MITOS VT6 AIR USER MANUAL. 02/10/2015 Manual_MITOS_VT6_AIR_ver3p3_eng

Similar documents
FAST SAMPLING CONVERTER

Please enter the identity code of your device here!

OVEN INDUSTRIES, INC. Model 5C7-362

TOSVERT VF-AS1 PID control Instruction Manual

HD 9408T BARO - HD 9408TR BARO HD 9908T BARO - HD 9408PS 50

MA7200 PLUS INVERTER SERIES PID Quick Start Manual For Fan and Pump Applications

Please enter the identity code of your device here!

STR-LCF. Security Advice Caution. Notes on Disposal. Electronic Fan Coil Thermostat (Flush mounting) Datasheet. Application

HITACHI. L100-M Series Inverter Quick Reference Guide. Hitachi Industrial Equipment Systems Co., Ltd. Single-phase Input 100V Class

Ultrasonic level transmitter, non-contact

Series 10-ZSE80/10-ISE80

LCC-100 software User manual

+GF+ SIGNET Temperature Transmitter Instructions

( F L O W I Z F A M I L Y )

vacon 100 flow ac drives application manual

DP2500 DP0100 DP0250 Differential Pressure Transmitter

DP2500 DP0100 DP0250 Differential Pressure Transmitter

Series 10-ZSE30A(F)/10-ISE30A

TOSVERT TM VF-nC3 Parameter List

PRESSURE SENSORS I INSTALATION AND OPERATION INSTRUCTIONS ACCUTRON MDP BIDIRECTIONAL DIFFERENTIAL PRESSURE SENSOR

Configuration of class 210 transmitters by keypad

WATER MADE EASY MARINE ENERGY MUNICIPAL INDUSTRIAL

12 30 ripple included external fuse 3,0 A Current consumption A 1,0 2,6 depending from solenoid current. V ma. V ma. Output current A 1,0-1,6-2,6

Invertek Optidrive E3 Frequency Inverter (IP20, 3ph output) Easy Start Guide

APPENDIX APPENDIX A 1

Please completely read through operating instructions! Do not discard! The warranty shall be invalidated by damage caused by operating errors!

3400HD Series TECHNICAL MANUAL X-3400HD DTI-3400HD D-3400HD. 3400HD Unwind (using 3400ce Circuit Board) Montalvo. Unwind Tension Controllers

CZ-K Series. RGB Digital Fiberoptic Sensors. Description MAIN MENU PRODUCTS APPLICATIONS INDEX SELECTION GUIDE

The SFC 1000PA P2DAAA can be mounted on a prover trailer, which can be moved from field to field to provide proving services.

RCMS460 and RCMS490 Series

Electronic regulator for PWM controlled proportional solenoid valves FABER -

Series T. Amphenol Advanced Sensors. Differential Pressure Transmitters

Warranty conditions are available on this website: only in English version

6.9 Jump frequency - Avoiding frequency resonance

Monitoring Relay MR 50

MS 5000 CIAO SENSOR EXTREMELY EASY TO INSTALL THANKS TO PATENTED WRAPPER FIXING SYSTEM

Express Delivery. Axial. Connection

Jacket heater, etc Mounting bracket for Pipe wrapping. (Optional) Temperature sensor. Output (To heater) (Optional)

ISOMAG UNIQUE PID REGULATOR + MAG CONVERTER THE FRIENDLY MAG METER

7 Function description 7.1 Digital filter Alarm output

SS2 Linear / Rotary. Smart Valve Positioner. Smart performance with innovative and ever-strong coil drive even under harsh working environments

mass flowmeter for compressed air

AMANO PIX-21. Electronic Time Recorder. Operation Manual

Temperature Humidity < THA 300

User Manual TH300 > CTV310 > TH300 > < TT300 TT300 > Air velocity. Temperature Humidity. Temperature. Pressure CP300 > Standard probe.

Enhanced PID for Air Compressors F7 Drive Software Technical Manual

Series T. General Eastern Differential Pressure Transmitters. GE Sensing. Description

CONFIGURING DRIVE PARAMETERS

Temposonics. R-Series SSI. Absolute, Non-Contact Position Sensors. Temposonics RP and RH Stroke length mm. Perfect data processing 0.

Generator Speed Controller Model GSC 1

NX Series Inverters. HVAC Pocket Programming Guide

Varlogic NR6, NR12. Power factor controller. User manual

GB QUICK GUIDE FOR THE CONFIGURATION OF VARIABLE SPEED DRIVES

ADJUSTABLE SPEED DRIVES FS1

JUMO Wtrans Receiver Universal Receiver for JUMO Wireless Measuring Probes

SPECIFICATION NO Model Automatic GTAW Welding System

MHPS MHPS. Modular pressure transmitter. Technical documentation. Table of content. Characteristics - applications - technical data

P-SERIES VFD 1-40HP (200~230VAC), 1-400HP (380~480VAC),3Ø Dual Rated for Constant & Variable Torque Integrated PID Control

SJ100 Series Inverter Quick Reference Guide. Single-phase Input 200V Class Three-phase Input 200V Class Three-phase Input 400V Class

THYFREC-VT210S 400V System 37 to 315kW (C/T) 400V System 45 to 370kW (V/T) QUICK START GUIDE

Application Note CTAN #287

KINAX SR 719 Programmable Transmitter for Position Feedback

DPS 100 DPS 100. Gauge- / Differential- / Absolute Pressure Transmitter

USER MANUAL Version: 1.1

ED701 General Industry Pressure Transmitter

Please enter the identity code of your device here!

Connecting Mains Electrical Power

1-2 VOLTS PER HERTZ CHARACTERISTICS EXERCISE OBJECTIVE

JUMO Wtrans Receiver with Wireless Data Transmission

Operating Instructions

Analogue temperature controllers

Closed-Loop Position Control, Proportional Mode

Please enter the identity code of your device here!

control & display PROGRAMMABLE SENSOR CONTROLLER COMPLETE VERSATILITY OF SENSOR MANAGEMENT & DATA COMMUNICATIONS

Servomotor for butterfly valves VF, VFH. delta-elektrogas.com EE157-01/16

ITP14. Universal process indicator. User guide

Solid State Pressure Sensors D8M

Operation of a Three-Phase PWM Rectifier/Inverter

Dynamic Power Factor Correction Using a STATCOM

INSTRUMENTATION AND CONTROL TUTORIAL 3 SIGNAL PROCESSORS AND RECEIVERS

PORTABLES ANEMOMETERS

MTY (81)

VSD Series II Variable Speed Micro Drives (VSM II) FS1 FS5

HANDY DRIVE HANDHELD CONTROL SYSTEM TO DRIVE THE

HPVFP High Performance Full Function Vector Frequency Inverter

1 Digital input (24Vac or dry contact) Inputs

RISH EM 3490 SS Kilowatt Hour Energy Meter With Rs485 RISH EM 3490 SS. Application : Product Features: Indication: Pulse Indication:

Simplified Operations for TM-3100 Series Digital Tachometer

J Series induq VMZ MAGNETIC INDUCTIVE FLOW SENSORS. DB_Magnetic_Inductive_Flow_Sensors 05/2016

REACTa. Installation Commissioning Maintenance Installation circular version Legend to figures 3-5: Min. 500 mm. Min.

Variable Frequency Drive / Inverter (0.4 ~ 280kW)

Air flow meter For ventilation and air-conditioning Model A2G-25

D SERIES LM16. COMPACT DRIVE V/f and SLV CONTROL. LM16 COMPACT DRIVE V/f and SLV CONTROL

Disc Gap Control DGC-2. Technical Manual

Configuration of C310 multifunction transmitters by keypad

FLOWIZ ( M L ) Warranty conditions are available on this website: only in English version

Digital flow transmitter for continuous flow measurement

Medidores de vibración salida RS232 Datalogger VT-8204 LUTRON manual ingles

Control System Circuits with Opamps

TA Series. Analog And Non-Indicating Type, PID Control, Set Temperature By Dial. Features. Ordering Information TA S B 4 R P 4 C

Transcription:

MITOS VT6 AIR USER MANUAL 02/10/2015 Manual_MITOS_VT6_AIR_ver3p3_eng

Summary: GENERAL DESCRIPTION... 3 GENERAL FEATURES... 3 FUNCTIONING PARAMETERS... 4 FUNCTIONING MODE OF THE MITOS VT6 AIR... 7 FUNCTIONING JUST DISPLAY... 7 FUNCTIONING MANUAL... 8 FUNCTIONING AUTOMATIC PID... 9 PRESSURE / VELOCITY / FLOW RESET... 11 RESET INVERTER ALARM... 11 SELECTION OF SERIAL COMMUNICATION TTL/RS485... 11 CONNECTION FOR PRESSURE MEASURE / REGULATION... 12 CONNECTION FOR FLOW OR VELOCITY MEASURE/REGULATION... 14 MECHANICAL DIMENSIONS... 15 APPENDIX... 16 02/10/2015 2 / 17 Manual_MITOS_VT6_AIR_ver3p3_eng

GENERAL DESCRIPTION MITOS VT6 AIR is a measure, visualization and control device for pressure, velocity and flow. It has got a temperature sensor (internal) and a differential pressure sensor with two possible range: +/-999mmH 2 O +/-1% F.S. +/-2999mmH 2 O +/-1% F.S. The precision of the pressure measurement is optimized by the compensation in function of the temperature. It is equipped with 6 buttons and 1 LCD 16x2 lines display (2 lines and 16 fonts each line). It is also programmable by a menu. The control is done by a VF-S11, VF-FS1, VF-AS1 VF-NC3, VF-MB1, VF-S15 or VF-PS1 Toshiba inverter, using a simple TTL serial connection (VF-S11 inverter) or RS485 (other inverter) and it can be manual or automatic. The selection of the type of serial connection can be selected by a dip-switch placed on the back of the box. Manual control allow to command run/stop and/or the inverter frequency. The frequency sent is fixed and is programmable from the display menu. Automatic control commands run/stop and also regulate the frequency sent to the inverter in order to keep the pressure, velocity or flow (selectable) at a fixed level, programmable from the display menu. Automatic control uses a PID regulation characterized by proportional, integrative and derivative parameters, changeable from the programming menu. MITOS VT6 AIR can also visualize some functioning parameters of the inverter, such as current and power delivered, input and output voltage, frequency, hours of functioning, historic of the last four alarms. Available scales for pressure, velocity and flow are: Pressure: mmh 2 O; mbar; Pascal; Kpascal. Velocity: second meter Flow: hundreds of cube meters per hour; cube meters per second; litres per second. GENERAL FEATURES MITOS VT6 AIR has got the following features Case: Material: ABS. IP65 protection degree Alimentation: The alimentation is directly taken by the inverter through the serial connecting cable. The current consumption is: 25mA @ 24 VDC Working temperature: From -5 to +50 C Box dimensions: 120 x 65 x 35 mm. Weight: 350g. Input: 1 differential pressure gauge with two possible range +/-999mmH 2 O +/-1% F.S. +/-2999mmH 2 O +/-1% F.S. User interfaces: Monocromatic graphic display 2x32 types, 6 buttons (START, MAN/AUTO, UP, DOWN, MON, STOP/RESET) 02/10/2015 3 / 17 Manual_MITOS_VT6_AIR_ver3p3_eng

FUNCTIONING PARAMETERS The parameters programming menu is accessible in the normal functioning menu, by pushing MON button for at least 3 seconds. After the 3 seconds, it is necessary to insert a password. With UP and DOWN, you can change the number referred to the password, between 0 and 999. Once set the correct value, press MON to confirm. Each wrong password value allows to view just a part of the available parameters, the first eight in the following pattern. In the programming menu, you can select the parameter with the buttons UP and DOWN. Then, when the parameter is selected, the parameter will flash pressing the button MON. Value can be changed through buttons UP and DOWN. To store the new value, you need to press again MON (the parameter stops flashing). To quit the programming menu, just press MAN/AUTO. Here follow all the functioning parameters of MITOS VT6 AIR. PARAMETER FUNCTION POSSIBLE VALUES If the PID control is enabled, this act only if: V > Set point PID + Hysteresis Hysteresis or V < Set point PID - Hysteresis where V is the value measured by the controlled variable min = 0; max ( 2 ) appendix Constant PID Kp PID control proportional constant 0.0 300.0 Constant PID Ki PID control integrative constant 0.0 300.0 Constant PID Kd PID control derivative constant 0.0 300.0 ACC manual Value of the ACC parameter sent to the inverter when Type command = MANUAL. 0.1 320.0 sec. DEC manual Value of the DEC parameter sent to the inverter when Type command = MANUAL. 0.1 320.0 sec. ACC automatic Value of the ACC parameter sent to the inverter when Type command = AUTOMATIC. 0.1 320.0 sec. DEC automatic Value of the DEC parameter sent to the inverter 0.1 320.0 sec. Mode Rotation sense Feedback when Type command = AUTOMATIC. MITOS VT6 AIR can be used as a simple display, but it can also send run and/or frequency variation commends to the Inverter Sense of engine rotation Type of variable where the control PID is performed - COMMAND - VISUALIZATOR - AHEAD - BACK - PRESSURE - VELOCITY - FLOW Pressure unit Pressure Unit of measurement - mmh 2 O - Pa - kpa - mbar Flow unit Flow Unit of measurement - m 3 / h (value per 100) - m 3 / s - l / s Velocity unit Velocity Unit of measurement m / s PID Set point Set the set-point of the variable where the PID control is performed min = 0; max ( 2 ) appendix 02/10/2015 4 / 17 Manual_MITOS_VT6_AIR_ver3p3_eng

PARAMETER FUNCTION POSSIBLE VALUES PID Type PID ACC/DEC delay Type of PID control In AUTOMATIC mode, Inverter starts working through ACC/DEC ramps equal to ACC MANUAL/DEC MANUAL. When the controlled variable reaches the set-point, ACC/DEC are automatically set to the values ACC AUTOMATIC / DEC AUTOMATIC. This configuration remains till the stop of the Inverter. If the controlled variable does not reach the setpoint within PID ACC/DEC Delay seconds from the start, ACC/DEC are set to the values ACC AUTOMATIC/DEC AUTOMATIC - PID proport.-integr.-derivative - PI proportional.-integrative - P proportional - PD proportional.-derivative 0-999 sec. Velocity calculation Type of velocity calculation. The setting AIR has to be used in case the fluid present in the pipe is air. Otherwise, you may use the GENERIC setting. During velocity calculation with the section AIR, you need to set also the fluid temperature in C, through the parameter Fluid Temperature. The calculation of the velocity with GENERIC setting is base on the following formula:: GENERIC AIR v = k P [m/s] where k = Velocity Constant (settable) and P is the differential pressure in mmhh 2 O. Pipe type Sets the pipe section. - RECTANGUL. - CIRCULAR Pipe diameter Circular pipe diameter (mm) 0 2000 mm Pipe side 1 Rectangular pipe s side 1 size (mm) 0 2000 mm Pipe side 2 Circular pipe s side 1 size (mm) 0 2000 mm Fluid temperature Temperature of the fluid in the pipe ( C) 0 200 C Speed constant Sets the constant value in the generic formula for 0.01 99.99 Language Sets the language of the menu - GERMAN - ITALIAN - ENGLISH - SPANISH Command type If the MITOS VT6 AIR is enabled to send commands to the inverter (Mode = COMMAND) and it has the complete control of the inverter (run-stop and frequency variation ( 1 )), the Command type parameter determines the way the commands are sent - MANUAL - AUTOMATIC (PID) 02/10/2015 5 / 17 Manual_MITOS_VT6_AIR_ver3p3_eng

PARAMETER FUNCTION POSSIBLE VALUES Sets the monitor variable shown in the first line of the normal functioning display menu. Var. monitor1 will be visualized only in the following cases: Var. monitor1 Mode = MONITOR or 1) Mode = COMMAND 2) the MITOS VT6 AIR has only the run/stop command ( 1 ) see appendix ( 3 ) Var. monitor2 Sets the monitor variable shown in the second line of the normal functioning display menu. Var. monitor2 will always be visualized and can be changed pushing UP and DOWN buttons while keeping F2 key pushed. But in this case the selection will be kept only until the device is on see appendix ( 3 ) Set point manual Sets the value of the frequency sent to the inverter in MANUAL functioning. This value can be modified from the normal functioning menu 0.0 500.0 Hz Store set point It allows to store automatically or not the set point variation chosen with the UP and DOWN keys. Selecting YES, the set point variation (of the frequency or of the variable regulated in the PID control) from the normal functioning menu, is automatically stored. Selecting NO, the set point variation is not automatically stored and when you turn on the device again the value reloaded is the one saved using the parameters programming menu. - YES - NO 02/10/2015 6 / 17 Manual_MITOS_VT6_AIR_ver3p3_eng

FUNCTIONING MODE OF THE MITOS VT6 AIR The possible functioning modes of MITOS VT6 AIR are: Just display: it displays just the values of some parameters ( 3 ) Frequency Manual: it displays the values of some parameters ( 3 ) and it has just the control of the frequency Start/Stop Manual: it displays the values of some parameters ( 3 ) and it has just the manual control of the start/stop Complete Manual: it displays the values of some parameters ( 3 ) and it has the manual control of the start/stop and of the frequency Automatic PID: it displays the values of some parameters ( 3 ) and it has the automatic control (PID) of the frequency. The automatic control can have the start/stop control. You have the Just display mode through the setting of Modality parameter to the value VISUALIZATOR. All the other functioning modes are reachable setting the parameter Modality to the value COMMAND or changing CMOD, FMOD and command Type, as described in the appendix ( 1 ). It is possible to set the Modality parameter just through the parameters programming menu. If the Modality parameter is set on COMMAND, the setting of parameter command Type is possible through the programming menu and through the normal functioning menu, pressing for at least 3 seconds the button MAN/AUTO. The continuous pressure MAN/AUT allows to change the value from AUTOMATIC to MANUAL, and vice versa. Pressing the button MAN/AUTO for less then 3 seconds, you can only see the type of functioning selected at the moment. FUNCTIONING JUST DISPLAY In the JUST DISPLAY mode, MITOS VT6 AIR allows to display just: some parameters of the Inverter measured pressure or velocity or flow set-point (frequency set-point, or pressure/velocity/flow set-point) In appendix ( 3 ) you can find the complete list of the parameters. In the first line of the display you can find the information selected through the parameter Variable Monitor 1. In the second line of the display, after the card start, you can find the information selected through the parameter Variable Monitor 2. However, through the keys UP and DOWN, it is easy to reach all the other information available. 02/10/2015 7 / 17 Manual_MITOS_VT6_AIR_ver3p3_eng

FUNCTIONING MANUAL In manual functioning, the MITOS VT6 AIR allows to control run-stop and/or change the frequency of inverter functioning, to a fix value which can be set through the parameter manual Set point. To enable the manual functioning the following points are necessary: Modality = CONTROL Control type = MANUAL It is possible to set the Modality only by the programming menu. If the Modality parameter is set to COMMAND, the setting of the parameter command Type is possible through the programming menu and through the normal functioning menu, pressing for at least 3 seconds the button MAN/AUTO. The continuous pressure MAN/AUT allows to change the value from AUTOMATIC to MANUAL, and vice versa. Pressing the button MAN/AUTO for less then 3 seconds, you can only see the type of functioning selected at the moment. The possibility to control just the run-stop, just the frequency or both, depends on the CMOD and FMOD values of Inverter, as shown in the appendix ( 1 ). If the MITOS VT6 AIR has the frequency control ( 1 ), you will see the real frequency reference value in the first line of the display. Otherwise, in case of lack of frequency control, in the first line of the display you will see the information selected through the parameter Variable Monitor 1. In the second line of the display, after the card start, you can find the information selected through the parameter Variable Monitor 2. However, through the keys UP and DOWN, it is easy to reach all the other information available. The value Manual Set point can be changed through the parameters programming menu and through the normal functioning mode. In this last case, if the Set point Storing is set on YES, the change of the set point is automatically stored and it will be kept even when the card is off; otherwise, if this parameter is set on NO, the change of the set-point won't be stored. The change of the Manual Set Point from normal functioning menu is performed as follows: 1. with keys UP and DOWN, program "Set" in the second line of the display 2. press the button MON (the second like will flash) 3. change the value through UP and DOWN 4. press the button MON (the second line will stop flashing and the value will be stored) If the MITOS VT6 AIR has the run-stop control, ( 1 ), pressing START the inverter will start work; pressing STOP/RESET the inverter will stop. When the inverter is in start and the engine is in spin, in the first line of the display, on the right side, it appears a symbol to indicate the rotation way. In the manual functioning, ACC and DEC Inverter parameters are automatically set equal to the values of ACC manual/ DEC manual parameters. 02/10/2015 8 / 17 Manual_MITOS_VT6_AIR_ver3p3_eng

FUNCTIONING AUTOMATIC PID In automatic functioning, the MITOS VT6 AIR does an automatic regulation of the frequency sent to the inverter so as to maintain the controlled variable (pressure, speed or flow) to a settable fixed value through the parameter Set point PID. The sent frequency will have like limits the values of parameters UL (upper limit) and LL ( lower limit) set up in the inverter, that s will be always: UL frequency unchanged LL The regulation uses a control type PID, P, PI, PD, which can be selected through the parameter Type PID. To enable the automatic regulation, it is necessary that: Modality = CONTROL Control type = AUTOMATIC MITOS VT6 AIR must have the complete control frequency variation ( 1 ) The Modality setting is possible only from parameters programming menu. If the parameter Modality is set up on COMANDO, the Control type is possible is possible also from normal functioning menu, pressing more than 3 seconds button MAN/AUTO. The continuous pressure of MAN/AUTO allows to change the value from AUTOMATIC to MANUAL and vice versa. Pressing the button MAN/AUTO for less than three seconds you will only see the functioning selected at the moment. The setting of reference value (Set point PID) can be varied from menu programming parameters menu and also from the menu of normal operation. In this case, if the parameter Store set point is set on YES, the changing of set point is automatically stored and it will remain even if the card is turned off and on again; on the other hand, if this parameter is set on NO, the set point changing won't be stored. The variation of Set point PID from the menu of normal operation is carried out as follows: 1. through buttons UP and DOWN set up SET on the second line of the display 2. press the MON button (the second line flashes) 3. through buttons UP and DOWN vary the value 4. press the MON button (the second line stop to flash and the value comes acquired) If MITOS VT6 AIR has the march-arrest control ( 1 ), pressing the button START, the inverter start, pressing the button STOP/RESET the inerter stops. When the inverter it s in start and the motor is in rotation, in the first line of the display a little symbol appears on the right and this indicates the direction of rotation. After the command of start, the operation is manual with fixed set-point frequency, as the value of the inverter UL parameters and ACC/DEC ramps with the same value of ACC manual/ DEC manual parameters respective. When one of the two condition are verify: an equal time to second delay ACC/DEC PID passes the controlled variable catches up the set-point control PID of the frequency enters automatically in function and moreover, ACC/DEC ramps comes set up respective to the ACC automatic/dec automatic parameters. Below there is a graphical representation of what is said previously 02/10/2015 9 / 17 Manual_MITOS_VT6_AIR_ver3p3_eng

The meaning f the several numbers is the following one: 1. moment in which there is the start 2. moment in which the controlled variable is catches up the set-point and starts the PID regulation 3. moment in which there is the stop 4. equal time to the value of the Delay ACC/DEC PID after which PID regulation enter however in function The figure a is relative to the case in which between the start and stop inverter the controlled variable never doesn t catch up the set point. The figure b is relative to the case in which between the start and stop inverter the controlled variable catch up the set point ( in correspondence of the point 2). The purpose of the two couples of different ramps in manual and automatic is to allow a slower answer during the startup, a quicker one when you are working at full speed. If the system can be led to instability (permanent waver), an empirical way to find the values of integrative, derivative and proportional constants is the following one: 1) Set Ki and Kd to zero 2) Staring from Kp low, increase Kp slowly to reach a waver of controlled variable 3) Reduce Kp at the half of precedent value 4) If necessary, increase Ki to bring to zero errors in stationary system 5) If necessary, increase Kd to speed up the answer If you change the unit of measurement to the controlled variable, you need to calibrate again the PID parameters. 02/10/2015 10 / 17 Manual_MITOS_VT6_AIR_ver3p3_eng

PRESSURE / VELOCITY / FLOW RESET Due to the change of weather conditions, humidity etc., pressure or flow or speed viewed on the display, can change lightly on equal pressure on the sensor. To restore the correct value, you need to reset the offset. To do this, you may press at the same time the buttons STOP/RESET and MON when the engine is not working yet, and the vents of pressure sensor are both opened. CAUTION! The reset has to be performed only when the size on the display (pressure, velocity or flow) with open vent is different from zero, when the device is on since at least 15 minutes. RESET INVERTER ALARM In the case in which the inverter it had to go in alarm, TO INV REG visualizes to display the same code of alarm visualized on the display of the inverter. To reset the alarm is enough to press button STOP/RESET. SELECTION OF SERIAL COMMUNICATION TTL/RS485 Depending on the kind of inverter used, the dip-switch with two levers on the back of the box, has to be configured as follows: VF-S11 VF-FS1 VF-AS1 VF-PS1 1=ON 1=OFF 1=OFF 1=OFF 2=ON 2=OFF 2=OFF 2=OFF VF-NC3 VF-S15 VF-MB1 1=OFF 1=OFF 1=OFF 2=OFF 2=OFF 2=OFF 02/10/2015 11 / 17 Manual_MITOS_VT6_AIR_ver3p3_eng

CONNECTION FOR PRESSURE MEASURE / REGULATION The pressure measure/regulation must be performed using the connections of the following figure It is recommended the use of filtered outputs to limit possible damages to the internal pressure sensor. These filtered outputs thwart the dust or other elements to go up to the pressure sensor and to small elements to obstruct the flow into the pipes. It is possible not to use the filtered outputs, but to the detriment of the instrument. The filtered outputs have to be mounted directly on the filter, where there are usually the air outputs pipes. It is necessary to install a filtered output for each pressure pipe, applied when necessary. In the following image, you can see the particular of a filtered output. 02/10/2015 12 / 17 Manual_MITOS_VT6_AIR_ver3p3_eng

Ø20 FILTER WALL 4 IMPLANTATION HOLES Ø3,75 PACKING IN RUBBER HOLES LOW PRESSURE (3-5 Ø4 IN THE CENTER WITHIN A DIAMETER OF 20mm) WADDING SCREW Ø4,25 02/10/2015 13 / 17 Manual_MITOS_VT6_AIR_ver3p3_eng

CONNECTION FOR FLOW OR VELOCITY MEASURE/REGULATION For velocity and flow regulation it s necessary to use the Pitot Pipe applied to the vent of MITOS VT6 AIR. The choice of Pitot pipe lenght has to be made following the dimensions of the pipe, in order to put it at least up to the central part of the tubing. 02/10/2015 14 / 17 Manual_MITOS_VT6_AIR_ver3p3_eng

MECHANICAL DIMENSIONS Legend: 1: Pressure negative Input 2: Pressure positive Input 3: Connector for serial connection 4: TTL/RS485 serial line selector 5: Fixing brackets The pipes connected to the pressure sensor must have an internal diameter of 4 mm 02/10/2015 15 / 17 Manual_MITOS_VT6_AIR_ver3p3_eng

APPENDIX ( 1 ) If Modality parameter is set on COMMAND, the control type of MITOS VT6 AIR on inverter is fixed by the parameter settings CMOD and FMOD of inverter, and by the Command Type parameter, as you can see in the following chart: VF-S11 VF-FS1 VF-AS1 VF-PS1 Manual frequency Manual start/stop Manual complete Automatic PID (with start/stop) Automatic PID (without start/stop) CMOD 1 CMOD = 1 FMOD 4 CMOD = 1 CMOD = 1 CMOD 1 CMOD 2 FMOD 4 FMOD = 5 FMOD 5 FMOD = 5 FMOD = 5 FMOD = 5 FMOD = 5 FMOD 5 FMOD = 5 FMOD = 5 FMOD = 5 VF-NC3 VF-S15 VF-MB1 Manual frequency Manual start/stop Manual complete Automatic PID (with start/stop) Automatic PID (without start/stop) CMOD 2 FMOD = 3 FMOD 3 FMOD = 3 FMOD = 3 FMOD = 3 CMOD 2 FMOD 4 FMOD 4 ( 2 ) The maximum values which can be set for Set point PID and Hysteresis in case of pressure, velocity and flow are: Full scale 1000 mmh2o Pressure: mmh 2 O: 999 Pa: 9796 kpa: 9.79 mbar: 99.7 Velocity: m/s: 999.9 02/10/2015 16 / 17 Manual_MITOS_VT6_AIR_ver3p3_eng

Flow: m 3 /h: 32767 (hundreds of m 3 /h) m 3 /s: 3276.7 l/s: 32767 Full scale 3000 mmh2o Pressure: mmh 2 O: 2999 Pa: 29410 kpa: 29.41 mbar: 294.1 Velocity: m/s: 999.9 Flow: m 3 /h: 32767 (hundreds of m 3 /h) m 3 /s: 3276.7 l/s: 32767 ( 3 ) Possible values and its meaning for parameters Variable monitor 1 and Variable monitor 2 SET frequency or pressure or velocity set point programmed * POWER real power in kw absorbed by the engine CURRENT real current absorbed by the engine, measured in Ampere VIN tension in Volt in inverter input VOUT tension in Volt in engine input ALARM1 last alarm ALARM2 next to last alarm ALARM3 third from last alarm ALARM4 fourth last alarm CNT hours counter TEMPERATURE temperature measured in grades centigrades PRESSURE/VELOCITY/FLOW value of measured pressure/velocity/flow * FREQUENCY real frequency of inverter functioning * frequency if the functioning is MANUAL; one of the remaining, if the functioning is AUTOMATIC. In this second case, the selection between "pressure", "velocity" and "flow" depends on the value of Feedback parameter. ** the selection between pressure, velocity and flow depends on the value of Feedback parameter. 02/10/2015 17 / 17 Manual_MITOS_VT6_AIR_ver3p3_eng