Partial Discharge Inception and Propagation Characteristics of Magnet Wire for Inverter-fed Motor under Surge Voltage Application

Similar documents
Estimation of Partial Discharge Inception Voltage of Magnet Wires under Inverter Surge Voltage by Volume-Time Theory

This is an author-deposited version published in : Eprints ID : 18192

THE PROPAGATION OF PARTIAL DISCHARGE PULSES IN A HIGH VOLTAGE CABLE

Prediction of Transient Transfer Functions at Cable-Transformer Interfaces

CHAPTER 2. v-t CHARACTERISTICS FOR STANDARD IMPULSE VOLTAGES

SURFACE CORONA INCEPTION ON STRESS GRADING SYSTEM IN END-TURN REGIONS OF ROTATING MACHINES

CHAPTER 5 CONCEPT OF PD SIGNAL AND PRPD PATTERN

LOW VOLTAGE PWM INVERTER-FED MOTOR INSULATION ISSUES

The University of New South Wales. School of Electrical Engineering and Telecommunications. High Voltage Systems ELEC9712. Appendix Partial Discharge

Testing and PD Diagnosis of MV Cable Systems with DAC Voltage Educational Session May St Pete Beach, Fl

OPTICAL EMISSION CHARACTERISTICS OF HELIUM BREAKDOWN AT PARTIAL VACUUM FOR POINT TO PLANE GEOMETRY

Design and Construction of a150kv/300a/1µs Blumlein Pulser

Visualization of the Ionization Phenomenon in Porous Materials under Lightning Impulse

Breakdown in short rod-plane air gaps under positive lightning impulse stress

Effect of Shielded Distribution Cable on Very Fast Transients

USING DAMPED AC VOLTAGES

Characteristics of Insulation Diagnosis and Failure in Gas Turbine Generator Stator Windings

Type Test of a 145 kv Termination Type TS 145-II

Electrical Power Engineering Group, School of Electronics and Computer Science, University of Southampton, Highfield, Southampton, SO17 1BJ, UK 2

Strathprints Institutional Repository

Investigation of PD Detection on XLPE Cables

Generation of Sub-nanosecond Pulses

PWM Control Method for NPC Inverters. with Very Small DC-Link Capacitors

Partial Discharge Patterns in High Voltage Insulation

EFFECT OF INTEGRATION ERROR ON PARTIAL DISCHARGE MEASUREMENTS ON CAST RESIN TRANSFORMERS. C. Ceretta, R. Gobbo, G. Pesavento

Accurate Modeling of Core-Type Distribution Transformers for Electromagnetic Transient Studies

Basics of Partial Discharge. Prepared for 2015 Phenix RSM Meeting January 2015

BY JASON SOUCHAK, Megger

The Nottingham eprints service makes this work by researchers of the University of Nottingham available open access under the following conditions.

IEEE TRANSACTIONS ON POWER ELECTRONICS, VOL. 21, NO. 1, JANUARY

Measurement of Surge Propagation in Induction Machines

Power Electronics. Exercise: Circuit Feedback

Proposal of double voltage transmission line pulse generator using four coaxial cables

VSD cables in. Working with. industrial & automation applications

Partial Discharge Analysis of a Solid Dielectric Using MATLAB Simulink

CHAPTER 1 INTRODUCTION

Analysis by Simulation of the Over-voltages in PWM-Inverter Fed Induction Motors

6. du/dt-effects in inverter-fed machines

L. B. Gordon Space Power Institute 231 Leach Center Auburn University, Alabama 36849

Investi ations Into the Use of Temperature Detectors as # tator Winding Partial Discharge Detectors

Experimental Challenges when Measuring Partial Discharges under Combined DC and High Frequency AC Voltage

PULSED BREAKDOWN CHARACTERISTICS OF HELIUM IN PARTIAL VACUUM IN KHZ RANGE

Lecture 36 Measurements of High Voltages (cont) (Refer Slide Time: 00:14)

This is an author-deposited version published in : Eprints ID : 18223

Partial Discharge Theory, Modeling and Applications To Electrical Machines

Extended analysis versus frequency of partial discharges phenomena, in support of quality assessment of insulating systems

6 - Stage Marx Generator

Investigations on a Combined Resonance/VLF HV Test System Partial Discharge (PD) characteristics at VLF and DAC voltages

CONDITION ASSESSMENT OF XLPE MV CABLE JOINTS BY USING AN INSULATION TESTER

Transformer Factory Testing

ON THE IGNITION VOLTAGE AND STRUCTURE OF COPLANAR BARRIER DISCHARGES

3 THE REVIEW OF DISSERTATION

Electric Stresses on Surge Arrester Insulation under Standard and

CO 2 Circuit Breaker Arc Model for EMTP Simulation of SLF Interrupting Performance

OFFLINE PD DIAGNOSTICS USING SEVERAL EXCITATION VOLTAGES

Effect of Shielded Distribution Cables on Lightning-Induced Overvoltages in a Distribution System

Product Application Note

Application Note. Motor Bearing Current Phenomenon. Rev: Doc#: AN.AFD.17 Yaskawa Electric America, Inc August 7, /9

AN electromagnetic launcher system can accelerate a projectile

Oscilloscope Applications MREC Rural Energy Conference 2012 Prepared by Paul Ortmann, P.E. /

Increasing Accuracy of Winding Insulation State Indicator of Three Phase Inverter-fed Machines using Two Current Sensors only

Power Engineering II. High Voltage Testing

Pre location: Impulse-Current-Method (ICE)

A Study on Partial Discharge Phenomena of Winding Wires

2012 IEEE. Personal use of this material is permitted. Permission from

Measurement and Analysis for Switchmode Power Design

A Reflectometer for Cable Fault Location with Multiple Pulse Reflection Method

NOVEL METHOD FOR ON-SITE TESTING AND DIAGNOSIS OF TRANSMISSION CABELS UP TO 250KV

DIELECTRIC HEATING IN INSULATING MATERIALS AT HIGH DC AND AC VOLTAGES SUPERIMPOSED BY HIGH FREQUENCY HIGH VOLTAGES

HVDC Transmission. Michael Muhr. Institute of High Voltage Engineering and System Performance Graz University of Technology Austria P A S S I O N

IEEE Transactions on Power Delivery. 15(2) P.467-P

CVVOZE Power Laboratories (CVVOZEPowerLab)

Measurement and reduction of EMI radiated by a PWM inverter-fed AC motor drive system

A Neuro-Fuzzy Approach for the Detection of Partial Discharge

Partial Discharge Signal Detection by Piezoelectric Ceramic Sensor and The Signal Processing

Research Article A Simplified High Frequency Model of Interleaved Transformer Winding

Design and construction of double-blumlein HV pulse power supply

Alternative Coupling Method for Immunity Testing of Power Grid Protection Equipment

9. How is an electric field is measured?

HV AC TESTING OF SUPER-LONG CABLES

INVESTIGATION OF PULSED MICRO-DISCHARGES AND OZONE PRODUCTION BY DIELECTRIC BARRIER DISCHARGES

Modeling and Analysis of Common-Mode Voltages Generated in Medium Voltage PWM-CSI Drives

> Introduction. > What is a partial discharge?

U.S. Government work not protected by U.S. copyright

Performance Analysis of Single Phase Induction Motor Coated with Al 2 O 3 Nano Filler Mixed Enamel

High-Voltage Test Techniques

IN THE high power isolated dc/dc applications, full bridge

EXPERIMENTAL INVESTIGATION OF A TRANSIENT INDUCED VOLTAGE TO AN OVERHEAD CONTROL CABLE FROM A GROUNDING CIRCUIT

PIEZOELECTRIC TRANSFORMER FOR INTEGRATED MOSFET AND IGBT GATE DRIVER

HV Module Systems for Testing, Training and Research

Testing 320 kv HVDC XLPE Cable System

Sources of transient electromagnetic disturbance in medium voltage switchgear

High Voltage Engineering

Long lengths transmission power cables on-site testing up to 500 kv by damped AC voltages

A Study of Medium and High Voltage Form-Wound Coil Turn-to-Turn Insulation of Converter Fed Rotating Machines

A New Soft Recovery PWM Quasi-Resonant Converter With a Folding Snubber Network

FAULT IDENTIFICATION IN TRANSFORMER WINDING

LM78S40 Switching Voltage Regulator Applications

UNIT 4 PRINCIPLES OF CIRCUIT BREAKERS SVCET

2006 2nd International Conference on Power Electronics Systems and Applications

Transcription:

IEEE Transactions on Dielectrics and Electrical Insulation Vol. 14, No. 1; February 27 39 Partial Discharge Inception and Propagation Characteristics of Magnet Wire for Inverter-fed Motor under Surge Voltage Application Naoki Hayakawa, Masato Morikawa Department of Electrical Engineering and Computer Science Nagoya University Furo-cho, Chikusa-ku, Nagoya, 464-863, Japan and Hitoshi Okubo EcoTopia Science Institute Nagoya University Furo-cho, Chikusa-ku, Nagoya, 464-863, Japan ABSTRACT In inverter-fed motor coils, surge voltages with the rise time of several tens or hundreds of nano-second may cause partial discharge (PD) and degradation of electrical insulation performance of the inverter-fed motor coils. This paper discusses PD inception characteristics as well as PD propagation characteristics after PD inception for magnet wire of inverter-fed motor under surge voltage application. Experimental results firstly revealed that PD inception voltage (PDIV) decreased with the increase in the length of enamel-coated wire, which was evaluated in terms of the stressed wire contact length under surge voltage application, i.e. size effect. We proposed a regression line for the size effect on PDIV for the electrical insulation design of inverter-fed motor coils. Secondly, PD propagation characteristics were also investigated under the higher voltage application, and their mechanisms were discussed in terms of generation probability of initial electrons, space charge behavior in the wedge-shaped air gap, charging on the enamel surface and so on. Index Terms Inverter-fed motor, inverter surge, partial discharge, inception voltage, initial electron, charge behavior. 1 INTRODUCTION THE operating voltage of inverter-fed motors is being increased for higher performance, e.g., higher power output and compactness. Inverter-fed motors utilize power electronic devices such as IGBTs with high-speed switching ability, and they are exposed to transient surge voltage, so called inverter surge. Inverter surge with the rise time of several tens or hundreds of nano-second in inverter-fed motor coils may cause partial discharge (PD) and degradation of electrical insulation performance. Therefore, rational electrical insulation design and evaluation techniques for the inverterfed motors are strongly required, which should take account of the PD mechanisms under surge voltage application [1-4]. From the above background, we have been investigating the Manuscript received on 2 February 26, in final form 26 July 26. PD inception characteristics as well as PD propagation characteristics after PD inception for inverter-fed motor coil samples under surge voltage application [5-7]. In this paper, we focused on the PD inception voltages (PDIV) of inverterfed motor coil samples with different lengths of enamelcoated wire under surge and ac voltage application. Together with the dependence of PDIV on the repetition rate and polarity reversal of the applied surge voltage, PD inception mechanisms under surge voltage application were discussed and compared with those under ac voltage application. Moreover, focusing on the PD propagation after PD inception, we measured the transition of number of PD generation, PD light pulses and PD light emission images under different surge voltages higher than PDIV. These PD propagation characteristics were discussed from the viewpoint of charge behavior in the wedge-shaped air gap and on the enamel surface. 17-9878/7/$25. 27 IEEE

4 N. Hayakawa et al.: Partial Discharge Inception and Propagation Characteristics of Magnet Wire for Inverter-fed Motor 2 EXPERIMENTAL SETUP AND PROCEDURE 2.1 EXPERIMENTAL SETUP FOR PD INCEPTION CHARACTERISTICS Figure 1 shows test samples used in this experiment: (a) twisted pair samples and (b) coil samples. Each sample was composed of two enamel-coated copper wires. The conductor diameter is.845 mm, the coated thickness is.3 mm (polyester imide:.23 mm, polyamide imide:.7 mm) and the dielectric constant is 3.85. The twisted pitch and length of the twisted pair samples are 7 mm and 13 mm, respectively. On the other hand, the coil samples were used as an intermediate model between the simplified twisted pair and the actual motor winding such as a random wound motor. In the coil samples, two enamel-coated copper wires were wound in parallel on 1 layer around a PMMA cylinder with the diameter of 5 mm. The turn numbers of the coil samples are 1, 5, 1, 2, 4, 1 and 2, respectively. Figure 2 shows the relationship between the turn number and the wire contact length of the coil samples. The wire contact length of the coil samples is confirmed to be proportional to the turn number. The capacitance of the coil samples is also proportional to the wire contact length, i.e. turn number. The experimental setup for the measurement of PD characteristics of the test samples is shown in Figure 3. For both twisted pair and coil samples, after surface cleaning by alcohol, one of the copper wires was grounded, and surge or (a) Twisted pair Wire contact length [m] 8 6 4 2 (b) Coil samples Figure 1. Test samples. 5 1 15 2 25 Turn number [turn] Figure 2. Relationship between turn number and wire contact length of coil samples. HV PMMA cylinder (φ5mm) ac H.V. generator or Surge H.V. generator Oscilloscope (1GHz, 5GS/s) Voltage divider C CT2 Test sample CT1 Image intensifier P.M.T. PMT Still camera High frequency CT (1GHz) Figure 3. Experimental setup for PD inception characteristics. ac high voltage was applied to the other wire. A complementary capacitor with capacitance C was connected in parallel with the test samples. By arranging the value of C for each test sample, the total capacitance C Total of the test sample and the complementary capacitor was set at around 6, pf or 1, pf, which enabled us to control the rise time t r of the applied surge voltage within 45 ns to 6 ns (average t r =52 ns) for C Total =6, pf or within 7 ns to 9 ns (average t r =83 ns) for C Total =1, pf. The repetition rate of the surge voltage f was within 6 pps (pulse per second) to 6 pps. Single shot, positive or negative shot of the surge voltage were also possible. The time width of the single shot was 1 μs. The frequency of ac voltage was 6 Hz. PD measurement with current pulse detection by CT under surge voltage is generally difficult because of a large charging current due to steep wavefront of the applied surge voltage. Thus, optical PD measurement by photo multiplier tube (PMT) is often used under surge voltage application. Thus, in this paper, PDIV of the test samples was measured by PMT under both surge and ac voltage applications. PD light emission images were also taken by a still camera through an image intensifier (I.I.) with setting the exposure time to 5 s. We also measured the PD current pulse signal under ac voltage application through high frequency CT (1 GHz); CT1 for the test sample and CT2 for the complementary capacitor. According to our previous research using twisted pair [5], PDIV measured by PMT was at most 5 % higher than that by CT with the PD detection sensitivity of about 1 pc, which may be attributed to the invisible PD in the blind region of test sample. Environmental conditions such as temperature, pressure and humidity were controlled in the shielding room with air conditioning. 2.2 EXPERIMENTAL SETUP FOR TRANSITION OF PD CHARACTERISTICS Figure 4 shows the experimental setup for the measurement of PD propagation characteristics of a twisted pair sample with the same specification as those in 2.1. On the other hand, the inverter surge generation circuit is different from that in 2.1, which consists of dc high voltage supply, high voltage semiconductor switch, pulse generator and coaxial cable. It can generate damped oscillating surge voltages with flexible surge parameters such as peak value, rise time, pulse width,

IEEE Transactions on Dielectrics and Electrical Insulation Vol. 14, No. 1; February 27 41 Figure 4. Experimental setup and measurement system for transition of PD characteristics. repetition rate and polarity. In this experiment, the peak value V a was ~ 171 V peak, t r =12 ns, the pulse width was 1 μs and f=1 pps, respectively. PDIV was measured by PMT, and a still camera through an I.I. also took PD light emission images. The detected PD light intensity signals were recorded by an oscilloscope (2.5 GHz, 2 GS/s, 64 MWord) and analyzed by the partial discharge current pulse waveform analysis (PD-CPWA) method [8]. PD-CPWA is a PD detection/analysis system developed for the purpose of pursuing the transition of PD current pulse waveforms, and it was applied to PD light intensity waveforms by PMT in this experiment. PDIV was defined as the peak value of the applied voltage, and converted into the value at the standard atmospheric condition (2 C,.1 MPa). 3 PD INCEPTION CHARACTERISTICS 3.1 PD GENERATION CHARACTERISTICS Typical PD light intensity and applied voltage waveforms at PD inception are shown in Figure 5 under (a) surge voltage application (t r =52 ns, f=6 pps, positive polarity) and (b) ac voltage application (6 Hz), respectively, for the 1 turn coil sample. The surge PDIV was 178 V peak and the ac PDIV was 716 V peak, respectively. In both figures, PD signal was detected at around the peak of the applied voltage waveform. Figure 6 shows (a) a picture of 2 turn coil sample and (b) PD light emission image at V a =14 V peak under surge voltage application (t r =52 ns, f=6 pps, positive polarity). Using mirrors at left and right back of the coil sample, as shown in Figure 6a, PD light emission image at any location of the sample could be observed. PD light emission image was so faint at around PDIV (=1276 V peak ). With the increase in V a, the PD light emission image became clear and was found to be spread over the whole surface of the coil sample in Figure 6b. Thus, PD phenomena of inverter-fed motor coil samples under surge voltage application could be verified, located and visualized as a light emission image by the optical PD measurement technique. 3.2 SIZE EFFECT ON PD INCEPTION VOLTAGE PDIV of twisted pair and coil samples under surge voltage application (f=6 pps, positive and negative polarity) are shown in Figure 7, where the history of PDIV for sequential (a) Surge voltage (t r =52 ns, f=6 pps, positive polarity) (b) ac voltage (6Hz) Figure 5. Applied surge voltage and PD light intensity waveforms (1 turn coil sample). Left back Front Right back (a) Picture of 2 turn coil sample Left back Front Right back (b) PD light emission image at V a =14V peak Figure 6. Surge PD light emission images (2 turn coil sample, t r =52 ns, f=6 pps, positive polarity).

42 N. Hayakawa et al.: Partial Discharge Inception and Propagation Characteristics of Magnet Wire for Inverter-fed Motor 2 18 16 Surge (Positive, single) Surge (Positive, 6pps) Surge (Positive-Negative, 5sec interval) ac 14 PDIV [V peak ] 12 1 Figure 7. Surge PDIV for different test samples (t r=52 ns, f=6 pps). shots of measurements is designated for each sample. PDIV decreased with the increase in the turn number of the coil samples, i.e. wire contact length. There existed a small conditioning effect and no polarity effect in PDIV. Then, the last 5 PDIVs which seem to be stable in 15 measurements will be taken for the evaluation and analysis of PDIV, hereinafter. Figure 8 shows surge PDIV for (a) t r =52 ns, (b) t r =83 ns and ac PDIV as a function of wire contact length. Each figure represents the average value and the standard deviation of PDIV under different voltage applications. In the case of repetitive positive-negative surge voltage application, the time interval of surge application was 5 s. In each case, PDIV decreased with the increase in the wire contact length. For example, PDIV of 1 turn coil decreased into 85 % of PDIV of 1 turn coil under surge (positive, single) voltage application. Such a decrease in PDIV with the increase in the stressed length, area or volume is generally referred to as the size effect. The PD threshold behavior on the size effect is attributed to the increase in the initial electrons in the wedgeshaped air gap between enamel-coated copper conductors as well as on the enamel surface. With the increase in the turn number of coil samples, i.e. stressed wire contact length, the generation probability of initial electrons would be increased, and then PDIV could be decreased. In order to quantitatively evaluate the size effect, the regression lines in Figure 8 for the coil samples were expressed by the following equation (1): 1 B PDIV = A λ (1) where A and B are constants, and λ is the wire contact length. Table 1 summarizes the values of A and B under different voltage conditions. PDIV decreased with the increase in λ, repetition rate of surge voltage application and polarity reversal. The surge PDIV (f=6 pps) normalized by ac PDIV (6 Hz), referred to as the impulse ratio, was 1.4 to 2.. The impulse ratio for t r =83 ns tended to decrease with the increase in λ; which means that the generation probability of initial electrons would increase under the longer contact length of stressed wire or the larger volume of wedge-shaped air gap between the enamel-coated copper conductors. PDIV [V peak ] 8 6 2 18 16 14 12 1 8 6.1 1 1 1 Wire contact length λ [m] (a) t r=52 ns (C Total=6, pf).1 1 1 1 Wire contact length λ [m] (b) t r=83 ns (C Total=1, pf) Figure 8. PDIV as a function of wire contact length λ. Table 1. Constant A and B under different voltage applications. C total t r =52ns t r =83ns A B A B Surge (Positive, single) 125 26.5 1375 21. Surge (Positive, 6pps) 1118 4.5 1392 17.8 Surge (Positive-Negative) 965 25.4 967 24.5 ac 79 33.3 829 77.9 In addition, PDIV for t r =52 ns was lower than that for t r =83 ns. Thus, PDIV would be influenced not only by the rise time of the applied surge voltage, but also by the other factors on surge voltage waveform. Furthermore, the surge PDIV at the polarity reversal was lower than those for single

IEEE Transactions on Dielectrics and Electrical Insulation Vol. 14, No. 1; February 27 43 shot or repetitive shot with an identical polarity. This may suggest the possibility of charge generation at the applied surge voltage lower than PDIV. 4 PD PROPAGATION CHARACTERISTICS 4.1 TRANSITION OF PD CHARACTERISTICS In this section, PD propagation characteristics after PD inception are discussed using a twisted pair sample. Figure 9 shows typical applied surge voltage and PD light intensity waveforms at V a =15 V peak under repetitive surge voltage application (t r =12 ns, f=1 pps). PDs were usually generated at both the instant of rise and fall time regions of surge voltage waveform. The PDIV was obtained as 117 V peak for the twisted pair sample used in this experiment. Figure 1 shows the transition of peak value of PD light intensity for different applied voltages higher than PDIV (positive polarity, f=1 pps) for the twisted pair sample with PDIV=117 V peak. PD generation was intermittent in Figures 1a (V a =117 V peak =PDIV) and 1b (V a =13 V peak =1.11 PDIV) and became continuous with the larger intensity in Figure 1c (V a =171 V peak =1.46 PDIV) with the higher V a. The number of PD generation in Figure 1c reached 2/s, which means that PD was generated 2 times in each voltage application of f=1 pps, as was shown in 4. 3. 2. 1. 4. 3. 2. 1. 4. 3. 2. 1..2.4.6.8 (a) V a =117 V peak (PDIV, Upward).2.4.6.8 (b) V a =13 V peak (1.11 PDIV, Upward).2.4.6.8 1. 1. 1. Time [2μs/div] 4. 3. 2. 1. (c) V a =171 V peak (1.46 PDIV, Downward).2.4.6.8 1. 4. 3. 2. 1. (d) V a =13 V peak (1.11 PDIV, Downward).2.4.6.8 1. Time [2ns/div] (e) V a =117 V peak (PDIV, Downward) Figure 9. Applied surge voltage and PD light intensity waveforms for the twisted pair sample (t r =12 ns, f=1 pps). Figure 1. Transition of PD light intensity as a function of voltage enhancement and reduction (Twisted pair sample, t r =12 ns, f=1 pps).

44 N. Hayakawa et al.: Partial Discharge Inception and Propagation Characteristics of Magnet Wire for Inverter-fed Motor Figure 9. In the downward process of V a in Figure 1d (V a =13 V peak =1.11 PDIV), PD generation was still continuous with 2 pps, in spite of the same V a as in Figure 1b, and became intermittent with the smaller intensity in Number of PD generation [pps] 25 2 15 1 5 1 Downward PDEV PDIV Upward 12 14 16 Applied voltage V a [V peak ] 18 Figure 11. Transition of number of PD generation as a function of applied voltage (Twisted pair sample, t r =12 ns, f=1 pps) 3. 2.5 2. 1.5 1..5 1 Upward 12 14 Downward 16 Applied voltage V a [V peak ] Figure 12. Transition of PD light intensity as a function of applied voltage (Twisted pair sample, t r =12 ns, f=1 pps) 18 Figure 1e (V a =117 V peak =PDIV). PD extinction voltage (PDEV) was 18 V peak lower than PDIV (117 V peak ). Figure 11 and 12 summarize the transition of the number of PD generation and PD light intensity, respectively, as a function of applied voltage. The number of PD generation in Figure 11 clearly shows the hysteresis characteristics. PD light intensity in Figure 12 also shows the hysteresis characteristics, where the intensity in the downward process was smaller than that in the upward process. These results mean that in the downward process of V a, smaller PD was frequently generated compared with that in the upward process. Figure 13 shows the PD light emission images at (b) V a =13 V peak (1.11 PDIV, upward), (c) V a =171 V peak (1.46 PDIV, upward), (d) V a =13 V peak (1.11 PDIV, downward) and (e) V a =117 V peak (PDIV, downward). PD light emission at the both ends of the sample was stronger in the upward process (Figures 13b and 13c), whereas that in the middle area remained in the downward process (Figure 13e). 4.2 DISCUSSION OF PD GENERATION MECHANISMS From the above experimental results, PD generation mechanisms were discussed. PD characteristics can be classified into the following three regions: (1) V a =PDIV (2) PDIV < V a < 1.1 PDIV (3) V a >1.1 PDIV Here, 1.1 PDIV corresponds to the applied voltage, where the number of PD generation starts to increase distinctively, as shown in Figure 11. In the region (1), the generation probability of initial electrons would be low, because the time exposed to high electric field stress for the small wedge-shaped air gap was short under the damped oscillating surge voltage. For this reason, PD generation was unstable, as shown in Figure 1a. In the region (2), positive ions, negative ions and electrons would already exist by repetitive PDs at the higher applied voltage. Therefore, the number of PD generation would increase gradually by the initial electrons originated from negative ions and electrons. However, PD generation was still intermittent, as shown in Figure 1b, because the time (a) Twisted pair sample (b) V a =13 V peak (1.11 PDIV, Upward) (c) V a =171 V peak (1.46 PDIV, Upward) (d) V a =13V peak (1.11 PDIV, Downward) Figure 13. Transition of PD light emission images (Twisted pair sample, t r =12 ns, f=1 pps). (e) V a =117V peak (PDIV, Downward)

IEEE Transactions on Dielectrics and Electrical Insulation Vol. 14, No. 1; February 27 45 exposed to high electric field stress for the wedge-shaped air gap was still as short as several hundreds of nano-second under the damped oscillating surge voltage. On the other hand, in the region (3), the generation probability of initial electrons for several hundreds of nanosecond would increase sufficiently, because the electric field stress in the wedge-shaped air gap is high enough in such a high voltage region. The charge density and distribution in the wedge-shaped air gap and on the enamel surface can also affect the successive PD generation and its magnitude, which would bring about the hysteresis characteristics and the scattering of PD light intensity, as shown in Figures 1 to 12. PD could be generated at both the instant of rise and fall time regions of surge voltage waveform because of the charge behavior in the wedge-shaped air gap, and then the number of PD generation reached 2 pps. 5 CONCLUSIONS PD inception characteristics and PD propagation characteristics after PD inception for twisted pair and coil samples under surge voltage application were obtained and quantitatively evaluated. The main results are summarized as follows: (1) PDIV decreased with the increase in the wire length, which was evaluated in terms of the stressed wire contact length, i.e. size effect. (2) The regression lines for the size effect on PDIV were quantitatively evaluated and expressed in the form of PDIV=A λ -1/B, where A and B are constants and λ is the wire contact length. (3) PDs under repetitive surge voltage application were usually generated at both the instant of rise and fall time regions of surge voltage waveform. (4) Number of PD generation increased with the increase in the applied voltage under repetitive surge voltage application. Number of PD generation and PD light intensity exhibited hysteresis characteristics. (5) PD generation mechanisms were discussed from the viewpoint of the charge behavior in the wedge-shaped air gap and on the enamel surface. REFERENCES [1] M. Kaufhold, Stress Related Challenges of Converter Fed Drives Survey of Requirements, Concepts and Strategies, INSUCON, pp. 131-136, 22. [2] S. Grzybowski and N. P. Kota, Lifetime Characteristics of Magnet Wires under Multistress Conditions, IEEE CEIDP, pp. 65-68, 25. [3] K. Bauer, M. Kaufhold, A. Maeurer and K. Schaefer, Machine Insulation for Converter Fed Low Voltage Drive Systems- Requirements and Design, INSUCON, pp. 362-366, 22. [4] D. Fabiani, G. C. Montanari, A. Cavallini and G. Mazzanti, Relation Between Space Charge Accumulation and Partial Discharge Activity in Enameled Wires Under PWM-like Voltage Waveforms, IEEE Trans. Dielectr. Electr. Insul., Vol. 11, pp. 393-45, 24. [5] N. Hayakawa and H. Okubo, Partial Discharge Characteristics of Inverter-Fed Motor Coil Samples under AC and Surge Voltage Conditions, IEEE Elect. Insul. Mag., Vol. 21, No. 1, pp. 5-1, 25. [6] M. Morikawa, N. Hayakawa and H. Okubo, Partial Discharge Inception and Degradation Characteristics of Inverter-Fed Motor Sample under Surge Voltage Condition, IEEE CEIDP, pp. 426-429, 25. [7] H. Okubo, Y. Lu, M. Morikawa and N. Hayakawa, Partial Discharge Inception Characteristics Influenced by Stressed Wire Length of Inverter-Fed Motor, IEEE CEIDP, pp. 442-445, 24. [8] H. Okubo, N. Hayakawa, A Novel Technique for Partial Discharge and Breakdown Investigation Based on Current Pulse Waveform Analysis, IEEE Trans. Dielectr. Electr. Insul., Vol. 12, pp. 736-744, 25. Naoki Hayakawa (M 9) was born on 9 September 1962. He received the Ph.D. degree in 1991 in electrical engineering from Nagoya University. Since 199, he has been at Nagoya University and presently he is an Associate Professor of Nagoya University at the Department of Electrical Engineering and Computer Science. From 21 to 22, he was a guest scientist at the Forschungszentrum Karlsruhe /Germany. He is a member of IEEE and IEE of Japan. Masato Morikawa was born on 17 March 1982. He received the B.S. degree in 24 in electrical engineering from Nagoya University. Currently, he is a Master Course student at Nagoya University in the Department of Electrical Engineering and Computer Science. Hitoshi Okubo (M 81) was born on 29 October 1948. He received the Ph.D. degree in 1984 in electrical engineering from Nagoya University. He joined Toshiba Corporation, Japan in 1973 and was a Manager of HV laboratory of Toshiba. From 1976 to 1978, he was at the RWTH Aachen, Germany and the TU Munich, Germany. In 1989 he was an Associate Professor and presently he is a Professor at Nagoya University in the EcoTopia Science Institute. He is a member of IEEE, IEE of Japan, VDE and CIGRE.