Protection Relays. U-MLEs-PLv. Ultra Line. DC SUBSTATION PROTECTIVE RELAY (double voltage Line Test) 32, 45, 49, 64, 76, 79, 80

Similar documents
Protection Relays. U-MLEs-PLv-Ts. Ultra-Ts. DC SUBSTATION PROTECTIVE RELAY (double voltage Line Test) 32, 45, 49, 64, 76, 79, 80

Protection Relays. U-MLEs-PLs-Ts. Ultra-Ts. DC SUBSTATION PROTECTIVE RELAY (single voltage Line Test) 32, 45, 49, 64, 76, 79, 80

FMR. Ultra Line FEEDER MANAGER RELAY

MHCO MHCO-RI. General Characteristics The transducer MHCO provide a measurement of current or voltage fully isolated and safe.

Fault indicator. Application. SPEF 3A2 C 1MRS MBG Issued: April 1999 Status: Updated Version: B/ Data subject to change without notice

REF 610 Feeder Protection Relay. Technical Reference Manual

BUS2000 Busbar Differential Protection System

NTG MULTIFUNCTON GENERATOR PROTECTION RELAY. NTG-Slide

High-set undervoltage stage with definitetime. or inverse definite minimum time (IDMT) characteristic. Low-set undervoltage stage with definitetime

Stabilized Differential Relay SPAD 346. Product Guide

RETROFITTING. Motor Protection Relay. Two mountings are available, Flush Rear Connection (EDPAR) or Projecting Rear Connection (SDPAR).

PD300. Transformer, generator and motor protection Data sheet

FMR-TR (Multiple I/O Boards) ULTRA Line

INSTRUCTIONS MANUAL DEVICE FOR THE PERMANENT CONTROL OF INSULATION ON THE SUPPLY LINES IN MEDICAL PRACTICE PLACES INSTALLATIONS HRI-R40W

SPAD 346 C Stabilized differential relay

sw rev. 55B DEVICE FOR THE PERMANENT CONTROL OF INSULATION ON THE SUPPLY LINES IN MEDICAL PRACTICE PLACES INSTALLATIONS

BU: EPBP GPG: DIN Rail Products Devices for the permanent control of insulation on supply lines for medical locations ISOLTESTER-DIG-RZ/RS/PLUS

Multimeter 500CVD21 RTU500 series

MT 560/UMT TRANSDUCER & ANALYZER

Protection relays and transformers

AC CURRENT GENERATOR POC-6000 (current from 0 to 1000 ARMS)

SPAA 341 C. Feeder Protection Relay. User s manual and Technical description SPAA 341 C. U aux V ~ V. f n. t 2 > [ s ] 0 I 0 >> Trip

NPRG860 & NPRG870 perform synchronization and paralleling of generators with electrical network. NPRG860 features a speed adjustment function.

Modular range of digital protection relays

NPRG860 NPRG870 REGULATION. Automatic Synchronizer for Generator

N100. example of application Ethernet www/ ftp. Ethernet TCP IP RS X MeaSUreMent of power network parameters.

new! nd30 - METER OF POWER NETWORk PARAMETERS EXAMPlE OF APPliCATiON MEASUREMENT AND ViSUAliZATiON OF POWER NETWORk PARAMETERS

Single Channel Loop Detector

Data Sheet. RISH Master Record %THD

Data Acquisition Modules/ Distributed IO Modules

M.3. Electrical measurement and control. Electrical energy meters for partial consumption

Monitoring Electric Network Via Internet

nd30 EXAMPlE OF APPliCATiON MEASUREMENT AND ViSUAliZATiON OF POWER NETWORk PARAMETERS Ethernet www/ ftp Modbus TCP Modbus RS-485

Power quality Harmonics up to 40th harmonic Rotary field components Distortion factor THD-U / THD-I

Addendum Operation Manual IM30-DREK MICROPROCESSOR OVERCURRENT AND DIRECTIONAL EARTH FAULT PROTECTION RELAY + AUTORECLOSE TYPE IM30-DREK ADDENDUM

- Protective & control functions

NETWORK ANALYZERS Analyzers

Phase and neutral overcurrent protection

ATV12HU40M3 variable speed drive ATV12-4kW - 5hp V - 3ph - with heat sink

Data sheet CPU 013C (013-CCF0R00)

(240 ) Measurement of DC currents and DC voltages. Size (mm): Q48 Q144 Q72 Q144 Q48 Q144

A proven distribution feeder solution with integrated protection, monitoring, and control

T/3000 T/3000. Substation Maintenance and Commissioning Test Equipment

7PG21 Solkor R/Rf Pilot Wire Current Differential Protection Answers for energy

Fixed Series Compensation

Data sheet VIPA CPU 314SC DPM (314-6CG23)

ATV12H018F1 variable speed drive ATV kW hp V - 1ph

DRTS 66 The new generation of advanced test equipments for Relays, Energy meters, Transducers and Power quality meters

ATV12H037F1 variable speed drive ATV kW hp V - 1ph - with heat sink

90 ReStart AUTOMATIC RECLOSING DEVICES

SPAC 335 C and SPAC 336 C Feeder terminals

Industrial Modbus I/O Modules

EE Lecture 14 Wed Feb 8, 2017

Dimension diagrams All dimensions in mm. Typical connection UMG 604-PRO. Power Analyser UMG 604-PRO. Front view. Side view. Versorgungsspannung

PEM353. Universal measuring device

SPAA 120 C and SPAA 121 C Feeder protection relay

200ADM-P. Current Injection System with Phase Shift A 3.000s 2.000A 50.00Hz 0.0. Features

SPAJ 111 C. Sensitive earth-fault relay SPAJ 111 C. User s manual and Technical description. U aux V ~ V. f n. n ( I o>> SPCJ 1C7

PLA 33. Power line analyzer. User and service manual. version 2.4

ATV12HU22M2. Main. Range of product Altivar 12. Component name Quantity per set Set of 1. Built-in fan. Motor power hp Communication port protocol

IM30-DRE MICROPROCESSOR OVERCURRENT AND DIRECTIONAL EARTH FAULT PROTECTION RELAY + AUTORECLOSE TYPE IM30-DRE OPERATION MANUAL

Measuring transducers

Harmonic restraint earth fault or single-phase overcurrent protection

Side view View from below Rear view

UMG 509-PRO. Multifunction power analyser with RCM

MICROPROCESSOR-BASED METERING EQUIPMENT SECTION 16901C PART 2

nd30pnet - METER Of POwER NETwORk PARAMETERS with profinet EXAMPlE Of APPlICATION MEASUREMENT ANd VISUAlIZATION Of POwER NETwORk PARAMETERS

DUCATI INSTRUMENTS COMPARISON TABLE

presentation contents application advantages

XR1 Rotor Earth Fault Relay. Manual XR1 (Revision C)

ISO 9001:2000 SIA C. Dual Power Overcurrent Protection Relay INSTALLATION GUIDE. Guia_SIA-C_Rev / 32

Energy Management. Type WM14 DIN Advanced version. Product Description 3-phase advanced power analyzer with integrated programming

ALPHA 50 MULTIFUNCTION METER (ALPHA SERIES)

Digital Input Output Module 24 V for Ex n Zone 2 Series 9472/35

Data sheet CPU 314ST/DPM (314-6CF02)

XIOC technology and networking modules

SPAS 348 C. Feeder Protection Relay. User s manual and Technical description SPAS 348 C V ~ V. t 2 > [ s ] f n = 50Hz 60Hz

Numbering System for Protective Devices, Control and Indication Devices for Power Systems

MULTIFUNCTION GRAPHICAL UNIT MGU 800

Complex Solution for the Distribution Substation REF 542plus. Application and Setting Guide

PROMUX Distributed MODBUS I/O Modules Catalog and Design Guide

SPAJ 110 C. Earth-fault relay SPAJ 110 C. User s manual and Technical description. U aux V ~ V f n. n ( I o>> SPCJ 1C8

DIN rail mounting temperature controller with current transformer input deltadue series D1 line

Company Replaces previous document Document ID Issue E.ON Elnät Sverige AB Ny engelsk utgåva D

SPAS 120 C Directional earth-fault relay

ZHUHAI PILOT TECHNOLOGY CO., LTD.

Data sheet CPU 313SC (313-5BF13)

DPX³ 250 Electronic 4P - ModbusTable LGR EN v1.01.xls

ASHIDA Numerical 3OC + 1EF Protection Relay

ES-777-MV-P2_A1 03/01/10

Z-10-D-IN. RS485 Modbus Module 10 Digital Inputs

NO WARRANTIES OF ANY KIND ARE IMPLIED ON THE INFORMATION CONTAINED IN THIS DOCUMENT.

1S24. Arc Fault Monitoring System. Arc fault protection to provide high speed detection and clearance of arcing faults.

a * example of application MeaSUreMent and ViSUalization of power network parameters Ethernet TCP IP RS-485 USB HOST /SD CARD

DMTME-96 2CSG133030R4022 M DMTME-I Operation and assembly instructions 2CSG163030R4022 M CSG445001D0202

Energy Management Energy Meter Type EM340

Temperature Controller

XUA1 AC Voltage and phase balance relay. (August 1996) Manual XUA1 (Revision New)

Networks IT, TN, TT networks 3 and 4-phase networks Up to 4 single-phase networks. Measured data memory 256 MByte Flash 32 MB SDRAM

XR1 Rotor Earth Fault Relay. (May 2007) Manual XR1 (Revision New)

Transcription:

Ultra Line DC SUBSTATION PROTECTIVE RELAY (double voltage Line Test) 3, 45, 49, 64, 76, 79, 80 D.C. Feeder protection relay with setting parameters programmable locally or via serial communication. Suitable for protection of D.C. feeders with High-Speed DC Breakers, for railway application. The relay measures the Line current and voltage through one current transducer and one voltage transducer. The transducers (type MHCO and MHIT) are galvanically insulated. Via fiber optic and have the following measuring ranges: Line voltage : (0 )Vn Line current : (0 0)In Insulation voltage 0kVac min. Real time measurements of primary input values can be read continuously both from the display and via ports communication. Relay settings can be done via the front and via rear serial communication. Pannel The associated Circuit Breaker can be controlled via the frontal keyboard and via serial communication. Settings, events and oscillographic recordings are stored in a non-volatile memory (E PROM). Besides the normal Watchdog and Powerfail functions, a comprehensive program of self-test and self diagnostic provides: Diagnostic and functional test with checking of programroutines and memory contents, running every time the auxiliary power supply is switched on. Dynamic functional test running during normal operation. Complete Test activated by the keyboard or via the communication bus. Any internal fault detected is indicated by a fault message on the display and by de-energization of associated I.R.F. output relay. The relay is available in three different executions: Flush mounting. Surface mounting. 9 Rack mounting.

Protective Functions Thermal image protection of the Cable/Line 4 Overcurrent levels Forward/Reverse programmable Current Step level with di/dt dependance Rate of rise level Impedance monitoring level with di/dt dependance Current monitoring level with di/dt dependence Frame Fault Current and Voltage monitoring levels 4 Shot Automatic Reclosure Overvoltage levels Undervoltage levels Automatic programmable Line Test Energy counter pulse C/B Lock Remote Trip Control Trip circuit supervision Associated Circuit Breaker control (OPEN / CLOSE) Breaker failure protection Breaker interruption energy i t Recording Two complete setting programs switchable locally or remotely Blocking input and Blocking output for pilot wire selectivity coordination and intertripping scheems Event Recording (last 00 events) Trip Recording (last 0 trips) complete with cause of tripping and values of the input quantities at the moment of trip Oscillographic recording of input quantities Communications Modbus RTU, Modbus RTU on TCP-IP and IEC870-5-03 communication protocols RS3 communication port on Front Face RS485 or RJ45 (optional) communication port on Back Panel Synchronisation with other relays (resolution ms) CanBus line for control of slave I/O Expansion modules Technical Characteristics Graphic Display (8x64 dots) 4 LEDS for: Power on/internal relay fault, Trip / alarm, Trip circuit fault 6 Output relays totally user programmable 4 Digital inputs user programmable Mounting Module box, totally draw-out execution IP44 protection case (on request IP54) Totally draw-out execution Power Supply Ratings Type : 4V(-0%) / 0V(+5%) a.c. - 4V(-0%) / 5V(+0%) d.c. Type : 80V(-0%) / 0V(+5%) a.c. - 90V(-0%) / 50V(+0%) d.c. Software MSCom Program interface for device management Accessories High-Voltage Current/Voltage measuring Transducer with Fiber Optic output : Type MHCO-T/V-I High-Voltage Current measuring Transducer with Fiber Optic output : Type MHCO-T-I. High-Voltage Voltage measuring Transducer with Fiber Optic output : Type MHCO-T-V Voltage measuring reciver with fiber optic input and 3 Analogic outputs : Type MHCO-R-V Current measuring reciver with fiber optic input and 3 Analogic outputs : Type MHCO-R-I Input/Output Expansion Module: UX0-4 - 0 Digital Inputs + 4 Outputs Relay UX4DI - 4 Digital Inputs UX4DO - 4 Outputs Relay Line Test Contactor Line Test Resistor Rail Earthing Contactor Other protection Relay SCADA and Communication systems

3 Real Time Measurements I = Current V = Voltage P = Power +Wh, = Exported Energy -Wh, = Imported Energy F49 (T>): Thermal Image element with prealarm Temperature prealarm Continuous admissible current Time constant F - 67/50/5 (I>): st Overcurrent Element F - 67/50/5 (I>): nd Overcurrent Element 3F - 67/50/5 (3I>): 3rd Overcurrent Element 4F - 67/50/5 (4I>): 4th Overcurrent Element F - (DI): st DI Element Minimum di/dt level to start DI : Tal = (0 00)%Tn : Is = (0.5.5) : Kt = ( 600)min step %Tn step 0.0 step 0.0min : Is = (0. 4)In step 0.0In : ts = (0.0 00)s step 0.0s : Is = (0. 4)In step 0.0In : ts = (0.0 00)s step 0.0s : Is = (0. 0)In step 0.0In : ts = (0.0 00)s step 0.0s : Is = (0. 0)In step 0.0In : ts = (0.0 00)s step 0.0s : DI = (00 9990)A step 0A : di = (4 400)A/ms step A/ms : tdi = (0 500)ms step ms Detection reset time delay : tdi = (0 00)ms step ms F - (DI): st DI Element Minimum di/dt level to start DI : DI = (00 9990)A step 0A : di = (4 400)A/ms step A/ms : tdi = (0 500)ms step ms Detection reset time delay : tdi = (0 00)ms step ms

4 F - (di/dt): st Current Rate of Rise Element F - (di/dt): nd Current Rate of Rise Element Rapp: Impedance monitoring with di/dt dependence Arc Voltage Internal Resistance Total Resistance of the circuit Internal Inductance Total Inductance of the circuit Resistance trip level Limit value of di/dt Iapp: Current monitoring with di/dt dependence Current trip level when di/dt = 0 Current trip level when di/dt ³ [g] Limit value of di/dt Drop-out percentage : G = (4 400)A/ms : tg = ( 500)ms : G = (4 400)A/ms : tg = ( 500)ms step A/ms step ms step A/ms step ms : Va = (0 800)V : Ri = (0 0.50)W step V step 0.00W : Rt = (0.00.5)W step 0.00W : Li = (0.00 0.0)H step 0.00H : Li = (0.00 0.05)H step 0.00H : R* = (0 00)W step 0.0W : g = (0 500)A/ms step A/ms : g = (0 00)ms step ms : Ia = (500 5000)A step 0A : I* = (400 500)A step 0A : g = (30 500)A/ms step A/ms : Res = (80 00)%Iapp step %Iapp : tr = (0 5)s step 0.0s F - 64 (Ig): st Frame Fault Element Current setting range : Is = (0. 4)Ign step 0.0Ign Voltage setting range : Us = (0.0 )Ugn step 0.0Ugn : ts = (0.0 00)s step 0.0s F - 64 (Ig): nd Frame Fault Element Current setting range : Is = (0. 4)Ign step 0.0Ign Voltage setting range : Us = (0.0 )Ugn step 0.0Ugn : ts = (0.0 00)s step 0.0s

5 RCL: Automatic Reclosure Number of Reclosure Reclaim time : ShN = / / 3 / 4 : tr = ( 00)s step s Time first reclosure : t = (0. 000)s step 0.s Time second reclosure : t = (0. 000)s step 0.s Time third reclosure : t3 = (0. 000)s step 0.s Time fourth reclosure : t4 = (0. 000)s step 0.s LT: Automatic Line Test (Double Voltage Line test) Number of Test Minimum residual voltage downstream : TestN = 0 / / 3 / 4 : Vv< = (0 )Vn step 0.00Vn Minimum residual voltage upstream : Vm< = (0 )Vn step 0.00Vn Minimum residual resistance : RR< = (0 500)W step W Minimum line voltage : VFast = (0.5 )Vn step 0.Vn Waiting time after C/B closing : tp = (0 30)s step s Duation of the Line Test : tt = ( 0)s step s Wait time between consecutive tests : tcy = ( 60)s step s Wait time to start recl.after succes fine test : tw = (0 0)s step s F - 59 (U>): st Overvoltage Element : Us = (0.5.5)Un step 0.0Un : ts = (0 650)s step s F - 59 (U>): nd Overvoltage Element : Us = (0.5.5)Un step 0.0Un : ts = (0 650)s step s F - 7 (U<): st Undervoltage Element : Us = (0. )Un step 0.0Un : ts = (0 650)s step s F - 7 (U<): nd Undervoltage Element : Us = (0. )Un step 0.0Un : ts = (0 650)s step s Wi: Circuit Breaker Energy Maintenence : Ii = (0. 99)In step 0.In Conventional interrupption current : Wi = ( 9999) step RT: Remote Trip : ts = (0 0)s step 0.0s Wh: Energy Counter Pulse Energy level : WpP = (0 000)kW step 0kW Pulse duration : Pulse = (0. )s step 0.0s CB-L: C/B Lock Breaker Failure Element Alarm time delay : tbf = (0.05 0.75)s step 0.0s

6 (Example with MHCO Transducer) R PL + - LINEE LINEA FRAME-TO-GROUND VOLTAGE MONITORING INPUT FRAME-TO-GROUND CURRENT MHCO-TV MHCO-TVI MONITORING INPUT MHCO-RV MHCO-R-I MHCO-R-V 3 4 (4) (4) (8) (9) 45 46 3 4 5 47 48 POWER SUPPLY ALIM. AUSILIARA. OPTION OPTION In 0In _ MS-SCE387-R0 = ULTRA D.C. Feeder Manager Relay POWER TRIP ON OFF BPU R R R3 R4 R5 FRONT - RS3 R6 RS485 CAN R R R3 R4 R5 R6 D D D3 D4 ETHERNET A(S+) B(S-) C C H L RJ45 5 6 5 4 4 35 N.O. 34 N.C. 3 33 3 3 3 8 8 9 9 38 7 7 6 36 37 TRIP COIL SUP. (5) OUTPUT RELAY RELE' DI USCITA DIGITAL INPUTS INGRESSI DIGITALI RS485 AI MODULI AGGIUNTIVI TO EXPANSION MODULE RJ45 (ModbusOnTCP) RJ45 (Serial on Ethernet) RJ45 (IEC6850) RS485 (Modbus RTU) Typical Characteristics Accuracy at reference value of influencing factors Input Averange power supply consumption Output relays % FS for measurements % +/- 0ms for times 0 0 ma < 0 VA rating 5A; Vn = 380V A.C. resistive switching = 00W (380V max) make = 30A (peak) 0.5 sec. break = 0.3A, 0Vcc L/R = 40ms (00.000 op.) Order code - Example : Power Supply Configuration R (4-5) = Type = N.O. = Type = N.C. st Expansion module = None = UX0-4 3 = 4DI 4 = 4DO nd Expansion module = None = UX0-4 3 = 4DI 4 = 4DO Communication Protocol = ModbusRTU (standard) = Modbus TCP-IP 3 = IEC6850 The performance and the charecteristics reported in this document are not binding and can modified ant any moment without notice. Microelettrica Scientifica S.p.A. - 0089 Buccinasco (MI) - Via Lucania, Italy Tel. +39 0 57573 - Fax +39 0 5750940 - E-Mail: sales.relays@microelettrica.com www.microelettrica.com