EIG DNP V3.0 Protocol Assignments

Similar documents
DNP V3.00 LEVEL 2 Protocol Assignments

SERIES PM172 POWERMETERS COMMUNICATIONS. DNP Communications Protocol REFERENCE GUIDE

DNP V3.00 Protocol Assignments

Series PM130 PLUS Powermeters PM130P/PM130E/PM130EH

E50 MODBUS POINT MAP

MICROPROCESSOR-BASED METERING EQUIPMENT SECTION 16901C PART 2

PowerPlex PowerPlex. DNP3 Interface Option Manual. June 15, 2010 ML0009 Document Revision C 2010 by Bitronics, LLC

C191HM POWERMETER AND HARMONIC MANAGER COMMUNICATIONS REFERENCE GUIDE

Data Sheet. RISH Master Record %THD

Bulletin 1403 Ethernet Communications Card

DIRIS A40/A41 RS485 PROFIBUS DP. Operating instructions F GB D I NL E P. SOCOMEC GROUP switching PROTECTION & ups

MultiComm. DNP3 Protocol Option Manual. June 15, 2010 ML0005 Document Revision C 2010 by Bitronics, LLC

Installation and Operating Instructions

Installation Operation Programming

EASTRON SDM630MCT-RJV / SDM630MCT-RJA User Manual V1.1. Three phase multifunction din rail energy meter

DIRIS A40/A41 RS485 PROFIBUS DP COM. Operating instructions. PROFIBUS Certification

COMMUNICATION MODBUS PROTOCOL MFD44 NEMO-D4Le

Installation and Operating Instructions Quadratic Integra 1530 Digital Metering Systems

Metasys Integrator Power Measurement Ltd. Application

Centrale de mesure Power Meter PM500 Merlin Gerin

Contents. Introduction and description Package contents Device identification PM Options... 80

RISH Master Digital Multifunction Instrument with onsite pluggable output options. Application : Product Features:

UNIVERSAL MEASURING INSTRUMENTS. TNM 34xx. TNM 3410 / 3420 / 3430 / 3440 Universal measuring instrument 1/49

H8238/MCM MODBUS POINT MAP

ENGLISH 3 Phase Multi-function Power Meter 1/5A MID MID

Digital Multifunction Instrument - Rish Master 3440

RISH Master 3430 DIGITAL MULTI-FUNCTION TRANSDUCER. Electro-Meters

Series PM130 PLUS Powermeters PM130P/PM130E/PM130EH

Know your energy. Modbus Register Map EM etactica Power Meter

Know your energy. Modbus Register Map EB etactica Power Bar

ALPHA 50 MULTIFUNCTION METER (ALPHA SERIES)

Integra 1560 and 1580 Digital Transducer Systems

ULTRA RAPID POWER QUALITY ANALYZER

E Electro Industries/GaugeTech 1800 Shames Drive Westbury, New York 11590

InfraStruXure Manager v4.x Addendum: Building Management System Integration

Installation Instructions and Reference Handbook. Installation instructions

RISH Master 3440i/3440iDL 0.2S

DIRIS Ap RS485 JBUS/MODBUS COM. Systèmes de Coupure et de Protection Industrial Switching and Protection Systems ON 1

TCSS 372 Laboratory Project 2 RS 232 Serial I/O Interface

SUPPLY NETWORK ANALYZER CVM-96 SERIES

Technical Data Sheet AMIK 300 / 301

MultiCube Multi-Function Electricity Meter. Installation and Operation

Line-to-line RMS Volts, 3 phases 4 digits (XXX.X) Volts

RI-F200 Series. Single and Three Phase Multifunction Energy Meter. Telephone : +44 (0) Displayed Parameters

EVDP610 IXDP610 Digital PWM Controller IC Evaluation Board

ELECTRICAL VARIABLE ANALYZER RELAY EVAR

MODBUS RS485 SERIAL PROTOCOL

Application Note Assigning and Reducing the DNP V3.0 Points List on the ABB PCD Timothy S. Fahey, PE

RISH EM 3490 DS Dual Source Energy Meter (With All Display Parameters) RISH EM 3490 DS. Application : Product Features:

745 Transformer Protection System Communications Guide

Interface Description A2000. Multifunctional Power Meter Communications Protocol per DIN Draft /2.15

King Fahd University of Petroleum & Minerals Computer Engineering Dept

70 SERIES MEASUREMENT SYSTEM

Metering Devices, Protective Relays, Software and Connectivity

Application Alpha 20 Measures important electrical parameters in 3 phase 4 Wire and 3 phase 3 Wire Network & replaces the multiple analog panel meters

Operating Guide October 2006

User's Manual. ServoCenter 4.1. Volume 2: Protocol Reference. Yost Engineering, Inc. 630 Second Street Portsmouth, Ohio

E Electro Industries/GaugeTech

USER S MANUAL EMPOWER POWER METER TRINITY. Empower Operational Manual

Mx7x. Manual. Mx7x. Modbus for Bitronics 70 Series GRID

TAS APFC Controller / Load Managers with MOD-BUS Interface

PM 305 Operating Guide

AMIK 200 / 201 Technical Data Sheet

Interface Description A2000. Multifunctional Power Meter Communications Protocol per EN /1.15

Ziegler EM 1320/30/40

The MP SERIES CONTROLLER. User s Manual. ISE, Inc.

PM130 PLUS Powermeter Series PM130P/PM130E/PM130EH

Modular Metering System ModbusTCP Communications Manual

VIP Current & Power Multimeter

Servo 8 Torque Board Doc V 1.2

Multimeter 500CVD21 RTU500 series

OHIO SEMITRONICS, INC. DIGITAL AC POWER MONITOR OSI SPECIFICATIONS

Installation & Operation Manual ELNet VIP

MultiComm & MultiComm RTH

EM-72 Electricity Meters for Current Transformers

Energy Management Modular Power Analyzers Type WM2-96

Copley ASCII Interface Programmer s Guide

PM130 PLUS Powermeter Series PM130P/PM130E/PM130EH

PEM353. Universal measuring device

isma-b-w0202 Modbus User Manual GC5 Sp. z o.o. Poland, Warsaw

ALPHA 20 MULTIFUNCTION METER (ALPHA SERIES)

Loss Compensation in 50 Series SCADA Meters. Loss Compensation in 50 Series SCADA Meters. Bitronics D/3 Orion. Loss Compensation in 50 Series 1

DM-III Multitest & DM-III Multitest F Power Quality Recorders

JEMSTAR. Digital Multifunction Electricity Meter. Application Notes

NO WARRANTIES OF ANY KIND ARE IMPLIED ON THE INFORMATION CONTAINED IN THIS DOCUMENT.

RISH PQM. Power Quality Monitor. Preliminary Datasheet subject to change without notice. Individual Harmonics measurement upto 56th Harmonics

Metasys Integrator ESAM E as VND device Application

UNICOM 2500 UNICOM Installation Operation Programming. Universal Communication Converter

PMAC770 Multifunction Power Meter. Installation & Operation Manual V2.0 ZHUHAI PILOT TECHNOLOGY CO., LTD.

PREMIER INSTALLATION AND OPERATING INSTRUCTIONS

Mate Serial Communications Guide This guide is only relevant to Mate Code Revs. of 4.00 and greater

PowerLogic power-monitoring units. PM700 series power meter. Technical data sheet

MODBUS INSTRUCTION MANUAL. Request publication DNP INSTRUCTION MANUAL. Request publication Basler Electric

Soluciones! Para el ahorro y control de la energía eléctrica. Distribuidor autorizado:

ASCO 5210 Digital Power Meter. Operator s Manual DANGER

GIMA Multi-Function Electricity Meter OPERATOR S MANUAL

INTELLIGENT DIGITAL MULTI POWER METER [DIC-MPM]

Circuit Monitor Series 2000

RISH EM 3490 SS Kilowatt Hour Energy Meter With Rs485 RISH EM 3490 SS. Application : Product Features: Indication: Pulse Indication:

Operating Manual RISH EM 1320/30/ _Rev. C - 9/2014

Transcription:

E Electro Industries/G augetech "The Leader in Web Accessed Power Monitoring" EIG DNP V3.0 Protocol Assignments For Futura+ and DM Series Power Monitors Version 1.14 July 15, 2003 Doc # E100-7-03 V1.14 Electro Industries/GaugeTech assumes no responsibility for any inaccuracies and/or errors that may appear in this document. The information printed in this document is subject to change without notice and should not be construed as commitment by Electro Industries/GaugeTech E.I. Electronics, Inc. All comments pertaining to this document should be forwarded to: Attn: Engineering Dept. - DNP Object Mappings Electro Industries/GaugeTech 1800 Shames Drive Westbury, New York 11590 Tel: (516) 334-0870 Fax: (516) 338-4741

DNP is a trademark of the DNP Users Group. Copyright 2003 E.I. Electronics, Inc. Electro Industries/GaugeTech. All rights reserved. Printed in the U.S.A.

E Electro Industries/G augetech "The Leader in Web Accessed Power Monitoring" Table of Contents 1. DNP IMPLEMENTATION... 1 1.1 PHYSICAL LAYER...1 1.1.1 RS-232C...1 1.1.2 RS-485...1 1.1.3 Communication Parameters...1 1.1.4 Baud Rates...1 1.2 DATA LINK LAYER...2 1.2.1 Length Field / Buffer Size...2 1.2.2 Control Field...2 1.2.2.1 Control Bits...2 1.2.2.2 Function Codes...2 1.2.2.2.1 Reset of Data Link ( Function 0 )...2 1.2.2.2.2 User Data ( Function 3 )...2 1.2.2.2.3 Unconfirmed User Data ( Function 4 )...2 1.2.3 Address...2 1.3 TRANSPORT LAYER...3 1.3.1 Transport Header...3 1.4 APPLICATION LAYER...4 1.4.1 Application Headers...4 1.4.1.1 Application Control Field...4 1.4.1.2 Function Codes...4 1.4.1.2.1 Read ( Function 1 )...4 1.4.1.2.2 Write ( Function 2 )...4 1.4.1.2.3 Select ( Function 3 ) (Futura Only)...4 1.4.1.2.4 Operate ( Function 4 ) (Futura Only)...4 1.4.1.2.5 Direct Operate ( Function 5 )...4 1.4.1.2.6 Direct Operate - No Acknowledgment ( Function 6 )...5 1.4.1.2.7 Response ( Function 129 )...5 1.4.2 Application Data...5 1.4.2.1 Object and Variation...5 1.4.2.1.1 Binary Input Status ( Obj. 1, Var. 2 ) (Futura Only)...6 1.4.2.1.1.1 Digital Inputs ( Points 0-3 )...6 1.4.2.1.2 Binary Output Status ( Obj. 10, Var. 2 )...7 1.4.2.1.2.1 Energy Reset State ( Point 0 )...7 Doc# E100-7-03 V1.14 i DNP Implementation

1.4.2.1.2.2 Demand Reset State ( Point 1 ) (Futura Only)...7 1.4.2.1.2.3 Relay States ( Points 2-4 ) (Futura Only)...7 1.4.2.1.3 Control Relay Output Block ( Obj. 12, Var. 1 )...8 1.4.2.1.3.1 Energy Reset ( Point 0 )...8 1.4.2.1.3.2 Demand Reset ( Point 1 ) (Futura Only)...8 1.4.2.1.4 32-Bit Binary Counter Without Flag ( Obj. 20, Var. 5 )...9 1.4.2.1.4.1 Hour Readings ( Point 0-3 )...9 1.4.2.1.5 16-Bit Analog Input Without Flag ( Obj. 30, Var. 4 )...10 1.4.2.1.5.1 Health Check ( Point 0 )...10 1.4.2.1.5.2 Phase Current ( Point 1-3 )...10 1.4.2.1.5.3 Phase-to-Neutral Voltage ( Point 4-6 )...10 1.4.2.1.5.4 Total Power ( Point 7-8 )...11 1.4.2.1.5.5 Phase Power ( Point 9-14 )...11 1.4.2.1.5.6 CT & PT Ratios ( Point-15-18 )...12 1.4.2.1.5.7 Neutral Current ( Point 19 )...12 1.4.2.1.5.8 Frequency ( Point 20 )...12 1.4.2.1.5.9 VA, Phase and Total ( Point 21-24 )...12 1.4.2.1.5.10 Power Factor, Phase and Total ( Point 25-28 )...13 1.4.2.1.5.11 Phase-to-Phase Voltage ( Point 29-31 )...13 1.4.2.1.5.12 Total Harmonic Distortion ( Point 32-37 )...13 1.4.2.1.5.13 Maximum Demands of Total Power ( Point 38-41 )...13 1.4.2.1.6 Time & Date ( Obj. 50, Var. 1 ) (Futura Only)...15 1.4.2.1.6.1 Current Time ( Point 0 ) (Futura Only)...15 1.4.2.1.6.2 Mass Memory Storage Timestamp ( Point 1-3 ) (Futura Only)...15 1.4.2.1.7 Class 0 Data ( Obj. 60, Var. 1 )...16 1.4.2.1.8 Internal Indications ( Obj. 80, Var. 1 )...17 1.4.2.1.8.1 Device Restart ( Point 7 )...17 1.4.2.2 Qualifier and Range...18 APPENDIX A : ANALOG INPUT SECONDARY TO PRIMARY CONVERSION...19 CONVERTING FRACTIONAL TO SECONDARY...19 Example 1...19 CT AND PT RATIOS...20 Example 2...20 CONVERTING FRACTIONAL TO PRIMARY...21 Example 3...21 Example 4...21 APPENDIX B : ANALOG INPUT SCALING FOR ALTERNATE BACK MODULES...22 STANDARD BACK MODULE (120 V)...22 G BACK MODULE (300 V)...22 L BACK MODULE (75 V)...22 Doc# E100-7-03 V1.14 ii DNP Implementation

E Electro Industries/G augetech "The Leader in Web Accessed Power Monitoring" 1. DNP Implementation 1.1 PHYSICAL LAYER Electro Industries meters are capable of using either RS-232C or RS-485 as the physical layer. This is supplied through the use of the appropriate optional communication module, which can be ordered with the meter or separately. 1.1.1 RS-232C RS-232C is used for point-to-point communication only. Electro Industries meters are DCE devices; they transmit on Pin 2 and receive on Pin 3. To connect to a DTE device, like the COM port of a computer, a direct connection cable may be used. To connect to another DCE, a Null Modem cable ( one which flips pins 2 and pin 3 ) must be used. 1.1.2 RS-485 RS-485 provides multi-drop network communication capabilities. Multiple meters may be placed on the same bus, allowing for a Master device to communicate with any of the other devices. Appropriate network configuration and termination should be evaluated for each installation to insure optimal performance. 1.1.3 Communication Parameters Electro Industries meters communicate in DNP V3.0 using the following communication settings: 8 Data Bits No Parity 1 Stop Bit 1.1.4 Baud Rates Electro Industries meters are programmable to use several standard baud rates, including: 1200 Baud 2400 Baud 4800 Baud 9600 Baud Doc# E100-7-03 V1.14 1 DNP Implementation

1.2 DATA LINK LAYER The Data Link Layer as implemented on Electro Industries meters is subject to the following considerations: 1.2.1 Length Field / Buffer Size The internal buffers are limited to 256 bytes. After removing checksums and the headers for the Data Link, Transport and Application Layers, this leaves 212 bytes for application data. Thus, the largest Length allowable is 222 ( 0xDE ). Messages should be constructed with this limitation in mind. 1.2.2 Control Field The Control Byte contains several bits and a Function Code. Specific notes follow. 1.2.2.1 Control Bits Communication directed to the meter should be Primary Master messages ( DIR = 1, PRM = 1 ). Response will be primary Non-Master messages ( DIR = 0, PRM = 1 ). Acknowledgment will be Secondary Non-Master messages ( DIR = 0, PRM = 0 ). 1.2.2.2 Function Codes follow. Electro Industries meters support all of the Function Codes for DNP V3.0. Specific notes 1.2.2.2.1 Reset of Data Link ( Function 0 ) Before confirmed communication with a master device, the Data Link Layer must be reset. This is necessary after a meter has been restarted, either by applying power to the meter or reprogramming the meter. The meter must receive a RESET command before confirmed communication may take place. Unconfirmed communication is always possible and does not require a RESET. 1.2.2.2.2 User Data ( Function 3 ) After receiving a request for USER DATA, the meter will generate a Data Link CONFIRMATION, signaling the reception of that request, before the actual request is processed. If a response is required, it will also be sent as UNCONFIRMED USER DATA. 1.2.2.2.3 Unconfirmed User Data ( Function 4 ) After receiving a request for UNCONFIRMED USER DATA, if a response is required, it will be sent as UNCONFIRMED USER DATA. 1.2.3 Address DNP 3.0 allows for addresses from 0-65534 ( 0x0000-0xFFFE ) for individual device identification, with the address 65535 ( 0xFFFF ) defined as an all stations address. Electro Industries meters addresses are programmable from 0-9999 ( 0x0000-0x270F ), and will recognize address 65535 ( 0xFFFF ) as the all stations address. Doc# E100-7-03 V1.14 2 DNP Implementation

1.3 TRANSPORT LAYER The Transport Layer as implemented on Electro Industries meters is subject to the following considerations: 1.3.1 Transport Header Multiple-frame messages are not allowed for Electro Industries meters. Each Transport Header should indicate it is both the first frame ( FIR = 1 ) as well as the final frame ( FIN = 1 ). Doc# E100-7-03 V1.14 3 DNP Implementation

1.4 APPLICATION LAYER The Application Layer contains a header ( Request or Response Header, depending on direction ) and data. Specific notes follow. 1.4.1 Application Headers Application Headers contain the Application Control Field and the Function Code. 1.4.1.1 Application Control Field Multiple-fragment messages are not allowed for Electro Industries meters. Each Application Header should indicate it is both the first fragment ( FIR = 1 ) as well as the final fragment ( FIN = 1 ). Application-Level confirmation is not used for Electro Industries meters. 1.4.1.2 Function Codes The following Function codes are implemented on Electro Industries meters. 1.4.1.2.1 Read ( Function 1 ) Objects supporting the READ function are: Binary Inputs (Object 1) (Futura Only) Binary Outputs ( Object 10 ) Counters ( Object 20 ) Analog Inputs ( Object 30 ) Time & Date ( Object 50 ) (Futura Only) Class ( Object 60 ) These Objects may be read either by requesting a specific Variation available as listed in this document, or by requesting Variation 0. READ request for Variation 0 of an Object will be fulfilled with the Variation listed in this document. 1.4.1.2.2 Write ( Function 2 ) Objects supporting the WRITE function are: Internal Indications ( Object 80 ) 1.4.1.2.3 Select ( Function 3 ) ( Futura Only ) Objects supporting the SELECT function are: Control Relay Output Block ( Object 12 ) Use of this function starts a 1 second timer for a legal use of the Operate ( Function 4 ) function. 1.4.1.2.4 Operate ( Function 4 ) ( Futura Only ) Objects supporting the OPERATE function are: Control Relay Output Block ( Object 12 ) Use of this function can legally be performed only within 1 second of reception of the appropriate Select ( Function 3 ) function. 1.4.1.2.5 Direct Operate ( Function 5 ) Objects supporting the DIRECT OPERATE function are: Control Relay Output Block ( Object 12 ) Doc# E100-7-03 V1.14 4 DNP Implementation

1.4.1.2.6 Direct Operate - No Acknowledgment ( Function 6 ) Objects supporting the DIRECT OPERATE - NO ACKNOWLEDGMENT function are: Control Relay Output Block ( Object 12 ) 1.4.1.2.7 Response ( Function 129 ) Application responses from Electro Industries meters use the RESPONSE function. 1.4.2 Application Data Application Data contains information about the Object and Variation, as well as the Qualifier and Range. 1.4.2.1 Object and Variation The following Objects and Variations are supported on Electro Industries meters: Binary Input Status (Object 1, Variation 2) (Futura Only) Binary Output Status ( Object 10, Variation 2) Control Relay Output Block ( Object 12, Variation 1 ) 32-Bit Binary Counter Without Flag ( Object 20, Variation 5 ) 16-Bit Analog Input Without Flag ( Object 30, Variation 4 ) Time & Date ( Object 50, Variation 1 ) (Futura Only) Class 0 Data ( Object 60, Variation 1 ) Internal Indications ( Object 80, Variation 1 ) READ requests for Variation 0 will be honored with the above Variations. Doc# E100-7-03 V1.14 5 DNP Implementation

1.4.2.1.1 Binary Input Status ( Obj. 1, Var. 2 ) ( Futura Only ) Binary Input Statuses support the following functions: Read ( Function 1 ) A READ request for Variation 0 will be responded to with Variation 2. Binary Input Statuses may be indexed with Qualifier Codes 0, 1, 2 or 6. Binary Input Statuses are used to communicate the following data measured by Electro Industries meters: Digital Inputs 1.4.2.1.1.1 Digital Inputs ( Points 0-3 ) Some Electro Industries meters are optionally capable of monitoring digital inputs. Binary Input Status points report the state of these inputs. If the feature is not present on this device, the point is reported as being off-line. If the feature is present, the point is reported as being on line. Doc# E100-7-03 V1.14 6 DNP Implementation

1.4.2.1.2 Binary Output Status ( Obj. 10, Var. 2 ) Binary Output Statuses support the following functions: Read ( Function 1 ) A READ request for Variation 0 will be responded to with Variation 2. Binary Output Statuses may be indexed with Qualifier Codes 0, 1, 2 or 6. Binary Output Statuses are used to communicate the following data measured by Electro Industries meters: Energy Reset State Demand Reset State ( Futura Only ) Relay States ( Futura Only ) 1.4.2.1.2.1 Energy Reset State ( Point 0 ) Electro Industries meters accumulate power generated or consumed over time as Hour Readings, which measure positive VA Hours and positive and negative W Hours and VAR Hours. These readings may be reset using a Control Relay Output Block object ( Obj. 12 ). This Binary Output Status point reports whether the Energy Readings are in the process of being reset, or if they are accumulating. Normally, readings are being accumulated and the state of this point is read as 0. If the readings are in the process of being reset, the state of this point is read as 1. 1.4.2.1.2.2 Demand Reset State ( Point 1 ) ( Futura Only ) Electro Industries meters maintain maximum readings on most parameters. These readings may be reset using a Control Relay Output Block object ( Obj. 12 ). This Binary Output Status point reports whether the Demand Readings are in the process of being reset or, if they are active. Normally, maximums are being monitored and the state of this point is read as 0. If the readings are in the process of being reset, the state of this point is read as 1. 1.4.2.1.2.3 Relay States ( Points 2-4 ) ( Futura Only ) Some Electro Industries meters are optionally capable of producing digital outputs using relays. These Binary Output Status points report the state of these relays. If the feature is not present on this device, the point is reported as being off-line. If the feature is present, the point is reported as being on-line. A reading of 1 equals Open, or de-energized. A reading of 0 equals Closed, or energized. Doc# E100-7-03 V1.14 7 DNP Implementation

1.4.2.1.3 Control Relay Output Block ( Obj. 12, Var. 1 ) Control Relay Output Blocks support the following functions: Select ( Function 3 ) ( Futura Only ) Operate ( Function 4 ) ( Futura Only ) Direct Operate ( Function 5 ) Direct Operate - No Acknowledgment ( Function 6 ) Control Relay Output Blocks may be indexed with Qualifier Codes 7, 8 or 9 when used with the Select ( Function 3 ) and Operate ( Function 4 ) functions. Control Relay Output Blocks may be indexed with Qualifier Codes 0, 1 or 2 when used with the Direct Operate ( Function 5 ) and Direct Operate No Acknowledge ( Function 6 ) functions. Control Relay Output Blocks are used for the following purposes: Energy Reset Demand Reset ( Futura Only ) 1.4.2.1.3.1 Energy Reset ( Point 0 ) Electro Industries meters accumulate power generated or consumed over time as Hour Readings, which measure positive VA Hours and positive and negative W Hours and VAR Hours. These readings may be reset using Point 0. Use of the SELECT ( Function 3 ) and OPERATE ( Function 4 ) functions will operate using any settings for the parameters of Control Code, Count, On Time, Off Time and Status. Use of the DIRECT OPERATE ( Function 5 ) or DIRECT OPERATE - NO ACKNOWLEDGE ( Function 6 ) functions will operate only with the settings of Pulsed ON ( Code = 1 of Control Code Field ) once ( Count = 0x01 ) for ON 1 millisecond and OFF 0 milliseconds. 1.4.2.1.3.2 Demand Reset ( Point 1 ) ( Futura Only ) Electro Industries meters maintain maximum readings on most parameters. These readings may be reset using Point 1. Use of the SELECT ( Function 3 ) and OPERATE ( Function 4 ) functions will operate using any settings for the parameters of Control Code, Count, On Time, Off Time and Status. Use of the DIRECT OPERATE ( Function 5 ) or DIRECT OPERATE - NO ACKNOWLEDGE ( Function 6 ) functions will operate only with the settings of Pulsed ON ( Code = 1 of Control Code Field ) once ( Count = 0x01 ) for ON 1 millisecond and OFF 0 milliseconds. Doc# E100-7-03 V1.14 8 DNP Implementation

1.4.2.1.4 32-Bit Binary Counter Without Flag ( Obj. 20, Var. 5 ) Counters support the following functions: Read ( Function 1 ) A READ request for Variation 0 will be responded to with Variation 5. Counters may be indexed with Qualifiers Codes 0, 1, 2 or 6. Counters are used to communicate the following data measured by Electro Industries meters: Hour Readings 1.4.2.1.4.1 Hour Readings ( Point 0-3 ) Point Readings Unit 0 +kw Hour kwh 1 -kw Hour kwh 2 +kvar Hour kvarh 3 -kvar Hour kvarh *These readings may be cleared by using the Control Relay Output Block. Doc# E100-7-03 V1.14 9 DNP Implementation

1.4.2.1.5 16-Bit Analog Input Without Flag ( Obj. 30, Var. 4 ) Analog Inputs support the following functions: Read ( Function 1 ) A READ request for Variation 0 will be responded to with Variation 4. Analog Inputs may be indexed with Qualifier Codes 0, 1, 2 or 6. meters: Analog Inputs are used to communicate the following data measured by Electro Industries Health Check Phase Current Phase-to-Neutral Voltage Total Power Phase Power CT & PT Ratios Neutral Current Frequency VA, Phase and Total Power Factor, Phase and Total Phase-to-Phase Voltage Total Harmonic Distortion Maximum Demands of Total Power 1.4.2.1.5.1 Health Check ( Point 0 ) The Health Check point is used to indicate problems detected by the meter. A value of zero ( 0x0000 ) indicates the meter does not detect a problem. Non-zero values indicate a detected anomaly. 1.4.2.1.5.2 Phase Current ( Point 1-3 ) Point Reading 1 Phase A Current 2 Phase B Current 3 Phase C Current These points are formatted as 2 s complement fractions. They represent a fraction of a 10 A Secondary input. Inputs of above 10 A Secondary will be pinned at 10 A Secondary. For a further explanation of the format of these readings, see Appendix A. 1.4.2.1.5.3 Phase -to-neutral Voltage ( Point 4-6 ) Point Reading 4 Phase AN Voltage 5 Phase BN Voltage 6 Phase CN Voltage Doc# E100-7-03 V1.14 10 DNP Implementation

These points are formatted as 2 s complement fractions. For a standard back meter, they represent a fraction of a 150 V Secondary input. Inputs of above 150 V Secondary will be pinned at 150 V Secondary. For a further explanation of the format of these readings, see Appendix A. For units with back modules other than the standard back module, ( G or 300 V, or L or 75 V ), see Appendix B. 1.4.2.1.5.4 Total Power ( Point 7-8 ) Point Reading 7 Total Watt 8 Total VAR These points are formatted as 2 s complement fractions. For a standard back meter, they represent a fraction of 4500 W Secondary in normal operation, or 3000 W Secondary in Open Delta operation. Inputs above/below +/-4500 or +/-3000 W Secondary will be pinned at +/-4500 or +/-3000 W Secondary, respectively. For a further explanation of the format of these readings, see Appendix A. For units with back modules other than the standard back module, ( G or 300 V, or L or 75 V ), see Appendix B. 1.4.2.1.5.5 Phase Power ( Point 9-14 ) Point Reading 9 Phase A Watt 10 Phase B Watt 11 Phase C Watt 12 Phase A VAR 13 Phase B VAR 14 Phase C VAR These points are formatted as 2 s complement fractions. For a standard back meter, they represent a fraction of 1500 W Secondary. Inputs above/below +/-1500 W Secondary will be pinned at +/-1500 W Secondary. When in Open Delta operation, these points are always zero. For a further explanation of the format of these readings, see Appendix A. For units with back modules other than the standard back module, ( G or 300 V, or L or 75 V ), see Appendix B. Doc# E100-7-03 V1.14 11 DNP Implementation

1.4.2.1.5.6 CT & PT Ratios ( Point-15-18 ) Point Value 15 CT Ratio Numerator 16 CT Ratio Denominator 17 PT Ratio Numerator 18 PT Ratio Denominator These points are formatted as 2 s complement integers. They can be used to convert from units in terms of the Secondary of a CT or PT into units in terms of the Primary of a CT or PT. The ratio of Numerator divided by Denominator is the ratio of Primary to Secondary. Electro Industries meters typically use Full Scales relating Primary Current to 5 Amps and Primary Voltage to 120 V. However, these Full scales can range from ma s to thousands of ka s, or mv s to thousands of kv s. The following rules apply: Full Scales containing fractions of Amps or Volts are truncated before being represented. Full Scales below 32,767 A : 5 A or 32,767 V : 120 V will be represented exactly, in that format. ( Ex. 14.40 kv : 120 V ( 120 : 1 ) would be represented as PT Ratio Numerator = 14,400 ( 0x3840 ), PT Ratio Denominator = 120 ( 0x0078 ) ). Full Scales above 32,767 A : 5 A or 32, 767 V : 120 V are represented as a Primary in terms of a Secondary which is a power of 2. This may produce a ratio that is not exact. ( Ex. 50 ka : 5 A ( 10,000 : 1 ) would be represented as CT Ratio Numerator = 20,000 ( 0x4E20 ), CT Ratio Denominator = 2 ( 0x0002 ) ). Full Scales which are above 32,767 A : 1 A or 32,767 V : 1 V get pinned at 32,767 A : 1 A or 32,767 V : 1 V. 1.4.2.1.5.7 Neutral Current ( Point 19 ) This point is formatted as a 2 s complement fraction. It represents a fraction of 15 A Secondary. Inputs above 15 A Secondary will be pinned at 15 A Secondary. When in Open Delta operation, this point is always zero. For a further explanation of the format of these readings, see Appendix A. 1.4.2.1.5.8 Frequency ( Point 20 ) This point is formatted as a 2 s complement integer. It represents the Frequency as measured on Phase A Voltage in units of chz ( centihertz, 1/100 Hz ). Inputs below 45.00 Hz are pinned at 0 ( 0x0000 ), while inputs above 75.00 Hz are pinned at 9999 ( 0x270F ). 1.4.2.1.5.9 VA, Phase and Total ( Point 21-24 ) Doc# E100-7-03 V1.14 12 DNP Implementation

Point Reading 21 Phase A VA 22 Phase B VA 23 Phase C VA 24 Total VA These points are formatted as 2 s complement fractions. Points 21-23 represent a fraction of 1500 W Secondary. Inputs above/below +/-1500 w Secondary will be pinned at +/-1500 W Secondary. When in Open Delta, points 21-23 are always zero. Point 24 represents a fraction of 4500 W Secondary in normal operation, or 3000 W Secondary in Open Delta operation. Inputs above/below +/-4500 or +/- 3000 W Secondary will be pinned at +/-4500 or +/-3000 W Secondary, respectively. For a further explanation of the format of these readings, see Appendix A. For units with back modules other than the standard back module, ( G or 300 V, or L or 75 V ), see Appendix B. 1.4.2.1.5.10 Power Factor, Phase and Total ( Point 25-28 ) Point Reading 25 Phase A Power Factor 26 Phase B Power Factor 27 Phase C Power Factor 28 Total Power Factor These points are formatted as 2 s complement integers. They represent Power Factors from 1.000 ( 0x0FC18 ) to +1.000 ( 0x003E8 ). When in Open Delta operation, Phase Power Factor ( Points 25-27 ) are always zero. 1.4.2.1.5.11 Phase -to-phase Voltage ( Point 29-31 ) Point Reading 29 Phase AB Voltage 30 Phase BC Voltage 31 Phase CA Voltage These points are formatted as 2 s complement fractions. For a standard back meter, they represent a fraction of a 300 V Secondary input. Inputs of above 300 V Secondary will be pinned at 300 V Secondary. For a further explanation of the format of these readings, see Appendix A. For units with back modules other than the standard back module, ( G or 300 V, or L or 75 V ), see Appendix B. 1.4.2.1.5.12 Total Harmonic Distortion ( Point 32-37 ) Point Reading 32 Phase AN Voltage THD 33 Phase BN Voltage THD 34 Phase CN Voltage THD 35 Phase A Current THD 36 Phase B Current THD 37 Phase C Current THD Doc# E100-7-03 V1.14 13 DNP Implementation

These points are formatted as 2 s complement integers. They represent the percentage of Total Harmonic Distortion (THD) in units of hundredths of a percent (1 / 100 %) fractions. 1.4.2.1.5.13 Maximum Demands of Total Power (Point 38-41 ) Point Reading 38 Maximum Positive Demand Total Watts 39 Maximum Negative Demand Total Watts 40 Maximum Positive Demand Total VAR 41 Maximum Negative Demand Total VAR These points are formatted as 2 s complement fractions. For a standard back meter, they represent a fraction of 4500 W Secondary in normal operation, or 3000 W Secondary in Open Delta operation. Inputs above/below +/-4500 or +/-3000 W Secondary will be pinned at +/-4500 or +/-3000 W Secondary, respectively. For a further explanation of the format of these readings, see Appendix A. For units with back modules other than the standard back module, ( G or 300 V, or L or 75 V ), see Appendix B. Doc# E100-7-03 V1.14 14 DNP Implementation

1.4.2.1.6 Time & Date ( Obj. 50, Var. 1 ) (Futura Only) Time & Dates support the following functions: Read ( Function 1 ) A READ request for Variation 0 will be responded to with Variation 1. Time & Dates may be indexed by Qualifier Codes 0, 1, 2 or 6. Time & Dates are used to report the following information stored in an Electro Industries meter: Current Time Time of most recently stored Snapshot, Event and Waveform Meters that do not have real-time capability do not support the Time & Date Object. 1.4.2.1.6.1 Current Time ( Point 0 ) ( Futura Only ) Meters that have real-time capability use this point to report the Current Time. Meters that could have real-time capability, but do not have it installed, return the default time of midnight, January 1, 1970. 1.4.2.1.6.2 Mass Memory Storage Timestamp ( Point 1-3 ) ( Futura Only ) Point Reading 1 Most Recent Snapshot 2 Most Recent Event 3 Most Recent Waveform Meters that have Mass Memory capability use these points to report the time of the most recent Snapshot, Event and Waveform. Should a log be empty or not present on a particular meter, it will return the default time of midnight, January 1, 1970. Doc# E100-7-03 V1.14 15 DNP Implementation

1.4.2.1.7 Class 0 Data ( Obj. 60, Var. 1 ) Class Data support the following functions: Read ( Function 1 ) for Futura Power Monitors A request for Class 0 Data from an Electro Industries meter will return four Object Headers. Specifically, it will return 16-Bit Analog Input Without Flags ( Object 30, Variation 4 ), Points 0-41, followed by 32-Bit Counters Without Flags ( Object 20, Variation 5 ), Points 0 3, followed by Binary Output Status ( Object 10, Variation 2 ), Points 0-4, followed by Binary Input Status ( Object 1, Variation 2), Points 0-3. Read ( Function 1 ) for DM Series Power Monitors A request for Class 0 Data from an Electro Industries meter will return four Object Headers. Specifically, it will return 16-Bit Analog Input Without Flags ( Object 30, Variation 4 ), Points 0-31, followed by 32-Bit Counters Without Flags ( Object 20, Variation 5 ), Points 0 3, followed by Binary Output Status ( Object 10, Variation 2 ), Point 0-0. (There is NO Object 1.) A request for Object 60, Variation 0 will be treated as a request for Class 0 Data. Class Data may be indexed with Qualifier Code 6. Doc# E100-7-03 V1.14 16 DNP Implementation

1.4.2.1.8 Internal Indications ( Obj. 80, Var. 1 ) Internal Indications support the following functions: Write ( Function 2 ) Internal Indications may be indexed by Qualifier Codes 0, 1 or 2. 1.4.2.1.8.1 Device Restart ( Point 7 ) This bit is set whenever the meter has reset. The polling device may clear this bit by Writing ( Function 2 ) to Object 80, Point 7. Doc# E100-7-03 V1.14 17 DNP Implementation

1.4.2.2 Qualifier and Range Electro Industries meters operate with Qualifier Codes 0, 1, 2 or 6. For codes 0, 1 and 2, the Range field contains 1 byte ( Q-code = 0 ), 2 byte ( Q-code = 1 ) or 4 byte ( Q-code = 2 ) Start Range and Stop Range values, as Indices of data. Qualifier Code 6 may also be used with the following objects: Counter (object 20) Analog Inputs (object 30) Time & Dates (object 50) (Futura Only) Class & Data (object 60) Request with Qualifier Code 6 will return all of the points of the specified object. Doc# E100-7-03 V1.14 18 DNP Implementation

E Electro Industries/G augetech "The Leader in Web Accessed Power Monitoring" Appendix A: Analog Input Secondary to Primary Conversion Converting Fractional to Secondary Most of the Analog Input ( Object 30 ) points are formatted as 2 s complement fractions. The Analog Input value varies from +32,767 to -32,768. Divided by 32,768, this produces the fraction. Multiplying the fraction by the Secondary scale of the particular Analog Input produces the Secondary value. The equation is therefore: Example 1: Secondary Value Analog Input = Secondary Scale 32768 Analog Input Point 4 ( Phase AN Voltage ) returns with the value of 16,384 ( 0x4000 ). The Secondary Scale for this point is 150 Volts Secondary. By the above equation, the Secondary Value is: 16384 32768 150 V Secondary = 75 V Secondary Doc# E100-7-03 V1.14 DNP Implementation: Appendices

CT and PT Ratios To convert from Secondary to Primary, the CT and/or PT Ratio is needed. These ratios may be found by dividing the Ratio Numerator ( Object 30, Point 15 or 17 ) by the corresponding Ratio Denominator ( Object 30, Point 16 or 18 ). The equation is therefore: Ratio = Ratio Numerator Ratio Denominator Example 2: Analog Input Point 17 ( PT Ratio Numerator ) = 19,200 ( 0x4B00 ) and Point 18 ( PT Ratio Denominator ) = 16 ( 0x0010 ). By the above equation, the PT Ratio is: 19200 16 = 12001 : EElectro Industries/GaugeTech Doc# E100-7-03 V1.14 DNP Implementation: Appendices

Converting Fractional to Primary Combining the above two equations, the method of converting a 2 s complement fraction representing a Secondary value into the equivalent Primary value would use the following equation: Primary Value = Analog Input 32768 Secondary Scale Ratio Numerator Ratio Denominator Example 3: Analog Input Point 1 ( Phase A Current ) returns with a value of 9,871 ( 0x268F ), Analog Input Point 15 ( CT Ratio Numerator ) with a value of 2,000 ( 0x07D0 ) and Analog Input Point 16 ( CT Ratio Denominator ) with a value of 5 ( 0x0005 ). The Secondary Scale for Point 1 is 10 A Secondary. By the above equation, the Primary Value is: Example 4: 9871 32768 2000 10 A Secondary = 1205 A Primary 5 The meter is in Open Delta operation. Analog Input Point 7 ( Total Watt ) returns with a value of -12,754 ( 0xCE2E ), Analog Input Point 15 ( CT Ratio Numerator ) with a value of 1000 ( 0x03E8 ), Analog Input Point 16 ( CT Ratio Denominator ) with a value of 5 ( 0x0005 ), Analog Input Point 17 ( PT Ratio Numerator ) with a value of 12,000 ( 0x2EE0 ) and Analog Input Point 18 ( Pt Ratio Denominator ) with a value of 120 ( 0x0078 ). When operating in Open Delta, the Secondary Scale for Point 7 is 3000 W Secondary. By the above equation, the Primary Value is: 12754 32768 1000 12000 3000 W Secondary = 23. 35 MW Primary 5 120 EElectro Industries/GaugeTech Doc# E100-7-03 V1.14 DNP Implementation: Appendices

E Electro Industries/G augetech "The Leader in Web Accessed Power Monitoring" Appendix B: Analog Input Scaling for Alternate Back Modules Standard Back Module (120 V) Voltage readings are scaled relative to the range of the voltage back module. A standard back meter is capable of measuring voltages Phase-to-Neutral up to 150 Volts secondary, and Phase-to- Phase up to 300 Volts secondary. PT Ratios are entered relative to 120 Volts secondary. Voltage and Power readings are scaled as described in their respective sections. G Back Module (300 V) A G Back meter is capable of measuring voltages Phase-to-Neutral up to 300 Volts secondary and Phase-to-Phase up to 600 Volts secondary. PT Ratios are entered relative to 300 Volts secondary. The difference in PT Ratios introduces a difference in scaling voltage and power readings. An extra factor of 300/120, or 2.5, is introduced when interpreting voltage and power readings on a G Back meter. The scaling of phase-to-neutral voltages is to 375 Volts secondary, not 150 Volts secondary, phase-to-phase voltages is to 750 Volts secondary, not 300 Volts secondary. Watt, VAR and VA per phase values are scaled to 3750 Watt, VAR or VA secondary, and not to 1500. Total Watt, VAR and VA values are scaled to 7500 Watt, VAR or VA secondary in DELTA and 11,250 Watt, VAR or VA secondary WYE, instead of 3000 in DELTA or 4500 in WYE. L Back Module (75 V) An L Back meter is capable of measuring voltages Phase-to-Neutral up to 75 Volts secondary and Phase-to-Phase up to 150 Volts secondary. PT Ratios are entered relative to 75 Volts secondary. The difference in PT Ratios introduces a difference in scaling voltage and power readings. An extra factor of 75/120, or 5/8 (0.625), is introduced when interpreting voltage and power readings on an L Back meter. The scaling of phase-to-neutral voltages is to 93.75 Volts secondary, not 150 Volts secondary; phase-to-phase voltages is to 187.5 Volts secondary, not 300 Volts secondary. Watt, VAR and VA per phase values are scaled to 937.5 Watt, VAR or VA secondary, and not to 1500. Total Watt, VAR and VA values are scaled to 1875 Watt, VAR or VA secondary in DELTA and 2812.5 Watt, VAR or VA secondary WYE, instead of 3000 in DELTA or 4500 in WYE. Doc# E100-7-03 V1.14 DNP Implementation: Appendices

EElectro Industries/GaugeTech Doc# E100-7-03 V1.14 DNP Implementation: Appendices