Gas-Insulated Metal-Clad Switchgears Express-Diagnostics Method on Partial Discharge Characteristics

Similar documents
PD Solutions. On-Line PD Measurement Devices

Africa Utility Week Focus Day Substation Condition Monitoring Benefits of Ultrasound

OMICRON Seminar on Partial Discharge Diagnostics on HV Assets. January 30, 2018 Beirut, Lebanon

International Journal of Advance Engineering and Research Development. Comparison of Partial Discharge Detection Techniques of Transformer

Condition Assessment of High Voltage Insulation in Power System Equipment. R.E. James and Q. Su. The Institution of Engineering and Technology

Advancements in online partial discharge monitoring and assessment of MV through EHV Substation assets

Calculation of Transient Overvoltages by using EMTP software in a 2-Phase 132KV GIS

Software System for Finding the Incipient Faults in Power Transformers

Testing of 400 kv GIS

Specialists in HV and MV test and diagnostics. Testing in Substations

THE PROPAGATION OF PARTIAL DISCHARGE PULSES IN A HIGH VOLTAGE CABLE

Why partial discharge testing makes good sense

CHAPTER 5 CONCEPT OF PD SIGNAL AND PRPD PATTERN

Electrical Equipment Condition Assessment

PD Testing Considerations for MV Plant Cables

Experimental Investigations and Calculations in 6-35 kv Networks with Various Neutral Conditions

The Generators and Electric Motor Monitoring and Diagnostics Systems

THE POWER OF LIFE. WinTech Partial Discharge based Predictive Intelligence of insulation system to eliminate power failure risk.

10. DISTURBANCE VOLTAGE WITHSTAND CAPABILITY

Modeling insulation in high-voltage substations

EI HIGH VOLTAGE INSULATION TESTING POLICY

PARTIAL DISCHARGE MEASUREMENT AS A DIAGNOSTIC TOOL FOR CURRENT TRANSFORMER

Measurement Of Partial Discharge (PD) In High Voltage Power Equipment

Basics of Partial Discharge. Prepared for 2015 Phenix RSM Meeting January 2015

Knowledge Is Power SM Apparatus Maintenance and Power Management for Energy Delivery. Application of EMI Diagnostics to Hydro Generators

PARTIAL DISCHARGE DETECTION - AN OVERVIEW

HVDC Transmission. Michael Muhr. Institute of High Voltage Engineering and System Performance Graz University of Technology Austria P A S S I O N

Power Frequency Withstand Voltage On-site testing of 400 kv GIS

Estimation of Re-striking Transient Overvoltages in a 3-Phase 132KV Gas insulated Substation

ELECTRICAL EQUIPMENT. Inspection. H.H. Sheik Sultan Tower (0) Floor Corniche Street Abu Dhabi U.A.E

ECP HV INSULATION TESTING

Estimation of Re-striking Transient Over voltages in a 132KV Gas insulated Substation

GIS Instrument Transformers: EMC Conformity Tests for a Reliable Operation in an Upgraded Substation

Partial Discharge Detection of High Voltage Switchgear Using a Ultra High Frequency Sensor

The University of New South Wales. School of Electrical Engineering and Telecommunications. High Voltage Systems ELEC9712. Appendix Partial Discharge

IMPORTANCE OF ACCURATE MEASUREMENTS DURING THE LIFE CYCLE OF UTILITIES

1409. Comparison study between acoustic and optical sensors for acoustic wave

IEEE Transactions on Power Delivery. 15(2) P.467-P

PD ANALYSIS OF GAS INSULATED MEDIUM VOLTAGE SWITCHGEAR DURING FACTORY ASSEMBLY AND SITE COMMISSIONING

Application Note. Detection of Partial Discharge Using Ultrasound. Detection of Partial Discharge Using Ultrasound. Problem. iriss.

Practical Experience in On-Line Partial Discharge Measurements of MV Switchgear Systems

High Field Electrical Conduction and Breakdown in Solid Dielectrics

GIS Disconnector Switching Operation VFTO Study

Abstract. 1 Introduction

USING DAMPED AC VOLTAGES

The importance of partial discharge testing throughout the development and operation of power transformers

Simulation Model of Partial Discharge in Power Equipment

Testing and PD Diagnosis of MV Cable Systems with DAC Voltage Educational Session May St Pete Beach, Fl

On-line Partial Discharge Assessment and Monitoring of MV to EHV Cables

CHAPTER 2. v-t CHARACTERISTICS FOR STANDARD IMPULSE VOLTAGES

Partial Discharge Measurements on 110kV Current Transformers. Case Study. Results

Partial Discharge Measurement and Monitoring on High Voltage XLPE Cables

TECHIMP Power Transformer Monitoring

The Application of Partial Discharge Measurement and Location on CGIS

Modeling and Analysis of a 3-Phase 132kv Gas Insulated Substation

ROEVER ENGINEERING COLLEGE ELAMBALUR, PERAMBALUR DEPARTMENT OF ELECTRICAL & ELECTRONICS ENGINEERING

ECP HV INSULATION TESTING

PD Diagnostic Applications and TechImp solutions

Sources of transient electromagnetic disturbance in medium voltage switchgear

CONTENTS. 1. Introduction Generating Stations 9 40

Electromagnetic Disturbances of the Secondary Circuits in Gas Insulated Substation due to Disconnector Switching

NEW MV CABLE ACCESSORY WITH EMBEDDED SENSOR TO CHECK PARTIAL DISCHARGE ACTIVITY

TECHNICAL REPORT. Insulation co-ordination

PORTABLE COMPLEX FOR REMOTE CONTROL OF HIGH-VOLTAGE INSULATORS USING WIRELESS DATA COLLECTION AND TRANSMISSION MODULE

The influence of environment on condition of location damage in screen of the coaxial cable. 1. Introduction

ON-LINE PARTIAL DISCHARGE TESTING OF SOME OF THE WORST PERFORMING CIRCUITS ON A UTILITY DISTRIBUTION SYSTEM

Cable testing and diagnostics

OMICRON Seminar on Substation Testing and Diagnosis. October 23, 2017 Dubai, United Arab Emirates. October 24, 2017 Abu Dhabi, United Arab Emirates

MONTRANO. Continuous monitoring system for power transformers

A Reflectometer for Cable Fault Location with Multiple Pulse Reflection Method

CVVOZE Power Laboratories (CVVOZEPowerLab)

Gas-Insulated Medium-Voltage Switchgear siemens.com/8dab12

ELEC Transmission i and

Reuse of SF 6 Gas in Electrical Power Equipment and Final Disposal. CIGRE Report #117. July 1997

INTEGRATED TRANSMISSION PLAN Glossary

Substation Preventive Maintenance

Abstract. 1 Introduction

KEYWORDS On-line diagnostics, cable termination, partial discharge (PD), ultra-high frequency (UHF), sensitivity check.

NOISE REDUCTION AND SOURCE RECOGNITION OF PARTIAL DISCHARGE SIGNALS IN GAS-INSULATED SUBSTATION

Investigation of PD Detection on XLPE Cables

Session Four: Practical Insulation Co-ordination for Lightning Induced Overvoltages

TECHIMP Technologies & Services for Diagnostics and Monitoring of High Voltage Assets

NOVEL METHOD FOR ON-SITE TESTING AND DIAGNOSIS OF TRANSMISSION CABELS UP TO 250KV

Partial discharge diagnostics on very long and branched cable circuits

PARTIAL DISCHARGE MEASUREMENT

PHG 70 TD PD / PHG 80 TD PD

Digital Signal Processing for the Detection and Location of Acoustic and Electric Signals from Partial Discharges

Insulation Level and Test Technology of. 1000kV Power Transformer

The R Portable Device for Partial Discharge Measurement and Analysis in High Voltage Equipment Insulation

Partial Discharge Theory, Modeling and Applications To Electrical Machines

Extended analysis versus frequency of partial discharges phenomena, in support of quality assessment of insulating systems

2000 Mathematics Subject Classification: 68Uxx/Subject Classification for Computer Science. 281, 242.2

Field Measurement of Transmission Cable Dissipation Factor

FAULT IDENTIFICATION IN TRANSFORMER WINDING

High-Voltage Test and

Application of HFCT and UHF Sensors in On-Line Partial Discharge Measurements for Insulation Diagnosis of High Voltage Equipment

Aspects of PD interpretation in HV power cables. by Edward Gulski, Piotr Cichecki, Rogier Jongen

Comparison of capacitive and inductive sensors designed for partial discharges measurements in electrical power apparatus

C I R E D 21 st International Conference on Electricity Distribution Frankfurt, 6-9 June 2011

ELECTRICAL POWER ENGINEERING

Transcription:

Gas-Insulated Metal-Clad Switchgears Express-Diagnostics Method on Partial Discharge Characteristics ALEXANDRA KHALYASMAA 1, STANISLAV EROSHENKO 1, EGOR MARYSHKO 2, ALEXANDR OVSIANNIKOV 2 1 Ural Federal University named after the first President of Russia B. N. Yeltsin Mira Str. 19, 620002, Ekaterinburg 2 Novosibirsk State Technical University Prospekt K.Marksa Str. 20, 630073, Novosibirsk RUSSIA lkhalysmaa@mail.ru Abstract: - This paper describes a method for the express diagnostics of gas-insulated metal-clad switchgears (GIS) based on the characteristics of partial discharges. The research objects in this work were GIS of 110 kv and above. The subject of the research were methods of detecting partial discharges (PD) in GIS and highvoltage bushings of the air SF6 type, interpreting the measured signals for selection from interference, locating the PD seat, determining the type of defect and assessing its danger for continued operation. The purpose of this work was to improve the diagnostic method for GIS in operation based on the PD characteristics. In the framework of this research, physical and mathematical modeling of the devices protecting the signal from external interference and measuring the PD characteristics in the laboratory and in operating conditions were carried out; digital methods of analysis and processing of PD signals were used. Key-Words: - gas-insulated switchgear, partial discharge, technical diagnostics, express diagnostics, SF6 gas. 1 Introduction Nowadays in modern power engineering gasinsulated equipment is increasingly being used for new construction and renovation: switchgear, high-voltage switches, current and voltage transformers, gas-insulated transmission lines, power transformers [1]. The equipment with SF6 insulation is highly reliability, has compact dimensions, low fire risks, environmental safety and other benefits. The weakest elements of GIS are breakers and disconnectors. To a lesser extent, the switchgear rooms as a whole, voltage transformers and air SF6 bushings are damaged. In most cases, the insulation structures of these elements fail, and in turn, their damage and aging are in many ways due to the influence of partial discharges (PD). GIS have a number of insulation problems despite the high reliability: by-products of SF6 gas decomposition by the arc and PD; environmental hazard of SF6 gas; high-frequency overvoltages in commutations; reliability of support insulators; contamination of SF6 gas with metal particles. Many installation errors and inadequate quality assurance procedures can lead to highintensity PD that, in the presence of moisture, cause toxic by-products of SF6 gas. Typical GIS faults are: SF6 gas leakage; contamination of SF6 gas with metal or dielectric particles; contamination of SF6 with arcing products; roughness, protrusions and burrs on conducting parts; internal defects of supporting insulation in the form of gas cavities, peelings or cracks. With the exception of leakage, all other faults are potential seats of the PD occurrence and, accordingly, can be detected when detecting certain characteristics of the PD. For these reasons, the development of lowcost, effective and non-destructive diagnostic methods for partial discharge identification in gas-insulated switchgear is of crucial importance. ISSN: 2367-8976 17 Volume 3, 2018

2 Partial discharges The PD is a localized electrical discharge inside an insulating medium located between two electrodes. Various types of discharges, such as the corona, electron avalanche, multi-avalon (Townsend) discharges, streamers, barrier discharges and microdischarges in the impact of charged particles can be attributed to the PD. The PD is a very complex phenomenon that has a chaotic, nonstationary or fractal type of behavior with unpredictable transitions between different physical mechanisms. The confusion in the classification of PD mechanisms is a consequence of the diversity of geometric, physical and chemical factors affecting the PD. In most of the cases considered, the PD is a gas discharge in the cavities of a solid dielectric. The type of dielectric can affect the behavior of the PD due to the formation of secondary electrons or changes in the local field because of the accumulation of surface or space charge. Essentially, the PD process can be described by a system of differential equations. In general, the PD model should include both physical and chemical processes associated with changes in the properties of the medium and the dielectric at the PD location and leading to a change in the PD behavior. Now, the PD recording has become an obligatory element of quality control of GIS elements at the manufacturing plants and quality control of the GIS assembly in the pre-start tests. As practice shows, the PD intensity indicates the state of GIS insulation also in the process of operation. It is noted that the PD intensity begins to rapidly increase to (20 100) pc a few days before the failure. Today, acoustic, electric, electromagnetic and chemical methods are used to record PD in GIS. 3 Express-diagnostics of Gasinsulated Switchgear Currently, the most common methods for registration of partial discharges in gasinsulated switchgear include taking out of service for repair and diagnostics or the installation of a real-time stationary partial discharge monitoring system. Both options presuppose significant financial costs [2]. For these reasons, the development and implementation of new non-destructive control methods of the gas-insulated switchgear are of great importance. Based on the analysis of national and foreign practical experience, the following key steps of the diagnostics were identified: analysis of main design solutions of the switchgear; selection of the type and location of partial discharge sensors; providing measures against external and internal interference; identification of partial discharge source location; identification of possible causes of partial discharge effect occurrence; determination of the danger rate of the partial discharges; providing recommendations for further actions. 3.1 Gas-insulated switchgear Before starting the diagnostics, when analyzing the design of the switchgear, special attention is paid to the following aspects [3]: the type of the switchgear assembly; constructive design of separate modules connection of gas-insulated switchgear; the presence of radio-transparent windows in the shell of the switchgear; the presence of inputs cable - SF6 ; the presence of air-gas-insulated inputs with condenser type insulation; the presence of built-in sensors of partial discharges (inductive, capacitive, electromagnetic). 3.2 Partial discharge sensors selection and allocation Based on the analysis of design features of the gasinsulated switchgear under consideration, types of sensors and a list of places suitable for partial discharge registration are selected [4]: built-in capacitive partial discharge sensors; high-frequency current transformers (HCTT) on the grounding conductors of cables shields, grounding of cones of cable glands or testing airgas-insulated inputs; add-on electromagnetic sensors on dielectric windows; add-on electromagnetic high-voltage or ultrahigh-voltage sensors on dielectric belts at the junctions of modules; ISSN: 2367-8976 18 Volume 3, 2018

The second step is to determine the location of the partial discharge source inside the switchgear. It is made on the basis of time tag comparison of the signals, arriving to separate sensors of the metering circuit (Figure 2). The distance X between the sensors is calculated from the design drawings of the switchgear. Then (1) the distance between (1) the partial discharge source and the first sensor is calculated according to the following equation: X1 X X1 X2 2 X c T 2 (2) acoustic sensors on the surface of the switchgear shell. The calculation of the optimal number of partial discharge sensors, which is necessary for effective control of the entire internal volume of the gasinsulated switchgear, is carried out according to the following expression: DPD 3 Ninp TGIS Nbus where N inp the number of gas-insulated switchgear inputs; N bus the amount of switching points of gas-insulated switchgear buses; T GIS gas-insulated switchgear design (for single-phase 3, for three-phase 1). The proposed approach requires 3-4 times smaller number of partial discharge sensors, than in case of each gas-insulated switchgear compartment control. where Х the distance between the first and the second sensor, Х 1 the distance between the partial discharge source and the first sensor, Х 2 the distance between the partial discharge source and the second sensor, с electromagnetic wave propagation speed с=0,3 m/ns, T the difference between the time tags of the sensors. 3.3 External and internal interference reduction methods The problem of transmitted signal protection from induced interference is solved using a developed fiber optic channel, the functional diagram of which is shown in Figure 1. The fiber optic channel includes the following elements [5]: transmitter that converts the electrical signal at the output of the discharge sensor; signal transmission channel - fiber-optic communication line; receiver - a device, that converts an optical signal into an electrical signal. Fig.1. Fiber-optical measuring channel: 1-sensor, 2-transmitter, 3-fiber-optic link, 4-receiver, 5-recording device 3.4 Partial discharge source identification Firstly, it is necessary to identify whether the source of the partial discharge is inside the object under consideration or outside it. When performing express diagnostics, the switchgear is not taken out of the operation, therefore, it is not an isolated object and it is connected to other substation equipment by means of cable links or by means of busbars via air-gas-insulated inputs. Fig.2. Identification of the distance between the sensor and partial discharge source in gas-insulated switchgear 3.5 Determination of possible causes of partial discharge and the danger level for the subsequent operation Depending on the location of the partial discharge source, it is possible to determine the potential causes of its occurrence, as described in Table 1. Table 1. Partial discharge causes Partial discharge source Defect description A typical source of partial Located in the junction of discharges are microcavities or the compartments of gasinsulated switchgear separating the compartments of microcracks in support insulators gas-insulated switchgear Located near the module, containing a current or voltage transformer Located near the cable or overhead wire input Located near the busbar module, which does not contain any additional equipment The potential source of the partial discharge is the damaged insulation of the current or voltage transformer The potential source of the partial discharge is the end of the input "cable - SF6 gas" or the input "air - SF6 gas" Potential source of partial discharge is free metal particles ISSN: 2367-8976 19 Volume 3, 2018

4 Case Study The validation of the developed method of express registration of partial discharges is carried out on the basis of diagnostics of the technical state of a 220 kv SF6 switchgear at 220 kv Substation Vlasikha in Barnaul, Russia. Measurements for partial discharges identification was carried out using highfrequency current transformers RFCT-4 manufactured by Dimrus and a digital oscilloscope Tektronix DPO3014. The following measurements were made: synchronous measurement of the signals from different points of sensors connection on the cable entry; synchronous measurement of signals on the grounding of the cones of the three phases of the "cable-sf6" inputs; synchronous measurement of signals on the grounding of the cones of all cable inputs, separately for each phase. The identification of the source of the signal within the diagnosed object was determined using a time-of-flight (wave) method. The results are shown in Table 2. Channel Table 2. First negative peak parameters Signal arrival Peak delay relative to recording the time of the time, ns first registration, ns Signal amplitude, mv 1 129592.8 0.4 26.78 2 129592.4 0 28.19 3 129737.6 145.2 3.23 4 129660.0 67.6 2.76 The calculation of the signal travel time and the distance from the source of partial discharge to the sensor 2 is carried out according to (3): T L 2 T 2 c, X L c T (3) (3) 2 2 The propagation velocity of the signal was assumed to be equal to the speed of light c = 299792458 m/s. Based on the design documentation, the distance between the sensors of the 1st and 2nd channels was determined, where the signal from the partial discharge source was initially detected L = 18 m. The running time to the second channel sensor was T2 = 28 ns, which corresponds to a distance of 8.4 m. The most accurately recorded signal (Figure 3) in terms of the amplitude and the shape corresponds to the oscillogram obtained for the defect model "current conductor protrusion - shell of the switchgear", combined with dielectric particles in the discharge gap (Figure 4). The cause of the protrusion appearance on the conductor can be the low quality of surfacing of the current conductor during production or the damage, obtained during installation of the switchgear. Dielectric particles inside the pressurized shell of the switchgear compartment is usually a metal dust, that appeared inside the shell during installation works. Such dust is usually concentrated around the increased electric field strength. The apparent charge of partial discharges calculated from the oscillogram is 4.98 pc. The following conclusions can be drawn: The source of partial discharge is a small protrusion on the current conductor, possibly with the presence of free dielectric particles in the discharge gap. The apparent charge of the partial discharge does not exceed 5 pc and in accordance with [6] does not exceed the marginal level for the equipment. The equipment is in a good technical state, further operation is possible. Fig.3. Oscillogram of the signal registered inside the switchgear Fig.4. Signal template of the defect "protrusion on current conductor gas-insulated switchgear shell "plus dielectric particles 5 Conclusion The gas-insulated equipment has established itself as a reliable and technological alternative to equipment with oil or air insulation. However, the relatively high cost restrains its widespread introducing into operation. At the same time, new equipment requires more careful monitoring of its ISSN: 2367-8976 20 Volume 3, 2018

parameters, which contributes to the development of new methods for monitoring and diagnosing the technical state and improving existing ones. Diagnostics or monitoring of the technical state of gas-insulated switchgear requires the control of the pressure of SF6 gas and its properties, as well as the detection and assessment of the number of defects on the basis of partial discharge intensity records. Most of the types of partial discharge analysis are carried out in the framework of commissioning tests at the installation site of the switchgear, and the installation of continuous monitoring systems requires additional capital investment. The possibility of using the developed methodology for the operational recording of partial discharges in GIS is checked in practice. New methods of simulating the partial discharge for calibrating the registration system are proposed. In practice, the possibility of using the developed method of express registration of partial discharges in the switchgear is verified. References: [1] Report of CIGRE WG 23.10. SF6 and the Global Atmosphere // Electra. 1996. No. 164. pp.121 132. [2] Arakelian, V.G. Diagnostics for the condition of SF6 equipment based on physico-chemical parameters / V.G. Arakelian, A.J Kovalenko // IEEE Elec-trical Insulation Magazine. 2001. Vol. 17, No. 2. pp. 42-51. [3] Van Brunt, R.J. Stochastic Properties of Partial-Discharge Phenomena [Текст] / R.J. Van Brunt // IEEE Trans. Elec. Insul. 1991. Vol. 26. pp. 902 948. [4] Arshansky, I.S. The development of SF6- insulated test-sets for GIS die-lectric tests / I.S. Arshansky, S.Y. Matveev, [et al] // Proc. of 9th Intern. Symp. on High Voltage Engineering, Graz, Austria, 1995. Report 5276. [5] Halkiadis, I.S. A high-voltage low-cost wideband fiber optic transmission system with improved linearity [Текст] / I.S. Halkiadis, N.G. Theofanous, D.A. Greaves // Electric Power Systems Research. 1996. No. 37. pp. 121 128. [6] National Standard GOST 1516.3-96 Alternating current power equipment 1 750 kv. Insulation requirements (1996). ISSN: 2367-8976 21 Volume 3, 2018