EH27401 Communication and Control in Electric Power Systems Lecture 2. Lars Nordström

Similar documents
EH2741 Communication and Control in Electric Power Systems Lecture 2

Texas Reliability Entity Event Analysis. Event: May 8, 2011 Loss of Multiple Elements Category 1a Event

Single Line Diagram of Substations

ESB National Grid Transmission Planning Criteria

Unit 2. Single Line Diagram of Substations

Fatima Michael college of Engineering and Technology

How to maximize reliability using an alternative distribution system for critical loads

CONTENTS. 1. Introduction Generating Stations 9 40

Level 6 Graduate Diploma in Engineering Electrical Energy Systems

Central Hudson Gas & Electric Corporation. Transmission Planning Guidelines

Electrical Power Systems

Coil Products Beginnings 1960 State of the Art. Customer partnership around the globe. Continuous innovation since 1900

Notes 1: Introduction to Distribution Systems

SRI VIDYA COLLEGE OF ENGG AND TECH

Substation: From the Outside Looking In.

THE IMPACT OF NETWORK SPLITTING ON FAULT LEVELS AND OTHER PERFORMANCE MEASURES

Utility Interconnection and System Protection

Fundamental Concepts of Dynamic Reactive Compensation. Outline

HVDC High Voltage Direct Current

Tab 2 Voltage Stresses Switching Transients

UProtection Requirements. Ufor a Large scale Wind Park. Shyam Musunuri Siemens Energy

Electrical Engineering. Power Systems. Comprehensive Theory with Solved Examples and Practice Questions. Publications

Protection of Electrical Networks. Christophe Prévé

Self Healing Single Phase Looped Network AUTOMATED RECONFIGURATION FOR POWER OUTAGE MANAGEMENT. Team Members

ATCO ELECTRIC LTD. (Transmission System) SERVICE QUALITY AND RELIABILITY PERFORMANCE, MEASURES AND INDICES Revision 0

ECE 422/522 Power System Operations & Planning/Power Systems Analysis II 5 - Reactive Power and Voltage Control

La protection sélective des réseaux électriques

High Voltage DC Transmission 2

EE 741. Primary & Secondary Distribution Systems

VSC Transmission. Presentation Overview. CIGRE B4 HVDC and Power Electronics HVDC Colloquium, Oslo, April LCC HVDC Transmission

ELEC Transmission i and

BE Semester- VI (Electrical Engineering) Question Bank (E 605 ELECTRICAL POWER SYSTEM - II) Y - Y transformer : 300 MVA, 33Y / 220Y kv, X = 15 %

Jason Harchick, P.E. Sr. Manager, System Planning and Protection Ryan Young Manager, Substation Engineering

No. SSIEC-PRC SHINSUNG. Polymer Recloser SIREC SERIES 15kV, 27kV, 38kV 400A, 630A, 800A

Impact of Distributed Generation on Network Voltage Levels

Introduction to HVDC Transmission. High Voltage Direct Current (HVDC) Transmission

Numbering System for Protective Devices, Control and Indication Devices for Power Systems

ISO Rules Part 500 Facilities Division 502 Technical Requirements Section Aggregated Generating Facilities Technical Requirements

G. KOEPPL Koeppl Power Experts Switzerland

The Advantages and Application of Three Winding Transformers

POWER QUALITY ENHANCEMENT BY DC LINK SUPPLIED INDUSTRIAL SYSTEM

Distance Protection for Distribution Feeders. Presented By: Yordan Kyosev, P.Eng. & Curtis Ruff, P.Eng.

A short introduction to Protection and Automation Philosophy

Electricity Ten Year Statement November Electricity Ten Year Statement November Appendix D

Protection Basics Presented by John S. Levine, P.E. Levine Lectronics and Lectric, Inc GE Consumer & Industrial Multilin

INTEGRATED TRANSMISSION PLAN Glossary

Line protection with transformer in the protection zone

CHAPTER 4 POWER QUALITY AND VAR COMPENSATION IN DISTRIBUTION SYSTEMS

Delayed Current Zero Crossing Phenomena during Switching of Shunt-Compensated Lines

ELE-CMOS-E-2001 Electrical Engineer PERSONAL DATA EDUCATION LANGUAGES COMPUTER SKILLS TRAINING COURSES AND CERTIFICATIONS

, ,54 A

GRID CODE COMPATIBLE PROTECTION SCHEME FOR SMART GRIDS

10. DISTURBANCE VOLTAGE WITHSTAND CAPABILITY

MV network design & devices selection EXERCISE BOOK

Electrical PIP ELEGL03 Guidelines for Power Systems Analysis

ELECTRICAL POWER TRANSMISSION TRAINER

MV, HV AND EHV SWITCHGEAR TESTING & COMMISSIONING

Substation Preventive Maintenance

EVALUATION OF DIFFERENT SOLUTIONS OF FAULTED PHASE EARTHING TECHNIQUE FOR AN EARTH FAULT CURRENT LIMITATION

Chapter -3 ANALYSIS OF HVDC SYSTEM MODEL. Basically the HVDC transmission consists in the basic case of two

Experience with Connecting Offshore Wind Farms to the Grid

Progress Report on Failures of High Voltage Bushings with Draw Leads By Jim McBride and Larry Coffeen, JMX Services / NEETRAC 7/26/2010

Earth Fault Protection

Case Study 1. Power System Planning and Design: Power Plant, Transmission Lines, and Substations

Delayed Current Zero Crossing Phenomena During Switching of Shunt-Compensated Lines

POWER FACTOR CORRECTION. HARMONIC FILTERING. MEDIUM AND HIGH VOLTAGE SOLUTIONS.

SPTS 1 - Ratings and General Requirements for Plant, Equipment and Apparatus for The ScottishPower System and Connection Points to it.

Highgate Converter Overview. Prepared by Joshua Burroughs & Jeff Carrara IEEE PES

Joe Warner, Electric Power Industry Conference (EPIC), November 15, 2016 Advances in Grid Equipment Transmission Shunt Compensation

Hamdy Faramawy Senior Application Specialist ABB Sweden

Fixed Series Compensation

INVESTIGATION INTO THE POWER QUALITY AND RELIABILITY OF SUPPLY IN THE INDUSTRIAL NETWORKS WITH DISTRIBUTED GENERATION

Overview of Actuation Thrust

High Voltage DC Transmission Prof. Dr. S. N. Singh Department of Electrical Engineering Indian Institute of Technology, Kanpur

Topic 6 Quiz, February 2017 Impedance and Fault Current Calculations For Radial Systems TLC ONLY!!!!! DUE DATE FOR TLC- February 14, 2017

Appendix D Fault Levels

DG TRANSFER CONNECTION SCHEME IN ACTIVE DISTRIBUTION NETWORKS

LV/MV/HV CIRCUIT BREAKERS (SWITCH GEAR) DESIGN, INSPECTION, MAINTENANCE, REPAIR & TROUBLESHOOTING

Overview of Actuation Thrust

ETM521. Lecture 1 - Power System Overview Barış Sanlı 1 / 72

Quanta Technology Advancing the Grid. Flexible AC Transmission System (FACTS) BGE Technology - Application Cases January 4, 2008 Q U A N T A SERVI CES

Advanced Test Equipment Rentals ATEC (2832) CP RC. Resonance circuit for GIS testing

Distribution System Development & Preliminary Studies

Application for A Sub-harmonic Protection Relay. ERLPhase Power Technologies

Document C-29. Procedures for System Modeling: Data Requirements & Facility Ratings. January 5 th, 2016 TFSS Revisions Clean Open Process Posting

SIMPLE SOLUTIONS FOR IMPROVING LIFE OF BREAKERS USED IN TRANSMISSION AND DISTRIBUTION SYSTEMS

Embedded Generation Connection Application Form

Education & Training

SAFETY ASPECTS AND NOVEL TECHNICAL SOLUTIONS FOR EARTH FAULT MANAGEMENT IN MV ELECTRICITY DISTRIBUTION NETWORKS

Embedded Generation Connection Application Form

SOLID-STATE TRANSFORMERS

SHORT CIRCUIT ANALYSIS OF 220/132 KV SUBSTATION BY USING ETAP

BC HYDRO REAL TIME OPERATIONS OPERATING ORDER 7T-30A. NORTH COAST INTERCONNECTION: SKEENA BOB QUINN SUBSYSTEM Supersedes OO 7T-30A dated 07 July 2014

MAJOR ADVANCES IN MV/LV SUBSTATIONS. Th.Grima et JF.Faltermeier. Groupe CAHORS, France SUMMARY

U I. HVDC Control. LCC Reactive power characteristics

Lightning test in lab. Symmetrical fault and protection. Olof Samuelsson

Dynamic Model Of 400 Kv Line With Distance Relay. Director Research, The MRPC Company, Hyderabad, India 2

Sequence Networks p. 26 Sequence Network Connections and Voltages p. 27 Network Connections for Fault and General Unbalances p. 28 Sequence Network

PJM Manual 07:: PJM Protection Standards Revision: 2 Effective Date: July 1, 2016

Chapter # : 17 Symmetrical Fault Calculations

Transcription:

EH27401 Communication and Control in Electric Power Systems Lecture 2 Lars Nordström larsn@ics.kth.se 1

Course map 2

Outline 1. Power System Topologies Transmission Grids vs Distribution grids Radial grids vs Meshed grids Low Voltage feeders 2. Power System Apparatus & Models Line & Switchyard equipment Compensators 3. Substation Configurations Reliable switching configurations 3

Frequency Control 4

Tools for Voltage Control Main goal is to keep an even voltage profile. Generators with automatic voltage regulator (AVR) control voltage at generator bus Transformers with tapchanger. Step-wise control of voltage at one side Shunt reactors consume reactive power, which decreases the voltage Shunt capacitors produce reactive power, which increases the voltage Shunt compensation can be controlled manually (from the control room) with voltage automatic control with time control by a centralised logic 5

Voltage Control Hierarchy 6

Transmission Grids 7

Meshed MV Grid 8

LV Feeders 9

Distribution Networks Design of Distribution Network varies significantly depending on: Type of area(s) served Voltage levels Type of overlying network Overhead or underground networks Sizing of Distribution substations Required performance of the network Projected load growth Losses Historical/Cultural factors Cost of installation Cost of ownership 10

Selection of Voltage level What are the determining factors? High voltage Low losses Low voltage Less insulation problems, smaller equipment Other factors Already installed equipment Availability of spare parts, price, Overlying network Distances 0,4 1 3,3 6 10 11 20 25 33 11

Simple design example Assume 1600 loads Located 40*40 Each at S = 5 kva Equidistant 25 m 12

Small Distribution transformer Assume 25 kva trafo 5 Loads per transformer 320 substations MV substation in center 2 MVA per feeder 80 substations per feeder 13

Larger Distribution transformer Assume 125 kva trafo 25 Loads per transformer 64 substations MV substation in center 2 MVA per feeder 16 substations per feeder Etc.. 14

Adding some economic data Trafo Rating (kva) Number LV length (km) MV length (km) OH $/kva Cable $/kva 25 320 32 9,7 128 670 125 64 38,4 8,9 80 338 250 32 39,2 5,1 68 275 500 16 39,6 4,5 77 248 1000 8 52 3,5 79 294 Assuming some typical budget figures for MV & LV cables MV & LV OH lines Distribution Transformers Example courtesy of Control & Automation of Electric Power Distribution Networks J Northcote-Green. 15

Additional concerns In addition to cost of building and operating the distribution network, the reliability of the network is essential. A number of indices are used to determine the quality of service delivered. Additionally, regulators specify levels of quality and or cost caps that the distribution company must follow or be fined. 16

System Performance Indices SAIDI System Average Interruption Duration Index Sum of all customer interruption durations Total number of customers SAIFI System Average Frequency of Interruption Index Total number of customer interruptions Total number of customers 17

Customer Performance Indices CAIDI Customer Average Duration of Interruption Index Sum of all customer interruption durations Total number of interruptions CAIFI Customer Average Interruption Frequency Index Total number of interruptions Number of customers that have experienced an interruption CTAIDI Customer Total Average Interruption Duration Index Sum of all customer interruption durations Number of customer that have experienced an interruption 18

Some typical data (US) Source: APPA 2003: Distribution System Reliability & Operations Survey 19

Main challenge for DSOs Designing and operating a distribution network at low cost while maintaining high level of reliability 20

Underground distribution net Radial Feeder A fault disconnects entire feeder at CB 21

Underground distribution net Open loop feeders At fault, service can be restored by closing NOP. (Normally open point) 22

Underground distribution net Closed loop feeders At fault, CBs disconnect at both sides of fault. 23

Typical Overhead network CBs with Auto reclosers Radial Feeder A fault disconnects entire feeder at CB 24

Typical Overhead network Open loop Feeder A fault disconnects entire feeder at CB Supply is restored by closing NOP 25

Typical Overhead network Open loop with spurs Combination of the previous designs 26

Outline 1. Power System Topologies Transmission Grids vs Distribution grids Radial grids vs Meshed grids Low Voltage feeders 2. Power System Apparatus & Models Line & Switchyard equipment Compensators 3. Substation Configurations Reliable switching configurations 27

AC Power line Three phase AC Transfers energy with low losses Voltage levels from 0,4kV to 400 kv(+) 28

PI model of Lines Short line models Medium line models Long line models Line parameters (Y,R,X) vary with line type 29

Power Transformer Transfers energy between different voltage level Higher voltages are single pole Can shift phase angles 30

Tap changer 31

Power System models 32

Series capacitor Compensates for inductance in long power lines Connected manually/mechanically 33

Shunt capacitors Compensates for inductive loads by drawing leading current 34

Shunt Reactance Consumes reactive power Compensates for shunt capacitances in long power lines 35

Disconnectors Disconnects equipment Cannot break load currents 36

Circuit Breakers Basic types divided according to how the arc is extinguished Vaccum insulated Gas insulated (SF6) Oil insulated Air insulated 37

HVDC link Direct Current Rectifier stations convert to/from AC Controllable energy transfer with low losses No reactive components 38

SVC Shunt capacitor with greater controlability Capacitor banks in parallell with tyristor controlled inductance Part of the FACTS concept 39

TCSC Thyristor controlled series capacitor Series capacitor with greater controllability Series capacitor in parallel with inductance Part of the FACTS concept 40

Outline 1. Power System Topologies Transmission Grids vs Distribution grids Radial grids vs Meshed grids Low Voltage feeders 2. Power System Apparatus & Models Line & Switchyard equipment Compensators Generating equipment 3. Substation Configurations Reliable switching configurations 41

Transmission Substation Open air, vaccum insultated Gas Insulated 42

Distribution Substation 10-25 kv range Equipment housed in compartments Separate compartments for Disconnector Breaker Feeder Measurement 43

44

Evaluation Criteria Reliability Operation Flexibility Maintenance Flexibility Costs 45

Single Bus Configuration 46

Sectionalised Bus 47

Main & Transfer Bus Advantages: Maintain service and protection during circuit breaker maintenance Reasonable in cost Fairly small land area Easily expandable Disadvantages: Additional circuit breaker needed for bus tie Protection and relaying may become complicated Bus fault causes loss of the entire substation 48

Ring bus configuration Advantages: Flexible operation High reliability Double feed to each circuit No main buses Expandable to breaker-and-ahalf configuration Isolation of bus sections and circuit breakers for maintenance without circuit disruption Ring Bus Disadvantages: During fault, splitting of the ring may leave undesirable circuit combinations Each circuit has to have its own potential source for relaying Usually limited to 4 circuit positions, although larger sizes up to 10 are in service. 6 is usually the maximum terminals for a ring bus 49

Breaker & a half configuration 50

Double breaker 51