On-Site Partial Discharge Monitoring using the differential LEMKE PROBE LDP-5 and its accessories

Similar documents
PD Solutions. On-Line PD Measurement Devices

Africa Utility Week Focus Day Substation Condition Monitoring Benefits of Ultrasound

The University of New South Wales. School of Electrical Engineering and Telecommunications. High Voltage Systems ELEC9712. Appendix Partial Discharge

Why partial discharge testing makes good sense

Condition Assessment of High Voltage Insulation in Power System Equipment. R.E. James and Q. Su. The Institution of Engineering and Technology

Doble Solutions for Partial Discharge. Greg Topjian Solutions Manager

OMICRON Seminar on Partial Discharge Diagnostics on HV Assets. January 30, 2018 Beirut, Lebanon

PRODUCT PORTFOLIO TEST AND MEASURING SYSTEMS

Advancements in online partial discharge monitoring and assessment of MV through EHV Substation assets

Partial Discharge Measurement and Monitoring on High Voltage XLPE Cables

International Journal of Advance Engineering and Research Development. Comparison of Partial Discharge Detection Techniques of Transformer

EFFECT OF INTEGRATION ERROR ON PARTIAL DISCHARGE MEASUREMENTS ON CAST RESIN TRANSFORMERS. C. Ceretta, R. Gobbo, G. Pesavento

10. DISTURBANCE VOLTAGE WITHSTAND CAPABILITY

PD Diagnostic Applications and TechImp solutions

THE POWER OF LIFE. WinTech Partial Discharge based Predictive Intelligence of insulation system to eliminate power failure risk.

Diagnostic testing of cast resin transformers

NEW MV CABLE ACCESSORY WITH EMBEDDED SENSOR TO CHECK PARTIAL DISCHARGE ACTIVITY

High-Voltage Test and

KEYWORDS On-line diagnostics, cable termination, partial discharge (PD), ultra-high frequency (UHF), sensitivity check.

Onsite Mobile AC High Voltage Test System

Mitigating Murphy s Law While Test. Frédéric Dollinger

Electrical Equipment Condition Assessment

Specialists in HV and MV test and diagnostics. Testing in Substations

SGMF(T) series. Onsite Mobile AC High Voltage Test System. Applications:

HV AC TESTING OF SUPER-LONG CABLES

Partial Discharge Monitoring and Diagnosis of Power Generator

Application Note. Detection of Partial Discharge Using Ultrasound. Detection of Partial Discharge Using Ultrasound. Problem. iriss.

HZJF-9007 Fully Functional Partial Discharge Inspector USER MANUAL. Huazheng Electric Manufacturing(Baoding) Co.,Ltd

PARTIAL DISCHARGE MEASUREMENTS ON GENERATORS USING A NOISE GATING SYSTEM

UHF PARTIAL DISCHARGE DIAGNOSIS OF PLUG-IN CABLE TERMINATIONS

MONTRANO. Continuous monitoring system for power transformers

NOVEL METHOD FOR ON-SITE TESTING AND DIAGNOSIS OF TRANSMISSION CABELS UP TO 250KV

MEDIUM & HIGH VOLTAGE

CVVOZE Power Laboratories (CVVOZEPowerLab)

Investigation of PD Detection on XLPE Cables

Alternative Coupling Method for Immunity Testing of Power Grid Protection Equipment

PRY-CAM BREAKTHROUGH TECHNOLOGY FOR CONDITION ASSESSMENT AND ASSET MANAGEMENT

MPD 600. High-End Measurement and Analysis System for Partial Discharges (PD)

PERMANENT ON-LINE MONITORING OF MV POWER CABLES BASED ON PARTIAL DISCHARGE DETECTION AND LOCALISATION AN UPDATE

UltraTEV Locator Portable Partial Discharge (PD) investigation system.

CHAPTER 2. v-t CHARACTERISTICS FOR STANDARD IMPULSE VOLTAGES

Partial discharge diagnostics on very long and branched cable circuits

THE EVOLUTION OF NON-INTRUSIVE PARTIAL DISCHARGE TESTING OF MV SWITCHGEAR

Chapter-15. Communication systems -1 mark Questions

Parameters influencing Partial Discharge Measurements and their Impact on Diagnosis, Monitoring and Acceptance Tests of Power Transformers

TECHIMP Technologies & Services for Diagnostics and Monitoring of High Voltage Assets

MSR Series. Modular Series Resonant Systems kV; 500kVA...60,000kVA

NOVEL PROTECTION SYSTEMS FOR ARC FURNACE TRANSFORMERS

PARTIAL DISCHARGE DETECTION - AN OVERVIEW

Touchscreens, tablets and digitizers. RNDr. Róbert Bohdal, PhD.

C I R E D 21 st International Conference on Electricity Distribution Frankfurt, 6-9 June 2011

IMPORTANCE OF ACCURATE MEASUREMENTS DURING THE LIFE CYCLE OF UTILITIES

Testing and PD Diagnosis of MV Cable Systems with DAC Voltage Educational Session May St Pete Beach, Fl

PULSE-SEQUENCE ANALYSIS OF PARTIAL DISCHARGES IN POWER TRANSFORMERS

THE PROPAGATION OF PARTIAL DISCHARGE PULSES IN A HIGH VOLTAGE CABLE

Amateur Wireless Station Operators License Exam

MSR Series. Modular Series Resonant Systems kV; 500kVA...60,000kVA FEATURES BENEFITS APPLICATIONS 1/6

Partial Discharge, Survey or Monitor?

SENSITIVITY ASPECTS OF ON-LINE PD DIAGNOSIS OF MV POWER CABLES

UltraTEV Locator. Portable PD (Partial Discharge) investigation system. benefits. features. FACT: 85% of disruptive substation failures are PD-related

UHF PD-DIAGNOSIS AT HIGH VOLTAGE CABLE TERMINATIONS INTERNATIONAL CASE STUDIES

Measurement and Analysis for Switchmode Power Design

FGJTCFWP"KPUVKVWVG"QH"VGEJPQNQI[" FGRCTVOGPV"QH"GNGEVTKECN"GPIKPGGTKPI" VGG"246"JKIJ"XQNVCIG"GPIKPGGTKPI

OMICRON Seminar on Substation Testing and Diagnosis. October 23, 2017 Dubai, United Arab Emirates. October 24, 2017 Abu Dhabi, United Arab Emirates

HVDC Transmission. Michael Muhr. Institute of High Voltage Engineering and System Performance Graz University of Technology Austria P A S S I O N

System description 4. SERVICES ONSITE INSTALLATION AND TRAINING SYSTEM ACCEPTANCE MAINTENANCE... 7

IN HOUSE CALIBRATION OF PD DETECTOR SYSTEM FOR FIELD TEST RESULT RELIABILITY

Definitions of Technical Terms

Effectively Using the EM 6992 Near Field Probe Kit to Troubleshoot EMI Issues

IN ELECTRICAL ENGINEERING - I C M E T CRAIOVA

Advanced Test Equipment Rentals ATEC (2832) CP RC. Resonance circuit for GIS testing

H V T E S T S O L U T I O N S PA RT N E RS F O R H V & E M C

PARTIAL DISCHARGE MEASUREMENT AS A DIAGNOSTIC TOOL FOR CURRENT TRANSFORMER

The importance of partial discharge testing throughout the development and operation of power transformers

ArresterFacts-002. Field Testing Arresters ArresterWorks.com. ArresterFacts are information modules pertaining to the arrester world.

A New Approach for Transformer Bushing Monitoring. Emilio Morales Technical Application Specialist Qualitrol

MPD 500. Partial Discharge Measuring System for Routine Test Applications

ALM473 DUAL MONO \ STEREO AUDIO LEVEL MASTER OPERATION MANUAL IB

Evaluation of Partial Discharge in Power Transformers by Acoustic Emission Method and Propagation Modeling of Acoustic Signal

TD-100. HAEFELY HIPOTRONICS Technical Document

Abstract. 1 Introduction

Title: Southern States Type SLS Smart Sectionalizer Solid Dielectric Three Phase Sectionalizer. Product Specification Guide TABLE OF CONTENTS

CHAPTER -15. Communication Systems

Underwater Spark Sources: Some experimental information.

Surge Mitigation Component Overview

Fault location on power cables. Fault location on power cables

GENERATOR TESTING APPLICATION GUIDE. reliable. precision.

Practical aspects of PD localization for long length Power Cables

Insulating oil testing

CITY SERIES. Compact, fully equipped cable fault location, test and diagnostic systems

Substation Preventive Maintenance

Power Frequency Withstand Voltage On-site testing of 400 kv GIS

Partial Discharge Detection of High Voltage Switchgear Using a Ultra High Frequency Sensor

Computer Networks Lecture -4- Transmission Media. Dr. Methaq Talib

Device Interconnection

1409. Comparison study between acoustic and optical sensors for acoustic wave

Sources of transient electromagnetic disturbance in medium voltage switchgear

Dielectric response and partial discharge measurements on stator insulation at varied low frequency. Nathaniel Taylor

Use optocouplers for safe and reliable electrical systems

Measurement at defined terminal voltage AN 41

Transcription:

Workshop 2000, lexandria, Virginia, 13 & 14 September 2000 paper No.: 8 On-Site Partial Discharge Monitoring using the differential LEMKE PROE and its accessories Dirk Russwurm, HV Technologies, Inc. bstract The differential LEMKE PROE can be used for an quick scan of the partial discharge (PD) level of the different high voltage equipment, like cable accessories, power transformers, instrument transformers, switchgear and insulators. To adapt the LEMKE PROE to the different measuring tasks, a set of different sensors can be used. Ranging from galvanic connection on the simple side to ultra-high frequency and ultrasonic adapters on the most sophisticated side. These adapters are explained together with their working principle, advantages and limitations. 1. Introduction Partial Discharges are known to be the major reason for the electrical aging of high voltage insulations. They can be used as an important indicator for aged or damaged insulation, before a breakdown occurs. Recent developments ease the difficulties partial discharge measurement faces under on-site conditions, like electrical noise, crosstalk and outdoor conditions. The differential LEMKE PROE can be used for an inexpensive PD scan of the different high voltage equipment on-site. The work of the equipment is not effected and no outages are required for the testing with the LEMKE PROE. Hence a regular survey can be used for detecting dangerous PD spots, which allows conditiondependent maintenance, increases the reliability and avoids unnecessary preventive exchange of equipment. Measurements on-site are often affected by electromagnetic noise. Therefore powerful noise suppression is necessary. The modular approach of the LEMKE PROE and its sensors and accessories gives the user the opportunity to customize the system. For different measuring tasks, the use of different sensors for the LEMKE PROE is necessary. The sensors and other equipment to be used with the LEMKE PROE are explained more in detail. 2. Common Sensors for PD Measurements 2.1. Standard PD Measurement Circuit The can work as an inexpensive analogue PD detector if connected to a high voltage coupling capacitor and a measuring impedance. This is the setup recommended in IEC-270 and other standards. - Standardized test setup - Standardized calibration procedure - High sensitivity Copyright HV Technologies, Inc. - 2000 8-1

- Needs a direct connection with the high voltage - Mostly restricted to the use in the laboratory - Cannot be applied while DUT is in service PD measurement by the electric field C S1 PD standard measurement (acc. to IEC 270 etc.) C S2 - Differential LEMKE probe - Coupling capacitor C - Measuring impedance LDM-5 D - Connection cable Figure 1: PD measurements according to IEC-270 2.2. Capacitive Sensor C D The stray capacitance between the high voltage parts of the DUT and the electrode of the capacitive sensor are working as the coupling capacitor in this case. Figure 2: Lemke Probe with C-Sensor - Differential LEMKE probe - Capacitive sensor (electrical field sensor, C-sensor) CS1 - Stray capacitance between HV and CS2 - Stray capacitance between and ground Figure 3: Using the C-Sensor - No connection to the high voltage is required, can be used while the test object stays in service - No coupling capacitor required - Easy test allows a quick scan of all substation equipment - When put on a hot-stick, the is potential-free and can be moved near the high voltage. - Requires direct line-of-sight to the high voltage connection of the DUT - Does not work thru electrical shields, metals screens etc. - Not very sensitive (depending on sensor size) - Not very directional, can be influenced by noise sources (corona on connectors, pd in nearby equipment, M stations etc) To improve the sensitivity, larger sensors and direct grounding of the probe can be used. Differential mode One special mode of operation is the differential mode. It requires two small C-sensors and is used to pinpoint PD locations. The two C-sensors are connected to the positive and negative input of a differential amplifier. If both sensors see exactly the same signal, the output reads zero. So the goal is to zero-out the PD signal by moving the until the PD source is exactly in the middle between both C- HV Technologies, Inc. - Workshop 2000, 13 & 14 September, lexandria, Virginia 8-2

sensors. n accuracy of a fraction of an inch can be reached. The differential mode is best used for pin-pointing a PD failure within an unshielded insulation, like dry-type transformers, instrument transformers, unshielded cable joints and terminals. 2.3. Inductive Sensor The working principle of the inductive sensor (Lsensor) is known from current transformer and the Rogowski coil. The magnetic field around a wire (e.g. the ground connection) caused by the HF currents induces a voltage in the winding of the inductive sensor. This voltage is measured. Figure 4: in Differential Mode PD location by differential mode Figure 6: Lemke Probe with L-Sensor PD current measurement by the magnetic field - PD site in the insulation (not shielded) - Differential LEMKE probe with two small C-sensors at the differential inputs Figure 5: Differential mode for fault location - Differential LEMKE probe - Inductive sensor (magnetic field sensor, L-sensor) Figure 7: Using the L-Sensor HV Technologies, Inc. - Workshop 2000, 13 & 14 September, lexandria, Virginia 8-3

Figure 8: PD Measurement in a Substation - No connection to the high voltage is required - Can be used while the test object stays in service - No coupling capacitor required - Easy test allows a quick scan of all substation equipment - Very sensitive - Has no directional selectivity - Does not work thru shields - Requires direct access to e.g a grounding wire The L-sensor has to be held in parallel to the wire. Do not thread the wire thru the sensor opening. 2.4. Galvanic Coupling The galvanic coupling uses the voltage drop over e.g. a piece of the shielding to measure the signal. - No connection to the high voltage is required - Can be used while the test object stays in service - No coupling capacitor required - llows a measurement of currents flowing on the surface of a shield - Needs a direct galvanic contact to the wire or shield used lways press both tips firmly on the surface. The galvanic coupling is seldom used. Figure 9: Lemke Probe for direct measurement 3. Specialialized Sensors These specialized sensors fulfill tasks that are impossible with the standard test setup. 3.1. UHF/VHF Sensor Depending of the discharge conditions, the PD can have a frequency spectrum reaching up to several Giga-Hertz (GHz). The range above several hundred Mega-Hertz is called Ultra High Frequency, abbreviated UHF. Many TV stations and cell phones e.g. are using this frequency band. Using this frequency band for PD detection offers many advantages under certain circumstances. Many noise sources, like radio stations, semiconductor switches or even the corona PD in air have a lower frequency spectrum and therefore don t affect the measurement. These ultra-high frequencies will be rapidly attenuated within solid or liquid insulations, allowing a precise pinpointing of a PD location. These characteristics also prevent the detection of a PD fault deep within a solid or liquid insulation. On the other hand many shields designed for 60 Hz are not very effective at several hundred Mega-Hertz, thus allowing the detection of PD on otherwise shielded equipment. HV Technologies, Inc. - Workshop 2000, 13 & 14 September, lexandria, Virginia 8-4

Figure 10: with UHF-Sensor LD-5/U PD location by ultrahigh frequency (UHF) - PD site in the insulation - Differential LEMKE probe C - UHF adapter LD-5/U C Figure 11: Using the UHF Sensor LD-5/U - No connection to the high voltage is required - Can be used while the test object stays in service - No coupling capacitor required - Perfectly suited for PD measurements on SF 6 gas insulated switchgear and lines (GIS and GIL) - est solution for pin-pointing a PD fault within shielded insulations, like power cables, cable joints and terminations - Requires special built-in sensors for GIS and GIL - Works only near the PD source in solid or liquid insulations (within inches) - Needs proximity to the insulation surface. Safety distances to HV terminals can prevent the use - In other than SF 6 insulated GIS a calibration for the PD level makes no sense. The common power equipment behaves very different in the UHF band. Many electrical resonances in the equipment, the strong attenuation of the signals on short distances, the short wavelength of the UHF signal and the strong influence of the calibrator connections result in a calibration not representing the real conditions in the PD fault. Instead an adapted calibration will be used which ensures the same input sensitivity of the detectors. The UHF sensor is direction sensitive. Turn it until the maximum reading is reached. The propagation of HF electromagnetic waves has to be taken into account. 3.2. Ultrasonic Sensors Figure 12: Cable Joint testing with the UHF- Sensor in a Manhole partial discharge generates not only a fast transient electromagnetic field, which is picked up by the other sensors described in this paper, but also other phenomena like a light flash or an acoustic pressure wave are emanated. Under certain circumstances it is advantageous to use the acoustic impulse for detection. The general limitations for acoustic detection are: - No calibration possible. There is no relationship between the electrical discharge and the generated sound wave, which could be used for calibration. The level of the sound HV Technologies, Inc. - Workshop 2000, 13 & 14 September, lexandria, Virginia 8-5

wave is strongly depended on the location of the fault and the wave distribution. - Many PD faults cannot be recognized, because the attenuation of the signal path between fault and detector is too high. This is especially true if the signal has to pass thru several layers of different materials or extruded insulation. Ultrasonic PD detection F - ccurate location of the defects from a safe distance - est results for locating corona discharges in air or surface discharges (tracking) on insulators - est suited for scanning of insulator chains etc. - Needs a line-of-sight between the PD failure and the detector - Cannot locate internal PD - Location can be misguided by the reflection of the ultrasonic wave on walls and other straight surfaces. - No calibration possible C G - PD in the insulation oil - Conducted ultrasonic sound C - Differential LEMKE probe D - Ultrasonic adapter LD-5/S E - Ultrasonic transducer for conducted sound F - PD on a pin in air ("corona") G - Ultrasonic transducer for sound in air Figure 13: Ultrasonic sensor LD-5/S 3.2.1. Parabolic Reflector E D C One characteristic of ultrasonic waves compared to electromagnetic waves of the same frequency is that the wavelength is much shorter. This allows the design of highly directional sensors with reasonable mechanical dimensions. One example is the parabolic reflector (dishmirror). It concentrates the sound waves coming from one direction onto the transducer in its focal point. With its sights the user can determine the location of the discharge site from up to one hundred feet away. The use of ultrasonic frequencies (above 20kHz) makes the equipment more sensitive and results in a better signal-to-noise ratio compared to the normal audio range. - No connection to the high voltage is required, can be used while the test object stays in service 3.2.2. Transducer Steel conducts ultrasound very well while it screens the electromagnetic field. Therefore it is possible to detect partial discharge inside an oilfilled power transformer steel tank by its emanated ultrasound. n ultrasonic transducer (a microphone for surface waves) is pressed against the outer side of the steel wall and receives the shock wave from the partial discharge in the transformer oil. This also allows locating the PD sources by triangulation, if e.g. three transducers are used. The location is made difficult by reflections inside the transformer, refraction in different materials or caused by different oil temperatures, and the much higher speed of propagation in steel than in oil. Therefore it requires an experienced operator with a sound knowledge of the layout of the transformer and the propagation of the ultrasonic waves to reliably locate the PD source. - No connection to the high voltage is required, can be used while the test object stays in service - llows PD detection thru the transformer steel tank - Locating the PD source is possible - est used for oil-filled transformer with steel tank - est detection results for PD in oil with direct line-of-sight to the steel wall - No detection of PD possible inside the winding, in the bushing and possible air cushion above the oil - Calibration not possible For transformer testing, a combination of electrical and acoustic testing gives the best re- HV Technologies, Inc. - Workshop 2000, 13 & 14 September, lexandria, Virginia 8-6

sults. The electrical measurement detects PD in the winding and in the bushing. It gives the pc reading to estimate the severity of the PD fault. The electric signal can also trigger the acoustic measurement, thus simplifying the location. 4. Noise Suppression The conditions for PD measurement in the field are far from optimal. M radio stations, other transmitters, variable frequency drives and other electronic devices as well as other HV substation equipment generates a multitude of electrical noise which affects the PD measurement. Noise sources can be divided into two different kinds. - Narrowband noise: Examples are M radio stations. They generate a strong electromagnetic signal on a very small frequency range. Normally this noise is continuous. Often the modulation (music, talk) can be heard from the built-in speaker of the Lemke Probe. - This noise can be suppressed with an additional filter or the built-in RIV suppression. - Wideband impulse noise: Generated from all kind of electrical switching and other PD sources. Examples are thyristor switches (light dimmer), transistor switches (variable frequency drives), activated circuit breakers. n example for often undesired PD noise is the corona discharge from overhead power lines. - This can be suppressed with the noise impulse comparator LDK-5. - Sometimes these noise pulses are stable in respect to the power voltage phase angle (Thyristor and transistor switches). In this case these signals can be deleted from the recorded signal afterwards, using the software noise suppression of the LDS-5. Each kind of noise has to be treated differently to suppress this noise. The operator needs experience to correctly identify and suppress the noise. 4.1. uilt-in RIV Suppression To suppress noise from M stations, the has a built-in RIV function (RIV = Radio Interference). Its working principle is as follows: ecause the PD detector has to integrate the signal over a given time, the continuous M narrowband wave with a relatively small peak voltage (amplitude) gives the same reading as a short impulse with a higher peak voltage. y providing an adjustable threshold voltage, the smaller M wave will be attenuated much more than the PD impulse and will be entirely suppressed. Figure 14:Operating the (RIV Reduction on the Lefthand Side) - Improves the signal-to-noise ratio - PD signals below the noise level can be detected - Suppresses only M noise effectively - Creates a non-linearity in the reading If used, it has to be used for the calibration also. The RIV suppression makes the integration process nonlinear. The reading at the calibration setpoint still fits, but higher PD values might be less than indicated while smaller pulses will be displayed even less (e.g. when calibrated with 100 pc, a 50pC signal might be displayed as 40pC). 4.2. Noise Filter LDF-5 The wideband integration of the Lemke Probe makes the use of band-stop filters possible. and-stop Filter suppresses only a small portion of the frequency spectrum but passes on the rest. The loss of a small frequency band does not affect the operation of a wideband detector; the calibration process will compensate for this. HV Technologies, Inc. - Workshop 2000, 13 & 14 September, lexandria, Virginia 8-7

When adjusted to the frequency of the narrowband noise, the Noise Filter LDF-5 will suppress this noise. n improvement of the signal-tonoise ratio by a factor of ten is possible under good conditions. The noise gating uses an electronic gating circuit and closes the gate for the measurement when the noise level is above an adjustable threshold level, thus blocking the noise (and possible PD happening at the same time) from reaching the display. Usually impulse noise happens only for a short time of some Microseconds. Therefore the likelihood of blocking PD signals together with the noise is small. It is very unlikely that it blocks two or three PD signals in a row, so the PD level and pattern will still be the same while using noise gating. Sometimes the measuring time can be increased to compensate for the loss in PD events. Example for noise suppression Figure 15: Noise Filter LDF-5 - Improves the measurement sensitivity if narrowband noise occurs - Does not affect the linearity of the PD detector - Multiple narrowband noise with widely different frequencies will not be suppressed effectively If the noise filter LDF-5 does not seem to work, check the battery first. It needs the battery also in the passive mode. LDK-5 C D 4.3. Noise Gating with the LDK-5 The electrical waveshape of impulse noise is very similar to a PD pulse. Therefore it cannot be filtered out as narrowband noise. The approach to suppress impulse noise uses a second Lemke Probe to record the noise events only from a place where the noise is strong but the PD signals will not appear (e.g. the low-voltage power line). Then both signals, the PD signal with the noise disturbances and the noise signal alone will be fed into the Noise Comparator LDK-5. The LDK-5 has two modes of operation: Noise gating and noise subtracting. The noise subtracting basically subtracts the noise from the PD plus noise signal. While seeming straightforward, it is difficult to adjust and therefore the less recommended mode. - with disturbed signal - 2nd for catching the noise C - Noise comparator LDK-5 D - Display (e.g. LDS-5) Figure 16: Use of the Noise Impulse Comparator - llows PD measurements in areas with strong impulse noise - Very useful for measurements in substations and power plants - Can suppress some PD signals together with the noise - second is needed together with the LDK-5 Take care not to compensate too much or set the gating threshold level to low. good test is to check if most of the calibration signals can still be seen on the calibration. HV Technologies, Inc. - Workshop 2000, 13 & 14 September, lexandria, Virginia 8-8

5. Digital PD Measurement Digital PD measuring systems offer many advantages over the older analog detectors. The clearer display at the measurement, the recording of each single PD event on the hard disk and especially the advanced analysis make the diagnosis easier and more accurate. Most digital PD detectors are designed for the HV laboratory. To get a digital PD measuring systems for field tests, the Lemke Probe can be combined with the LDS-5, basically a selected laptop in a sturdy carry case. The LDS-5 digitizes displays and records the whole PD measurement on the hard disk. PD signal recording Figure 18: Digital On-Site PD Measurement - Differential LEMKE probe - PD Measuring system LDS-5 (portable laptop computer) Figure 17: Digital PD Detector System by combining and LDS-5 - Converts the analog Lemke Probe or other analog PD detectors, e.g. the LDD-5, to a digital PD measuring system - Records every PD event with respect to its magnitude, time and phase angle on the hard disk for later analysis - Real-time display of the recorded PD gives an immediate overview and helps to recognize noise. - Comprehensive analysis possible on-site or later in the office - Comparing the data with datasets previously recorded shows trending. - nalysis software creates e.g. a digital fingerprint of the PD characteristics and shows the maximum likelihood of the failure reason based on an internal database of previously recorded fingerprints. This can greatly simplify the analysis. - The LDS-5 can be used advantageously for all kinds of PD tests. - Connection of the computer to e.g. the Internet let you share data and experience. - The laptop computer can handle max. 10,000 PD events per second. If two PD pulses are less than 100µs apart, only the larger one will be recorded. HV Technologies, Inc. - Workshop 2000, 13 & 14 September, lexandria, Virginia 8-9

6. Summary The Lemke Probe is a small hand-held partial discharge detector for on-site measurements and PD location. This paper showed the application of the different sensors of the Lemke Probe for the different measurement tasks, together with noise suppression and digital recording. The modular approach lets you start with e.g. the Lemke Probe and add the needed components, like special sensors, noise suppression and the computer system LDS-5 later. Figure 19: Recorded PD Pattern 7. References /1/ Partial discharge measurements. IEC Publication 270, 1981. /2/ Manual Differential Lemke Probe, Lemke Diagnostics, Germany, 1994 /3/ Manual UHF/VHF Converter LD-5/U, Lemke Diagnostics, Germany, 1997 /4/ Manual Ultrasonic PD Sensor LD-5/S, Lemke Diagnostics, Germany, 1997 Figure 20: 3-D-Representation of the PD Recording /5/ Manual PD Noise Filter LDF-5, Lemke Diagnostics, Germany, 1994 /6/ Manual PD Noise Impulse Comparator LDK-5, Lemke Diagnostics, Germany, 1995 /7/ Manual Partial Discharge Measuring System LDS-5, Lemke Diagnostics, Germany, 1998 /8/ Lemke, E., Schmiegel, P.: Introduction to fundamentals of PD diagnostics, Lemke Diagnostics, Germany, 1991 Figure 21: utomatic Failure Diagnosis /9/ Lemke, E.: new partial measuring procedure based on the evaluation of the cumulative charge, Conference on PD in Electrical Insulation, angalore / India, 1976, pp. 1-22. /10/ Lemke, E.: new method for PD measurement on poly ethylene insulated power cables 3rd ISH Milan / Italy, 1979, paper 43.13 /11/ Lemke, E.: new procedure for partial discharge measurements on the basis of an HV Technologies, Inc. - Workshop 2000, 13 & 14 September, lexandria, Virginia 8-10

electromagnetical sensor 5th ISH runswig, 1988, paper 41.02. /12/ Lemke E.: PD probe measuring technique for on-site diagnosis tests on HV equipment 6th ISH New Orleans / U.S.., 1989, paper 15.08 /13/ Lemke E., Schmiegel P.: Progress in PD probe measuring technique, 7th ISH Dresden / Germany, 1991, paper 72.01 /14/ Lemke, E., Schmiegel, P.: Fundamentals of the PD Probe measuring technique, Lemke Diagnostics, Germany, 1992 HV Technologies, Inc. - Workshop 2000, 13 & 14 September, lexandria, Virginia 8-11