A Special Ferro-resonance Phenomena on 3-phase 66kV VT-generation of 20Hz zero sequence continuous voltage

Similar documents
Ferroresonance Experience in UK: Simulations and Measurements

A Study on Ferroresonance Mitigation Techniques for Power Transformer

FERRORESONANCE SIMULATION STUDIES USING EMTP

Modeling Ferroresonance Phenomena on Voltage Transformer (VT)

Ferroresonance Conditions Associated With a 13 kv Voltage Regulator During Back-feed Conditions

Capacitive Voltage Substations Ferroresonance Prevention Using Power Electronic Devices

Ferroresonance in MV Voltage Transformers: Pragmatic experimental approach towards investigation of risk and mitigating strategy

Validation of a Power Transformer Model for Ferroresonance with System Tests on a 400 kv Circuit

Effects of Phase-Shifting Transformers, and Synchronous Condensers on Breaker Transient Recovery Voltages

Calculation of Transient Overvoltages by using EMTP software in a 2-Phase 132KV GIS

The Effect of Various Types of DG Interconnection Transformer on Ferroresonance

Tab 2 Voltage Stresses Switching Transients

ELECTRICAL POWER ENGINEERING

Accurate Modeling of Core-Type Distribution Transformers for Electromagnetic Transient Studies

Three-Phase/Six-Phase Conversion Autotransformers

Estimation of Re-striking Transient Overvoltages in a 3-Phase 132KV Gas insulated Substation

Do Capacitor Switching Transients Still Cause Problems?

Estimation of Re-striking Transient Over voltages in a 132KV Gas insulated Substation

DEPARTMENT OF EEE QUESTION BANK

GIS Disconnector Switching Operation VFTO Study

TECHNICAL BULLETIN 004a Ferroresonance

Problems connected with Commissioning of Power Transformers

POWER QUALITY A N D Y O U R B U S I N E S S THE CENTRE FOR ENERGY ADVANCEMENT THROUGH TECHNOLOGICAL I NNOVATION

VFTO STUDIES DUO TO THE SWITCHING OPERATION IN GIS 132KV SUBSTATION AND EFFECTIVE FACTORS IN REDUCING THESE OVER VOLTAGES

POWER FACTOR CORRECTION. HARMONIC FILTERING. MEDIUM AND HIGH VOLTAGE SOLUTIONS.

The Analysis Results of Lightning Overvoltages by EMTP for Lightning Protection Design of 500 kv Substation

2. Current interruption transients

2 Grounding of power supply system neutral

System grounding of wind farm medium voltage cable grids

Study of High Voltage AC Underground Cable Systems Silva, Filipe Miguel Faria da; Bak, Claus Leth; Wiechowski, Wojciech T.

Adi Mulawarman, P.E Xcel Energy Minneapolis, MN. Pratap G. Mysore, P.E Pratap Consulting Services, LLC Plymouth, MN

Laboratory ferroresonance measurements in power transformers

CO 2 Circuit Breaker Arc Model for EMTP Simulation of SLF Interrupting Performance

Analysis of Temporary Over-Voltages from Self-Excited Large Induction Motors in the Presence of Resonance - Case Studies

Ferroresonances during Black Starts - Criterion for Feasibility of Scenarios

Simulation Analysis of Ferromagnetic Resonance of Low Magnetic Flux Density-Type PT under Single-Phase Earth Fault of 10kV Power Grid

ANALYSIS OF VOLTAGE TRANSIENTS IN A MEDIUM VOLTAGE SYSTEM

AORC Technical meeting 2014

Evaluating the Response of Surge Arresters

USING OVER-DAMPING METHOD TO SUPPRESS THE FERRO-RESONANCE OF POTENTIAL TRANSFORMER

Revision of TRV Requirements for the Application of Generator Circuit-Breakers

Parameter Study of Ferro-Resonance with Harmonic Balance Method

Simulation and Analysis of Ferroresonance in Power System

Investigation of Inter-turn Fault in Transformer Winding under Impulse Excitation

ABSTRACT 1 INTRODUCTION

Protection of Electrical Networks. Christophe Prévé

Calculation of Transients at Different Distances in a Single Phase 220KV Gas insulated Substation

Research Article Resistive Ferroresonance Limiter for Potential Transformers

A Simple Simulation Model for Analyzing Very Fast Transient Overvoltage in Gas Insulated Switchgear

Solving Customer Power Quality Problems Due to Voltage Magnification

Effect of High Frequency Cable Attenuation on Lightning-Induced Overvoltages at Transformers

Power Systems Modelling and Fault Analysis

CONTENTS. 1. Introduction Generating Stations 9 40

of the improved scheme is presented. Index Terms Inrush current, power quality, transformer.

Experimental Investigations and Calculations in 6-35 kv Networks with Various Neutral Conditions

Overvoltage and undervoltage. Dr Audih 1

A Pyrotechnic Fault Current Limiter Model for Transient Calculations in Industrial Power Systems

Distribution Transformer Random Transient Suppression using Diode Bridge T-type LC Reactor

Research Article Ferroresonance Study on the VT in the Karoon 4 Power Plant 400 kv GIS Substation

The study of ferroresonance effects in electric power equipment

Analysis of a 405 km transmission line with series compensation

Effect of Circuit Breaker Shunt Resistance on Chaotic Ferroresonance in Voltage Transformer

Autotransformer Inadvertent Energization Through Circuit Breakers Gradient Capacitors

Surge Protection for Ladle Melt Furnaces

Transient Recovery Voltage at Transformer Limited Fault Clearing

EVALUATION OF DIFFERENT SOLUTIONS OF FAULTED PHASE EARTHING TECHNIQUE FOR AN EARTH FAULT CURRENT LIMITATION

Ironing out resonance

TRANSFORMERS FOR GIS APPLICATIONS VOLTAGE VOLTAGE TRANSFORMERS FOR GIS APPLICATIONS

Earth Fault Protection

Spectral analysis of voltages and currents during different modes of ferroresonance in switchgear

Protection Basics Presented by John S. Levine, P.E. Levine Lectronics and Lectric, Inc GE Consumer & Industrial Multilin

UProtection Requirements. Ufor a Large scale Wind Park. Shyam Musunuri Siemens Energy

Switching Induced Transients:

Frequency Domain Analysis of Capacitor Transient Overvoltages

Electrical Power and Energy Systems

Non-conventional instrument transformers and power quality aspects an overview

Sensitivity studies on power transformer ferroresonance of a 400 kv double circuit

Switching and Fault Transient Analysis of 765 kv Transmission Systems

High voltage engineering

TECHNOLOGIES FOR TOMORROW

Proceedings of the 5th WSEAS Int. Conf. on SIMULATION, MODELING AND OPTIMIZATION, Corfu, Greece, August 17-19, 2005 (pp )

Connection Impact Assessment Application

Overvoltages While Switching Off a HV- Transformer with Arc-Suppression Coil at No-Load

ISSN: X Impact factor: (Volume 3, Issue 6) Available online at Modeling and Analysis of Transformer

ACCURACY OF VOLTAGE TRANSFORMERS DESIGN CRITERIA AND A SURVEY ON THE PRECISION AND REPRODUCIBILITY OF A NEW MODEL-BASED CALIBRATION APPROACH

Energization of a no-load transformer for power restoration purposes: Impact of the sensitivity to parameters.

Reducing the magnetizing inrush current by means of controlled energization and de-energization of large power transformers

ANALITICAL ANALYSIS OF TRANSFORMER INRUSH CURRENT AND SOME NEW TECHNIQUES FOR ITS REDDUCTION

DIFFERENCE BETWEEN SWITCHING OF MOTORS & GENERATORS WITH VACUUM TECHNOLOGY

A Laboratory Investigation into the use of MV Current Transformers for Transient Based Protection.

Numbering System for Protective Devices, Control and Indication Devices for Power Systems

Ferroresonance on Transformer 13-kV Ungrounded Tertiary at Arab

VT guard Frequntly Asked Questions

MODIFICATION OF THE ARRESTER ARRANGEMENT WHEN CONVERTING THE METHOD OF NEUTRAL TREATMENT

Ground Fault Currents in Unit Generator-Transformer at Various NGR and Transformer Configurations

Experimental Study and Circuit Analysis Model of Lightning Isolation Transformer for Railway Signal System

Effect of Shielded Distribution Cables on Lightning-Induced Overvoltages in a Distribution System

Simulation and Analysis of Lightning on 345-kV Arrester Platform Ground-Leading Line Models

Methodology Utilized in Black-Start Studies on EHV Power Networks

Power Quality and Reliablity Centre

Transcription:

A Special Ferro-resonance Phenomena on 3-phase 66kV VT-generation of Hz zero sequence continuous voltage S. Nishiwaki, T. Nakamura, Y.Miyazaki Abstract When an one line grounding fault in a transmission line was removed, the insulation of the earthed voltage transformer(vt) broke down at the substation of a petroleum refinery which was provided with electric power from both an on-premises power generation plant and an outside power company. At this time, the abnormal Hz zero sequence continuous voltage was recorded. Initially, the cause was not known, however it was found from an analysis using EMTP that this was a ferro-resonance phenomenon of the VT. This abnormal Hz zero sequence continuous voltage could be reproduced by computation. It is thought that the main causes of the ferro-resonance were the existence of a single phase VT connected in addition to a 3-phase VT, and also the fact that the system became completely ungrounded neutral system after the one line grounding fault was removed. Keywords: Ferro-resonance, Voltage transformer, Hz zero sequence continuous voltage, One line grounding fault, 3-phase circuit I. INTRODUCTION 66kV voltage transformer (VT) was broken and a very A special voltage waveform was recorded in an electric facility of a petroleum refinery. An abnormal Hz zero sequence continuous voltage was recorded. At first, we did not understand their causes. By analysis with computation using EMTP, it was found the causes were ferro-resonance on 3-phase VT. The petroleum refinery owns an electric power generation plant and is also supplied by an outside electric power company. When a ground fault at a transmission line of the electric power company was removed by the operation of a circuit breaker at a far substation of the electric power company, the ferro-resonance started. In the electric facility of the petroleum refinery, one phase VT was connected in addition to the 3-phase VT. It was found that this additional S. Nishiwaki is with Toshiba Corporation, Ukishima-Cho, Kawasaki-Ku, Kawasaki-Shi -86, Japan (e-mail of corresponding author: susumu.nishiwaki@glb.toshiba.co.jp). T. Nakamura is with Toshiba Corporation, Ukishima-Cho, Kawasaki-Ku, Kawasaki-Shi -86, Japan (e-mail: tatsuaki.nakamura@toshiba.co.jp) Y. Miyazaki is with Toshiba Mitsubishi-Electric Industrial Systems Corporation, Mita 3-Chome, Minato-Ku, Tokyo 8-73, Japan (e-mail: MIYAZAKI.yasuhiro@tmeic.co.jp). Presented at the International Conference on Power Systems Transients (IPST 7) in Lyon, France on June 4-7, 7 one phase VT was one of the causes of the ferro-resonance phenomena that we experienced. By the open operation of the circuit breaker at the substation of the electric power company, the power transformer with neutral grounding resister (NGR) was removed, and the system became completely isolated neutral. It was found that this was also a cause of the ferro-resonance. It was suggested that the continuous large excitation current flowed in the VT due to the iron core magnetic saturation with the ferro-resonance. The VT was broken by the over-heating in the winding. There are many reports concerning the phenomena of ferro-resonance []. The phenomenon of ferro-resonance, which is well known with regard to the voltage transformer, is caused by a series circuit consisting of capacitor between the terminals of an open circuit breaker and a VT []. The phenomenon of ferro-resonance that occurs in a 3-phase transformer due to an open phase is also known [3] [4]. There is also an example of report concerning ferro-resonance of a VT under the similar system conditions reported in this paper below, that is, the condition in which the voltages of the three phases are applied normally in an ungrounded system [5]. In this example, the stray capacitance of the neutral point of the power source is the main cause of ferro-resonance. This is different from the example reported in this paper. II. PHENOMENA THAT OCCUR IN A POWER SYSTEM The situation when the generation of a Hz zero sequence continuous voltage and VT burnout were experienced simultaneously is as follows. Figure is the configuration of the power system at this time. The petroleum refinery which has its own power generation plant had been supplied with power from the power company s 66 kv transmission lines. ) An accident of one line grounding fault occurred at point a along the transmission line. ) Circuit breaker b of the substation Ass opened. 3) Circuit breaker c of the petroleum refinery did not operate. Consequently, the system was energized by the output voltage of the power generation plant of the petroleum refinery. 4) The one line grounding fault disappeared naturally. 5) A Hz zero sequence continuous voltage was

Bss L fault Ass The insulation of the VT broke down after the phenomenon of section b continued for several minutes. 66kV 74m 4.km.8km 8.5km III. REPRODUCING THE HZ ZERO SEQUENCE VOLTAGE BY a b COMPUTATION.4km A. Computation Circuit Initially, the recorded waveform of Fig. could not be 47m NGR: 9 ohm explained. By performing analysis using EMTP-ATP, it was -phase VT found that the waveform was produced by magnetic saturation of the core of the VT, and was a ferro-resonance phenomenon. c Computation was performed by simulating the circuit of Petroleum refinery 3-phase VT Fig. in three phases. The modeling for each item of equipment is shown below. ) 3-phase VT at the petroleum refinery Ge generator overhead line cable primary secondary 6H 946 ohm.9mh.764 ohm Fig.. Configuration of the power system where the ferro-resonance happed. generated for several minutes. 6) The insulation of one phase of the 3-phase VT broke down. A marten was found lying on the ground beneath the transmission line tower where the one line grounding fault occurred. It was presumed that the marten had climbed the transmission line tower, and touched an insulator, resulting in the grounding fault. It is thought that the disappearance of the one line grounding fault in item 4) above was the result of the marten falling off the tower. It is also conceivable that after circuit breaker b opened, the system became completely ungrounded, reducing the grounding fault arc current, which in turn caused the arc to disappear naturally. Figure shows the voltage waveforms recorded at the petroleum refinery. It is considered that the one line grounding fault continues at time section a in Fig., because a 6 Hz zero sequence voltage appears in this time section. Upon entering time section b, the zero sequence voltage abruptly changes from 6 Hz to Hz. At this time, distortion also appears on each line voltage of the three phases. a [Weber*T] 6 load 3.3 ohm/phase.4mh.46 ohm (a) equivalent circuit 4-4 tertiary -.5.5 - b -6 (b) i-ψ curve of iron core Fig.3. Modeling of 3-phase VT 6 ohm [A] zero sequence voltage U-V voltage V-W voltage W-U voltage Fig.. Voltage waveforms recorded in a petroleum refinery

) -phase VT at the petroleum refinery One phase of the VT of ) above was used. The connection is at V phase. 3) 66 kv transmission line A 3-phase untransposed transmission line constants was used. Computation of the constants was performed using the EMTP-ATP supporting program of Line Constants. 4) Cable Simulation was performed using pf/m. 5) Main transformer of the petroleum refinery Neutral point of Y connection was not grounded. 6) Main transformer of Ass Neutral point of Y connection was ground via a high resistance (9ohm). B. Computation Results The computation results are shown in Fig. 4. With reference to Fig. 4, an one line grounding fault is made to occur at time point a, the Ass circuit breaker is caused to open at time point b, and the one line grounding fault is removed at time point c. In actual fact, the time from the operation of the circuit breaker at time point b until the removal of the grounding fault at time point c is longer period, but it is shortened in the computation. The computed waveform of Fig. 4 (a) corresponds to the recorded waveform shown in Fig.. Simultaneous with the removal of the one line grounding fault at time point c the zero sequence voltage changes from 6 Hz to Hz. At this time, distortion appears on each line voltage of the three phases. It can be seen that the computed waveform agrees well with the actually recorded waveforms that are shown in Fig.. It was possible to reproduce the occurrence of the Hz zero sequence continuous voltage that actually occurred, by computation. Figure 4 (b) shows the excitation currents at iron cores of 3-phase VT. From time point c, core magnetic saturation currents starts to flow. The time point c corresponds to the start of generation of the Hz zero sequence voltage. It can be seen that the generation of the Hz zero sequence voltage is due to ferro-resonance caused by magnetic saturation of the iron cores of the VT. It is presumed that as a result of this continuous magnetic saturation current, the windings of the VT overheated, leading to a breakdown of the insulation of the VT. Because the winding resistance of the VT is large, marked overheating occurs as a result of a continuous current of several A. Figure 4 (c) is the voltages to ground at the 66kV terminals of the VT. It can be seen that when ferro-resonance occurs, an overvoltage of about. pu occurs continuously. A Hz zero sequence component is included in each phase voltage. Figure 4 (a) shows the tertiary open delta and secondary voltages of 3-phase VT. The waveforms in Fig. as well are the waveforms observed on the tertiary open delta and secondary sides of the VT. On the other hand, in the computation, the zero sequence voltage was tried to be calculated by adding the 3-phase terminal voltages to ground on the 66 kv side of the VT. As a result, this voltage was found to be almost the same as the zero sequence voltage waveform of Fig. 4 (a). The calculated waveforms of the 3- phase 66 kv line voltages were also found to be almost identical to the observed line voltage waveforms of Fig.4 (a). From these facts, it is thought that even if the core magnetic saturation current shown in Fig. 4 (b) flows, output voltage waveforms of the tertiary open delta and secondary sides of the VT will be faithful to the 66 kv primary side voltage waveforms with high accuracy. IV. DISCUSSIONS A. Effect of Single Phase VT As shown in Fig., a single phase VT was connected to the line side of the petroleum refinery in addition to the 3- phase VT. This single phase VT was removed, and computation was performed. In this computation, the time point a when the one line grounding fault occurred, time point b when the circuit breaker at Ass operated, and time point c when the grounding fault was removed agreed with the computation of Fig. 4. The waveforms resulting from the computation without the single phase VT are shown in Fig. 5. From Fig. 5, it was found that ferro-resonance did not occur. In Fig.5, after the one line grounding fault is removed at time point c, magnetic saturation of the core occurs temporarily, and the excitation current in Fig. 5 (b) becomes large temporarily, but subsequently decays again. This core magnetic saturation temporary current is caused by the residual charge on the transmission line discharging through the VT. The zero sequence voltage in Fig. 5 (a) and the voltage to ground in Fig. 5 (c) fall along with the decay in the excitation current after time point c. The fact that ferro-resonance ceases to occur when the single phase VT is removed indicates that it is possible that an imbalance in the 3-phase circuit is one of the causes of ferro-resonance. B. Effect of Neutral Grounding High Resistance Computation was carried out under the condition where the neutral point of the main transformer at the petroleum refinery was grounded through a high resistance (9 ohm), and also under the same conditions as those used to obtain the waveforms of Fig. 4. As a result, the ferro-resonance did not occur. As shown in Fig., the neutral point of the main transformer at Ass was grounded through a high resistance. However, after the circuit breaker at Ass operates, the petroleum refinery system becomes completely ungrounded. Consequently, the neutral point potential can oscillate freely. It is thought that this is one of the causes of ferro-resonance.

5. 8 7. 5 5. 6. 5. - 6. 5-5. - 8 7. 5-5.... 4. 6. 8 [ s ]. ( f i l e T A I Y O. p l 4 ; x - v a r t ) v : V T 3 W - V T 3 W Z 5 5-5 - - 5 -... 4. 6. 8 [ s ]. ( f i l e T A I Y O. p l 4 ; x - v a r t ) v : V T U - V T V 5 5-5 - - 5 -... 4. 6. 8 [ s ]. ( f i l e T A I Y O. p l 4 ; x - v a r t ) v : V T V - V T W 5 5-5 - - 5 -... 4. 6. 8 [ s ]. ( f i l e T A I Y O. p l 4 ; x - v a r t ) v : V T W - V T U. 5.. 5. -. 5 -. -. 5... 4. 6. 8 [ s ]. ( f i l e T A I Y O. p l 4 ; x - v a r t ) c : V T U - V T N. 5.. 5. -. 5 -. -. 5... 4. 6. 8 [ s ]. ( f i l e T A I Y O. p l 4 ; x - v a r t ) c : V T V - V T N. 5.. 5. -. 5 -. -. 5... 4. 6. 8 [ s ]. ( f i l e T A I Y O. p l 4 ; x - v a r t ) c : V T W - V T N 5 5-5 - - 5... 4. 6. 8 [ s ]. ( f i l e T A I Y O. p l 4 ; x - v a r t ) v : T R U v : T R V v : T R W 5 5-5 - - 5... 4. 6. 8 [ s ]. ( f i l e T A I Y O. p l 4 ; x - v a r t ) v : T R U 5 5-5 - - 5... 4. 6. 8 [ s ]. ( f i l e T A I Y O. p l 4 ; x - v a r t ) v : T R V 5 5-5 - - 5... 4. 6. 8 [ s ]. ( f i l e T A I Y O. p l 4 ; x - v a r t ) v : T R W zero sequence voltage U-V voltage [V] - V-W voltage W-U voltage - - -..4.6.8. (a) Computed waveforms that correspond to recorded waveforms of Fig., tertiary open delta and secondary side voltages [A] U current V current W current - - -..4.6.8. (b) Excitation currents at iron cores of 3-phase VT 5 [V] 3- phase voltages U voltage V voltage W voltage..4.6.8. (c) Voltages to ground at 66kV terminals of 3-phase VT a b c one line grounding fault removal of the grounding fault operation of the circuit breaker at Ass Fig. 4. Waveforms of ferro-resonance reproduced by the computation

5. * 3 8 7. 5 5. 6. 5. - 6. 5-5. - 8 7. 5-5.... 4. 6. 8 [ s ]. ( f i l e T A I Y O 5 5. p l 4 ; x - v a r t ) t : V 5 5-5 - - 5... 4. 6. 8 [ s ]. ( f i l e T A I Y O 5 5. p l 4 ; x - v a r t ) v : T I S K U - T I S K V 5 5-5 - - 5... 4. 6. 8 [ s ]. ( f i l e T A I Y O 5 5. p l 4 ; x - v a r t ) v : T I S K V - T I S K W 5 5-5 - - 5... 4. 6. 8 [ s ]. ( f i l e T A I Y O 5 5. p l 4 ; x - v a r t ) v : T I S K W - T I S K U. 5. -. 5 -. -. 5... 4. 6. 8 [ s ]. ( f i l e T A I Y O 5 5. p l 4 ; x - v a r t ) c : V T U - V T N. 5.. 5. -. 5 -. -. 5... 4. 6. 8 [ s ]. ( f i l e T A I Y O 5 5. p l 4 ; x - v a r t ) c : V T V - V T N. 5.. 5. -. 5 -. -. 5... 4. 6. 8 [ s ]. ( f i l e T A I Y O 5 5. p l 4 ; x - v a r t ) c : V T W - V T N ( f i l e T A I Y O 5 5. p l 4 ; x - v a r t ) v : T R U v : T R V v : T R W 5 5-5 - - 5... 4. 6. 8 [ s ]. ( f i l e T A I Y O 5 5. p l 4 ; x - v a r t ) v : T R U 5 5-5 - - 5... 4. 6. 8 [ s ]. ( f i l e T A I Y O 5 5. p l 4 ; x - v a r t ) v : T R V 5 5-5 -. 5. - 5... 4. 6. 8 [ s ]. ( f i l e T A I Y O 5 5. p l 4 ; x - v a r t ) v : T R W zero sequence voltage U-V voltage [V] - V-W voltage W-U voltage - - -..4.6.8. (a) Computed waveforms that corresponds to recorded waveforms of Fig., tertiary open delta and secondary side voltages [A] U current V current W current - - -..4.6.8. (b) Excitation currents at iron cores of 3-phase VT 5 [V] 5 3- phase voltages U voltage 5-5 - - 5... 4. 6. 8 [ s ]. V voltage W voltage..4.6.8. (c) Voltages to ground at 66kV terminals of 3-phase VT a b c one line grounding fault removal of the grounding fault operation of circuit breaker at Ass Fig. 5. Computed voltage waveforms without the single phase VT, no generation of the ferro-resonance.

C. Effect of The Timing of Removal of The One Line Grounding Fault In Fig. 4, when the computation was performed with changing time point c, which is the timing of removal of the one line grounding fault, ferro-resonance ceased to occur. It can be seen that the occurrence of ferro-resonance is affected by the initial conditions of the system. Yasuhiro Miyazaki received the B.S. degree in electrical engineering from Kyusyu University in 986. In 986, he joined in the Industrial Substation Systems Engineering Section of Toshiba Corporation, Tokyo, Japan. And in 3 he transferred to Toshiba Mitsubishi-Electric Industrial Systems Corporation. Since 986 he has been engaged in engineering and development of industrial substation systems. D. Effect of The Load on The VT When computation was performed after increasing the load on the VT secondary side, ferro-resonance ceased to occur. V. CONCLUSION It was possible to reproduce ferro-resonance in a 66 kv VT, which was actually happened in a field, by means of analysis using EMTP. It was possible to explain the recorded abnormal Hz zero sequence continuous voltage and also the insulation breakdown of the VT. Ferro-resonance occurs under a variety of conditions. It is considered that the main causes of the ferro-resonance reported here are the existence of a single phase VT connected in addition to another 3- phase VT, and also the fact that the system became completely ungrounded after the one line grounding fault was removed. VI. REFERENCES [] Slow Transient Task Force of the IEEE Working Group on Modeling and Analysis of System Transients Using Digital Programs, "Modeling and Analysis Guidelines for Slow Transients Part3: The study of Ferroresonance, IEEE Tran. On Power Delivery, Vol.5 No., Jan., pp.55-65 [] Z. Emin, B. A. T. Zahawi, Y. K. Tong, Voltage Transformer Ferroresonance in 75kV substation, Proceedings of th International Symposium on High Voltage Engineering, pp83-86 vol. [3] Allan Greenwood, Electrical Transients in Power System, Second Edition, Wiley Interscience, pp.6 [4] R. H.E. Hopkinson, Ferroresonance During Single-Phase Switching of 3-Phse Distribution Transformer Banks, IEEE Trans. on PAS, April 965, pp.89-93 [5] Slow Transient Task Force of the IEEE Working Group on Modeling and Analysis of System Transients Using Digital Programs, "Modeling and Analysis Guidelines for Slow Transients Part3: The study of Ferroresonance: Chapter 3, A. Case Study #: VT Ferroresonance on Floating System, IEEE Tran. On Power Delivery, Vol.5 No., Jan., pp.6-63 VII. BIOGRAPHIES Susumu Nishiwaki received the B.S. degree in electrical engineering from Yokohama National University and Ph.D. degree from Nagoya University in 969 and 98, respectively. In 969, he joined the High Power Laboratory of Toshiba Corporation, Kawasaki, Japan. Since then he has been engaged in research and development of gas-insulated switchgears, surge arresters and switching transients Dr. Nishiwaki is a member of IEE of Japan and a Fellow of IEEE. Tatsuaki Nakamura In 964, he joined the Instrument Transformer Designing Section of Toshiba Corporation, Kawasaki, Japan. Since then he has been engaged in design and development of Instrument Transformers.