Maintaining Voltage-Current Phase Relationships in Power Quality Monitoring Systems

Similar documents
Experiment 45. Three-Phase Circuits. G 1. a. Using your Power Supply and AC Voltmeter connect the circuit shown OBJECTIVE

Simulation & Hardware Implementation of APFC Meter to Boost Up Power Factor Maintain by Industry.

Sizing the neutral wire cross-section and minimization of neutral currents using microgeneration in low voltage networks

AUTO-TRANSFORMER. This is having only one winding; part of this winding is common to both primary and secondary.

RISH EM 3490 DS Dual Source Energy Meter (With All Display Parameters) RISH EM 3490 DS. Application : Product Features:

Data Sheet. RISH Master Record %THD

Digital Multifunction Instrument - Rish Master 3440

MICROPROCESSOR-BASED METERING EQUIPMENT SECTION 16901C PART 2

RISH Master Digital Multifunction Instrument with onsite pluggable output options. Application : Product Features:

Provisional Specifications

AMIK 200 / 201 Technical Data Sheet

Application Alpha 20 Measures important electrical parameters in 3 phase 4 Wire and 3 phase 3 Wire Network & replaces the multiple analog panel meters

CHAPTER 4 HARMONICS AND POWER FACTOR

Jewell DPM Power / Power Factor Size 96/96 BEST IN CLASS

Transformer Waveforms

Integra 1560 and 1580 Digital Transducer Systems

ACCURACY OF VOLTAGE TRANSFORMERS DESIGN CRITERIA AND A SURVEY ON THE PRECISION AND REPRODUCIBILITY OF A NEW MODEL-BASED CALIBRATION APPROACH

ALPHA 50 MULTIFUNCTION METER (ALPHA SERIES)

RISH EM 3490 SS Kilowatt Hour Energy Meter With Rs485 RISH EM 3490 SS. Application : Product Features: Indication: Pulse Indication:

Power Factor. Power Factor Correction.

Power Quality Analysis in Power System with Non Linear Load

Power Quality Monitoring and Power Metering Tutorial

Bus protection with a differential relay. When there is no fault, the algebraic sum of circuit currents is zero

CHAPTER 5 POWER QUALITY IMPROVEMENT BY USING POWER ACTIVE FILTERS

ISSN: ISO 9001:2008 Certified International Journal of Engineering Science and Innovative Technology (IJESIT) Volume 2, Issue 3, May 2013

Principles of Analog In-Circuit Testing

Electrical Theory. Power Principles and Phase Angle. PJM State & Member Training Dept. PJM /22/2018

A Thyristor Controlled Three Winding Transformer as a Static Var Compensator

EASTRON SDM630MCT-RJV / SDM630MCT-RJA User Manual V1.1. Three phase multifunction din rail energy meter

Unit 3 Magnetism...21 Introduction The Natural Magnet Magnetic Polarities Magnetic Compass...21

Dynamic Power Factor Correction Using a STATCOM

UNIVERSAL MEASURING INSTRUMENTS. TNM 34xx. TNM 3410 / 3420 / 3430 / 3440 Universal measuring instrument 1/49

Preface...x Chapter 1 Electrical Fundamentals

Introduction to Voltage Regulator Settings

ARE HARMONICS STILL A PROBLEM IN DATA CENTERS? by Mohammad Al Rawashdeh, Lead Consultant, Data Center Engineering Services

THE COMPREHENSIVE APPROACH TO FACILITY POWER QUALITY

Transformer circuit calculations

Impact of transient saturation of Current Transformer during cyclic operations Analysis and Diagnosis

2C73 Setting Guide. High Impedance Differential Relay. Advanced Protection Devices. relay monitoring systems pty ltd

WATT TRANSDUCER. Instruction Manual

ALPHA 20 MULTIFUNCTION METER (ALPHA SERIES)

SECTION LOW VOLTAGE ACTIVE HARMONIC FILTER SYSTEM NEMA 1 ENCLOSED

Technical Data Sheet AMIK 300 / 301

Alternative Testing Techniques for Current Transformers. Dinesh Chhajer, PE Technical Support Group MEGGER

Chapter 7. Copyright The McGraw-Hill Companies, Inc. Permission required for reproduction or display.

ISSN: Page 298

RISH Master 3430 DIGITAL MULTI-FUNCTION TRANSDUCER. Electro-Meters

Power Conditioning Equipment for Improvement of Power Quality in Distribution Systems M. Weinhold R. Zurowski T. Mangold L. Voss

CHAPTER 2. Basic Concepts, Three-Phase Review, and Per Unit

6L]LQJ$8366\VWHP )RU1RQ/LQHDU/RDGV

Electrical Motor Power Measurement & Analysis

Line to Ground Voltage Monitoring on Ungrounded and Impedance Grounded Power Systems

2C73 Setting Guide. High Impedance Differential Relay. relay monitoring systems pty ltd Advanced Protection Devices

Design and Implementation of Economical Power Factor Transducer

1. Introduction to Power Quality

Advanced Paralleling of LTC Transformers by VAR TM Method

MILWAUKEE SCHOOL OF ENGINEERING LABORATORY SESSION 4 THREE PHASE TRANSFORMERS

Harmonic Solutions. Clean Power Drive Solution to Harmonic Distortion

Effects of Harmonic Distortion I

Improvement of Power Quality in Distribution System using D-STATCOM With PI and PID Controller

AC Power Instructor Notes

Comparative Testing of Synchronized Phasor Measurement Units

Analysis and modeling of thyristor controlled series capacitor for the reduction of voltage sag Manisha Chadar

JEMSTAR. Digital Multifunction Electricity Meter. Application Notes

Improvement of Islanding Detector Using Interharmonics Current Injection Method and Its Applications

Application for A Sub-harmonic Protection Relay. ERLPhase Power Technologies

Dranetz-BMI : the award-winning hand-held 3-phase power analyzer

Technical Paper. Harmonic Distortion in Data Centers

Why Accuracy Matters!

Radio Frequency Power Meter Design Project

Low Pass Harmonic Filters

TECHNICAL BULLETIN 004a Ferroresonance

Manual Supplement. This supplement contains information necessary to ensure the accuracy of the above manual.

Issued: September 2, 2014 Effective: October 3, 2014 WN U-60 Attachment C to Schedule 152, Page 1 PUGET SOUND ENERGY

CASE STUDY. Implementation of Active Harmonic Filters at Ford Motor Company SA Silverton Plant

Dynamic Harmonic Mitigation and Power Factor Correction

Section 6 - Electronics

Power Sensors Ltd. PQube 3 AC Analyzer IEC Class 0,2 S Accuracy Compliance Report

AC/DC Current Probe CT6844/CT6845/CT6846

SHRI RAMSWAROOP MEMORIAL COLLEGE OF ENGG. & MANAGEMENT B.Tech. [SEM I (EE, EN, EC, CE)] QUIZ TEST-3 (Session: ) Time: 1 Hour ELECTRICAL ENGINEE

Testing Power Sources for Stability

HARMONIC contamination, due to the increment of nonlinear

NOVEL PROTECTION SYSTEMS FOR ARC FURNACE TRANSFORMERS

Generator Operation with Speed and Voltage Regulation

Aligarh College of Engineering & Technology (College Code: 109) Affiliated to UPTU, Approved by AICTE Electrical Engg.

A Review on Simulation and Implementation of Thyristor controlled reactor and Shunt Hybrid Power Filter

Power Quality Improvement in Distribution System Using D-STATCOM

UNIT 1 CIRCUIT ANALYSIS 1 What is a graph of a network? When all the elements in a network is replaced by lines with circles or dots at both ends.

Improving CDM Measurements With Frequency Domain Specifications

EXPERIMENT 1 TITLE: SINGLE PHASE TRANSFORMERS - TRANSFORMER REGULATION

CHAPTER 9. Sinusoidal Steady-State Analysis

New Features of IEEE Std Digitizing Waveform Recorders

Sizing Generators for Leading Power Factor

BED INTERCONNECTION TECHNICAL REQUIREMENTS

A Single Phase Power Factor Correction Using Programmable Interface Circuit

~=E.i!=h. Pre-certification Transformers

IJESR/Nov 2012/ Volume-2/Issue-11/Article No-21/ ISSN International Journal of Engineering & Science Research

Reliable Power Meters Multipoint Power Recorder

APPLICATION NOTE. Achieving Accuracy in Digital Meter Design. Introduction. Target Device. Contents. Rev.1.00 August 2003 Page 1 of 9

Jewell DPM EINE BEST IN CLASS

Transcription:

Maintaining Voltage-Current Phase Relationships in Power Quality Monitoring Systems Brian Kingham, Utility Market Manager, Schneider Electric, PMC Division Abstract: Historical power quality measurement devices focused on voltage-only measurements for analysis, survey and troubleshooting purposes. In order to increase their return on capital investment, utilities are looking for measurement devices capable of meeting more than one business need: for example, a device capable of simultaneously monitoring power quality and providing revenue-accurate data. This desire drives a new requirement to maintain phaseangle relationships between previously independent voltage and current circuits so that energy accuracy is preserved. This paper describes the system components (such as transformers and PQ monitor components) that can affect V-I phase relationships and methods to eliminate or compensate for these errors. In conclusion, it is shown how requirements for leading revenue accuracy standards and IEC 61000-4-30 Class A Power Quality compliance can not only be met but exceeded. T I. Introduction HE increasing cost of energy has intensified the need for more accurate end-to-end metering systems. At the same time, utilities are looking to leverage new technologies to reduce capital expenditure costs, leading them to install multifunction devices within their measurement and monitoring systems. This paper describes how total system measurement accuracy can be affected by components both internal and external to metering devices. The paper then introduces available technologies that, with proper application, are capable of mitigating the error introduced to provide system measurement accuracy that is orders of magnitude greater than was historically possible. II. Sources of Phase Error There are many potential sources of phase and magnitude errors within an electrical network. For the purposes of this paper, we are focused on those components near the metering point that can affect the accuracy of the metered parameters. As shown in Figure 2, these sources are identified as the power transformer (A), the instrument transformers (B), the current transformers inside the meter (C), and the analog front-end of the meter (D). B A C Front-End D CPU Figure 2. Sources of phase and magnitude error in metering systems Figure 1. Rise in US energy price, 1993-2006 Brian Kingham is with Schneider Electric in Victoria, BC (email: brian.kingham@ca.schneider-electric.com)

A. Power Transformer Error Substation power transformers provide highly efficient voltage and current magnitude transformation but still introduce both ratio error (the difference, expressed in RMS volts or amps, between the primary and secondary magnitudes after the turns ratio has been accounted for) and phase error (the difference in phase, expressed in degrees, between the primary and secondary sinusoidal waveforms). Both these sources of errors are due to the magnetizing inductance required by the core and the impedance of the windings (see Figure 3). The resistive losses will cause ratio error and the inductance of the windings and core will cause both ratio and phase error from the primary to the secondary side of the transformer. of the core, phase shift through a CT will be nonlinear. C. Metrology CT Error An often overlooked component of the metering system is the current transformer used inside the meter itself. Like any other transformer, this internal CT introduces another source of ratio and phase error. Passive CTs are inexpensive magnetic transformers which produce output current proportional to input current but which incorporate both a magnitude loss and phase error. Figure 4. Equivalent circuit of a passive CT Figure 3. Equivalent circuit of a power transformer B. Instrument Transformer Error Instrument transformers, including current transformers (CTs) and potential transformers (PTs), are used to provide low-voltage and lowcurrent inputs to meters. Like power transformers, instrument transformers are a source of both ratio and phase error. In order to maximize the accuracy of voltage transformation, PTs are designed to minimize voltage drop in the transformer windings and magnetization current. The equivalent circuit for a PT is essentially the same as shown in Figure 3 for a power transformer. Phase error introduced by passive CTs varies with the impedance of the core, and is therefore susceptible to changes in load or temperature. Because of this multi-variable dependency, it is difficult to fully compensate for passive CT phase error through calibration. Active CTs are also a source of magnitude error, but use a feedback loop to replace lost current and maintain a zero-flux core. Because of this feedback loop, there is no phase error though an active CT. CTs, however, are more sensitive to the magnetization current flowing through the transformer core. Due to the complex impedance

Figure 5. Equivalent circuit of an active CT D. Analog Front-End Error Finally, a source of error particular to multifunction power quality and energy meters is the introduction of low-pass RLC filters in the analog front-end. These filters are required by international power quality standards such as IEC 61000-4-30 and IEC 61000-4-7 to ensure that high frequency signals are not aliased into the reported values for individual harmonic magnitudes or total harmonic distortion. The insertion of any RLC filter will produce ratio and phase shift error between measurement channels which must also be corrected if power and energy accuracy is to be maintained. III. Phase Error Correction Methods A. Power Transformer Correction Method 2 uses empirical data from the in-situ transformer to determine the amount of compensation necessary. The measured Watt and VAR losses are entered into the loss compensation calculations along with system resistance and reactance information. Like Method 1, these coefficients can either be programmed into the meter for real-time correction or used in postprocessing applications. Rather than attempting to compensate for power transformer ratio and phase errors measured at a meter s three-phase voltage and current input channels, the industry-standard approach is to correct for errors in the resulting Watt and VAR totalized values. One of two sets of calculations is used to achieve this, dependent on the input coefficients available. Method 1 uses manufacturer-supplied test sheet data to calculate the Watt and VAR losses caused by the transformer. The test sheet data (VA TXtest, LWFe TXtest and LWCu TXtest ) are entered into the loss compensation calculations along with actual voltage and current levels, %Excitation and %Impedance. The results of these calculations can then be either programmed into a meter for realtime compensation or used for post-processing of energy data.

B. Instrument Transformer Correction Unlike power transformer correction, instrument transformer correction (ITC) corrects for error in the individual voltage and current circuits in real time. This produces the same benefit to power and energy calculations as the power transformer correction method but with the advantage of also correcting the individual voltage and current readings. Additionally, since each phase of a three-phase PT or CT can have a unique error correction curve, per-phase rather than total error correction is preferred as it will be more accurate in unbalanced systems than total error correction. To implement ITC, a series of ratio correction and phase angle correction data points are provided from transformer manufacturers specifications or from test results (see Figure 6). These coefficients are programmed into an algorithm that interpolates between data points to best fit the error curve of the transformer. curves can be calculated for the entire current range and for multiple power factors. Because the error curves vary by power factor, an approximation is always employed to compensate for points not covered by the calibration process. Because of the active compensation circuit, active CTs have no phase error and are thereby immune to changes in power factor. This allows manufacturers to use standard calibration techniques to compensate for the magnitude error of the CT in real time. An additional benefit of an active CT s dynamic compensation is correction for core magnetization. Half-wave signals (such as transients) can shift the magnetization of a CT core away from its ideal state. For passive core CTs, this will result in additional phase error. The feedback circuit in an active CT will compensate for the magnetization effect by injecting the necessary current to maintain zero magnetic flux. D. Analog Front-End Correction Figure 6. Phase angle error curve C. Metrology CT Correction To correct for errors introduced by the meter s metrology CT, passive correction is dependent on the ability to correctly model the phase and magnitude error. Given a highly accurate reference, sufficient memory and processing power to handle high-order polynomials, and enough time during the calibration process, error correction The amount of correction needed to compensate for ratio and phase errors introduced in the analog front-end depends greatly on the architecture being used. At a minimum, to comply with international harmonics measurement standards such as IEC 61000-4-7, sufficient filtering must exist in the signal chain to prevent aliasing of higher frequency components into lower harmonic measurements. Low-pass filters, introduced to prevent aliasing, will cause undesirable phase shift errors between voltage and current channels which then affect power and energy calculations. These phase shift errors can be corrected through calibration in a similar manner to instrument transformer correction. By modeling the error curves using laboratory-precision devices, compensation curves can be programmed into the meter to correct for errors in real-time. If matched filter packs are used to keep ratio and phase error

consistent between voltage and current channels, the correction can completely mitigate the error. IV. Results of Phase and Magnitude Error Correction A. Power Transformer Correction Results By its nature and the formulas used, power transformer correction applies correction factors directly to the Watt and VAR values of interest. This means that the effect of correction is dependent on the accuracy of the input variables used rather than an empirical measurement as in other correction methods. Using data supplied by the transformer manufacturer, a typical 7500 kva transformer operating at 3780 kva and unity power factor will introduce an error of 37.2 kw or 0.98%. This includes a phase error of 2.9 degrees. Power transformer correction will completely eliminate this error. B. Instrument Transformer Correction Results Because the voltage input to a PT tends to be fairly stable, PT accuracy limits are typically defined between 80 and 120% of nominal voltage. Within this range, PT phase error for a Class 0.5 PT is limited to about 0.35 degrees. The allowable ratio error is included in the accuracy class number (0.5% at nominal voltage for a Class 0.5 PT). These errors are fairly small, and unless in-situ data is provided the effect of instrument transformer correction on a PT will be limited. CT error, particularly phase error, can be much higher. CTs are expected to be subjected to most of their dynamic range as loading levels change. Because of the relationship between current, magnetic flux and inductance within a CT, phase error is non-linear and larger than within a PT. The same accuracy Class 0.5 CT can introduce phase errors between 0.5 degrees and 1.5 degrees and a Class 1 CT can be up to 3 degrees. The ability to use high-voltage, highly-accurate current sensors has allowed empirical observations of ITC results. Table 1 shows the results with and without ITC, where it can be seen that an improvement of up to 1.5% has been realized through error compensation of an instrument CT. Voltage V RMS Current A RMS Power Factor Error (%) Without ITC Error (% ) With ITC 120 20 Unity -0.92-0.017 120 20 0.6 lag 1.63-0.10 120 50 0.6 lag 0.89-0.003 120 100 0.6 lag 0.65 0.056 120 50 0.6 lag 0.55 0.067 Table 1 Effect of instrument transformer correction C. Metrology CT Correction Results With passive CT error approximation and correction, power and energy accuracy can be brought to within industry standard requirements of 0.2%. Due to the non-linear phase error, it is difficult to improve error correction beyond this level except at discrete calibration points (e.g. unity power factor and full load). Active CT correction results are much better and more consistent over the entire operating range of the meter due to the zero phase error. Using active CT correction, the error of the meter can be brought to within the bounds of calibration reference standards; typically four to ten times more accurate than the most stringent 0.2% energy error tolerance. Empirical results of active CT correction show an improvement in metering error (and thereby system error) of 0.15%. D. Analog Front-End Correction Results The total benefit of analog front-end correction depends greatly on the architecture chosen for the meter. If all filter components are perfectly matched on all input channels, phase error is negated. Using a combination of matched component filter packs and calibration

compensation, improvements in power and energy accuracy of up to 0.2% have been achieved. V. Conclusion With system measurement error becoming increasingly important as energy prices rise, power transformer correction, instrument transformer correction, active CTs and analog front-end calibration can all contribute to increased accuracy in power and energy measurements. Proper selection and application of these methods has shown total system error improvements of over 3%, and should be considered integral to the implementation of a Class 0.2 metering system. VI. Author Biography Brian Kingham received his Bachelor of Electrical Engineering from the University of Victoria in 1995. In 1995 he joined Power Measurement (now Schneider Electric) and is currently the Utility Market Manager for the company s Power Monitoring and Control (PMC) division. VII. References [1] P. Doig, C. Gunn, L. Durante, C. Burns & M. Cochrane, "Reclassification of Relay-Class Current Transformers for Revenue Metering Applications", IEEE 2005