K Factor Power Transformers

Similar documents
Brown University Revised 2/1/2006 Facilities Design & Construction Requirements SECTION 16461C - DRY TYPE TRANSFORMERS

MGM Transformer. Vacuum Pressure Impregnated (VPI) Dry-Type Substation Transformer Specification Guide

Title Substation Auxiliary Transformer from Rectifier Transformer Secondary. Reference Number PDS 01 (RIC Standard: EP SP)

Series P. Applications

GE Ventilated Dry-Type Transformers. Secondary Substation Transformers - 5 and 15kV Class

ULTRA-K Series 600K - he

KNOW MORE ABOUT THE TRANSFORMERS. Glossary Transformers

Cast resin transformers HARMONY TM

and cured to reduce hot spots and seal out moisture. The assembly shall be installed on vibration-absorbing pads.

General Description & Features Selection Charts Definition of Terms... 42

Dry Type Distribution Transformers NON-LINEAR TRANSFORMER PRESENTATION

ELECTRICAL NETWORKS SPECIFICATION TECHNICAL SPECIFICATION FOR A 230V/110V AND 400V/110V TRANSFORMER

500 kva Dry-type Isolation Transformer V-Delta to 208Y/120V 3PH - NEMA 1/Indoor

QUINT-PS/ 3AC/24DC/10

DMRC ELECTRICAL STANDARDS & DESIGN WING (DESDW)

PURCHASE SPECIFICATIONS 500KVA DRY TYPE TRANSFORMER FOR OIL RIG APPLICATIONS

Electrical Description

(

CAST RESIN DRY TRANSFORMER

QUINT-PS/ 3AC/24DC/40

TECHNICAL INFORMATION

SPECIFICATION GUIDE. ABB Power Technology, S.A. Zaragoza, SPAIN. ABB Power Technologies Distribution Transformers

Dry Type Transformers Full Line Catalog. jeffersonelectric.com

DATA SHEET FOR LIGHTING TRANSFORMER APPD. BY VDV PROJECT NO

save energy, it is precious SYNERGY transformers Mfg. of all types of Distribution / Power & Furnace Transformers

INTERNATIONAL TRANSFORMERS. Acme Electric s broad selection of CSA energy efficient transformers

MESP TECHNICAL SPECIFICATION FOR AN ESSENTIAL SERVICES SUPPLY STEP UP TRANSFORMER

UNIVERSITY OF MISSOURI Liquid-Filled Utility Transformers 2016 Q1

Load Isolation Transformers

TECHNICAL SPECIFICATION FOR POWER TRANSFORMER

Notes: Note1: Efficiency is tested at nominal input and full load at +25 C ambient. Output Voltage 400VAC 320VAC 360VAC 400VAC 400VAC

Power Quality. Answering Today s Power Challenges. Why Your Existing Transformer May Be Inadequate. How Harmonics Affect Transformers

Type CP-S, CP-C & CP-A Switch mode

QUINT-PS/ 1AC/24DC/20

75 kva Isolation Transformer V Delta Primary Voltage - 480Y/277 Secondary Voltage - NEMA 3R

LCL Series. SIngle Output Industrial Supplies. High Efficiency. Low Cost. 150 W Convection Cooled. 300 W & 500 W with Internal Fans

10/2 Product overview. 10/3 4AC3 0, 4AC3 1 bell transformers. 10/5 4AC AC3 6 transformers for permanent loads. 10/8 4AC2 4 power supply units

OIL-IMMERSED ARC-SUPPRESSION COILS

Energy Efficient Distribution Transformers

SAMSUNG ELECTRO-MECHANICS CO., LTD

5 kva Isolation Transformer - 115V Primary Voltage - 230V Secondary Voltage - Single Phase - NEMA 3R

Basic Principles and Operation of Transformer

Amveco Toroidal Solutions. Acme Electric s class leading toroidal magnetics is the perfect solution for the most challenging applications.

P2 Power Solutions Pvt. Ltd. P2 Power Magnetics. Quality Power within your Reach. An ISO 9001:2008 Company

Premium 30 Energy Efficient, Low Voltage Transformers General Purpose, Harmonic Mitigating, and K-Rated

Section 2 Outdoor Voltage Transformers

OUTDOOR VOLTAGE TRANSFORMERS (Indoor units available) Description:

Introduction. Centrado leading-edge transformer. Introduction

Notes: Note1: Efficiency is tested at nominal input and full load at +25 C ambient. Output Voltage 400VAC 400VAC

QUINT-PS AC/24DC/40

Unit 29 Three-Phase Transformers

Power Commander. Power Commander Plus. Electronic Line Voltage Regulators. 15 kva 150 kva SINGLE PHASE 15 kva 450 kva THREE PHASE SERIES 900

500 kva Isolation Transformer - 480V Delta Primary - 400Y/231 Wye Secondary - NEMA 3R

PRODUCT SPECIFICATION FOR A 15 AND 75 kva, THREE PHASE MODULAR POWER DISTRIBUTION SYSTEM WITH REGULATION AND CONDITIONING (Varian)

SINGLE PHASE BUCK & BOOST TRANSFORMERS INSTRUCTION MANUAL

CLP0205 Open Frame Power Supply Vac input; 5Vdc output; 200W Output Power; 0.25A stdby

225 kva Autotransformer - 240V Delta Primary Voltage - 220V Delta Secondary Voltage - NEMA 3R

CONSULTANT PROCEDURES & DESIGN GUIDELINES Liquid-Filled Utility Transformers UNIVERSITY OF MISSOURI

SPECIFICATION FOR STEP UP TRANSFORMER 0.415/11Kv and (630KVA & 1000KVA)

GENERAL PURPOSE DRY-TYPE DISTRIBUTION TRANSFORMERS

~=E.i!=h. Pre-certification Transformers

7.5 kva Isolation Transformer - 460V Primary - 230V Secondary - NEMA 3R - Single Phase - 50/60 Hz

PES & IAS NY Chapter And NY LMAG June 23 rd, 2015

Low Pass Harmonic Filters

Dry-Type Transformers

LDC480 Series is a single phase, extremely compact Power Supply with active PFC specially designed for space sensitive and demanding applications.

MESP TECHNICAL SPECIFICATION FOR AN AUXILIARY OR ESSENTIAL SERVICES AND AUXILIARY TRANSFORMER FOR USE IN A RAILWAY SUBSTATION

75 kva Isolation Transformer - 480V Delta Primary - 208V Delta Secondary - NEMA 3R

Single-phase isolating transformers to VDE / EN

Efficiency higher than 85% Power Factor >92% Case TC* Protection Storage Humidity

1.5 kva Single Phase Transformer - 120V Primary Voltage - 277V Secondary Voltage - NEMA 3R

INSTALLATION, OPERATION AND MAINTENANCE GUIDE

3 - Protection components Circuit-breakers

Low Voltage alternators - 4 pole LSA 46.2

Arild Furnes,ATPA OGP/Petrobras workshop, Dry type transformers-ideal for FPSO - Transformers for electrical and drive systems

POWER DELEGATOR SERIES 7200A POWER DISTRIBUTION UNIT WITH POWER CONDITIONING GENERAL SPECIFICATIONS

Application Note. Applicable Product: AC Drives

SHARDA Make Harmonics Filter

Effects of Harmonic Distortion I

Efficiency higher than 85% Power Factor >95% Case TC* Protec on

Convincing technology creates compact performance

80 kva Isolation Transformer - 480V AC Primary - 20V AC Secondary - NEMA 3R - Single Phase

2.2 American National Standards Institute Corporation and its applicable standards C39.1, C80.1, C89, C84.1.

ELETTROMECCANICA. Since english OIL IMMERSED DISTRIBUTION TRANSFORMERS

LDC240 Series is a single phase, ultra compact DIN Rail Switching Power Supply with active PFC, ideal for many applications.

EC centrifugal fan. forward curved, dual inlet with housing (flange)

MINI-PS AC/24DC/1.3

Resilient 3000 EP3000AC48IN Rectifier 3000W Output at 48 58Vdc

2.4. Transformers. Contents Description General-Purpose Encapsulated Transformers Catalog Number Selection... Product Selection... Product Description

Thermistor motor protection relays

Cooling Fans G-17. Cooling Fans G-17. AC Input/Low-Power Consumption EMU Series. AC Input/Compact Size MU Series

LED Driver Constant voltage

Cross Flow Fans. Additional Information. Cooling Fans. Introduction E-85 MF Series E-88 MFD Series E-92

75W Constant Current (700mA) LED Driver

2.5. Contents Description Motor Drive Isolation Transformers... Mini Power Centers... Totally Enclosed Non-Ventilated Transformers

Component Requirement Specification for SGI 500XT Isolation Transformer

CONTENTS XV300K GB r doc XV300K 2/13

Content. 1. Dimensiong of CT s. 2. Error definitions. 3. General design aspects. 4. Linear cores. Certified acc. to ISO 9001/14001, SN EN 45001

120/240 Watt AC-DC Front End with PFC W Series Convert Select 120 Convert Select 240

Transcription:

Ashley-Edison AsiaElectricTransformers (UK) K Factor Power Transformers DTKF series Low Voltage Dry Type K Factor Power Transformers AET-DTKF-2004-01: Page 1 Asia Electric Transformers, Entrepreneur Business Centre, 18 Kaki Bukit Road 3 #01-05 Singapore 415978 + 65 62988550, FAX: + 65 62996069

The widespread use of static rectification equipments and electronics loads such as computers and adjustable-speed-drive motors in light industrial, commercial and residential loads have created a need to apply harmonic loading practices to transformers. Transformers that are intended to supply loads with high harmonic content must be specified with a harmonic current distribution. Hence, a transformer has to be specially designed to cater such needs. To ensure the transformer is designed properly, our company has taken IEEE C57.110-1998 as the reference standard and tested accordance to IEC 60726. In IEEE C57.110-1998 standard, in order to protect against transformer overheating caused by harmonics, designers can specify de-rated equipment, i.e., oversized transformers that will run at a fraction of their rated capacity, or K-factor transformers specifically designed to accommodate harmonic currents. K-factor transformers are preferred because they have additional thermal capacity of known limits, design features that minimize harmonic current losses, and neutral and terminal connections sized at 200% of normal. K-factor transformers allow operation up to nameplate capacity without derating. K-Factor transformers differ from standard transformers. They have additional thermal capacity to tolerate the heating effects of the harmonic currents. Beyond that, well-designed K- Factor transformers will also minimize the winding eddy current losses through the use of parallel conductors and other winding techniques. The K- Factor indicates the multiple of the 50 Hz winding eddy current losses that the transformer can safely dissipate: Transformer load losses consist of winding I 2 R losses plus stray losses. Using UL1561 test methods, stray losses are assumed to be primarily winding eddy current losses for transformers 300 kva and smaller. The result is a larger, more expensive transformer. Figure 1 shows the relationship of a typical transformer capacity being de-rated as the K- factor increases. For example, For a load factor of K13, the capacity of the A typical transformer is reduced by 27%. Page 2

Design Overview K13 Dry Type Transformer is a 3 phase, indoor, insusceptibility to moisture, compact, common core and electro-statically shielded designed to provide a separately derived power source for computer and telecommunication equipment application. Its function is to absorb and reduce the harmonics generated by the equipments and to protect them from electrical noise and transient in the common modes. Due to isolation, there is no direct electrical connection between the primary and secondary within the transformer. The K13 Transformer is designed and manufactured to operate at 100% rated current for both linear and non-linear odd harmonics load up to 25 th harmonic. It is capable to withstand up to 27% overload with linear load at an ambient temperature of 40 o C. Iron Core Cold rolled, oriented grain steel sheet with low specific losses, insulated on both sides by thin organic coating. Windings Copper Strips with Class H (220 o C) enameled coated. Class H(NOMEX) Insulation material is used between overlapping turns or layers. Axial channels are used between layers of primary and secondary winding to provide air gap for uniform cooling. High temperature tolerant fiberglass boards are used as bobbins to separate the core and windings. Sized, transposed and shaped to minimize Eddy current losses. Sized additional 27% to carry triplen harmonics circulating current effect in the delta without overheating the transformer. Fully impregnated with class H varnish and oven dried. Electrostatic screen Neutral Conductor 200% Neutral conductor to cater for triplen and odd harmonics and unbalanced single phase loads. Low Inrush Current Special design measures are implemented to reduce the inrush current, such as Primary winding at outer layers to increase resistance High grade iron core with high saturation to prevent core saturation during startup. Protection Devices(Optional) Thermal protection devices; Thermister (Normally Closed, activated at 160 o C) Digital Temperature Controller Relays (for Auxiliary contacts) Testing Insulation Test at 1000Vdc and Hi-potential test at 2.5KV Resistance Test Open circuit Test (No-load Test) Short circuit Test Temperature Rise Test Noise Level Test Page 3

Standards In accordance with standards: IEC 60726 Dry Type Transformers IEEE C57.110-1998 Establishing Transformer When supplying nonsinusoidal load currents; Quality Assurance ISO 9001:2000 DNV Certification no. 0459-2003-AQ-SIN-RVA Conforming to European Union standards, EN 61558 Electrical Characteristics K13 (50kVA 400kVA) Rated Power (Kva) 50 75 100 150 175 200 250 300 350 400 Rated Primary Voltage Secondary Voltage (At No Load) Frequency Vector Group Insulation Type Test Voltage Enclosure Protection Degree Up to 690 Vac Up to 690 Vac 50/60Hz Dyn11 (If not specified) Class H 2.5kVac, 1 min IP21 Max Ambient Temperature( O c) 40 Max Allowable Temperature Rise( O c) 150 Approx Impedance Voltage (%) 2.5 2.5 3.0 3.0 3.0 3.0 3.0 3.0 3.5 3.5 Noise Level At 1m (db) 45 45 48 50 50 51 51 52 53 54 Losses (W) No-load Iron losses 400 500 600 700 800 900 1000 1100 1200 2500 On-Load Copper losses 800 1000 1500 2000 2800 3200 4000 4500 5000 5500 Electrical Characteristics K13 (450kVA 1000kVA) Rated Power (Kva) 450 500 550 650 750 800 850 900 950 1000 Rated Primary Voltage Secondary Voltage (At No Load) Frequency Vector Group Insulation Type Test Voltage Enclosure Protection Degree Up to 690 Vac Up to 690 Vac 50/60Hz Dyn11 (If not specified) Class H 2.5kVac, 1 min IP21 Max Ambient Temperature( O c) 40 Max Allowable Temperature Rise( O c) 150 Approx Impedance Voltage (%) 3.5 3.5 3.5 4.0 4.0 4.0 4.0 5.0 5.0 5.0 Noise Level At 1m (db) 55 56 56 57 57 58 58 60 60 61 Losses (W) No-load Iron losses 3600 4000 4400 5200 6000 6400 6800 7000 7500 8000 On-Load Copper losses 6000 6500 7000 7500 8200 9000 9500 10000 10500 11000 Non-standard ratings available upon request Page 4

Vector groups The vector group marks the circuitry of windings and their phase position to each other. It consists of a capital and small letter plus a code number. The capital letter refers to the input winding, the small to the output winding. The upper voltage is marked by 1 in front, the undervoltage by a 2 in front, regardless of input or output voltage. The numbers correlate to letters U V W and distinguish the 3 phases. The neutral point (star point) is always marked N. Page 5

Dimensions and weights - without enclosure housing(ip00) (1) Dimensions and weights indicated apply to the transformers with electrical characteristics shown in the previous table and subjected to minor variation of ± 5%. Dimensions: 50-400KVA Rated power (kva) 50 75 100 150 175 200 250 300 350 400 Dimensions (mm) A 500 600 650 720 800 850 880 900 930 960 B 300 330 350 380 380 400 450 450 480 480 C 550 650 700 750 800 850 900 950 980 1000 Approx Weight (Kg) 280 400 500 650 800 900 980 1050 1150 1200 Dimensions: 450-1000KVA Rated power (kva) 450 500 550 650 750 800 850 900 950 1000 Dimensions (mm) A 1000 1050 1100 1200 1300 1400 1450 1500 1550 1600 B 500 550 600 650 700 750 800 850 900 950 C 950 1000 1050 1200 1350 1450 1600 1700 1800 2000 Approx Weight (Kg) 1350 1400 1500 1650 1800 1900 2000 2150 2350 2550 Customized configuration available upon request. Schematic And Terminal Layout Vector Group :Dyn11 (1) Electrostatic screen and neutral are solidly grounded. (2) P1, P2, P3 refer to primary; S1, S2, S3 refer to secondary. P1 P2 P3 Gnd P1 P2 P3 Terminal Layout Top View S1 S2 S3 N S1 S2 Gnd N S3 Page 6

Dimensions and weights - with metal enclosure IP21 Accessories: Rating Plate Earthing points Lifting Lugs Mounting skids Forced air cooled fans Busbar terminals for primary and secondary Metal enclosure IP21 Electrostatic screen Temperature Controller (Optional) Fan Fuse Fan Optional Thermistors Temperature Controller Protection Relay (for Auxiliary Contacts) Mounting Hole 14mmØ Dimensions: 50-400KVA Rated power (kva) 50 75 100 150 175 200 250 300 350 400 No of Fans 2 X 4 2 X 4 2 X 6 2 X 6 2 X 6 4 X 6 4 X 6 4 X 6 6 X 6 6 X 6 Dimensions (mm) A 700 800 950 950 1000 1100 1200 1200 1300 1300 B 550 600 650 650 700 750 800 800 850 900 C 800 900 1000 1000 1100 1100 1200 1250 1300 1400 D 660 760 910 910 950 1050 1150 1150 1225 1225 E 400 500 550 550 550 550 600 600 650 700 F 100 Approx Weight (Kg) 300 430 530 700 850 950 1050 1150 1250 1350 Dimensions: 450-1000KVA Rated power (kva) 450 500 550 650 750 800 850 900 950 1000 No of Fans 6 X 6 8 X 6 8 X 6 12X6 12X6 12X6 16X6 16X6 16 X 6 16X 6 Dimensions (mm) A 1400 1500 1500 1600 1700 1700 1800 2000 2000 2000 B 900 900 950 950 1000 1000 1050 1100 1200 1200 C 1500 1600 1700 1800 1900 2000 2100 2200 2300 2500 D 1325 1425 1425 1525 1625 1625 1725 1925 1925 1925 E 700 700 750 750 800 800 850 900 1000 1000 F 100 Approx Weight (Kg) 1500 1600 1700 1800 2000 2100 2200 2400 2600 2800 Note: Number of fans and louvers are added depending on the capacity of transformer. Page 7

Ordering Specifications AET Dry Type Transformer DTKF series, in accordance with IEC 60726, EN 61558, IEEE C57.110-1998 for high harmonic environment application, suitable for indoor use, in ventilated rooms with a room temperature of -15 C / +40 C. Mandatory Information for quotation/order: Rated Power (kva) : No. of Phase : Input Voltage : Output Voltage : Frequency : Vector Group : Enclosure Protection Degree: : Quantity : Standard Material Iron Core: Cold rolled, oriented grain steel sheet insulated on both sides by thin organic coating. Windings: Copper Strips with Class H (220 o C) enameled coated. Class H(NOMEX) Insulation material. Fully impregnated with class H varnish and oven dried. Oversized by additional 27% of the rated current. 200% Neutral conductor Electrostatic screen Optional components: Thermal protection devices Thermister (Normally Closed, activated at 160 o C) Digital Temperature Controller Relays (for Auxiliary contacts) Ordering code: DTKF-P/S-TC C00 - Witout Casing C55 - IP55 Casing required Series Type Number Of Tappings T2 - Two Tappings required,eg. ±5% Power Rating(VA) 5K0-5kVA No. of Phase 3 - Three Phase S - Single Phase Primary Voltage P415-415V P2K5-2.5kV Secondary Voltage S230-230V S1K0-1000V Example, DTKF250-3P400/S230-T1C00 denote; 250kVA, 3 Phase transformer with input voltage 400V step-down to 230V, casing not required. Frequency by default will be 50/60Hz if not specified. Page 8