An Experimental Study on Uninterrupted Switching between Grid-Connected and Isolated Operation of Inverter Power Source

Similar documents
An Experimental Study on P-f and Q-V Droop Control of Photovoltaic Power Generation Contributing to Grid Frequency Operation

A Control Method of Parallel Inverter for Smart Islanding of a Microgrid

Power Quality and Reliability of the Overall Power Distribution of Microgrid System

Islanding Detection and Frequency Circuit Measurement by Power Distribution Relation Depending on the Angle

Active Power Sharing and Frequency Control of Multiple Distributed Generators in A Microgrid

Modelling and Simulation of High Step up Dc-Dc Converter for Micro Grid Application

Hybrid Anti-Islanding Algorithm for Utility Interconnection of Distributed Generation

Microgrid Connection Management based on an Intelligent Connection Agent

Improvement of Islanding Detector Using Interharmonics Current Injection Method and Its Applications

UPQC with Islanding and Grid Connection for Microgrid Applications

IJSRD - International Journal for Scientific Research & Development Vol. 4, Issue 01, 2016 ISSN (online):

Proposed test procedure for the laboratory characterisation of gridconnected

Anti-IslandingStrategyforaPVPowerPlant

Renewable Interconnection Standard & Experimental Tests. Yahia Baghzouz UNLV Las Vegas, NV, USA

Voltage Support and Reactive Power Control in Micro-grid using DG

A Novel Grid Connected PV Micro Inverter

Control of Power Converters for Distributed Generation

1200 MW Fault Induced Solar Photovoltaic Resource Interruption Disturbance Report

E N G I N E E R I N G M A N U A L

Control strategy for seamless transition from islanded to interconnected operation mode of microgrids

A New Control Strategy for Three- Phase Inverter Applied To Induction Motor of Micro Grid

Grid Converters for Photovoltaic

Inverter-Based Resource Disturbance Analysis

Optimal sizing of battery energy storage system in microgrid system considering load shedding scheme

Power Quality Improvement Utilizing Photovoltaic Generation Connected to a Weak Grid

Embedded Generation Connection Application Form

IEEE sion/1547revision_index.html

Maximum Power Point Tracking Performance Evaluation of PV micro-inverter under Static and Dynamic Conditions

A Control Topology to Enhance Performance of Weak Grid under Different Power Levels

PRC Generator Relay Loadability. Guidelines and Technical Basis Draft 5: (August 2, 2013) Page 1 of 76

Technical information Grid Support Utility Interactive Inverters for Sunny Central-US and Sunny Central Storage-US

Impact of High PV Penetration on Grid Operation. Yahia Baghzouz Professor of Electrical engineering University of Nevada Las Vegas

SPACE VECTOR PULSE WIDTH MODULATION SCHEME FOR INTERFACING POWER TO THE GRID THROUGH RENEWABLE ENERGY SOURCES

State of Charge (SOC)-Based Active Power Sharing Method for Distributed Generations in an Islanded Microgrid

BED INTERCONNECTION TECHNICAL REQUIREMENTS

Implementation of Revised IEEE Standard 1547

DISTRIBUTION LINE STRUCTURE AND GENERATION EFFICIENCY IMPROVEMENT: A CLUSTERED RESIDENTIAL GRID-INTERCONNECTED PV

Embedded Generation Connection Application Form

A Contribution to Isolated and Grid-Connected Photovoltaic Systems under Shadow Conditions

Grid Interconnection of Wind Energy System at Distribution Level Using Intelligence Controller

Matlab Simulation of a High Step-Up DC-DC Converter for a Micro grid Application

PRC Generator Relay Loadability. Guidelines and Technical Basis Draft 4: (June 10, 2013) Page 1 of 75

SYSTEM PERFORMANCE UNDER SOLAR IRRADIATION AND TEMPERATURE VARIATION OF GRID CONNECTED PHOTOVOLTAIC SYSTEM

An Accurate Power Sharing Method for Control of a Multi-DG Microgrid

Modeling & Simulation of Micro Grid Distribution System to reduce Harmonics Using Active Power Filters and PI controllers

Study on Voltage Controller of Self-Excited Induction Generator Using Controlled Shunt Capacitor, SVC Magnetic Energy Recovery Switch

Design of Single-Stage Transformer less Grid Connected Photovoltaic System

Study of Centralized Anti-Islanding Method on Large-Scale Photovoltaic Power Plants

Cost Based Dynamic Load Dispatch for an Autonomous Parallel Converter Hybrid AC-DC Microgrid

GRID CODE COMPATIBLE PROTECTION SCHEME FOR SMART GRIDS

Modelling of Photovoltaic power plants in SIMPOW

Embedded Generation Connection Application Form

Stability Enhancement for Transmission Lines using Static Synchronous Series Compensator

Delhi Technological University (formerly DCE) Delhi-42, India

INTERIM ARRANGEMENTS FOR GRID TIED DISTRIBUTED ENERGY RESOURCES. Technical Requirements for Grid-Tied DERs

Levels of Inverter by Using Solar Array Generation System

Synchronization and Smooth Connection of Solar Photovoltaic Generation to Utility Grid

ISO Rules Part 500 Facilities Division 502 Technical Requirements Section Aggregated Generating Facilities Technical Requirements

Design and Implementation of Quasi-Z-Source Inverter for Off-grid Photovoltaic Systems

MODELING AND SIMULATION OF UNIFIED POWER QUALITY CONDITIONER FOR POWER QUALITY IMPROVEMENT

Harmonizing the Changing Resource Mix Keeping the Grid Together

Fuel cell power system connection. Dynamics and Control of Distributed Power Systems. DC storage. DC/DC boost converter (1)

ADVANCED VECTOR SHIFT ALGORITHM FOR ISLANDING DETECTION

Ameren Illinois Company d/b/a Ameren Illinois Smart Inverter Specifications

Hardware Implementation of Interleaved Converter with Voltage Multiplier Cell for PV System

Suppression of Voltage Violation in PV Connected Distribution System via Cooperation of Battery Energy Storage System and SVR

Modelling of Five-Level Inverter for Renewable Power Source

Enhancement of Fault Current and Overvoltage by Active Type superconducting fault current limiter (SFCL) in Renewable Distributed Generation (DG)

Connection of Embedded Generating Plant up to 5MW

Tripping of circuit breakers in PV installations due to zero sequence field impedance

SUPERCONDUCTING MAGNETIC ENERGY

Protection of Microgrids Using Differential Relays

IEEE 1547: Standard for Interconnection and Interoperability of Distributed Energy Resources with Associated Electric Power Systems Interfaces

Technical information SUNNY TRIPOWER CORE1-US

Design and Development of MPPT for Wind Electrical Power System under Variable Speed Generation Using Fuzzy Logic

Arvind Pahade and Nitin Saxena Department of Electrical Engineering, Jabalpur Engineering College, Jabalpur, (MP), India

Microgrid Protection

ISSN Vol.03,Issue.07, August-2015, Pages:

Table of Contents. Introduction... 1

A FLEXIBLE AC DISTRIBUTION SYSTEM DEVICE FOR PHOTOVOLTAIC AND MPPT TECHNIQUE AT MICRO GRID

ADVANCES AND CONTROL TECHNIQUES IN GRID CONNECTED PHOTOVOLTAIC SYSTEM

A Novel Control Approach for Microgrids Islanded Operation - Load Step Pre-announcement and Bang-Bang Control

Chapter -3 ANALYSIS OF HVDC SYSTEM MODEL. Basically the HVDC transmission consists in the basic case of two

ISLANDING DETECTION USING DEMODULATION BASED FFT

SOLAR POWERED REACTIVE POWER COMPENSATION IN SINGLE-PHASE OPERATION OF MICROGRID

Power quality measurements in a singlehouse

Performance of Micro-grid connected Hybrid Photovoltaic/Fuel cell with ANN control to improve the Power quality

Parallel Operation of Distributed Generators by Virtual Synchronous Generator Control in Microgrids

Impacts of P-f & Q-V Droop Control on MicroGrids Transient Stability

IEEE Major Revision of Interconnection Standard

Available ONLINE

Application of Model Predictive Control in PV-STATCOM for Achieving Faster Response

Phase-phase/phase-neutral: 24/13.8 kv star, 13.8 kv delta, 12/6.9 kv star.

Transition from Grid Connected Mode to Islanded Mode in VSI fed Microgrids

MODELING AND CONTROL OF DISTRIBUTED ENERGY SYSTEMS DURING TRANSITION BETWEEN GRID CONNECTED AND STANDALONE MODES. A Dissertation.

TRANSFORMER LESS H6-BRIDGE CASCADED STATCOM WITH STAR CONFIGURATION FOR REAL AND REACTIVE POWER COMPENSATION

Microgrids and Energy Management SURYANARAYANA DOOLLA POWER ENGINEERING LAB DEPARTMENT OF ENERGY SCIENCE AND ENGINEERING INDIAN INSTITUTE OF

1

STUDY OF CIRCULATING CURRENT PHENOMENA IN MULTIPLE PARALLEL INVERTERS OPERATING IN MICROGRID

,, N.Loganayaki 3. Index Terms: PV multilevel inverter, grid connected inverter, coupled Inductors, self-excited Induction Generator.

Transcription:

An Experimental Study on Uninterrupted Switching between Grid-Connected and Isolated Operation of Inverter Power Source Yuki Kimpara, Muneaki Kurimoto, Yusuke Manabe, Toshihisa Funabashi, Takeyoshi Kato Abstract This paper develops a controller for Microgrid (MG) to perform uninterrupted switching between grid-connected and isolated operation so that MG can be practically useful even during wide area blackout due to disaster. The proposed method realizes uninterrupted switching by maintaining continuity of the modulation factor of system interconnection inverter and the output voltage phase at the moment of switching. The proposed method is implemented and tested using an experimental setup consisting of a grid simulated voltage source, an inverter power source, and resistive loads. As a result, the MG was uninterruptedly switched to the isolated operation when a significant grid voltage drop continues for a while and switched back to the grid-connected operation when the grid voltage is recovered. Keywords: Microgrid, Uninterrupted switching, Isolated operation, Grid-connected operation1 A I. INTRODUCTION s a result of insufficient electricity supply just after Tohoku earthquake in Japan, Microgrid (MG) has been reevaluated as self-sufficient power generation [1]. MG is a local energy grid which comprises of distributed generations and loads []. It usually operates connected to utility grid, but can operate independently. If MG contains a certain capacity of photovoltaic power generation (PV), MG can continue electricity supply even after the fuel stock for emergency generator is expired when large disturbance occurs [1]. Moreover, MG will be more useful if it can uninterruptedly switch between the grid-connected and isolated operation, because the opportunity losses caused by standstill of electric machines and the costs to introduce Uninterruptible Power Supply (UPS) can be reduced. The objective of this study is to develop a controller for MG that can perform uninterrupted switching between the gridconnected and isolated operation, and to examine the This work was supported in part by Institute of Materials and Systems for Sustainability (IMaSS), Nagoya University. Y. Kimpara, and M. Kurimoto are with Department of Electrical Engineering, Nagoya University, Furo-cho, Chikusa-ku, Nagoya, -83 Japan (e-mail: kimpara.yuuki@e.mbox.nagoya-u.ac.jp). Y. Manabe, T. Funabashi, and T. Kato are with Institute of Materials and Systems for Sustainability, Nagoya University, Furo-cho, Chikusa-ku, Nagoya, -83 Japan performance of controller by using an experimental setup. A lot of previous researches focused on developing a method for uninterrupted switching [3]-[7]. However, to the best of the authors knowledge, the investigation about switching under fault condition is not enough. In [7], a switching method using a Static Switch is investigated in CERTS Microgrid Test Bed. The MG is disconnected from the utility grid when a fault occurs inside the MG for avoiding the negative impact on the utility grid operation. On the other hand, our study focuses on uninterrupted switching to isolated operation when a fault occurs in the utility grid. In order to confirm successful switching without over-current and over-voltage, waveforms of transient voltages and currents caused by switching of operation are observed. The experimental setup used in this study consists of a several hundred Watts PV, an impedance load, and a kva voltage source for simulating three-phase voltage drop at grid connection point of MG. A generic mechanical switch instead of a static switch using a power semiconductor device is used as an interface to the utility grid for developing MG with lower investment. Usually, MG consists of multiple generators and multiple load. The MG used in this study, however, consists of single PV and single load. Although this conformation seems not common practice, this study assumes the situation where the PV in MG can solely supply enough electricity thanks to high-penetration PV in MG and stable and high solar irradiance. The development of integrated control of multiple power sources and consideration of fluctuations in solar irradiance are left as topics for future work. This paper is organized as follows. First, the experimental setup is explained together with the basic controller for PV inverter in the grid-connected operation. The basic controller is designed to meet the Fault Ride Through (FRT) requirement in which the over current during the grid voltage drop can be avoided and the quick power output recovery after the grid voltage recovery is realized. Then, a controller which can perform uninterrupted switching to the isolated operation and switching back to the grid-connected operation is proposed. Finally, experimental results on the performance of proposed controller are explained. Paper submitted to the International Conference on Power Systems Transients (IPST17) in Seoul, Republic of Korea June 9, 17

II. EXPERIMENTAL SETUP AND BASIC CONTROL A. Experimental Setup Fig. 1 shows the experimental setup used in this study. The setup consists of a three-phase inverter power source for simulating PV (PV simulator), an impedance load at both side of circuit breaker, and a AC voltage source of kva for simulating grid (grid simulator). MG consists of PV and an impedance load of W. As shown in Fig.1, PV simulator consists of an inverter (or Power Conditioning System (PCS) in other words), DC power source and parallel connected a set of series diodes to realize an I-V characteristic of PV module. The power output of PV simulator can be controlled ranging W. On the grid side, the terminal voltage of grid simulator is controlled by a computer to simulate voltage drop caused by a short circuit fault in the grid. The instantaneous drop of voltage amplitude can be controlled, while the phase of the voltage drop is out of control. Magnetic contactor (MC) is used as circuit breaker. The MC is controlled by the PCS to disconnect MG from the grid and reconnect MG to the grid according to the voltage on grid side. B. Basic controller for PCS in grid connected operation PCS used in the PV simulator consists of system interconnection inverter and DC/DC converter as shown in Fig. 1. Fig. shows the block diagram of controllers of system interconnection inverter controller and DC/DC converter in the grid connected operation. The DC/DC converter controller performs maximum power point tracking (MPPT). The inverter Vdc DC/DC converter Inverter PCS MG Fig. 1. Experimental setup Load (a) Block diagram of inverter controller MC Load AC Power Source controller maintains the DC voltage at 35V. The PCS output voltage is synchronized to the grid voltage by using phase locked loop (PLL). The inverter controller for grid-connected mode is equipped with an active islanding detector which can prevent MG from unintentionally continuing the grid-connected operation when MG is disconnected from the grid due to a grid fault. The active islanding detector injects the reactive current of 5 Hz square waveform with 5% amplitude of active current. When MG is disconnected from the grid, frequency fluctuates due to the injection of reactive power. If average absolute frequency deviation is over.75hz for.5sec, the MG is switched to isolated operation mode. Detection of islanding operation is one of the conditions when PCS is switched to isolated operation, besides under voltage detection. PCS is equipped with FRT capability. As described below, FRT capability is sophisticated by avoiding overcurrent during the voltage drop, and enhancing power output recovery by using time-varying change in the gain of PI controller. C. Switching Process of Grid Connected / Isolated Operation of MG and Related Controllers According to FRT requirements in Japan, a grid-connected PV is required to continue the operation for a short disturbance. However, a grid-connected PV must be disconnected from the utility grid when disturbance is longer than 3 ms [8]. Assuming that the FRT requirements is applied to MG including multiple power sources, this study develops controller for MG to realize disconnection from grid, uninterrupted switching to the isolated operation, and the reconnection to grid when the disturbance is cleared. At this moment, this study so far is the case of simple MG with single power source, investigation into MG including multiple power sources will be investigated in the future. Fig. 3 shows the flowchart of the whole switching process. Usually, MG continues power supply in the grid-connected operation. When the voltage drop occurs but the residual voltage is kept at % or higher, MG must continue the power supply. In the proposed controller, the limiter of output current is temporarily activated so that the overcurrent is prevented. Then, the grid voltage is recovered within 3 ms, the power output of MG is required to recover quickly. To perform this, this study proposes the time varying proportional gain of PI controller at leftmost in Fig. (a) described in Section 3. On the other hand, if the grid voltage is not recovered within 3 ms, MG is disconnected and switched to the isolated operation. To perform uninterrupted switching, this study proposes a novel controller described in Section. When the grid frequency and voltage are recovered to the normal range, MG is reconnected to the grid by adjusting the phase difference between both sides of circuit breaker within ±5. (b) Block diagram of converter controller Fig.. Controller for grid-connected operation

III. ADAPTATION TO FRT REQUIREMENTS Iu[A] Vuv[V] A. Overcurrent Protection When PV continues the grid-connected operation during short-circuit, an overcurrent may occur. In this study, therefore, the controller is modified so that a current limiter is temporarily activated when the output current exceeding the limit level is detected. In order to decide the limit level, PCS always records the average value of d-axis output current at 5 ms interval. When the voltage drop occurs, the limiter of output current is temporally activated and reference of d-axis output current is limited to the observed level of 5-55 ms before the voltage drop. If DC/DC converter continues MPPT while the limiter is activated, DC input voltage to inverter (V dc) rises because the power input would exceed the output. Therefore, DC/DC converter controller which performs MPPT is switched to controller to maintain V dc at 35V as shown in Fig.. This Start Grid-connected operation Voltage < 1V YES Limit output current Duration of voltage drop > 3ms YES MC opens Isolated operation 1V < Vsys <3V 59.Hz < f < 1.Hz For 1ms YES Synchronization control MC closes NO NO NO Fig. 3. Flowchart of switching process Time-varying Kp Fig.. DC/DC converter controller during voltage drop overcurrent protection is activated when line voltage of grid is under 1V and deactivated when grid voltage gets higher than 1V. The effect of this overcurrent protection method is examined by experiment which simulates three-phase short-circuit. As shown in Fig. 5 (a), the result without the overcurrent limiter shows that the output current considerably increases during voltage drop. On the other hand as shown in Fig. 5 (b), the result with the overcurrent limiter shows that current level is maintained even during voltage drop. B. Time-Varying Proportional gain of PI controller When the grid voltage is recovered within 3 ms, the power output of PCS has to recover quickly. For this purpose, the proportional gain K p of leftmost PI controller shown in Fig. (a) should be relatively small. On the other hand, for prioritizing the stable operation in steady state, K p should be relatively small, which may result in a long time for the power output recovery and be hard to satisfy FRT requirements. By changing K p, this study examined the power output recovery performance. The target voltage of the AC voltage source is dropped to % of the rated voltage for 5 ms. The transition time of voltage drop and voltage recovery are 1ms. As an example, result in power output when K p =.15 and K p =. is shown in Fig.. Before the voltage drop, the power output slightly fluctuates at 5Hz due to reactive power injection described above. During the voltage drop, power output is suppressed. As shown in Fig. (a), when K p =.15, after the voltage is recovered at around.85 sec, the power output is recovered but fluctuating by about 1 W for a few seconds. The reason for the fluctuation is small K p. On the other hand, when K p =. is selected to prioritize quick power output recovery, power output is recovered very quickly without the Iu[A] 8 - -8 8 - -8 Iu Vuv.....8 (a) Without overcurrent protection Iu Vuv....8 1. (b) With overcurrent protection Fig. 5. Experimental result 3 1-1 -3 3 1-1 -3 Vuv[V]

Power output [W] fluctuation, as shown in Fig. (b). However, power output is unstable including short-term fluctuation even in the steady state. In order to realize quick power output recovery after the grid voltage recovery together with stable operation during the usual operation, the proposed controller temporarily uses timevarying K p to leftmost PI controller in Fig. (a) for 1 ms after the grid voltage recovery. When voltage of d-axis becomes larger than 1V, grid voltage is regarded as recovered. Setting of K p is shown in Table I. K p is set large value (=.) just after voltage recovery ( ms) to achieve quick power output recovery. Then, K p is gradually decreased to default level (=.15) to realize stable operation. Fig. (a) shows the power output using time-varying K p together with fixed K p =.15, the power output is recovered quickly to stable operation in steady state without fluctuation. On the other hand as shown in Fig. (b), the short-term fluctuation due to large K p is eliminated. As a result, the controller using time-varying K p performs quick output recovery while realizing stable operation. IV. SWITCHING FROM GRID-CONNECTED OPERATION TO ISOLATED OPERATION A. Controller According to FRT requirements, MG must stop grid connected operation when short-circuit continues for more than 3 ms [8]. In this study, a controller which automatically disconnects MG from grid and switch MG to the isolated operation is developed. Power output [W] TABLE.I SETTING OF KP AFTER VOLTAGE RECOVERY K p Elapsed time from voltage recovery [ms] -. - 8. 8-1. 1 -.15 (Default) K p =.15 Time-varying K p 3 1....8 1. 1. Time [sec] 3 (a) With fixed K p (.15) and time-varying K p K p =. Time-varying K p 1....8 1. 1. Time [sec] (b) With fixed K p (.) time-varying K p Fig.. Power output recovery after grid voltage recovery The converter controller in the isolated operation is the same as that during voltage drop shown in Fig., which maintains V dc at 35V. Fig. 7 shows the developed inverter controller in the isolated operation, which maintains the output line voltage at V. The phase and frequency of PCS output voltage is determined based on the internal counter which creates Hz clock. Fig. 8 shows a conceptual diagram of the switching process. In the grid-connected operation before the voltage drop, the internal counter is calculated based on the measured line voltage between U and V phases. After the operation is changed from the isolated mode to the grid-connected mode, the internal counter is created in controller of PCS. At the instant of changing to the isolated operation, the internal counter value is set at the value in the grid-connected operation. The modulation factor of inverter and output voltage phase are also set at the value at the instant of changing to the isolated operation. As shown in Fig. 8, all three phases are switched to the isolated operation mode simultaneously. In the experimental test, MC starts to open when the line voltage under 1V continues for 3 ms. Then, by waiting for ms for MC to be completely opened, the controller for PCS is switched to the isolated operation. B. Experimental Result In order to validate the switching from the grid-connected to isolated operation, a three-phase voltage drop which lasts for 35 ms is simulated by the grid simulator. The transition time of voltage drop and voltage recovery are 1ms. Sensitive analysis regarding residual voltage and power output of PCS is conducted. Power output of PCS before the voltage drop varied from W to W and residual voltage varied from 5% to 5%. As an example, Fig. 9 shows the experimental result with W PCS power output and 5% residual voltage. The line Fig. 7. Block diagram of inverter controller for isolated operation 3ms from voltage drop MC opens Switiching of operation grid-connected operation Isolated operation ms Line Voltage (U-V) Counter of voltage phase (U-V) Counter is passed to isolated operation Fig. 8. Conceptual diagram of switching to isolated operation

Control signal of MC [V] Vuv [V] Control signal of MC [V] Vuv [V] voltage of MG (U-V) drops at.85 sec and the voltage drop continues. At 1.5 sec, after the voltage drop continues for 3 ms, the control signal of MC is turned off and MC starts to open. ms later, the PCS controller is switched to isolated operation. As a result, the line voltage is recovered quickly after switching as shown in Fig. 9. Uninterrupted switching was successfully performed in different conditions regarding voltage drop and PCS power output. The voltage recovery is slower as the power output before voltage drop is smaller. The reason is as follows. The output current during voltage drop is limited by the over current limiter at most to the current before the voltage drop. Therefore, when the PCS supplies small power output before the voltage drop, the deviation of power from the W load in isolated operation is large, resulting in longer time for changing the operation point after the voltage recovery. Study so far is the case of simple MG which have single power source; however, real MG usually has several power sources. As a future work, the investigation into such MG is required. If MG have multiple power sources, the controller has to be changed in order to cooperate with these sources. One of the cooperative controls is master-slave control. A power source becomes a master and it decides frequency and voltage level. The other sources become slaves and follow the frequency and voltage level of master. Development of switching method for MG which has multiple power sources and performs cooperative control can be a future work. V. SWITCHING FROM ISOLATED OPERATION TO GRID- CONNECTED OPERATION A. Controller After the grid voltage is recovered, MG in the isolated Control singal of MC Vuv 3 1-1 -3-1. 1.5 1.3 1.35 3 1-1 -3 -..5 1. 1.5..5 Fig. 9. Experimental result of switching to isolated operation operation should be reconnected to grid in order to resume electricity supply to all electricity load in MG. When reconnecting MG, the voltage at circuit breaker (or MC) on MG side must be in phase with that on grid side in order to realize smooth transition from the isolated operation to the gridconnected operation. However, during the isolated operation previously described, the voltage phase on MG side and grid side may be different because the frequency based on internal clock of PCS can be different from the grid frequency. Therefore, automatic switching from the isolated operation to the grid-connected operation with synchronization control is developed. In the practical situation, the voltage at MC s terminal on MG side must be synchronized to the grid side voltage. In the experimental test, however, the voltage at load terminal inside MG is controlled to synchronize to the grid side voltage, because the phase difference between these two terminals would be small due to no large reactive component between two terminals. MG is controlled to start reconnection when line voltage on grid side is recovered between 1 V and 3 V and frequency is recovered between 59. Hz and 1. Hz for 1 ms. For the purpose of synchronization, if the voltage phase on MG side lags more than. to the grid side voltage, the frequency of PV is changed to. Hz and if the voltage phase on MG side leads more than., the frequency is changed to 59. Hz, as shown in Fig. 1. When the phase difference is within 5 for 5 ms, the MC starts to reclose. ms later, when MC has completely closed, controllers for PCS are switched to the gridconnected operation. At the same time, output voltage phase and modulation factor of system interconnection inverter which are used in the isolated operation are passed to the gridconnected operation. B. Experimental Result The controller for switching back to the grid-connected operation is validated experimentally, in the case with the fault condition of 5% voltage drop for 1 sec. The transition time of voltage drop and voltage recovery are 1ms. Firstly, when MG performs the grid-connected operation before the voltage drop, the voltage phase difference is almost zero. However, after the voltage drop occurs and MG switches to the isolated operation at about 7 sec, the phase difference starts to vary continuously due to difference of frequency. After the gird voltage is recovered and synchronization control is activated at 1 sec, the phase difference gradually decreased and became smaller than 5. As a result, MC was closed, resulting in successful reconnection at 1 sec. Fig. 11 shows waveforms of voltages and current for 1 ms around the reconnection. As shown in Fig. 11 (a), the phase difference is smaller than 5 when MG is closed at 5 ms. Fig. 11 (b) shows U phase and V phase current of PCS output increases after switching to the grid-connected operation because converter resumes MPPT and input from PV is increased. However, at the instant of reconnection, the voltage does not rise sharply, therefore, reconnection is completed safely.

Voltage [V] Fig. 1. Conceptual diagram of synchronization control 1 3 5 7 8 9 1 Time [ms] Current [A] 8 Grid side line voltage MG side line voltage Phase difference [.5πrad/div] (a) MG side voltage, grid side voltage and phase difference Current of U phase Current of V phase -8 1 3 5 7 8 9 1 Time [ms] (b) PCS output current (U phase and V phase) Fig. 11. Experimental result of reconnection [] Keiichi Hirose, Tadatoshi Babasaki, Smart Power Supply Systems for Mission Critical Facilities, IEICE Transactions on Communications, vol. E95.B, No. 3, pp.35-33, 1. [3] R. H. Lasseter, J. H. Eto, B. Schenkman, J. Stevens, H. Vollkommer, D. Klapp, E. Linton, H. Hurtado, and J. Roy, CERTS Microgrid Laboratory Test Bed, IEEE Transactions on Power Delivery, vol., issue. 1, pp.35-33, Jan.11. [] Kimio Morino, Atsushi Denda, Kazuhiro Sato, Eisuke Shimoda, Takayuki Sugimoto, Hiroyuki Kihara, Yuji Yamamoto, Toshihiro Yamane and Kei Furukawa, Demonstration Tests of the Smart Grid at the Office Building in City of Albuquerque, Available: http://www.shimz.co.jp/tw/sit/report/vol9/pdf/9_1.pdf [5] J. Rocabert, A. Luna, I. Candela, P. Rodriguez, Seamless disconnection and reconnection transients for Micro-Grids, International Conference on Renewable Energies and Power Quality, Santiago de Compostela, Spain, 1. [] Yunwei Li, Mahinda Vilathgamuwa, Poh Chiang Loh, Design, Analysis, and Real-Time Testing of a Controller for Multibus Microgrid System, IEEE Transactions on Power Electronics, vol. 19, issue. 5, pp/1195-1, Sept.. [7] D. Klapp and H. Vollkommer, Aoolication of an intelligent static switch to the point of common coupling to satisfy IEEE 157 compliance, presented at the IEEE Power ENG. Soc. General Meeting Tampa, Jun, 7. [8] Grid-interconnection Code [13 supplement revision], JEAC 971-1, Mar. 13. VI. CONCLUSION In this paper, uninterrupted switching method between the grid-connected and isolated operation for MG is developed. As for the grid-connected operation, FRT requirements are satisfied due to overcurrent protection and time varying K p. Switching to the isolated operation is successfully completed by passing over the phase and inverter s modulation factor of the gird-connected operation. Switching to the grid-connected operation is also completed safely thanks to synchronization control which avoids overcurrent in connection. VII. ACKNOWLEDGEMENT This work was partly supported by Grant for Environmental Research Projects from The Sumitomo Foundation and the joint usage / research program of the Institute of Materials and Systems for Sustainability (IMaSS), Nagoya University. VIII. REFERENCES [1] Keiichi Hirose, Toyonari Shimakage, James T.Reilly, Hiroshi Irie, The Sendai Microgrid Operational Experience in the Aftermath of the Tohoku Earthquake: A Case Study, NEDO, Case Studies of Smart Community Demonstration Project. Available: http://www.nedo.go.jp/content/ 15173.pdf, 13.