International Journal of Advance Engineering and Research Development. Comparison of Partial Discharge Detection Techniques of Transformer

Similar documents
PARTIAL DISCHARGE DETECTION - AN OVERVIEW

Africa Utility Week Focus Day Substation Condition Monitoring Benefits of Ultrasound

CHAPTER 5 CONCEPT OF PD SIGNAL AND PRPD PATTERN

Condition Assessment of High Voltage Insulation in Power System Equipment. R.E. James and Q. Su. The Institution of Engineering and Technology

Basics of Partial Discharge. Prepared for 2015 Phenix RSM Meeting January 2015

High Field Electrical Conduction and Breakdown in Solid Dielectrics

THE POWER OF LIFE. WinTech Partial Discharge based Predictive Intelligence of insulation system to eliminate power failure risk.

PARTIAL DISCHARGE MEASUREMENT AS A DIAGNOSTIC TOOL FOR CURRENT TRANSFORMER

Software System for Finding the Incipient Faults in Power Transformers

Simulation Model of Partial Discharge in Power Equipment

Why partial discharge testing makes good sense

High Frequency Voltage Stress. Presented by: Flore Chiang Date: March 30, 2012

The University of New South Wales. School of Electrical Engineering and Telecommunications. High Voltage Systems ELEC9712. Appendix Partial Discharge

Partial Discharge Patterns in High Voltage Insulation

Doble Solutions for Partial Discharge. Greg Topjian Solutions Manager

Advancements in online partial discharge monitoring and assessment of MV through EHV Substation assets

1409. Comparison study between acoustic and optical sensors for acoustic wave

Testing and PD Diagnosis of MV Cable Systems with DAC Voltage Educational Session May St Pete Beach, Fl

Measurement Of Partial Discharge (PD) In High Voltage Power Equipment

PARTIAL DISCHARGE MEASUREMENT

Partial Discharge Monitoring and Diagnosis of Power Generator

Application Note. Detection of Partial Discharge Using Ultrasound. Detection of Partial Discharge Using Ultrasound. Problem. iriss.

OMICRON Seminar on Partial Discharge Diagnostics on HV Assets. January 30, 2018 Beirut, Lebanon

Extended analysis versus frequency of partial discharges phenomena, in support of quality assessment of insulating systems

The importance of partial discharge testing throughout the development and operation of power transformers

THE PROPAGATION OF PARTIAL DISCHARGE PULSES IN A HIGH VOLTAGE CABLE

Electrical Equipment Condition Assessment

Fault Detection in Transformer Using Frequency (Sweep) Response Analysis

HVDC Transmission. Michael Muhr. Institute of High Voltage Engineering and System Performance Graz University of Technology Austria P A S S I O N

Partial Discharge Analysis of a Solid Dielectric Using MATLAB Simulink

Partial Discharge (PD) techniques for measuring the condition of ageing HV/MV switchgear

Partial Discharge Theory, Modeling and Applications To Electrical Machines

High Frequency Modeling of Two Limb Series Loop Winding for Partial Discharge Localization

PD Solutions. On-Line PD Measurement Devices

Specialists in HV and MV test and diagnostics. Testing in Substations

CHAPTER 2. v-t CHARACTERISTICS FOR STANDARD IMPULSE VOLTAGES

EFFECT OF INTEGRATION ERROR ON PARTIAL DISCHARGE MEASUREMENTS ON CAST RESIN TRANSFORMERS. C. Ceretta, R. Gobbo, G. Pesavento

Diagnostic testing of cast resin transformers

PATTERN CLASSIFICATION OF PARTIAL DISCHARGE IN LV WINDING OF 1- TRANSFORMER USING PCA

EI HIGH VOLTAGE INSULATION TESTING POLICY

International Journal of Advance Engineering and Research Development. Analysis of Surge Arrester using FEM

EE 1402 HIGH VOLTAGE ENGINEERING

Abstract. 1 Introduction

TECHIMP Technologies & Services for Diagnostics and Monitoring of High Voltage Assets

PD Diagnostic Applications and TechImp solutions

CONTENTS. 1. Introduction Generating Stations 9 40

Simulation of Partial Discharge in High Voltage Power Equipment

USING DAMPED AC VOLTAGES

Gas-Insulated Metal-Clad Switchgears Express-Diagnostics Method on Partial Discharge Characteristics

Investigation of PD Detection on XLPE Cables

High-Voltage Test and

MAHALAKSHMI ENGINEERING COLLEGE

Partial Discharge Classification Using Acoustic Signals and Artificial Neural Networks

EVALUATION AND COMPARISON OF ON-LINE PD DETECTION METHODS FOR HIGH-VOLTAGE POWER CABLE

MEDIUM & HIGH VOLTAGE

ROEVER ENGINEERING COLLEGE ELAMBALUR, PERAMBALUR DEPARTMENT OF ELECTRICAL & ELECTRONICS ENGINEERING

A1-209 EXPERIENCES IN IDENTIFICATION OF PARTIAL DISCHARGE PATTERNS IN LARGE HYDROGENERATORS

Evaluation of Partial Discharge in Power Transformers by Acoustic Emission Method and Propagation Modeling of Acoustic Signal

The Effect of Practical Voltages on Maximum Amplitude of Partial Discharge with Considering Different Number of Cavities

High Sensitivity Interferometric Detection of Partial Discharges for High Power Transformer Applications

Field Measurement of Transmission Cable Dissipation Factor

Testing of 400 kv GIS

PARTIAL DISCHARGE MEASUREMENT ANALYSIS ON RING MAIN UNIT

On-Site Partial Discharge Monitoring using the differential LEMKE PROBE LDP-5 and its accessories

Comparison of measurement methods for partial discharge measurement in power cables

CHAPTER 1 INTRODUCTION

ECP HV INSULATION TESTING

CHAPTER 10 HIGH VOLTAGE TESTING OF ELECTRICAL APPARATUS

A New Approach for Transformer Bushing Monitoring. Emilio Morales Technical Application Specialist Qualitrol

WinTech Partial Discharge Testing and Monitoring Systems

PULSE-SEQUENCE ANALYSIS OF PARTIAL DISCHARGES IN POWER TRANSFORMERS

TECHNICAL SPECIFICATION

Case Studies of Electric Power Equipment Diagnostics Using Acoustic Emission

RESIDUAL LIFE ASSESSMENT OF GENERATOR TRANSFORMERS IN OLD HYDRO POWER PLANTS

Partial Discharge Detection For Condition Monitoring Of An 11-kV XLPE Cable-Part II

APPLICATIONS OF ACOUSTIC LOCALIZATION TO ONLINE POWER TRANSFORMERS

IN HOUSE CALIBRATION OF PD DETECTOR SYSTEM FOR FIELD TEST RESULT RELIABILITY

A STUDY ON THE PERFORMANCE OF IMPEDANCE MATCHING CIRCUIT IN PARTIAL DISCHARGE MEASURING SYSTEM

Underground System Design TADP 547

Transformer Shunt Fault Detection using Two Techniques

HV AC TESTING OF SUPER-LONG CABLES

IN ELECTRICAL ENGINEERING - I C M E T CRAIOVA

Partial Discharge Measurement and Monitoring on High Voltage XLPE Cables

PD ANALYSIS OF GAS INSULATED MEDIUM VOLTAGE SWITCHGEAR DURING FACTORY ASSEMBLY AND SITE COMMISSIONING

Detection of Partial Discharges and its Effect on Solid Insulation used in High Voltage Cable

CVVOZE Power Laboratories (CVVOZEPowerLab)

Knowledge Is Power SM Apparatus Maintenance and Power Management for Energy Delivery. Application of EMI Diagnostics to Hydro Generators

Dispersing the clouds gain clear insight into your bushings using advanced diagnostic methods

OPTIMIZATION OF ON-SITE PD MEASUREMENTS AND EVALUATION OF DIAGNOSTIC PARAMETERS FOR ASSESSING CONDITION OF DISTRIBUTION CABLE SYSTEM ELPIS J SINAMBELA

GUJARAT TECHNOLOGICAL UNIVERSITY

Trees, vegetation, buildings etc.

Partial Discharge, Survey or Monitor?

Visualization of the Ionization Phenomenon in Porous Materials under Lightning Impulse

ON-LINE PARTIAL DISCHARGE DETECTION ON TRANSFORMERS

Parameters influencing Partial Discharge Measurements and their Impact on Diagnosis, Monitoring and Acceptance Tests of Power Transformers

Understanding the Value of Electrical Testing for Power Transformers. Charles Sweetser, OMICRON electronics Corp. USA

NOVEL METHOD FOR ON-SITE TESTING AND DIAGNOSIS OF TRANSMISSION CABELS UP TO 250KV

Partial discharge diagnostics on very long and branched cable circuits

Design and construction of double-blumlein HV pulse power supply

Power Voltage Transformers for Air Insulated Substations. THE PROVEN POWER.

Transcription:

Scientific Journal of Impact Factor(SJIF): 3.134 International Journal of Advance Engineering and Research Development Volume 2,Issue 7, July -2015 e-issn(o): 2348-4470 p-issn(p): 2348-6406 Comparison of Partial Discharge Detection Techniques of Transformer Jindal Kanasagara 1, Ch.V.Sivakumar 2 1 P.G Student, 2 AssistantProfessor Electrical Engineering Department, Parul Institute of Engineering and Technology Abstract Power transformer is considered to be one of the essential and costly equipment of power system. Identifying insulation faults in the best possible time prevents the appearance of irreparable damages. Partial discharge (PD) is one of the most important insulation faults. The objective of this paper is to contrast the different techniques used for detection and localization of PD at the initial stage in power transformer winding and to investigate which is the best insulating materials (paper and epoxy resins) to be used to prolong the power transformers life expectancy. From literature, it is found that information regarding detection of PD in power transformer is not enough to perform necessary actionbecause the location of PD is still unknown. So localization of PD is necessary to recommend corrective actions. In order toovercome this problem, different techniques such as electrical method, acoustic method, UHF detection method and opticalmethods are used to locate and detect the PD. UHF detection method has a many advantages compared to other PD detectionmethods such as immunity against background noise and other unwanted signals that can affect the measurement, reduce thedesign complexity, reduce the design cost and provides the accurate and precise location of PD source. Keywords-Power transformers; Partial discharge detection; Insulation defect detection; Design parameters; Acoustic method; Electrical method; optical method; Partial Discharge (PD) UHF detection; I. INTRODUCTION Power transformers have been in service for many years under different environmental, electrical, and mechanical conditions. They are very expensive and form a high percentage of the investment of a power system. Extending transformer life as long as possible is not only economically valuable, but also prevents lost revenues when power outages occur. The power outages are a result of ageing processes, electrical overstressing or presence of defects introduced during manufacture. PD is one of the major reasons for the short life span of power transformers. PD might occur anywhere inside a transformer particularly along the transformer winding and the discharge signal can propagate along windings to the bushing and neutral to earth connections. Therefore, the identification of a PD source as well as its location is essential to ensure that PD monitoring allows evaluation and maintenance processes to be carried out effectively. IEC (International Electrotechnical Commission) standard 60270 has defined partial discharge as a localized electrical discharge that only partially bridges the insulation between conductors and which can or cannot occur adjacent to a conductor. Partial discharges are in general a result of local electrical stress concentration in the insulation or on the surface of insulation. PD within an insulating material is usually initiated within gas filled voids within the dielectric. since the dielectric constant of the void is considerably less than the surrounding dielectric, the electrical field across the void is significantly higher than that across an equivalent distance of dielectric. If the voltage stress across the void is increased above the corona inception voltage for the gas within the void, PD activity will start within the void. When PD is occur in gases, it is called as a corona discharge. There are some similarities between corona and PD. They both are precursor of total breakdown, they take place where the voltage gradient is higher and the discharging current is very small in relation to the final breakdown current. The differences are also there, Corona discharge takes place in the surrounding air and it causes no permanent damage. When the voltage is removed, the air becomes normal again. PD causes permanent damage. Corona discharge is visible and audible but PD is not. PD can occur in both AC and DC supply. It is different from fully discharge because of that equipment is not permanently damage. PD is partially damage, it is just a starting of failure in high voltage equipments, and therefore it is called PD. In general the duration of PD pulse is much less than 1µs. PD activity is usually observed in high voltage power equipments like powertransformers, machines, switchgears, underground cables, etc. II. NECESSITY OF PARTIAL DISCHARGE IN TRANSFORMER @IJAERD-2015, All rights Reserved 301

The process of manufacturing transformer winding insulation structure involves several stages starting from selection and preparation of raw material, processing of raw material, thermal or chemical treatment if essential etc. The entire process of providing electrical insulation in a winding involves man, material, machines and different environmental conditions. It is therefore very difficult to achieve a perfect electrical insulation without defects as it may get contaminated during the process of manufacturing. The influence of surrounding thermal, electrical, mechanical and environmental stresses may also cause defects in electrical insulation during its operation. So some impurity is their due to presence of air bubble in winding. It weakens the insulation region and responsible for appearance of PDs. The region behind it is, dielectric constant of the void is less than of its surrounding. So it causes insulation failure in high voltage power transformer winding. Partial discharge has less magnitude but it is responsible for degradation. Due to event of discharge ultimately failure occurs in the insulation of winding. Because of the above reason PD detection and measurement is necessary for predication of insulation life for power transformer winding. [6] III. CLASSIFICATION OF PARTIAL DISCHARGE Partial discharge is mainly divided in two parts 3.1 External Partial Discharge External partial discharge takes place outside of the power equipments. Such types of discharges occur in overhead lines and armature etc. [1] 3.2 Internal Partial Discharge The discharges which take place inside of the power equipments are internal partial discharge. Partial discharge is defined as a localized discharge process in which the distance between two electrodes is only partially bridged i.e., the insulation between the electrodes is partially punctured. Partial discharges may originated directly at one of the electrodes or occur in a cavity in the dielectric some of the typical partial discharges are, (i) Corona discharge: Corona discharge takes place due to non-uniformity of electric field on sharp edges of conductor subjected to high voltage. The insulation supplied for such type of discharge is gas or air or liquid. Such type of discharges appears for a long duration around the bare conductor. They are not attacking directly to the insulation system like internal and surface discharges. just by the indirect action of ozone formed by corona deteriorates insulating materials used. Figure- 1 (a) Corona Discharges, (b) Electrical Treeing inside solid insulation (ii) Surface discharge: Surface discharges takes place on interfaces of dielectric material such as gas/solid interface as gets over stressed times the stress on the solid material. This may occur in bushing, end of cable, any point on insulator surface between electrodes (high voltage terminal & ground). The occurrence of such discharge depends on various factors such as 1. Permittivity of the dielectric material 2. Voltage sharing between the conductor 3. Properties of the insulating medium where PD occur Figure-2 Different kinds of cavities in a solid insulation (iii) Treeing channel: High intensity fields are produced in an insulating material at its sharp edges and it deteriorates the insulating material. That is responsible for production of continuous PD, called as Treeing channel @IJAERD-2015, All rights Reserved 302

Figure.-3 Surface Discharge (a) On the bushing surface close to the transformer flange, (b) On the end of outer semiconductor in a cable termination (iv) Cavity discharge: The cavities are generally formed in solid or liquid insulating materials. The cavity is generally filled with gas or air. When the gas in the cavity is over stressed such discharges are taking place. IV. EFFECT OF PD IN TRANSFORMER WINDING PD is the main reason for degradation of insulating material and responsible for breakdown in winding insulation. The occurrence of repetition rate of discharge is the reason for mechanical and chemical degradation of transformer winding. The conductivity property of insulating material rises due to chemical change in the dielectric. PD generates energy in the form of heat. Heat energy is the main reason for degradation of insulation this effect is called thermal effect for high voltage power transformer. The deterioration of insulation of the insulation can be known by monitoring the PD activity and it should be monitored time to time by power engineer V. PD DETECTION METHOD There are various methods are explored for the PD measurement based on both electrical and non-electrical phenomenon. The methods which have been commonly known for measurement of PDs are, [7] Partial Discharge techniques Acoustic Emission Optical Method UHF Method Electrical Method Figure-4 Partial Discharge Detection Techniques 5.1 Optical Detection Method In optical detection method light is dissipated in the form of ionization, excitation process during the appearance of discharge. The discharge of light is dependent on the insulating medium used and other parameters like temperature and pressure. Transparent type of insulating material is applicable for this detection method. So some complexity arises in case of implementation in high voltage transformers due to opaque nature of mineral oil. 5.2 Acoustic Detection Method In acoustic detection method, acoustic sensors are placed outside of the high voltage equipment for detection of PDs. The acoustic method is effective for perceiving and encoding the acoustic Signal generated during a partial discharge event. Acoustic methods have many advantages over other methods. Acoustic methods are unaffected to @IJAERD-2015, All rights Reserved 303

electromagnetic interference (EMI), which can reduce the sensitivity of electrical methods. The limitation of this detection method is the nature of acoustic wave propagation is complicated due to the use of non-homogeneous device like high voltage transformer. This method is widely applicable for detection of the different types of PD, finding the location of insulation failure. The difficulty arises behind this method is requirement of sensitivity. 5.3 Electrical Detection Method Electrical detection method is one of the most popular methods in HV power equipment for partial discharge measurement. Electrical detection method has been used to simulate the measurement of PDs in the model transformer. It focuses on appearance of the current and voltage pulse created by the current streamer in the void and impurities. The pulses are less than one second and variation of frequency components in the range of KHz, The shape of the pulse and occurrence of phase location within the ac cycle gives the information about type of PD and information about insulation failure. Time domain recording device is used for observation of partial discharge impulses in this detection method. Different signal processing methods are applicable for identification/detection of PD signal. This method is also applicable for online electrical PD detection. Broadband and narrow band electrical noises are found during the operation of HV power equipment. It is not easy to divide those electrical noises and PDs. The impulses which are received in this detection method depend on the geometry of high voltage transformers. This method has several drawbacks but has wide application in power plant which helps the power engineer and technician by giving necessary and important information regarding the characteristic, appearance of different type of partial discharge as well as about the occurrence of insulation failure in high voltage power equipment like transformer, generator, cable etc. Comparison Of The PD Detection Methods. Table 1 Comparison of PD detection methods [7] Features Electrical Acoustic Optical UHF Detection Advantages Disadvantages Possible sensors Application for all kinds of high voltage equipment. Intensity source, type, location of PD is assessable The most suitable for continuous online PD monitoring High electromagnetic interference Relative expensive cost Capacitive Inductive High sensitivity Immunity against electrical noise Very efficient for localization of PD Low signal intensity Not good for continuous PD measurement Piezo-electric transducers Condenser microphones Immunity against electrical noise Easy to measure Provide critical information Go/No Go decision No information about magnitude of PD Optical fiber UV detector Photomultiplier Tube Immunity against electrical noise Very efficient for localization of PD Identification of PD source Relative expensive cost Complex design UHF sensors RF sensors Antennas(Hilber t, monopole, loop antenna etc) Main application area All High Voltage Equipment Transformers GIS Transformer GIS Cables All High Voltage Equipment Element which are used in the comparison between Electrical,UHF Detection,Optical methods and Acoustic method are advantages, disadvantages, possible sensors and main application area. Clear data is shown in Table 1.Element which are used in the comparison between and are advantages, disadvantages, possible sensors and main application area 5.4 UHF Detection Methods @IJAERD-2015, All rights Reserved 304

Ultra High Frequency (UHF) detection method is one of the online PD detection in power transformer. Thus UHF PD detection has an advantage of strong anti-interference ability over traditional detection approaches. Firstly, ultra-high frequency (UHF) partial discharge detection was mostly focused on gas insulation substation (GIS). In recent two decades, research fields about UHF partial discharge detection have mainly included propagation characteristic of UHF electromagnetic wave in GIS, sensor design and optimization, UHF amplifier, default models in GIS and pattern classification, signal processing and features extraction. UHF partial discharge detection applied in power transformer was rampantly investigated for the past few years. However, as a novel partial discharge detection method, the ultrahigh frequency partial discharge detection also can be used in non-gas insulation electrical power apparatus such as transformer, cables and so on. CONCLUSION From the literature review, it is found that acoustic detection methods have advantages over electrical detection methods. The primary advantage of acoustic detection over electrical method is that position information is readily REFERENCES [1] M.S. Naidu, V. Kamaraju: High Voltage Engineering McGraw-Hill, 2004 [2] Transformer design &Practise (Textbook) By S.V. Kulkarni [3] A.Akbari, P. Werle, H. Borsi, E. Gockenbach: Transfer Function-based Partial Discharge Localization in Power Transformers: A Feasibility Study, IEEE Electrical InsulationMagazine, Vol. 18, No. 5, Sep./Oct. 2002, pp. 22 32. [4] High-voltage Test Techniques Partial Discharge Measurements, British Standard BS EN 60270:2001, IEC60270:2000,2001 [5] High-voltage Test Techniques Partial Discharge Measurements, IEC standard 60270, Third Edition, 2000. [6] S. D. BARMAN, modeling of high voltage power transformer winding for partial discharge test National Institute of Technology Rourkela [7] I A Soomro and M N Ramdon Study on different techniques of partial discharge (PD) detection in power transformers winding: Simulation between paper and EPOXY resin using UHF method International Journal of Conceptions on Electrical and Electronics Engineering Vol. 2, Issue. 1, April 2014 @IJAERD-2015, All rights Reserved 305