Eaton s Cooper Power Series DEADFRONT ARRESTERS

Similar documents
Effective February 2017 Supersedes January 2012 (CP1122)

35 kv Class M.O.V.E. DirectConnect elbow arrester

UltraSIL Polymer-Housed Evolution Distribution Class Surge Arrester Certified Test Report

UltraSIL Polymer-Housed VariSTAR Normal-Duty, Heavy-Duty and Riser Pole Distribution-Class Arresters

Metal Oxide Varistor Elbow (M.O.V.E.) Surge Arrester

POSI-BREAK Metal Oxide Varistor Elbow (M.O.V.E.) Surge Arrester

CLU Arrester. Certified Test Report. IEEE Standard C

VariSTAR Type AZU heavy-duty distribution-class under-oil MOV surge arrester

VariSTAR Type AZL heavy-duty distribution-class MOV arrester

ANSI DESIGN TEST REPORT Report No. EU1295-H-00 Type PVN Station Class Surge Arrester

Two- and three-phase MagneX interrupter

COOPER POWER. UltraSIL Polymer-Housed VariSTAR Type U2Surge Arrester for Systems through 275 kv IEC 10-kA; Line Discharge Class 2 SERIES

Analysis of Major Changes to Arrester Standards IEC STEVE BREWER

Surge Arresters. VariSTAR Type AZS Normal Duty Distribution Class MOV Arrester

Figure 1. Two- and Three-phase MagneX Interrupter.

IEC Type Test Report Report No. EU1517-H-00.1 H4 Series Porcelain-housed Arrester 20,000 A Line Discharge Class 4

Tab 8 Surge Arresters

Qualification Test Report Mini-Universal MATE-N-LOK* Connector

Secondary Arresters. Figure 1. Type L secondary surge arrester rated 175 Vac, 125 Vdc.

Comparison of recloser and breaker standards

Type DMX-N Surge Arresters Maximum System Voltage 2 to 36 kv

The NOVA Recloser shall be designed and tested in accordance with the following standards as applicable:

PRODUCT SPECIFICATION

Qualification Test Report SlimSeal SSL Connector

PRODUCT SPECIFICATION

Comparison of CAN/CSA C88.1, IEEE C /01 & IEC 60137

Distribution/Substation Transformer

3EK8 distribution class surge arresters. Catalogue HP-AR Version siemens.com/arresters

Insulation Co-ordination For HVDC Station

Serial ATA (SATA) Connector

PRODUCT SPECIFICATION

Distribution Transformers

EE 1402 HIGH VOLTAGE ENGINEERING

Type 297, High-Voltage Mica Capacitors Corona-free Mica Coupling Capacitors for Medium-Voltage PDA s

TECHNICAL SPECIFICATION

Mar11 Rev D

Single-output models feature wide-range output adjustability to meet a wide variety of standard and user-specific output voltage requirements.

This convection-cooled series is designed for use in commercial and industrial environments in temperatures up to 50 C.

COOPER POWER SERIES. External application of a motor start capacitor on a single-phase voltage regulator. Voltage Regulators MN225063EN

UBC Technical Guidelines Section Edition Medium-Voltage Transformers Page 1 of 5

Single-Phase Mini Pad-Mounted Transformer Specification: Energy+ MPDL

Device Under Test: ALTEA VS- 24-I VS-24-I. 0 24/09/12 First issue A. Peretto L. Peretto 1 24/06/16 All text review E. Scala L. Peretto J. L.

COOPER POWER SERIES. Upgrade instructions for CL-6 series control firmware. Voltage Regulators MN225071EN

S. C. Electric Cooperative s Specification for a Single-Phase, Single Bushing Overhead Distribution Transformer (Revised 10/2013)

PEAK OUTPUT CURRENT 1. MAP V 4.7V to 5.8V 8A 11A 0.2% ±1% 1% 4.9V to 5.1V PEAK OUTPUT CURRENT 4 LINE REGULATION

Mar11 Rev J

LIGHTNING ARRESTOR. September 2017 WEST BENGAL STATE ELECTRICITY TRANSMISSION COMPANY LIMITED

3MElectrical Markets Division

NOV 18 Rev B

Date: December 10 th, Titre / Title HIGH RELIABILITY RF COAXIAL CONNECTORS SMA 2.9 TYPE, 50 OHMS (FEMALE CONTACT)

Under-Oil ARRESTERS Page 1 July 2016

Feb 13 Rev F

SPECIFICATION No SS-135/ kv METAL OXIDE SURGE ARRESTERS WITHOUT GAPS

Electric Stresses on Surge Arrester Insulation under Standard and

SEP 15 Rev A

PRODUCT SPECIFICATION. This specification defines the performance, test, quality and reliability requirements of the PwrBlade ULTRA product.


The Variable Threshold Neutral Isolator (VTNI)

AMENDMENT NO. 1 SEPTEMBER IS (Part 1) : 2001/IEC (1991) SURGE ARRESTORS

MAY 14 Rev B

MODIFICATION OF THE ARRESTER ARRANGEMENT WHEN CONVERTING THE METHOD OF NEUTRAL TREATMENT

QUALIFICATION TEST SUMMARY REPORT ESR-9414 Qualification Type Testing of Amphenol Corporation s 2M805 Series Connector

PRODUCT SPECIFICATION

Substation Design Volume VII

GS Product Specification. 1 of 19 N. QSFP+ Cable to Board Connector System 1.0 SCOPE 2.0 PRODUCT DESCRIPTION

CB75T 75 Watts Output Power

Prepared by Mick Maytum

A Case Study on Selection and Application of Lightning Arrester and Designing its Suitable Grounding Grid

Selection of MO surge arresters Overvoltage protection

SPECIFICATION SWITCHING POWER SUPPLY SINGLE POWER 250W BEST POWER SOLUTIONS, INC. 9F, NO.196-7, SEC.3, TA-TUNG RD SHI CHIH, TAIPEI, TAIWAN, R.O.C.

FTM2 Series HCMOS/TTL OSCILLATORS FOR SPACE APPLICATIONS 0.5MHz to 160 MHz. ( 5 x 3.2 mm, SMD, 2.5 V )

Energy Division. Bowthorpe LV/MV Surge Arresters

RF, COAXIAL. HYBRID COUPLERS POWER DIVIDERS and DIRECTIONAL COUPLERS GENERIC SPECIFICATION

MGM Transformer. Vacuum Pressure Impregnated (VPI) Dry-Type Substation Transformer Specification Guide

This specification covers performance, tests and quality requirements for MINIPAK* HDL Board Mount Receptacle or Plug Connector System.

PF100 Active power factor correction and harmonic attenuation module Vin, 100 watts

Fixed Series Compensation

A Review Comprehension: Guideline for Testing of HV, EHV and UHV Substation Equipment

PRODUCT SPECIFICATION. This specification defines the detailed requirements for the Minitek Pwr3.0 wire to wire and wire to board connectors.

Mar07 Rev B

WAVEFORM CORRECTOR (WAVEFORM CORRECTORS) REPLACES SURGE PROTECTION DEVICES (SPD) PREVIOUSLY KNOWN AS (TVSS)

3M IDC Ribbon Cable Socket. Series 891

SPECIFICATION SWITCHING POWER SUPPLY BPS-300SP/2U 6-OUTPUT WITH ACTIVE PFC FUNCTION SINGLE POWER 300W BEST POWER SOLUTIONS, INC.

RB single and dual-output DC/DC converters 14 32Vin & 18 32Vin, 5 28Vout, watts

For the electronic measurement of current: DC, AC, pulsed..., with galvanic separation between the primary and the secondary circuit.

Title: Southern States Type SLS Smart Sectionalizer Solid Dielectric Three Phase Sectionalizer. Product Specification Guide TABLE OF CONTENTS

WESTERN UNDERGROUND COMMITTEE GUIDE 2.6 (2.6/00/0868)

NEO TELE-TRONIX PVT. LTD. 6/7 Bijoygarh, Kolkata , Tel : ; Fax :

SOLARLOK PV BAR Junction Box

DSR120 Series. xxx Series. 120 Watts. AC-DC Power Supplies. Models & Ratings. Mechanical Details

PRODUCT SPECIFICATION

MW75S single-output AC/DC power supply Power factor corrected Vin, 2 28Vout, 75 watts. I - M3 inserts. Max

INTERNATIONAL STANDARD

DATA SHEET FOR LIGHTING TRANSFORMER APPD. BY VDV PROJECT NO

Insulation Coordination Fundamentals Where Arrester and Insulator Characteristics Meet

FTTC05 Series LVDS TCXO/VCTCXO FOR SPACE APPLICATIONS 10M Hz to 1400MHz. ( 5 x 7 mm, SMD, 2.5 V )

SAUDI STANDARD NO. SASO IEC : 2007 SWITCHES FOR HOUSEHOLD AND SIMILAR FIXED ELECTRICAL INSTALLATIONS

MV ELECTRICAL TRANSMISSION DESIGN AND CONSTRUCTION STANDARD. PART 1: GENERAL 1.01 Transformer

HEATSINK RANGE TECHNICAL INFORMATION

Evaluating the Response of Surge Arresters

Transcription:

File Ref: 235-65, 235-68, 235-97, 235-101 Effective June 2015 CT235001EN Supersedes CP9314 May 2011 CERTIFIED TEST REPORT Eaton s Cooper Power Series DEADFRONT ARRESTERS

CT235001EN Supersedes CP9314 May 2011 Page 2 of 28 Eaton s Cooper Power Series DEADFRONT ARRESTERS CERTIFICATION Statements made and data shown are, to the best of our knowledge and belief, correct and within the usual limits of commercial testing practice. June 29, 2015 Paul M. Roscizewski Chief Engineer Date

CT235001EN Supersedes CP9314 May 2011 Page 3 of 28 INTRODUCTION Eaton s Cooper Power series Deadfront M.O.V.E. and Parking Stand arresters are used to optimize the surge protection of deadfront URD systems. The arresters are designed to operate easily with a hotstick. The designs are compact and provide a clean profile within the smallest pad-mounted cabinets. Eaton s Cooper Power series 15 kv and 25 kv Class deadfront M.O.V.E. arresters are offered with the interface that mates to the 200 Amp loadbreak bushing that meets the dimensional requirements of IEEE Std 386-2006 standard for separable connectors. The duty-cycle ratings offered are 3 kv to 21 kv. Eaton s Cooper Power series 35 kv Class deadfront M.O.V.E arresters meet the dimensional requirements of IEEE Std 386-2006 standard figure 8, No. 1A. The duty-cycle ratings offered are 3 kv to 36 kv. Eaton s Cooper Power series 15 kv and 25 kv Class deadfront Parking Stand M.O.V.E arresters are offered with the 200 Amp loadbreak bushing interface that meets the dimensional requirements of IEEE Std 386-2006 standard for the separable connectors. The duty-cycle ratings offered are 3 kv to 21 kv. Eaton s Cooper Power series 25 kv Class deadfront POSI-BREAK M.O.V.E arresters are offered with the interface that mates to the 200 Amp loadbreak bushing that meets the dimensional requirements of IEEE Std 386-2006 standard for separable connectors. The duty cycle ratings offered are 3 kv to 21 kv. Eaton s Cooper Power series 35 kv Class DirectConnect M.O.V.E arresters are offered with an interface that with the use of an additional adapter mates to 35 kv Class 600 A deadbreak bushings that meet the dimensional requirements shown in IEEE Std 386-2006 standard Figure 13. The duty-cycle ratings offered for the M.O.V.E arresters are 27 kv to 36 kv.

CT235001EN Supersedes CP9314 May 2011 Page 4 of 28 TEST PROGRAM To demonstrate that Eaton s Cooper Power series M.O.V.E. deadfront arresters tested meet each design test listed on this page below. To demonstrate that Eaton s Cooper Power series POSI-BREAK M.O.V.E. deadfront arrester meets all performance requirements listed on page 5 of this document. To demonstrate that Eaton s Cooper Power series DirectConnect M.O.V.E. arrester meets all performance requirements listed on page 6 of this document. Procedure: The following design tests were performed on a sufficient number of samples to demonstrate that both Eaton s Cooper Power series M.O.V.E. deadfront arrester meets all performance requirements. Design Tests: A. Discharge Voltage Current Characteristics... Per IEEE Std C62.11-2005 standard, Para. 8.3.2.1 B. Discharge Voltage Time Characteristics... Per IEEE Std C62.11-2005 standard, Para. 8.3.2.2 F. Accelerated Aging Procedure... Per IEEE Std C62.11-2005 standard, Par. 8.5 G. Duty Cycle... Per IEEE Std C62.11-2005 standard, Par. 8.14 H. Low-Current, Long-Duration... Per IEEE Std C62.11-2005 standard, Par. 8.13 I. High-Current, Short-Duration... Per IEEE Std C62.11-2005 standard, Par. 8.12 J. Temporary Overvoltage... Per IEEE Std C62.11-2005 standard, Par. 8.15 K. Deadfront Arrester Failure Mode... Per IEEE Std C62.11-2005 standard, Par. 8.20 L. Corona Testing of Housing... Per IEEE Std 386-2006 standard, Par. 7.4 M. Impulse Testing of Housing... Per IEEE Std 386-2006 standard, Par. 7.5.3 N. AC Hipot Testing of Housing... Per IEEE Std 386-2006 standard, Par. 7.5.1 O. DC Hipot Testing of Housing... Per IEEE Std 386-2006 standard, Par. 7.5.2 See following design tests A through O for results.

CT235001EN Supersedes CP9314 May 2011 Page 5 of 28 TEST PROGRAM Deadfront POSI-BREAK M.O.V.E Arrester The design of the arrester portion of Eaton s Cooper Power series M.O.V.E. deadfront arrester has not been modified in any way, and the functionality of this product has not been altered. All expected electrical performance and surge protection provided by a specifically rated M.O.V.E deadfront arrester is maintained when substituting to the POSI-BREAK design interface. The only design change implemented in the POSI-BREAK M.O.V.E. deadfront arrester is in the mating interface of the rubber elbow housing. In addition, the current POSI-BREAK probe is used in place of the present M.O.V.E. deadfront probe. In order to demonstrate that the design of Eaton s Cooper Power series POSI-BREAK M.O.V.E. deadfront arrester meets the performance requirements to prevent partial vacuum induced switching flashovers and normal operating requirements, a sufficient number of samples shall pass the requirements of the tests listed below: P. Operating Force Test... Per IEEE Std 386-2006 standard, Par. 7.14 Q. Operating Interface AC Withstand Test... Per IEEE Std 386-2006 standard, Annex B, Option B R. Corona Testing of Housing... Per IEEE Std 386-2006 standard, Par. 7.4 S. Impulse Testing of Housing... Per IEEE Std 386-2006 standard, Par. 7.5.3 T. AC Hipot Testing of Housing... Per IEEE Std 386-2006 standard, Par. 7.5.1 U. DC Hipot Testing of Housing... Per IEEE Std 386-2006 standard, Par. 7.5.2 See following design tests P through U for results.

CT235001EN Supersedes CP9314 May 2011 Page 6 of 28 TEST PROGRAM Deadfront DirectConnect M.O.V.E Arrester The design of the arrester portion of Eaton s Cooper Power series DirectConnect M.O.V.E. arrester has not been modified in any way, and the functionality of this product has not been altered. All expected electrical performance and surge protection provided by a specifically rated deadfront M.O.V.E arrester is maintained when substituting to the DirectConnect arrester design interface. The only design change implemented in the deadfront DirectConnect M.O.V.E. arrester is in the mating interface of the rubber elbow housing. P. Operating Force Test... Per IEEE Std 386-2006 standard, Par. 7.14 R. Corona Testing of Housing... Per IEEE Std 386-2006 standard, Par. 7.4 S. Implulse testing of Housing... Per IEEE Std 386-2006 standard, Par. 7.5.3 T. AC Hipot Testing of Housing... Per IEEE Std 386-2006 standard, Par. 7.5.1 U. DC Hipot Testing of Housing... Per IEEE Std 386-2006 standard, Par. 7.5.2 See following design tests P through U for results.

CT235001EN Supersedes CP9314 May 2011 Page 7 of 28 TEST A DISCHARGE VOLTAGE CURRENT CHARACTERISTICS To determine the maximum discharge voltage characteristics of the arrester at 0.5, 1.5, 3.0, 5.0, 10.0 and 20 ka crest in accordance with IEEE Std C62.11-2005 standard, Paragraph 8.3.2.1. Sample arresters were connected directly to ground without using the normal 3 foot ground leads. The samples were impulsed using an 8x20 µs wave shape at 0.5, 1.5, 3.0, 5.0, 10.0 and 20 ka crest. The discharge voltage crest was measured. Chart 1 shows the maximum discharge voltages for deadfront M.O.V.E. arresters.

CT235001EN Supersedes CP9314 May 2011 Page 8 of 28 TEST B DISCHARGE VOLTAGE TIME CHARACTERISTICS To obtain the front-of-wave protective level of the arrester based on 5 ka crest impulse that results in a discharge voltage cresting in 0.5 µs in accordance with IEEE Std C62.11-2005 standard, Paragraph 8.3.2.2. Sample arresters were connected directly to ground without using the normal 3 foot ground leads. A classifying current of 5 ka crest was used to determine the protective level. The arresters were impulsed using front times of 8 µs, 2 µ and 1 µs. The maximum discharge voltage and the time to voltage crest were measured. The voltage/time measurements were plotted on linear voltage versus log time paper and the maximum voltage at 0.5 µs was determined. Chart 1 shows the front-of-wave protective levels for deadfront M.O.V.E. arresters.

CT235001EN Supersedes CP9314 May 2011 Page 9 of 28 TEST F ACCELERATED AGING PROCEDURE To verify the K C and K R ratios of Eaton s Cooper Power series deadfront arrester in accordance with IEEE Std C62.11-2005 standard, Paragraph 8.5. K C = MCOV Ratio K R = Duty Cycle Ratio These ratios were determined to calculate the test values of MCOV and duty cycle voltages used during testing. Samples were placed in an oven at 115 C and energized at MCOV for 2,000 hours. The watts loss was measured at 5 hours at the MCOV and duty cycle voltage levels. The watts loss was remeasured at 2,000 hours at MCOV and duty cycle voltage levels. K C = Watts Loss @ 2,000 Hrs @ MCOV Watts Loss @ 5 Hrs @ MCOV K R = Watts Loss @ 2,000 Hrs @ DC Voltage Watts Loss @ 5 Hrs @ DC Voltage If K C and K R 1, then K C and K R are equal to 1. K C and K R = 1.

CT235001EN Supersedes CP9314 May 2011 Page 10 of 28 TEST G DUTY CYCLE To demonstrate that Eaton s Cooper Power series deadfront arresters meet the duty cycle requirements in accordance with IEEE Std C62.11-2005 standard, Paragraph 8.14. Each sample was impulsed with a 5 ka crest, 8x20 µs wave and the discharge voltage measured. Each sample was energized at K R times the duty cycle voltage (K R = 1), for the duration of time needed to allow 20 impulses. Each sample was impulsed with a 5 ka crest surge of 8x20 µs wave shape. The impulse occurred at approximately 60 before the crest on the power frequency wave. Each sample was impulsed once every 50 to 60 seconds for 20 consecutive impulses. After the 20 th impulse, the sample was de-energized and placed into an oven until it stabilized at 85 C. Each sample was removed from the oven and immediately energized at K R times the duty cycle voltage, K R = 1 and impulsed twice more. Immediately after, the samples were energized at K C times MCOV, (K C =1), for 30 minutes minimum to show that there was no thermal recovery problem. Each sample was impulsed with a 5 ka crest 8x20 µs wave and the discharge voltage measured. The discharge voltage was compared to the discharge voltage taken prior to duty cycle to make sure that it did not vary by more than ±10%. The samples were inspected after testing to assure that no physical damage occurred. Eaton s Cooper Power series deadfront arresters met the duty cycle test requirements of 22 impulses, thermal recovery, <10% change in discharge voltage, and no physical damage.

CT235001EN Supersedes CP9314 May 2011 Page 11 of 28 TEST H LOW-CURRENT, LONG-DURATION To demonstrate that Eaton s Cooper Power series deadfront arresters meet the low-current, long-duration requirements in accordance with IEEE Std C62.11-2005 standard, Paragraph 8.13. Each sample was impulsed with a 5 ka crest, 8x20 µs wave and the discharge voltage measured. Each sample was impulsed six times, once every 50 to 60 seconds. The sample was allowed to cool to room temperature. This procedure was repeated two more times. Immediately after the 18 th shot, the sample was placed into an oven until it stabilized at 85 C. The sample was removed from the oven and impulsed two more times. Immediately after the 20 th shot, the sample was energized at K C times MCOV (K C = 1) for 30 minutes minimum to show that there was no thermal recovery problem. Each sample was impulsed with a 5 ka crest 8x20 µs wave and the discharge voltage measured. The discharge voltage was compared to the discharge voltage taken prior to the low-current, long-duration testing to make sure that it did not vary by more than ±10%. The samples were inspected after testing to assure that no physical damage occurred. Eaton s Cooper Power series deadfront arresters met the low-current, long-duration requirements of 20 impulses, thermal recovery, <10% change in discharge voltage, and no physical damage.

CT235001EN Supersedes CP9314 May 2011 Page 12 of 28 TEST I HIGH-CURRENT, SHORT-DURATION To demonstrate that Eaton s Cooper Power series deadfront arresters meet the high-current, short-duration requirements in accordance with IEEE Std C62.11-2005 standard, Paragraph 8.12. Samples were preheated to 45 C. Each sample was impulsed with a 40 ka crest current wave with a wave shape of 4x10 µs. After one impulse, the sample was placed back into a 45 C oven and stabilized at that temperature. Each sample was impulsed a second time. Immediately following the second impulse, the sample was energized at K C times MCOV (K C = 1) for 30 minutes to show that there was no thermal recovery problem. The samples were inspected after testing to make sure that no physical damage occurred to make them operate differently. Eaton s Cooper Power series deadfront arresters met the high-current, short duration requirements of two impulses, thermal recovery, and no physical damage.

CT235001EN Supersedes CP9314 May 2011 Page 13 of 28 SECTION J T.O.V. TEMPORARY OVERVOLTAGE To verify what levels of 60 cycle temporary overvoltage Eaton s Cooper Power series deadfront arresters survive in accordance with IEEE Std C62.11-2005 standard, Paragraph 8.15. Each sample was impulsed with a 5 ka crest, 8x20 µs wave and the discharge voltage measured. Samples were preheated to 85 C. Each sample was removed from the oven and immediately placed onto the bushing and energized at the overvoltage. The overvoltage was removed before sample failure. Within 1 second, each sample was energized at MCOV for 30 minutes. Sample current and temperature were monitored for thermal runaway. Each sample was impulsed with a 5 ka crest 8x20 µs wave and the discharge voltage measured. The discharge voltage was compared to the discharge voltage taken prior to the Temporary Overvoltage testing to make sure that it did not vary by more than ±10%. The samples were inspected after testing to assure that no physical damage occurred. Minimum recovery points were plotted. Graph 1 and Chart 2 show the performance results for deadfront M.O.V.E. arresters.

CT235001EN Supersedes CP9314 May 2011 Page 14 of 28 TEST K DEADFRONT ARRESTER FAILURE MODE To verify that Eaton s Cooper Power series deadfront arresters are able to withstand valve block failures without ejecting arrester parts through the body of the housing, in accordance with IEEE Std C62.11-2005 standard, Paragraph 8.20. 10 kv rated 15 kv Class M.O.V.E. arresters were used for this test. Samples were electrically failed using a higher than rated voltage from a low-current source transformer at 60 Hz. The overvoltage was left on the samples until the short circuit current level of the source transformer was reached. The overvoltage was turned off, and within a few cycles, rated voltage was applied. Three samples were tested with an available fault current of 500 Amps for 0.3 seconds. Three samples were tested with an available fault current of 10,000 Amps for 0.17 seconds. Eaton s Cooper Power series deadfront arrester samples withstood valve block failures without ejecting arrester parts through the body of the housing.

CT235001EN Supersedes CP9314 May 2011 Page 15 of 28 TEST L CORONA VOLTAGE LEVEL TEST To verify that Eaton s Cooper Power series deadfront arresters meet corona extinction levels in accordance with IEEE Std 386-2006 standard, Paragraph 7.4. Ten samples of each size and type of housing were tested. The test voltage was raised to 20% above the minimum corona voltage level. If the corona was less than 3 pc, the sample passed the tests. If the corona exceeded 3 pc, the test voltage was lowered to the minimum corona voltage. Corona readings were taken after 3 sec. and before 60 sec. The readings could not exceed 3 pc. kv Class Max. Voltage Rating (kv rms) 15 8.3 / 14.4 11 25 15.2 / 26.3 19 35 21.1 / 36.6 26 Min. Corona Voltage Level (kv rms) Eaton s Cooper Power series deadfront arrester samples all passed the minimum corona requirements of IEEE Std 386-2006 standard, Paragraph 7.4.

CT235001EN Supersedes CP9314 May 2011 Page 16 of 28 TEST M IMPULSE WITHSTAND VOLTAGE TEST (BIL) To demonstrate that Eaton s Cooper Power series deadfront arrester housings meet the impulse withstand voltage test in accordance with IEEE Std 386-2006 standard, Paragraph 7.5.3. Ten samples of each size and type of housing were tested. The samples were subjected to 3 positive and 3 negative 1.2x50 µs impulses. The crest values are listed below. The samples had to withstand all impulses without flashover or puncture. kv Class Max. Voltage Rating (kv rms) 15 8.3 / 14.4 95 25 15.2 / 26.3 125 35 21.1 / 36.6 150 Crest Voltage (kv) Eaton s Cooper Power series deadfront arrester samples all passed the impulse requirements of IEEE Std 386-2006 standard, Paragraph 7.5.3.

CT235001EN Supersedes CP9314 May 2011 Page 17 of 28 TEST N AC WITHSTAND VOLTAGE TEST To verify that Eaton s Cooper Power series deadfront arrester housings meet the ac withstand voltage levels in accordance with IEEE Std 386-2006 standard, Paragraph 7.5.1. Ten samples of each size and type of housing were tested. The test voltage was raised to the specified voltage withstand level listed below for one minute minimum. No flashover of puncture was allowed. kv Class Max. Voltage Rating (kv rms) 15 8.3 / 14.4 34 25 15.2 / 26.3 40 35 21.1 / 36.6 50 AC Withstand Level (kv) Eaton s Cooper Power series deadfront arrester samples all passed the ac withstand test in accordance with IEEE Std 386-2006 standard, Paragraph 7.5.1.

CT235001EN Supersedes CP9314 May 2011 Page 18 of 28 TEST O DC WITHSTAND VOLTAGE TEST To verify that Eaton s Cooper Power series deadfront arrester housings meet the dc withstand voltage level in accordance with IEEE Std 386-2006 standard, Paragraph 7.5.2. Ten samples of each size and type of housing were tested. The test voltage was raised to the specified voltage withstand level listed below for 15 minutes minimum. No flashover or puncture was allowed. kv Class Max. Voltage Rating (kv rms) 15 8.3 / 14.4 53 25 15.2 / 26.3 78 35 21.1 / 36.6 103 DC Withstand Level (kv) Eaton s Cooper Power series deadfront arrester samples all passed the dc withstand test in accordance with IEEE Std 386-2006 standard, Paragraph 7.5.2.

CT235001EN Supersedes CP9314 May 2011 Page 19 of 28 TEST P Operating Force Test To verify that the force necessary to operate Eaton s Cooper Power series deadfront POSI-BREAK M.O.V.E. arrester and DirectConnect arrester meet the requirements of Paragraph 7.14 of IEEE Std 386-2006 standard. Four samples of the POSI-BREAK M.O.V.E. arrester and four samples of the DirectConnect M.O.V.E. arrester were tested. The elbows were assembled with a probe and MOV block assembly. The connector system was lubricated in accordance with the manufacturer s instructions. The temperature of the components was set at 20 o C, +25 o C and +65 o C respectively, for three separate tests. Each test consisted of closing the connector and then reopening it within 10 minutes. The force was applied to the operating eye parallel to the axis of the probe at a rate of 127 mm/min (5 in/min). The required operating force over the environmental range of 20 o C to +65 o C shall be between 50-200 lbf. Eaton s Cooper Power series deadfront POSI-BREAK M.O.V.E. arrester samples and deadfront DirectConnect M.O.V.E. arrester samples all passed the operating force test in accordance with IEEE Std 386-2006 standard, Paragraph 7.14. Each set of four connector/bushing insert assemblies had operating forces between 50 lbf and 200 lbf at 20 o C, +25 o C and +65 o C.

CT235001EN Supersedes CP9314 May 2011 Page 20 of 28 TEST Q Operating Interface AC Withstand Test Annex B, Option B To demonstrate that Eaton s Cooper Power series deadfront POSI-BREAK M.O.V.E. arresters are capable of performing an opening operation under high operating force, low temperature, elevated voltage and zero load current conditions without a flashover to ground. Insulative plugs were assembled into 16 POSI-BREAK M.O.V.E. arrester housings in place of the arrester blocks. The 16 samples were then installed onto 25 kv bushing inserts with beveled latch ring catalog # LBI225 (p/n 2690557D53 rev. 70). The 200 Amp operating interface was lubricated according to the manufacturer s instructions with the complete contents of the packet of silicone grease supplied with the M.O.V.E arrester. All 16 connector assemblies were heat aged at 120 C + 5 o C for a total of 3 weeks. After the full 3 weeks in the oven at 120 C + 5 o C, all the connector assemblies were removed and allowed to cool to ambient. The test samples were then placed in a cold chamber at 20 to 25 o C for a minimum of 16 hours. For 12 of the 16 test samples, one sample was removed at a time from the cold chamber and mounted to the faceplate of a grounded test stand. Adjacent grounds were not required. The face plate mounting was equipped with threaded mounting studs and a bushing well clamp located in a manner duplicating a typical field application. The separable connector, POSI-BREAK M.O.V.E. arrester, was separated from the bushing within 5 minutes after removal from the cold chamber. The opening operation was performed with a positive continuous motion applied by a mechanical actuator at 35-in/sec average speed over the initial 1 inch of travel. The force was applied to the operating eye of the connector using suitable live-line tool or equivalent. The test circuit and circuit parameters are detailed in the following Figure A and Table A. The line-to-ground test voltage for the 15.2/26.3 kv rated connectors was 30.5 kv rms. (2x Rated L-G voltage.) The opening force of the four remaining samples was measured. A force was applied to the operating eye parallel to the axis of the probe at a rate of 5-in/min.

CT235001EN Supersedes CP9314 May 2011 Page 21 of 28 FIGURE A Circuit Diagram RS XS ELBOW CAP VL-G RG V LG = 2 X (RATED L-G Voltage) Z S = X S + R S X S /R S = 5.0 7.0 Z S 0.10 x R G I F = V/(Z S + R G ) 50 Amps TABLE A Circuit Parameters Twelve consecutive Eaton s Cooper Power series deadfront POSI-BREAK M.O.V.E. arresters were successfully switched when mated with an Eaton s Cooper Power series 25 kv bushing insert with beveled latch ring without flashover to ground at 30.5 kv line-to-ground test voltage in accordance with Annex B, Option B of IEEE Std 386-2006 standard. The opening force measured ranged from 165 258 lbf.

CT235001EN Supersedes CP9314 May 2011 Page 22 of 28 TEST R CORONA VOLTAGE LEVEL TEST 25 kv POSI-BREAK Interface 35 kv DirectConnect Interface To verify that Eaton s Cooper Power series deadfront POSI-BREAK M.O.V.E. arrester and DirectConnect M.O.V.E. arrester meet corona extinction levels in accordance with IEEE Std 386-2006 standard, Paragraph 7.4. Ten samples of the POSI-BREAK M.O.V.E. arrester housing and ten samples of the DirectConnect M.O.V.E. arrester were tested. The test voltage was raised to 20% above the minimum corona voltage level. If the corona was less than 3 pc, the sample passed the tests. If the corona exceeded 3 pc, the test voltage was lowered to the minimum corona voltage. Corona readings were taken after 3 sec. and before 60 sec. The readings could not exceed 3 pc. kv Max. Voltage Rating Min. Corona Voltage Level Class (kv rms) (kv rms) 25 15.2 / 26.3 19 Eaton s Cooper Power series deadfront POSI-BREAK M.O.V.E. arrester samples and DirectConnect M.O.V.E. arrester samples all passed the minimum corona requirements of IEEE Std 386-2006 standard, Paragraph 7.4.

CT235001EN Supersedes CP9314 May 2011 Page 23 of 28 TEST S IMPULSE WITHSTAND VOLTAGE TEST (BIL) 25 kv POSI-BREAK Interface 35 kv DirectConnect Interface To demonstrate that Eaton s Cooper Power series deadfront POSI-BREAK M.O.V.E. arrester and DirectConnect M.O.V.E. arrester housings meet the impulse withstand voltage test in accordance with IEEE Std 386-2006 standard, Paragraph 7.5.3. Ten samples of the POSI-BREAK M.O.V.E. arrester housing and ten samples of the DirectConnect M.O.V.E. arrester housing were tested. The samples were subjected to 3 positive and 3 negative 1.2x50 µs impulses. The crest values are listed below. The samples had to withstand all impulses without flashover or puncture. Results kv Max. Voltage Rating Crest Voltage Class (kv rms) (kv) 25 15.2 / 26.3 125 Eaton s Cooper Power series Deadfront POSI-BREAK M.O.V.E. arrester samples and DirectConnect M.O.V.E. arrester housings all passed the impulse requirements of IEEE Std 386-2006 standard, Paragraph 7.5.3.

CT235001EN Supersedes CP9314 May 2011 Page 24 of 28 TEST T AC WITHSTAND VOLTAGE TEST 25 kv POSI-BREAK Interface 35 kv DirectConnect Interface To verify that Eaton s Cooper Power series deadfront POSI-BREAK M.O.V.E. arrester and Deadfront DirectConnect M.O.V.E. arrester housings meet the ac withstand voltage levels in accordance with IEEE Std 386-2006 standard, Paragraph 7.5.1. Ten samples of the POSI-BREAK M.O.V.E. arrester housing and ten samples of the DirectConnect M.O.V.E. arrester housing were tested. The test voltage was raised to the specified voltage withstand level listed below for one minute minimum. No flashover of puncture was allowed. kv Max. Voltage Rating AC Withstand Level Class (kv rms) (kv) 25 15.2 / 26.3 40 Eaton s Cooper Power series deadfront POSI-BREAK M.O.V.E. arrester samples and Deadfront DirectConnect M.O.V.E. arrester housings all passed the ac withstand test in accordance with IEEE Std 386-2006 standard, Paragraph 7.5.1.

CT235001EN Supersedes CP9314 May 2011 Page 25 of 28 TEST U DC WITHSTAND VOLTAGE TEST 25 kv POSI-BREAK Interface 35 kv DirectConnect Interface To verify that Eaton s Cooper Power series deadfront POSI-BREAK M.O.V.E. arrester and Deadfront DirectConnect M.O.V.E. arrester housings meet the dc withstand voltage level in accordance with IEEE Std 386-2006 standard, Paragraph 7.5.2. Ten samples of the POSI-BREAK M.O.V.E. arrester housing and ten samples of the DirectConnect M.O.V.E. arrester housing were tested. The test voltage was raised to the specified voltage withstand level listed below for 15 minutes minimum. No flashover or puncture was allowed. kv Max. Voltage Rating DC Withstand Level Class (kv rms) (kv) 25 15.2 / 26.3 78 Eaton s Cooper Power series deadfront POSI-BREAK M.O.V.E. arrester samples and Deadfront DirectConnect M.O.V.E. arrester samples all passed the dc withstand test in accordance with IEEE Std 386-2006 standard, Paragraph 7.5.2.

CT235001EN Supersedes CP9314 May 2011 Page 26 of 28 CHART 1 M.O.V.E. ARRESTERS DUTY CYCLE VOLTAGE RATING (kv) MCOV kv EQUIVALENT FRONT-OF-WAVE (kv) MAXIMUM DISCHARGE VOLTAGE (kv CREST) 8/20 µs Current Wave) 1.5kA 3kA 5kA 10kA 20kA 3 2.55 11.0 9.0 9.7 10.4 11.4 13.0 6 5.1 22.0 18.0 19.4 20.8 22.7 26.0 9 7.65 31.7 26.0 28.0 30.0 32.8 37.4 10 8.4 33.0 27.0 29.1 31.2 34.1 38.9 12 10.2 41.5 33.9 36.6 39.2 42.9 48.9 15 12.7 51.8 42.4 45.7 49.0 53.6 61.1 18 15.3 62.2 50.9 54.9 58.8 64.3 73.4 21 17.0 66.0 54.0 58.2 62.4 68.2 77.9 24 19.5 77.0 63.0 67.9 72.8 79.6 90.8 27 22.0 87.2 71.4 76.9 82.4 90.1 103.0 30 24.4 97.1 79.5 85.7 91.8 100.0 115.0 33 27.0 108.0 87.8 95.1 102.0 112.0 127.0 36 29.0 116.0 95.3 103.0 110.0 120.0 137.0 CHART 2 TOV RECOVERY CAPABILITY OF M.O.V.E. ARRESTERS AT 85 C time, s per unit of MCOV 0.02 2.090 0.1 1.653 1 1.568 10 1.492 100 1.425 1000 1.368 10000 1.292

CT235001EN Supersedes CP9314 May 2011 Page 27 of 28 GRAPH 1 TOV Recovery Curve of M.O.V.E. Arresters at 85 C

CT235001EN Supersedes CP9314 May 2011 Page 28 of 28 REVISION TABLE REVISION NO. DATE WHAT WAS ADDED/CHANGED 3 9/21/04 Update standard references throughout report 4 3/01/07 Update Graph 1 5 3/20/07 Modify Chart 2 6 3/23/07 Modify report reference new standards 7 11/6/07 Add Test Results of POSI-BREAK M.O.V.E 8 9/15/10 Add 35 kv Class DirectConnect M.O.V.E. and VariGAP to Introduction 9 6/01/11 Add 36 kv Duty Cycle. Modify Chart 1 and Chart 3. 10 6/29/15 Removed VariGAP references, assigned new document number Eaton 1000 Eaton Boulevard Cleveland, OH 44122 United States Eaton.com 2300 Badger Drive Waukesha, WI 53188 United States Eaton.com/cooperpowerseries 2015 Eaton Eaton, Cooper Power, POSI-BREAK, and DirectConnect All Rights Reserved are registered trademarks of Eaton. Printed in USA Publication No.CT235001EN All other trademarks are property June 2015 of their respective owners.