Temperature transmitter with local display RIT 261

Similar documents
Process display RIA 261

Temperature transmitter itemp RTD DIN rail TMT 127

Temperature head transmitter itemp TC TMT 188

Temperature transmitter itemp PCP DIN rail TMT 121

Temperature head transmitter itemp PCP TMT 181

itemp HART DIN rail TMT112

0 2 1 â Ó. itemp HART TMT182. Technical Information

0 2 1 â Ó. itemp HART TMT182. Technical Information

PROGRAMMABLE FIELD TEMPERATURE TRANSMITTER

Temperature head transmitter itemp PCP TMT 181

itemp PA TMT184 Technical information

â Ó itemp TC TMT128 Technical information DIN rail mounted Temperature Transmitter for Thermocouples (TC)

Temperature Transmitters - DIN Rail Mounted

Temperature Transmitters - Head Mounted

Temperature Transmitter itemp RTD DIN rail TMT 127

â itemp Pt100 TMT127 Technical information Pt100 transmitter for DIN rail mounting for high accuracy temperature monitoring

Transmitter. Configuration Code TM01 Series 440 Programmable RTD Temperature Transmitter. Application Areas. Features and Benefits

SITRANS T measuring instruments for temperature

itemp HART TMT142 Technical Information

Digital Temperature Transmitters Model T12.10, Universally Programmable, Head Mounting Model T12.30, Universally Programmable, Rail Mounting

itemp HART TMT142 Technical Information

Temperature Measurement

Paperless Recorder PR20

Advanced Paperless Recorder eco-graph a

TT2780. Temperature head transmitter For resistance thermometers Pt100, settable using a PC, for installation in a sensor head Form B, BUZ, BUZ-H

Temperature measurement TMD 832 head transmitter

Level Limit Switch nivotester FTL 325 P

TMT122 DIN rail itemp HART

Technical Information itemp TMT180

RTD Temperature Sensor omnigrad T -TSM 480, TR 480. Hygienic RTD sensor with Pt 100, class A TSM 480 with electronics programmable via PC

RMA42. Technical Information

Temperature Measurement Transmitters for mounting in sensor head

Temperature Measurement Transmitters for mounting in sensor head

E+H Model PT TMT184. Temperature head transmitter with PROFIBUS-PA -interface. Supply and digital communication using PROFIBUS-PA

C330 / C330X PC-Programmable Universal, 2-wire Transmitter

omnigrad T - TSM 480, TR 480. Technical Information. RTD Temperature Sensor Hygienic design TSM 480 with electronics programmable via PC

Universal Intelligent 2-wire DIN Rail Transmitters

Technical Information RMA42

JUMO dtrans T02 Programmable 4-wire Transmitter (Smart Transmitter)

JUMO dtrans T02 Programmable 4-wire Transmitter (Smart Transmitter)

STT 3000 Series STT170 SMART TEMPERATURE TRANSMITTER Models STT171, STT173, STT17H, STT17F, STT17C

ph / ORP Measurement mypro CPM 431

SITRANS T measuring instruments for temperature

TF 02 / TF 02-Ex. Head mounted temperature transmitters, FOUNDATION Fieldbus (H1), Pt 100 (RTD), thermocouples, 1 or 2 independent channels

600T Series Transmitters. Specification Sheet. Model 653T Electronic temperature transmitter (PC programmable)

Temperature Measurement

Advanced Temperature Transmitter

HART field temperature transmitter Models TIF50, TIF52, TIF62

STT 3000 Series STT170 SMART TEMPERATURE TRANSMITTER Models STT171, STT173, STT17H, STT17F, STT17C

SINEAX V 624 Programmable Temperature Transmitter for RTD and TC inputs

Radar Level Measurement micropilot FMR 130 for stilling wells

High-quality digital indicator for panel mounting Model DI35-M, with multi-function input Model DI35-D, with two inputs for standard signals

C520 / C520X /C520S / C520XS HART Compatible, Universal, Dual-input 2-wire Transmitters

TEK-TEMP 2100A. Explosion-Proof Temperature Transmitter. TEMPERATURE. Technology Solutions

HART Compatible Intelligent 2-wire DIN Rail Transmitters

Head mounted Temperature Transmitter TF02/TF02-Ex

Plug-in module SIRAX V 606, 1 or 2 channels Programmable Temp. Transmitter for RTD and TC inputs

Two-Wire Programmable Transmitter for:

MCR-FL-TS-LP-I-EX SIL IEC Programmable Intrinsically Safe Loop-Powered Temperature Measuring Transducer With HART Protocol

Temperature Transmitters TMT 136, TMT 137

Universal Intelligent 2-wire In-head Transmitters

Universal Intelligent 2-wire DIN Rail Transmitters

Technical Information Barrier RB223

Rosemount 148 Temperature Transmitter

Multifunction Intelligent 4-wire Isolated Signal Conditioner

Temperature Measurement

The Rosemount 848T Wireless Temperature Transmitter

Conductivity Measuring Cells for High-Temperature Applications ConduMax H CLS 16

MODEL: B6U-B B6-UNIT. [2] LCD DISPLAY 0: Without 1: With

Temperature Measurement

itemp TMT82 Technical Information Dual-input temperature transmitter with HART protocol

HART Compatible Intelligent 2-wire In-head Transmitters

STT 3000 Smart Temperature Transmitter Series STT170 Specifications

Analogue Temperature Transmitter

Temperature Measurement

SEM210 SERIES. Programmable In-head Universal Temperature Transmitter INDEX SECTION CONTENTS PAGE NO.

600T Series Transmitters Model 653L Electronic temperature transmitter (PC programmable for RTD and resistance) Specification Sheet

FIELD DEVICES TEMPERATURE

Digital temperature transmitter Model T15.H, head mounting version Model T15.R, rail mounting version

High-precision process calibrator Model CED7000

FieldIT Temperature Transmitter, rail mounted TH102/TH102-Ex

Rosemount 148 Temperature Transmitter

Analogue Temperature Transmitter Model T24.10, PC configurable, Head Mounting

JUMO dtrans T01 HART / T01T HART / T01 Junior / T01 Ex / T01 HART Ex Programmable 2-wire transmitter

Technical Information itemp TMT84

PRODUCT SPECIFICATION AND MODEL SELECTION GUIDE

FieldIT Temperature Transmitter, head mounted TH02/TH02-Ex

Rosemount 148 Temperature Transmitter

JUMO dtrans T01 HART / T01T HART / T01 Junior / T01 Ex / T01 HART Ex Programmable 2-wire transmitter

3 Ex i Isolators. Temperature Transmitter with Output 0/ ma, without Limit Value Contact (Field Circuit Ex i) Type 9182/.0-5.

Digital temperature transmitter for resistance sensors Model T15.H, head mounting version Model T15.R, rail mounting version

3 Ex i Isolators. Temperature Transmitter without Output 0/ ma, with Limit Value Contact (Field Circuit Ex i) Type 9182/.

Rail mounted Temperature Transmitter TH102/TH102-Ex

Miniature resistance thermometer Explosion-protected version Model TR34, thread-mounted

SMART TEMPERATURE TRANSMITTERS. smar

Assembly. Front view. Parametrization interface. Power Bus

P5201 Universal Programmable Transmitters with Galvanic Isolation

FIELD DEVICES TEMPERATURE

Digital temperature transmitter with HART protocol Model T32.1S, head mounting version Model T32.3S, rail mounting version

DSCL, DSCP, SCTP. Industrial Loop Isolators and Transmitters DSCL, DSCP, SCTP. Industrial Loop Isolators and Transmitters

Transcription:

Technical Information TI 091R/2/ae Temperature transmitter with local display RIT 261 Universal field mounted transmitter provides an exceptional backlit temperature indication with five large digits and bargraph Features and benefits Economical temperature transmitter with process value display High accuracy, 0.08% of span Breakdown information in event of a sensor break or short circuit enables a quick maintenance intervention Up to.75 kv galvanic isolation from sensor input to the output Long term stability, < 0.05% / year Electromagnetic compatibility to IEC 6126 for use in noisy environments Customer specific linearization Hazardous area approvals for high safety: - FM, CSA and ATEX 5-digit display, 1 (26 mm) character height Trend bargraph in 10% increments Rear illumination without additonal power supply for easy reading in all weather conditions NEMA X (IP 66) ingress protection for field installation Application areas Plant and panel manufacturers Process monitoring Suitable for RTD thermometers, thermocouples TC, Ohm and mv inputs 2-wire transmitter with a linear temperature proportional analog output PC or HART programmable adds flexibility for the configuration The Power of Know How

I O RIT 261 Operation and system construction Measurement principle System component without own transmitter supply e.g. recorder, display, PLC Active barrier RN 221N RIT 261 as front end display Hazardous area Temperature sensor Example of a temperature application area Temperature transmitter for electronic monitoring, transforming and display in industrial temperature measurement. The device measures an analog measurement signal and indicates this on the display. The display is connected in a to 20 ma current loop and also derives the required power from the loop. Measurement system The temperature display (RIT 261) consists of two main components: a) The microprocessor controlled display with rear illuminated LCD. The set up for measurement range, decimal point, offset and lock is done either in the factory or in an opened housing using the three push buttons (+, -, E) inside the unit. Set up can be accomplished during operation. b) A temperature transmitter (itemp PCM TMT 181 or itemp HART TMT 182) as a two wire transmitter with an analog output, measurement inputs for resistance thermometers and resistance transmitters in 2- - or -wire connection modes, thermocouples and voltage transmitters. Set up is done either in the factory or using the appropriate configuration kit. Input values Measurement type Measurement range Temperature (linear temperature transmission), resistance and voltage Dependent on the sensor connection, the temperature transmitter monitors various measurement ranges (see chart, top of page ). 2

Input type Resistance thermometer (RTD) Input Description Measurement range limits Min. span To IEC 751 (a = 0.0085) Pt 100 Pt 500 Pt 1000 to IEC 751-28 to +1562 F (-200 to +850 C) -28 to +82 F (-200 to +250 C) -28 to +82 F (-200 to +250 C) To DIN 760 (a = 0.006180) Ni 100 Ni 500 Ni 1000 to DIN 760-76 to +82 F (-60 to +250 C) -76 to +02 F (-60 to +150 C) -76 to +02 F (-60 to +150 C) Resistance thermometer ( ) Designation Resistance ( ) Thermocouple (TC) Input To NIST Monograph 175, IEC 58 To ASTM E988 To DIN 710 Voltage transmitter (mv) Connection type: 2-, -, or -wire Software compensation of cable resistance is possible on 2-wire connection TMT 181, 0 to 20 TMT 182, 0 to 0 Maximum sensor cable resistance: 11 per cable on - or -wire connection Sensor current: TMT 181 0.6 ma TMT 182 0.2 ma Measurement range limits 10 to 00 10 to 2000 Description B (PtRh0-PtRh6) E (NiCr-CuNi) J (Fe-CuNi) K (NiCr-Ni) N (NiCrSi-NiSi) R (PtRh 1-Pt) S (PtRh 10-Pt) T (Cu-CuNi) C (W5Re-W26Re) D (WRe-W25Re)) L (Fe-CuNi U (Cu-CuNi) 1 Measurement range limits +2 to +08 F (0 to +1820 C) -5 to +182 F (-270 to +1000 C) -6 to +2192 F (-210 to +1200 C) -5 to +2501 F (-270 to +172 C) -5 to +272 F (-270 to +100 C) -58 to +21 F (-50 to +1768 C) -58 to +21 F (-50 to +1768 C) -5 to +752 F (-270 to +00 C) +2 to +208 F (0 to +220 C) +2 to +52 F (0 to +295 C) -28 to +1652 F (-200 to +900 C -28 to +1112 F (-200 to +600 C) 10 100 Cold junction: internal or external (Pt 100), 2 to 176 F (0 to 80 C) Cold junction accuracy: ± 1.8 F (1 C) Sensor current, 0 na 1 High measuring error increases for temperatures lower than 572 F (00 C) Min. span Min. span 900 F (500 C) 900 F (500 C) 900 F (500 C) 900 F (500 C) 900 F (500 C Designation Millivolt transmitter (mv) Measurement range limits TMT 181, -10 to +100 mv TMT 182, -10 to +75 mv Min. span 5 mv 5 mv Output values Output signal Transmission performance Breakdown information (to NAMUR NE ) Source impedance Filter Current requirement Current limit Analog to 20 ma, 20 to ma Temperature linear, resistance linear, voltage linear Breakdown information is created when the measuring information is invalid or not present anymore and gives a complete listing of all errors occuring in the measuring system. Under ranging: standard,.8 ma Over ranging: standard, 20.5 ma Sensor break, sensor short circuit low: to NAMUR NE,.6 ma Sensor break, sensor short circuit high: to NAMUR NE, 21.5 RIT with TMT 181: maximum (V power supply - 8V - 2V) / 0.025A e.g. (2V - 8V - 2V) / 0.025A = 50 Ω RIT with TMT 182: maximum (V power supply - 11.5V - 2V) / 0.022A e.g. (2V - 11.5V - 2V) / 0.022A = 77. Ω RIT with TMT 181: 1 st order digital filter, 0 to 8 seconds RIT with TMT 182: 1 st order digital filter, 0 to 100 seconds.5 ma RIT with TMT 181: 25 ma RIT with TMT 182: 2 ma

Power up delay Galvanic isolation seconds (during power up sequence I a =.8 ma) U = 2 kv AC (input/output) with TMT 182 Power supply Electrical connections 6 5 1 2 - + 2 1 11.5 to 5 V 11.5 to 0 V Ex to 20 ma TC 6 2-wire -wire -wire RTD W RTD W RTD W 6 6 6 6 6 6 5 5 5 5 Wire terminals Plug on screw terminals: terminal size 16 AWG (1.75 mm 2 ). External ground terminal for 1 AWG (2.5 mm 2 ). Power supply Ripple Cable entries RIT with TMT 181: U b = 10 to 5 VDC, polarity protected RIT with TMT 182: U b = 1.5 to 5 VDC, polarity protected Allowable ripple U SS V at U b 1 V, f max. = 1 khz Two 1/2 NPT cable entries or two Pg 11 cable glands Accuracy Response time Reference conditions Measurement deviation 1 second Calibration temperature: +7. F ± 9 F (+2 C ± 5 C) Description Measurement accuracy * Pt 100, Ni 100 0.6 F (0.2 C) or 0.08% Resistance RTD Pt 500, Ni 500 0.9 F (0.5 C) or 0.20% Pt 1000, Ni 1000 0.5 F (0. C) or 0.12% K, J, T, E, L, U typically 0.9 F (0.5 C) Thermocouple TC N, C, D typically 1.8 F (1 C) S, B, R typically.6 F (2 C) Measurement accuracy * Measurement range Resistance transmitter (Ω) ± 0.1 Ω or 0.08% 10 to 00 Ω ± 0.15 Ω or 0.12% 20 to 2000 Ω Voltage transmitter (mv) ± 20 µv or 0.08% -10 to +75 mv * % refers to the preset measurement range. The largest value is valid Power supply influence Ambient temperature influence (temperature drift) ± 0.01%/V deviation from 2 V (details are refered to Full Scale Deviation) Resistance thermometer (RTD): T d = ± (8. ppm/ F x max. meas. range + 27.8 ppm/ F x present measuring range + 55 ppm/ F) x ϑ Resistance thermometer Pt 100: T d = ± (8. ppm/ F x (range end value + 200) + 27.8 ppm/ F x present measuring range + 55 ppm/ F) x ϑ Thermocouple TC: T d = ± (8. ppm/ F x max. meas. range + 27.8 ppm/ F x present measuring range + 55 ppm/ F) x ϑ ϑ = Deviation of ambient temperature from the reference conditions (7. F ±9 F)

Long term stability Load influence Influence of cold junction Reference conditions (display) Measurement deviation (display) 0.18 F/year (0.1 C/year) (under reference conditions) or 0.05%/year (under reference conditions, % refers to the set up meas. range. The largest value is valid.) ±0.02%/100 W (all details are refered to Full Scale Deviation) Pt 100 IEC 751 CI.B (internal cold junction for thremocouples) T = 77 F (25 C) < 0.1% Full Scale Deviation Application conditions Installation Installation area: wall or stand pipe mounted, see accessories Installation positioning: no limitation Environmental conditions Ambient temperature Storage temperature Climatic classification Moisture condensation Ingress protection Vibration protection Shock resistance EMC/immunity - to +10 F (-20 to +60 C). For hazardous areas, refer to Ex certification. -1 to +158 F (-25 to +70 C) As per IEC 60 65-1, Class D1 Allowed NEMA X (IP 66) 0.7g / 5 to 100 Hz according to IEC 60 068-2-6 7 Nm housing / Nm glass according to EN 5001 The device meets all requirements listed under IEC 6126 Amendment 1, 1998 and NAMUR NE 21. This recommendation is an uniform and practical way of determining whether the devices used in laboratory and process control are immune to interference with an objective to increase its functional safety. Discharge of static electricity IEC 61000--2 6 kv cont., 8 kv air Electromagnetic fields IEC 61000-- 80 to 1000 Hz, 10 V/m Burst (signal) IEC 61000-- 1 kv, 2 kv (B), self recorvery TMT 182, 2 kv Transient voltage IEC 61000--5 1 kv unsym. / 0.5 kv sym. HF coupling IEC 61000--6 0.15 to 80 MHz, 10 V Mechanical construction Dimensions inches (mm) 6.89" (175) 2.56" (65).15" (80).21" (107) 1.57" (0) 6.2" (16) The temperature transmitter (TMT 181 or TMT 182 is fitted behind the hinged display cover. Internal dimensions: H = 2. (60 mm), W = 5.5 (10 mm). Housing can be lead sealed to prevent unauthorized entry. GORE-TEX filter for pressure compensation located left of the cable entries. 2.05" (52) E + - Enter push button (E) Selection push buttons (+, -) 5

Weight Approximately 1.8 lb (80 g) Materials Aluminum pressure die-cast epoxy coated housing with glass insert Wall/stand pipe mounting kit with tensioning band, 0 SS Display and operating system Display elements Display: 5-digit LCD, 1 (26 mm) character height, rear illuminated. Bargraph display in 10% increments, markers for over / under range display. Display range: -19999 to +99999 Offset: -19999 to +2767 Operation: push button operation (-, +, E) integrated in the unit, access when unit is opened Signals: measurement range over / under value Rear illumination: illumination brightness increases with an increase in loop current Display set-up (changes to factory default) Temperature transmitter set-up (changes to factory default) CE mark Approvals Other standards and guidelines Using the three front mounted pushbuttons allows changes to be made without the need for extra tooling. Open hinged cover to access pushbuttons. Set-up can be changed during unit operation. Parameter set-up: measurement range, decimal point, offset, set-up lock code (release code) Configuration kit for itemp PCP TMT 181: configuration kit TMT 181A-VP, set-up using PC software (ReadWin 2000) and PC interface connection cable TTL -/- RS 22 with plug. Configuration kit for itemp HART TMT 182: interface cable Commubox FXA 191, PC operating software COMMUWIN II, or ReadWin 2000, hand held programming unit HART DXR 275. Parameter set-up: sensor type and connection mode, measurement units ( C/ F), measurement range, internal/external compensation point, cable resistance compensation on 2-wire connection, fault condition. Output signal ( to 20/20 to ma), digital filter (damping), offset, measurement point tagging (8 characters), output simulation. Certificates and approvals By attaching the CE mark, confirms that the instrument fulfills all the requirements of the relevant EC directives FM approved intrinsically safe, NI, DIP; Class I, II, III; Division 1, 2; Groups A-G CSA approved intrinsically safe Class I, Division 1, 2; Groups A-D ATEX II 2(1)G EEx ia IIC T6/T5 Details regarding the availability of the intrinsically safe versions (FM, CSA, ATEX) can be obtained from. Relevant data for application protection can be found in separate documentation, available upon request (XA 01R/09/ae). IEC 60529: Degree of protection for housing (IP code) IEC 61010: Safety requirements for electrical measurement, control and lab instrumentation IEC 6126: Eletromagnetic compatibility (EMC requirements) NAMUR: Standarization association for measurement control and control in chemical and pharmaceutical industries (www.namur.de) NEMA: Standardization association for the electrical industry Supplemental documentation RIT 261 temperature display operation manual RIA 261 field display technical information TMT 181 itemp head transmitter technical information TMT 181 itemp operation manual TMT 182 itemp head transmitter technical information TMT 182 itemp operation manual Commuwin II operating software KA 125R/09/a TI 08R/2/ae TI 070R/2/ae KA 11R/09/a TI 078R/2/ae KA 12R/09/a BA 12F 6

Ordering information Application / set-up questionnaire Questionnaire itemp temperature transmitter Customer specific setup Standard setup Sensor TC ( ) B ( ) C ( ) D ( ) E ( ) J ( ) K ( ) L ( ) N ( ) R ( ) S ( ) T ( ) U RTD ( ) Pt100 ( ) Pt500 ( ) Pt1000 ( ) Ni100 ( ) Ni500 ( ) Ni1000 ( ) 2 wire ( ) wire ( ) wire Unit ( ) C ( ) F Range Low scale High scale,, Note!: Range and min. span (see Technical data) Expanded setup Reference junction ( ) internal ( ) external (only TC) [2...176 F; 0 to 80 C] Compensation wire resistance Failure mode ( ) <.6 ma ( ) > 21.0 ma [0...20 Ohm] (only RTD 2 wire) [0...0 Ohm] (only HART) Output ( )...20 ma ( ) 20... ma [ 0, 1, 2,..., 8s] [ 0, 1, 2,..., 100s] (only HART) Offset, [-18... 0...+18 F / -9.9... 0...+9.9 C PCP: 8 char. TAG HART: 8 char. Descriptor: 16 char. Default settings in bold RIT 261 Order code RIT 261-1 2 5 6 7 8 1 Certification A Nonhazardous area version B ATEX II 2(1)G EEx ia IIC T6 C FM IS, NI, DIP Cl I, II, III; Div. 1, 2; Grps A-G D CSA IS, Cl I, Div. 1, 2; Grps A-D, T6 2 Cable entries 1 Two Pg 11 (M20) cable glands 2 Two 1/2 NPT cable entries Accessories 1 Without accessories 2 Mounting bracket for wall/pipe mounting Built-in temperature head transmitter A PCP head transmitter TMT 181 B HART protocol TMT 182 head transmitter 5 Configuration transmitter connection A -wire standard factory configuration RTD -wire configuration RTD -wire configuration 2 RTD 2-wire configuration 1 TC thermocouple configuration 6 Temperature sensor configuration A Standard factory set-up, Pt 100 1 Pt 100, -28 to +1562 F (-200 to +850 C) 2 Ni 100, -76 to +82 F (-60 to +250 C) Pt 500, -28 to +82 F (-200 to +250 C) Ni 500, -76 to +02 F (-60 to +150 C) 5 Pt 1000, -28 to +82 F (-200 to +250 C) 6 Ni 1000, -76 to +02 F (-60 to +150 C) 7 Resistance, 10 to 00 Ohm, minimum span 10 Ohm 8 Resistance, 10 to 2000 Ohm, minimum span 100 Ohm B Thermocouple Type B,+2 to +08 F (0 to +1820 C) C Thermocouple Type C, +2 to +208 F (0 to +220 C) D Thermocouple Type D, +2 to +52 F (0 to +295 C) E Thermocouple Type E, -5 to +182 F (-270 to +1000 C) J Thermocouple Type J, -6 to +2192 F (-210 to +1200 C) K Thermocouple Type K, -5 to +2501 F (-270 to +172 C) L Thermocouple Type L, -28 to +1652 F (-200 to +900 C) N Thermocouple Type N, -5 to +272 F (-270 to +100 C) R Thermocouple Type R, -58 to +21 F (-50 to +1768 C) S Thermocouple Type S, -58 to +21 F (-50 to +1768 C) T Thermocouple Type T, -5 to +752 F (-270 to +00 C) U Thermocouple Type U, -28 to +1112 F (-200 to +600 C) V Voltage transmitter, -10 to 100 mv, minimum span 5 mv 7 Configuration A Standard configuration, 2 to 212 F (0 to 100 C) B Customer specific measurement range C Customer specific expanded thermocouple set-up D Customer specific expanded RTD set-up 8 Mode A Standard model B Factory calibration certificate, 5 measuring points 7

Accessories Mounting bracket B 2.99" (76) 1.57" (0) A 5.51" (10) 6.77" (172) (B) Wall and stand pipe mounting kit (position B), with tensioning band (position A) Order number: SONDST-AA (for North American region) Options (depending on transmitter used): TMT 181A-VP Configuration kit itemp PCP Set-up program (ReadWin) and PC interface cable (TTL/RS 22C) for setting up the temperature transmitter installed (if the factory default parameters are to be changed) Or: Configuration itemp HART TMT 182 using HART protocol. The measured values can also be checked using the HART protocol. There are two possibilities using HART communication: Operation using the HART hand held DXR 275 communicator. Operation with PC operating software ReadWin 2000, Commuwin II or a HART modem (Commubox FXA 191). For application and selection assistance, in the U.S. call 888-ENDRESS For total support of your installed base, 2 hours a day, in the U.S. call 800-62-877 Visit us on our web site, www.us.endress.com United States, Inc. 250 Endress Place Greenwood, IN 61 Phone: (17) 55-718 888-ENDRESS FAX: (17) 55-898 Canada Canada Ltd. 10 Graham s Lane Unit 1, Burlington ON, L7S 1W Phone: (905) 681-9292 800-668-199 FAX: (905) 681-9 Mexico Paseo del Pedregal No. 610 Col. Jardines del Pedregal 01900, Mexico D.F. Mexico Phone: (525) 568-205 FAX: (525) 568-759 TI 091R/2/ae/09.0 200, Inc.