McGill Power Sales & Engineering, INC.

Similar documents
Power Factor & Harmonics

Thyristorised Automatic Power Factor

Welcome to the rd. Annual Northern Ohio. 3 rd Energy Management Conference September 30, 2008

Power Factor improved by Variable Speed AC Drives By Mauri Peltola, ABB Oy, Drives

How Harmonics have led to 6 Power Factor Misconceptions

ARE HARMONICS STILL A PROBLEM IN DATA CENTERS? by Mohammad Al Rawashdeh, Lead Consultant, Data Center Engineering Services

World Academy of Science, Engineering and Technology International Journal of Electrical and Computer Engineering Vol:7, No:6, 2013

LV PFC Basics. Power Factor Correction - Basics FK PC PM PFC Januar 07 Page: 1

Active Harmonic Filter (AF3)

POWER FACTOR CORRECTION. HARMONIC FILTERING. MEDIUM AND HIGH VOLTAGE SOLUTIONS.

ECET Modern Power

ENERGY SAVINGS THROUGH POWER CONDITIONING WITH THE PowerGUARD SYSTEM

SIMPLE SOLUTIONS FOR IMPROVING LIFE OF BREAKERS USED IN TRANSMISSION AND DISTRIBUTION SYSTEMS

Welcome. Power Survey International

HARMONICS THE BASICS H A R M O N I C M I T I G A T I O N A N D D I S P L A C E M E N T P O W E R F A C T O R C O R R E C T I O N

Low Pass Harmonic Filters

Power Quality Monitoring and Power Metering Tutorial

Harmonics I Harmonics White Paper. Power Protection Products, Inc. by Dan Maxcy l 2018 Update

APQline Active Harmonic Filters. N52 W13670 NORTHPARK DR. MENOMONEE FALLS, WI P. (262) F. (262)

Introduction to Harmonics and Power Quality

E S C R I P T I V E B U L L E T I N .,.,.,. Bulletin DB-106. October, Square D Company Power System Studies ---1 I SQU ARED COMPANY --

Harmonics and Their Impact on Power Quality. Wayne Walcott Application Engineering Manager June, 2017

Power Factor. Power Factor Correction.

HARMONICS CAUSES AND EFFECTS

CHAPTER 5 POWER QUALITY IMPROVEMENT BY USING POWER ACTIVE FILTERS

7/15/2002 PP.AFD.08 1 of 28

Chapter L Power factor correction and harmonic filtering

PQ01. Harmonic Solutions for VFD s. Review of Power Control Harmonics, Power Factor, Distortion & Displacement

Harmonic Filters for Single Phase Equipment

CASE STUDY. Implementation of Active Harmonic Filters at Ford Motor Company SA Silverton Plant

How adjustable speed drives affect power distribution

Guide to Harmonics. Reactive Power and Harmonic Compensation POWER QUALITY. The Basics of Harmonics

PRUDENT PRACTICES TO IMPROVE POWER FACTOR AND REDUCE POWER LOSS.

Harmonic Solutions. Clean Power Drive Solution to Harmonic Distortion

Technical Application Papers No.8 Power factor correction and harmonic filtering in electrical plants

Principles for Controlling Harmonics

Harmonics, its Mitigation & Result of Case study of Spinning Mill

THE COMPREHENSIVE APPROACH TO FACILITY POWER QUALITY

Power Quality Overview

Technical News. Part 2: Harmonics. The link between harmonics and power factor. Industrial Electrical and Automation Products, Systems and Solutions

CHAPTER 3 IMPROVEMENT OF LOAD POWER FACTOR USING FACTS CONTROLLERS

Harmonic control devices

Analysis of Harmonic Distortion in Non-linear Loads

POWER QUALITY ASSESSMENT AND MITIGATION AT WALYA-STEEL INDUSTRIES AND ETHIO-PLASTIC SHARE COMPANY

Improve Power Factor and Reduce the Harmonics Distortion of the System

Power Quality and Power Factor Correction

P2 Power Solutions Pvt. Ltd.

3/29/2012 MAIN TOPICS DISCUSSED ELECTRICAL SYSTEMS AND ELECTRIC ENERGY MANAGEMENT SECTION K ELECTRIC RATES POWER COMPUTATION FORMULAS.

Power Quality Symptoms What Is Normal? Power Quality Approach. Other Power Quality Solutions

Power Quality and Circuit Imbalances Northwest Electric Meter School Presented by: Chris Lindsay-Smith McAvoy & Markham Engineering/Itron

Effects of Harmonic Distortion I

DSP-BASED CURRENT SHARING OF AVERAGE CURRENT CONTROLLED TWO-CELL INTERLEAVED BOOST POWER FACTOR CORRECTION CONVERTER

P2 Power Solutions Pvt. Ltd. P2 Power Magnetics. Quality Power within your Reach. An ISO 9001:2008 Company

2.10. Adjustable Frequency Drives. Clean Power Drives. Clean Power Drives

Peteris Spels, ABB Inc., WMEA, November 18, 2011 HARMONICS. ABB Group December 14, 2011 Slide 1

LINEATOR. Advanced Universal Harmonic Filter

POWER FACTOR CORRECTION AND ITS PITFALLS

KNOW MORE ABOUT THE TRANSFORMERS. Glossary Transformers

Fundamentals of Power Quality

There s Gold in Those Waveforms Richard P. Bingham, Dranetz-BMI

Power Quality in Metering

LV Compensation & Filtering Products

1C.4.1 Harmonic Distortion

A Single Phase Power Factor Correction Using Programmable Interface Circuit

Dynamic Harmonic Mitigation and Power Factor Correction

ELEKTROTEHNI KO PODJETJE Leskoπkova cesta 12, 1000 Ljubljana, SLOVENIA

International Research Journal of Engineering and Technology (IRJET) e-issn: Volume: 02 Issue: 04 July p-issn:

Emicon Engineering Consultants L.L.C.

Influence of Switching Elements on Harmonics and Power Factor Improvement

VARIABLE FREQUENCY DRIVE

Highgate Converter Overview. Prepared by Joshua Burroughs & Jeff Carrara IEEE PES

IMPROVING POWER QUALITY AND ENHANCING THE LIFE OF POWER EQUIPMENT, IN RAILWAY TSSs

VFDs and Harmonics in HVAC Applications

T-68 Protecting Your Equipment through Power Quality Solutions

Power Factor and Power Factor Correction

Simulation & Hardware Implementation of APFC Meter to Boost Up Power Factor Maintain by Industry.

Active Harmonic Filter

A Thyristor Controlled Three Winding Transformer as a Static Var Compensator

Do Capacitor Switching Transients Still Cause Problems?

Electrical Energy Saving and Economic Benefits from Power System Harmonics Mitigation in the Petrochemical Plants

Harmonic Mitigation for Variable Frequency Drives. HWEA Conference February 15, Kelvin J. Hurdle Rockwell Bus. Dev. Mgr.

Harmonic Power. A VFDs.com Whitepaper Written by Ernesto Jimenez

International Journal of Advance Engineering and Research Development ANALYSIS AND MITIGATION OF HARMONICS IN MEDICAL FIELD

Phoenix DX Clean Power (18 Pulse) AC Drive

Automatic Power Factor Correction by Using Synchronous Condenser with Continuous Monitoring.

Economical Solutions to Meet Harmonic Distortion Limits[4]

PQ Synergy Effective Harmonic Filter Designs for Commercial Implementation. Team Power Matrix, Sony Jacob.

ZIZTEL LIMITED web: tel: +44 (0) mail: 96 Rolleston Drive, Arnold, Nottingham, NG5 7JP United

PFCC-1000 series. Powerful Flexibility Durability - Quality. Medium Voltage Metal Enclose 5,15,25,35kV Power Factor Correction & Harmonic Filter

AN003. Basic Terms Used for DC Power Supplies. Elaborated by: Marco Geri (R&D Manager - NEXTYS SA.)

POWER QUALITY A N D Y O U R B U S I N E S S THE CENTRE FOR ENERGY ADVANCEMENT THROUGH TECHNOLOGICAL I NNOVATION

Liebert AF2 Next Generation Active Harmonic Filter. Power Protection for Business-Critical Continuity TM

Power Factor Correction of Inductive Loads using PLC

DETUNED INDUCTORS FOR PF IMPROVEMENT CAPACITORS

Power Quality Analysis: A Study on Off-Line UPS Based System

Section 11: Power Quality Considerations Bill Brown, P.E., Square D Engineering Services

Power Quality Analysers

Power Quality. Answering Today s Power Challenges. Why Your Existing Transformer May Be Inadequate. How Harmonics Affect Transformers

Power Quality Analysis in Power System with Non Linear Load

POWER FACTOR CORRECTION USING BOOST CONVERTER

Transcription:

1 McGill Power Sales & Engineering, INC.

Power Factor Correction Terry McGill President McGill Power Sales & Engineering Inc. 2007 Eaton Corporation. All rights reserved.

Agenda What is power factor? What are the costs of low power factor? What are the solutions to low power factor? Power factor correction selection considerations Design considerations and pitfalls 3

Power factor definition Power factor is the ratio between the real power and the apparent power of an electrical system kva kw kvar Real power = working power = kw Apparent power = Volts x Amps = kva Reactive power = magnetizing power = kvar 4

Is the Glass Half Empty or Half Full? Foam/Fizz Capacity (KVAR) Liquid (KW) Full Capacity (KVA) 5

Utility must generate, transmit, and distribute active AND reactive power 6

If reactive power could come from another source utility can reduce 7

Demonstration Power Factor Demonstration Unit 2007 Eaton Corporation. All rights reserved.

Why Consider PFC? PF correction provides many benefits: Primary Benefit: Reduced electric utility bill if there is a penalty (a typical payback period is less than two years) Other Benefits: 9 Increased system capacity Improved voltage regulation Reduced losses in transformers and cables May reduce harmonics on the power system (with harmonic filters)

Where has all the money gone? Energy (kwh) Demand (kw) PF Charges + Taxes 10

Typical Uncorrected Power Factor Industry Percent Uncorrected PF Brewery 76-80 Cement 80-85 Chemical 65-75 Coal Mine 65-80 Clothing 35-60 Electroplating 65-70 Foundry 75-80 Forge 70-80 Hospital 75-80 Machine manufacturing 60-65 Low PF typically results from unloaded or lightly loaded motors Unloaded motor PF =.20 Loaded motor rated PF =.85 Metal working 65-70 Office building 80-90 Oil-field pumping 40-60 Paint manufacturing 55-65 Plastic 75-80 Stamping 60-70 Steelworks 65-80 11 Textile 65-75

Typical Sources of Low Power Factor Reactive power is required by many loads to provide magnetizing current for: Motors Power transformers Welding machines Electric arc furnaces Inductors Lighting ballasts 12

Cost to end user or consumer- Utility fees and surcharges There is no free lunch!! Many utilities pass on the extra costs they incur through penalties, surcharges or other methods Methods of recovering these costs vary with each utility and can be confusing to customers 13

Where do PF charges appear on a bill? Explicit Power Factor Penalty Power Factor Adjustment Power Factor Multiplier Reactive Demand Charge Calculated Demand Billed Demand 14

Where do PF charges appear on a bill? Shift to Temp 624 Model 15

Price/KWH (cents) Escalation in Electrical Energy Cost Electrical Energy cost has increased nearly 50% over the last 10 years. The rate of increase has accelerated in the past few years. Currently the PF adjustment is being increased. 6.5 6 5.5 5 4.5 4 Industrial Electrical Energy Cost by Year 1997 1998 1999 2000 2001 2002 2003 2004 2005 2006 Year Source Energy Information Administration 16

Cost savings due to increased capacity Correcting poor power factor can significantly reduce the load on transformers and conductors and allow for facility expansion Transformers are rated by kva and must be sized accordingly 17

kvar =300 Example increase capacity with new transformer Existing plant has a power factor of 0.80 or 80% PF Existing transformer is 500kVA Plant needs to add new production line of 75kW kva = 500 kw = 400 18

Example increase capacity with new transformer Cost to increase capacity to accommodate new production New transformer next standard size 750kVA Long lead-time Plant shut down to add new transformer days? Labor and materials to install new transformer Upsize conductors for 750kVA transformer Disposal of old transformer 19

kvar = 100 kvar = 100 Example increase capacity by adding PFCC Correct power factor from 80% PF to 97% PF by adding 200kVAR power factor correction capacitor Keep existing 500kVA Add 75kW of new load Existing 500kVA transformer actually runs cooler than before!!!! Power Factor Correction kva = 412 kw =400 Power Factor Correction and addition of 75kW kva = 485 kw =475 20

Example increase capacity by adding PFCC Cost to increase capacity to accommodate new production New power factor correction capacitor Minimal interruption to energize and start up new capacitor system 21

How to correct poor power factor 2007 Eaton Corporation. All rights reserved.

Capacitor Selection Capacitor selection issues (besides size) Utility penalties Installed cost, payback of equipment, and NPV Load variability Voltage regulation Load requirements (Speed of changing PF) Harmonic resonance 23

Effect of Location R 1 R 2 Resistive Load Motor Load Place here for utility PF penalty Place here for line loss reduction and voltage improvement Place here for utility PF penalty (utility owned transformer) or Place here to reduce losses in transformer or free capacity 24

LV Fixed Capacitor Banks Designed for industrial and commercial power systems Lowest installed cost var Range: 1 kvar to 400 kvar 208 Volts through 600 Volts AC Must be harmonic free environment 25

LV Switched (Automatic) PFC Capacitors Banks Automatically sense changes in load Automatic Controller Steps of 50 kvar standard Smaller wall mounted units are available, and can be a real cost savings! 26

LV Harmonic Filtering Equipment Provides similar PF correction (as caps) Avoid harmonic capacitor interaction problems Filter harmonics to reduce voltage and current distortion 27

MV Capacitors Pole Mounted These banks have exposed live parts and are typically supported on a wood power pole. Rack Mounted These banks have exposed live parts and are supported on a steel structure. These banks are usually located in fenced-in substations. Metal Enclosed or Pad Mounted These banks are typically enclosed in a steel enclosure and are usually located within a fenced-in substation or switchgear room. 28

Cost of Power Factor Correction TABLE 4 INSTALLED COST COMPARISON OF POWER FACTOR CORRECTION EQUIPMENT TYPE OF CORRECTION INSTALLED COST, $/KVAR Fixed (LV motor applied) $15 Fixed (LV) $25 Fixed (MV) $30 Switched (LV) $50 Switched (MV) $50 Static Switched (LV) $75 Switched Harmonic Filter (LV) $75 Switched Harmonic Filter (MV) $60 Active Harmonic Filter (LV) $150 29

Additional Application considerations Switching transients Potential resonance 30

Capacitor switching transients Capacitor energization (common event) Voltage difference between system and capacitor Capacitor voltage cannot change instantaneously System voltage pulled nearly to initial capacitor voltage Inrush current as capacitor charges Voltage overshoots and oscillation occurs 31

Harmonics Definition Steady state components of voltage and current at higher frequencies than 60 Hz (or fundamental frequency) Causes Nonlinear loads, normally electronic loads In industrial facility, predominately motor drives (AC or DC), also large UPSs, computer loads, rectifiers These electronic loads draw non-sinusoidal current All load current (particularly transformers and motors) has some amount of harmonic content 32

Expected Harmonics Source Typical Harmonics* 6 Pulse Drive/Rectifier 5, 7, 11, 13, 17, 19 12 Pulse Drive /Rectifier 11, 13, 23, 25 18 Pulse Drive 17, 19, 35, 37 Switch-Mode Power Supply 3, 5, 7, 9, 11, 13 Fluorescent Lights 3, 5, 7, 9, 11, 13 Arcing Devices 2, 3, 4, 5, 7... Transformer Energization 2, 3, 4 * Generally, magnitude decreases as harmonic order increases H = NP+/-1 i.e. 6 Pulse Drive - 5, 7, 11, 13, 17, 19, 33

Harmonic Resonance The Self Correcting Problem Blown Fuses Failed Capacitor If a capacitor exists on the power system AND Harmonic producing loads are in use You MUST check for harmonic resonance. (Series and Parallel) 34

Harmonic Resonance - Solutions 1. Change the method of kvar compensation (harmonic filter, active filter, etc.) 2. Change the size of the capacitor bank to overcompensate or under-compensate for the required kvar and live with the ramifications (i.e. overvoltage or PF penalty). Natural System frequency of oscillation typically at 5th to 13th harmonic 35

When is resonance a concern? Several factors must converge simultaneously for resonance to be a potential problem 1) P.F. correction kvar >25% of xfmr kva 2) Nonlinear load > 25% of xfmr kva 3) Larger, fixed capacitance Often, resonance effects exist to some degree, but is not severe enough to cause problems 36

When is resonance not a concern? Resonance not generally a concern when: Total kvar <15% system kva Total nonlinear load <25% of system kva Adding capacitors to individual motors 37

How to know for sure? Resonance will happen when: Ht = (Sqrt ((xfmer kva / z)/kvar)) Ht = (Sqrt((1000/.058)/300) Ht = (Sqrt(17,241/300)) Ht = (Sqrt (57.47)) Ht = 7.58 Record harmonic data. Determine resonance points. Compare to required kvar. 38

Questions? 39

Power Quality Experience Center and Lab Overview of Lab and Capabilities Purpose To demonstrate and Test PQ Problems and Solutions Power Quality solutions, especially harmonic solutions, are difficult to understand Demystify solutions mis-information and confusion regarding PQ and energy savings Equipment (Harmonic Related) 18 Pulse Drives HMT s Active Filters Broadband Filters Passive (Fixed) Filters Passive (Switched) Filters Active Rectifier (UPS) Reactors Link:http://www.eaton.com/EatonCom/Markets/Electrical/ServicesSupport/Experi ence/index.htm Simply search on Google for Eaton Experience Center 40

41 Thank You.