RESIDUAL LIFE ASSESSMENT OF GENERATOR TRANSFORMERS IN OLD HYDRO POWER PLANTS

Similar documents
Effective Maintenance Test Techniques and Diagnostic Measurements to Improve the Performance and Reliability of Power System Transformers

Innovative Test Techniques and Diagnostic Measurements to Improve the Performance and Reliability of Power System Transformers

Effective maintenance test techniques for power transformers

CASE STUDY- FAULT IN POWER TRANSFORMER AT LOKTAK POWER STATION. - S K Mishra & S K Das NHPC Ltd O&M Division

Chapter 7 Conclusion 7.1 General

Cholla T809 Condition Assessment Report Provided by students of Northern Arizona University with the support of Arizona Public Service

Identification of Overheating in Transformer Solid Insulation by Polarization Depolarization Current Analysis

TesTIng of Power. Transformers are the largest, most. feature. By brandon dupuis

Transformer Factory Testing

Power transformer failure management on the Eskom distribution network in Limpopo

Understanding the Value of Electrical Testing for Power Transformers. Charles Sweetser, OMICRON electronics Corp. USA

TECHNIQUES AND STANDARD

KNOW MORE ABOUT THE TRANSFORMERS. Glossary Transformers

Understanding and Extracting Valuable Information from Basic and Advanced Power Transformer Testing Techniques

Power Transformer Condition Assessment Based on Standard Diagnosis

The importance of partial discharge testing throughout the development and operation of power transformers

OMICRON Seminar on Substation Testing and Diagnosis. October 23, 2017 Dubai, United Arab Emirates. October 24, 2017 Abu Dhabi, United Arab Emirates

Matz Ohlen Director Transformer Test Systems. Megger Sweden

Benefits of SFRA - Case Studies

We can classify test failure modes in power transformers according to transformer components

Using the Frequency Response Analysis (FRA) In Transformers Internal Fault Detection

Specialists in HV and MV test and diagnostics. Testing in Substations

Monitoring Solutions For Power Transformers, Reactors, Bushings and Instrument Transformers

Power Transformers Basics

SERVICE OFFERINGS FOR POWER SYSTEM STUDY & CONDITION MONITORING FOR STATIC EQUIPMENT

Assesment of health of transformer: a survey

Health indexes for power transformers: A case study

IDAX 300 Insulation Diagnostic Analyzer. Dielectric Frequency Response Also known as: Frequency Domain Spectroscopy

REPORT ON INVESTIGATION OF FAILURE OF 100 MVA, 220/66-33/11 KV POWER TRANSFORMER AT 220KV GEETA COLONY SUBSTATION OF DELHI TRANSCO LTD.

POWER TRANSFORMER SPECIFICATION, DESIGN, QUALITY CONTROL AND TESTING 18 MARCH 2009

Understanding the Value of Electrical Testing for Power Transformers. Charles Sweetser - OMICRON

Application of Polarisation Depolarisation Current (PDC) technique on fault and trouble analysis of stator insulation

CHAPTER 3 REVIEW OF POWER TRANSFORMER PROTECTION SCHEMES

IN ELECTRICAL ENGINEERING - I C M E T CRAIOVA

Transformers handling and transport

Transformer Shunt Fault Detection using Two Techniques

Power Measurements and Basic Electrical Diagnostic Tests

Variation in SFRA plot due to design and external parameter

ABB Power Products Service

Discipline Electrical Testing Issue Date Certificate Number T-2837 Valid Until Last Amended on - Page 1 of 6 LOCATION 1

7. INSPECTION AND TEST PROCEDURES

A Novel Technique to Precise the Diagnosis of Power Transformer Internal Faults

TRANSFORMER OPERATIONAL PRINCIPLES, SELECTION & TROUBLESHOOTING

EFFECETIVE TRANSFORMER CONDITION ASSESSMENT

Hands-On Transformer Testing and Maintenance

EPS AUSTRALIA SERVICES HV TESTING & COMMISSIONING CAPABILITY

Vallabh Vidyanagar, Anand, INDIA

FIELD ELECTRICAL TESTING SPX TRANSFORMER SOLUTIONS, INC.

Operational Management of Grid Transformers An Experience of POWERGRID

IMPORTANCE & PROCESS OF RLA STUDIES IN ASSESSMENT OF NEED FOR R&M - A CASE STUDY. CPRI, Bengaluru

Substation Preventive Maintenance

Why is water killing power transformer insulation? Water is a slow but deadly poison for power transformers

ON-LINE PARTIAL DISCHARGE DETECTION ON TRANSFORMERS

B3-102 THE ROMANIAN EXPERIENCE REGARDING THE RISK OF MANAGEMENT IN THE OPERATION AND MAINTENANCE OF LARGE POWER TRANSFORMERS IN HV SUBSTATIONS

Power transformer maintenance. Field Testing.

Dielectric analysis of high-voltage power transformers DIAGNOSIS ABSTRACT KEYWORDS. 1. Introduction

Transformer Protection

Presenting New Idea for Circumstance Monitoring of Transformers in Power Lines

DEFERRING REPLACEMENT OF A 600 MVA, 345GRD Y/138GRD Y/ 13.8 kv SHELL TYPE WESTINGHOUSE AUTOTRANSFORMER

Field Experience with Sweep Frequency Response Analysis for Power Transformer Diagnosis

Transformer condition assessment with an integrated test van

N S Sodha, Former Executive Director, POWERGRID Corpn, Gurgaon

Case Studies of Electric Power Equipment Diagnostics Using Acoustic Emission

Transformer Winding Design. The Design and Performance of Circular Disc, Helical and Layer Windings for Power Transformer Applications

Basic Principles and Operation of Transformer

Andy Morin & Associates PO BOX Bellemont, AZ 86015

Advanced Diagnostic Testing Services. Provides detailed and reliable results

Primary Test Manager (PTM) Testing and management software for primary assets

IJSRD - International Journal for Scientific Research & Development Vol. 2, Issue 04, 2014 ISSN (online):

Diagnostic measurements on instrument transformers. Part II. A classification and overview of diagnostic measurements DIAGNOSIS EVENTS ABSTRACT

Diagnostic measurements on instrument transformers

SAMPLE. Determining the health of your power transformer begins with Transformer Clinic s SAMPLE testing programs.

A New Approach for Transformer Bushing Monitoring. Emilio Morales Technical Application Specialist Qualitrol

Investigating Mechanical Integrity in Power Transformer Using Sweep Frequency Response Analysis (SFRA)

Testing and Diagnostic of Power Transformers & Distribution Transformers

Condition monitoring and diagnostic of large power transformers to improve its reliability and life cycle management

Importance of Transformer Demagnetization

Insulation Assessment of Oil Impregnated Paper Condenser Bushings using Dielectric Frequency Response Technique

PARTIAL DISCHARGE MEASUREMENT

Transformer Testing & Maintenance Fundamentals. AVO Training Institute, Inc. 2018

Use of On and Offline Oil Analysis on the ESB, Distribution and Generation Networks

CONTENTS. 1. Introduction Generating Stations 9 40

CHAPTER 5 CONCEPT OF PD SIGNAL AND PRPD PATTERN

TIGHTENING TORQUE ON WOODEN CORE CLAMP (Nm) (STEEL FASTENER) 1 M M M M M

A Comparative Diagnosis Approach on Transformer s Insulating Oil Ming-Jong Lin

Power Transformer Testing

HIGH VOLTAGE ENGINEERING(FEEE6402) LECTURER-24

Using DFR to determine dissipation factor temperature dependence

Correlation between time and frequency domain polarisation measurements for transformer moisture assessment

Condition Assessment of High Voltage Insulation in Power System Equipment. R.E. James and Q. Su. The Institution of Engineering and Technology

Software System for Finding the Incipient Faults in Power Transformers

Transformer Protection

Africa Utility Week Focus Day Substation Condition Monitoring Benefits of Ultrasound

(2) New Standard IEEE P (3) Core : (4) Windings :

A Study of Winding Failure Modes in Laboratory Scale Transformers

HOW TO SAFE GUARD THE TRANSFORMER..???

Bachelor s thesis in Technology for the degree of Bachelor of Science in Technology submitted for inspection in Vaasa, 7 th of September, 2010.

Acoustic Emission in power transformers. Ajusco 15, Colonia Portales, Delegación Benito Juárez, C.P , México, D.F.

HOLISTIC APPROACH TO ON-LINE TRANSFORMER MONITORING: KNOWLEDGE MANAGEMENT FIRST!

Transcription:

RESIDUAL LIFE ASSESSMENT OF GENERATOR TRANSFORMERS IN OLD HYDRO POWER PLANTS Authored by: Sanjay Srivastava, Chief Engineer (HE&RM), Rakesh Kumar, Director (HE&RM), R.K. Jayaswal, Dy. Director (HE&RM) & Amit Roy Singal, Asst. Director (HE&RM). Presented by: Rakesh Kumar, Director (HE&RM), CEA

INTRODUCTION Renovation, Modernization, Uprating and Life Extension (RMU&LE) has been recognized worldwide as a well proven cost effective technique for improving the performance, efficiency and reliability of old Hydro Power Plants (HPPs). Generator Transformer is one of the most important and costly component of power generation next only to the generator. Any discussion on the topic of Life Extension of the generating station will not be complete without discussing the ways and means of Life Extension of the Generator Transformers.

AGEING OF GENERATOR TRANSFORMERS Ageing of solid insulation materials like Paper, Press Board,Wood based laminates etc. Ageing and degradation of Insulating Oil. Wear and tear of moving parts like Tap Changing Mechanism, Pressure Relief Device, Monitoring equipments etc. Corrosion of metallic parts exposed to atmosphere. In addition to the above, accelerated ageing taking place in the transformer on account of the following abnormal operating conditions: Overloading of Transformers. Operation under overvoltage conditions. Impact of lightning/ switching surges from the system. Operation under short circuit conditions.

TESTS ON GENERATOR TRANSFORMERS Dissolved Gas Analysis (DGA) of transformer oil. Monitoring of water content in transformer oil. Monitoring of Capacitance and Tan-Delta values of Condenser Bushing. Partial Discharge (PD) measurement. Winding Resistance Measurement Percentage Impedance Measurement Insulation Resistance Test Furan Analysis Magnetizing Current Test Sweep Frequency Response Analysis (SFRA) DIRANA Test Harmonics Measurement

DISSOLVED GAS ANALYSIS (DGA) Number of gases are produced as by-products of the ageing taking place in the insulating materials 1. Hydrogen 5. Acetylene 2. Methane 6. Carbon Dioxide 3. Ethane 7. Carbon Monoxide 4. Ethylene 8. Oxygen

MECHANISM OF GAS GENERATION IN TRANSFORMERS Partial Discharge in Oil Large amount of H 2 and little CH 4 Arcing in Oil (Power Discharge) Large amount of H 2 and C 2 H 2 Oil Overheating CH 4, C 2 H 6, C 2 H 4 are formed in increasing order of severity Traces of C 2 H 2 in case of very high temperatures Cellulose Overheating by Electric Fault Large quantities of CO & CO 2

DISSOLVED GAS ANALYSIS (DGA) Method recommended by CIGRE Task force Gas Concentration Ratios Ratio Value Indication C 2 H 2 /C 2 H 6 H 2 / CH 4 CO 2 / CO C 2 H 2 / H 2 >1 >10 >10 <3 >2 (with C 2 H 2 >30) Discharge Partial discharge Cellulose overheating Cellulose degradation by electric fault Fault gases diffusing into main tank from OLTC

DISSOLVED GAS ANALYSIS (DGA) Method recommended by IEC 60599 (1999) Concentration ratio between gases Case Characteristic fault C 2 H 2 /C 2 H 4 CH 4 /H 2 C 2 H 4 /C 2 H 6 CO 2 /CO C 2 H 2 /H 2 O 2 /N 2 PD Partial discharges (*) < 0.1 <0.2 - - - D1 Low energy discharges >1 0.1-0.5 >1 - - - D2 High energy discharges 0.6-2.5 0.1-1 >2 - - - T1 Thermal fault (<300 o C) (*) (*) <1 - - - T2 Thermal fault (300,700 o C) <0.1 >1 1,4 - - - T3 Thermal fault (>700 o C) <0.2 >1 >4 - - - Cellulose (paper) degradation by electric fault Fault gases diffusing into main tank from OLTC Excessive consumption of oxygen as a result ofoil oxidation and/or paper ageing - - - <3 - - - - - - >2to3 - - - - - - <0.3 (*) Not significant Note: In some countries, the ratio CH 4 /H 2 is used instead of C 2 H 4 /C 2 H 6.

WATER CONTENT MEASUREMENT Hydrogen generated during ageing combines with the free oxygen present in the oil and forms water. A part of this is absorbed by the cellulose insulation and the balance remains as moisture in oil. As paper is highly hygroscopic in nature, when transformer is filled with oil, it absorbs the moisture from oil, which affects its insulation properties as well as reduces its life System Voltage of Transformer kv Water content ppm, max. Above Up to and including - 72.5 20 72.5 245 15 245 420 10 420 800 10

TAN DELTA AND CAPACITANCE ON WINDINGS AND BUSHINGS This test is used to assess the condition of the oil and cellulose in terms of moisture, insulation, etc. The advantage of this method is that it identifies the winding (HV or LV) that has a possible problem. Dissipation factor of 0.5% is considered high whereas value of 1% is considered hazardous for operation of transformer and may require its replacement if completed its normal operating life. Capacitance value of bushing in service need to be compared with factory test result value for deciding the extent of degradation.

WINDING RESISTANCE MEASUREMENT Transformer winding resistance measurement is carried out to calculate the I 2 R losses and to calculate winding temperature at the end of a temperature rise test. Winding resistance result should not vary by 5% with factory test results or duplicate transformer result.

PERCENTAGE IMPEDANCE MEASUREMENT The percentage impedance of a transformer is the volt drop on full load due to the winding resistance and leakage reactance expressed as a percentage of the rated voltage. Test results must verify the nameplate rating. Percentage error should be within 3%.

INSULATION RESISTANCE TEST Insulation resistance tests are made to determine insulation resistance between individual windings to ground or between individual windings. It shows the condition of insulation.

POLARIZATION INDEX TEST It is a ratio of the Insulation Resistance Measured for 10 minutes to the insulation resistance value measured after 1 minute. PI is a good indication of winding contamination, moisture ingress (leakage currents), and/or bulk insulation damage (conduction currents). Acceptable PI for Power Transformers is greater than 1.5. For Distribution Transformer, it should be at least 1.3.

DEGREE OF POLYMERISATION (DP) Remnant life of a transformer in service depends mainly on the degree of degradation of the insulating materials DP is the average molecule size and closely relates to the mechanical properties of paper Early and precise diagnosis of degradation not possible through DGA. IEEE C57.91 loading guide mentions that one should be able to operate a transformer well dried, oxygen free, and with 110 deg C hotspot for 135,000 hours until 25% of retained tensile strength (75% loss), or 150,000 hours until a DP of 200 is reached (80% loss of tensile strength).

LIFE ASSESSMENT BY DP METHOD

Limitations DEGREE OF POLYMERISATION (DP) Test is invasive in nature. Sample can be taken only after taking the equipment out of service. Taking paper sample is a tedious job. Collected sample may not be representative of entire insulation.

FURAN ANALYSIS The concentration of furans in the mineral oil of a power transformer is a good indicator of the condition of the cellulose materials such as paper, pressboard and cotton tapes used for insulation. Not an oil quality test. Historically used as a major input for RLA of transformers. Furan analysis is used as a supplement along with DGA & DP tests Limiting value of total furanic content is Good Health : <3mg/Kg Satisfactory health : 3-5 mg/kg Deteriorated health : >5mg/Kg

MAGNETIZING CURRENT TEST Magnetizing current test of Transformer is performed to locate defects in the magnetic core structure, shifting of windings, failure in turn-to-turn insulation or problem in tap changers. Useful in distinguishing between severe and less severe cases. An agreement to within 25% of the measured exciting current with the previous test is usually considered satisfactory. If the measured exciting current value is 50% higher than the value measured during pre-commissioning checks, then the winding needs further analysis.

SWEEP FREQUENCY RESPONSE ANALYSIS (SFRA) This test passes a range of frequencies (between 10 Hz to 2 MHz) through the transformer and then calculates the transfer function. From these responses, the mechanical condition can be assessed. Reliable and sensitive method to evaluate the mechanical and electrical integrity of transformers active part. FRA is also carried out periodically for detection of deformation of smaller magnitude, when transformer experiences several short circuit forces. Helps in monitoring health and condition assessment of transformers.

DIELECTRIC RESPONSE ANALYSER (DIRANA) TEST DIRANA determines the water content in paper without the need of oil sampling. It combines Frequency Domain Spectroscopy (FDS) and Polarization Depolarization Current (PDC+) The power dissipation factor of the insulation is measured over a wide frequency ranging from the µhz to the khz region. The resulting curve contains information about the insulation condition. The very low frequencies contain information on moisture in the solid insulation, while the position of the slope in the mid-range frequencies indicates the conductivity of the liquid insulation. DIRANA is the only device which compensates the influence of ageing byproducts. Otherwise, this would lead to an overestimation of the water content in aged transformers.

HARMONICS MEASUREMENT The harmful effects of harmonic voltages and currents on transformer performance often go unnoticed until an actual failure occurs. Application of non-sinusoidal excitation voltages to transformers increase the iron losses in the magnetic core of the transformer. A more serious effect of harmonic loads served by transformers is due to an increase in eddy current losses. The increase in transformer eddy current loss due to harmonics has a significant effect on the operating temperature of the transformer.

Insulation section TYPICAL CASE STUDY Test Results RLA Study on 5.888MVA, 6.6/66kV Generator Transformer in about 40 Year Old Hydro Power Plant Insulation Resistance 60sec (G ) Polarization Index Tan (%) Moisture content (%) HV Winding versus LV Winding connected to Grounded Tank 0.0724 0.98 11.016 5.11 HV Winding versus LV Winding (Ungrounded) 0.0907 0.99 11.474 5.40 LV Winding versus HV Winding connected to Grounded Tank 0.0367 1.00 9.786 5.65 Oil Test DGA Furan Analysis Parameters within permissible limits High concentration of ethylene 4.8 mg/kg

OBSERVATIONS ON TEST RESULTS Insulation Resistance shows poor condition of insulation. PI values less than 1 are questionable. Limit of Tan Delta for aged transformer is 1%. Tan Delta values for this transformer are very poor. Results largely exceed normal limits as per service life and indicate over ageing of transformers. Moisture content shows that the transformer is in wet condition. The oil test results are normal and the oil parameters are within permissible limits as per IS 1866:2000. The DGA results exhibits high concentration of ethylene gas indicating possible overheating or thermal fault in the transformer. Furan analysis shows presence of high quantity (4.8 mg/kg) of furanic compounds. This shows poor health of paper insulation.

Thank You