, A new approach to fault location in a single core underground cable system using combined fuzzy & wavelet analysis, Eighth IEE International Conference on Developments in Power System Protection 5-8 April 24,vol., pp. 228-23 [8] P. K. Dash, A. K. Pradhan, G. Panda, A Novel Fuzzy Neural Network Based Distance Relaying Scheme, IEEE Trans. On Power Delivery, vol. 5, no. 3, pp.92-97, 2 [9] MiCOM P39 Manual, Alstom, Paris, France, 999 [] M. Michalik and A. Juszczyk, Modelling of Transient Autoreclosure Effects in Medium Voltage Networks for Overcurrent Relaying Purposes Comparison of ATP Simulation and Field Measurement Relays, Proceedings of European EMTP- ATP User Group Meeting, Wroclaw, Poland, September 2, pp. 83-89 [] A. Juszczyk and J. Lorenc, Stabilization of Transients in Overcurrent Protection during Fast Autoreclosure Operations in MV Networks, Proceedings of the Modern Electric Power System Conference, MEPS 2, Wroclaw, Poland, September 22, pp. 353-356 5th PSCC, Liege, 22-26 August 25 Session 9, Paper 2, Page 6