Transformer Design: Economics & Reliability

Similar documents
Transformer Winding Design. The Design and Performance of Circular Disc, Helical and Layer Windings for Power Transformer Applications

Regional Technical Seminar SHORT CIRCUIT FORCES

Regional Technical Seminar SHORT CIRCUIT FORCES

Transformer Factory Testing

Hands-On Transformer Testing and Maintenance

Power Transformers Basics

POWER TRANSFORMER SPECIFICATION, DESIGN, QUALITY CONTROL AND TESTING 18 MARCH 2009

Western Mining Electric Association San Antonio TX Layer vs. Disk Windings Discussion NOVEMBER 15, SPX Transformer Solutions, Inc.

7. INSPECTION AND TEST PROCEDURES

KNOW MORE ABOUT THE TRANSFORMERS. Glossary Transformers

(2) New Standard IEEE P (3) Core : (4) Windings :

Basic Principles and Operation of Transformer

Transformer Protection

Transformer Technology Seminar What to consider at Design Reviews

Transformer Engineering

HOW TO SAFE GUARD THE TRANSFORMER..???

MGM Transformer. Vacuum Pressure Impregnated (VPI) Dry-Type Substation Transformer Specification Guide

Understanding and Extracting Valuable Information from Basic and Advanced Power Transformer Testing Techniques

CHAPTER 2 ELECTROMAGNETIC FORCE AND DEFORMATION

Electrical Design Process

CONTENTS. 1. Introduction Generating Stations 9 40

Tab 2 Voltage Stresses Switching Transients

FIELD ELECTRICAL TESTING SPX TRANSFORMER SOLUTIONS, INC.

Tertiary Winding Design in wye-wye Connected Transformers Restricted Siemens Energy 2013 All rights reserved.

PES & IAS NY Chapter And NY LMAG June 23 rd, 2015

Condition Assessment of High Voltage Insulation in Power System Equipment. R.E. James and Q. Su. The Institution of Engineering and Technology

Understanding the Value of Electrical Testing for Power Transformers. Charles Sweetser, OMICRON electronics Corp. USA

Understanding the Value of Electrical Testing for Power Transformers. Charles Sweetser - OMICRON

Siemens Transformer Technology Seminar Insulation & Thermal Design

DEFERRING REPLACEMENT OF A 600 MVA, 345GRD Y/138GRD Y/ 13.8 kv SHELL TYPE WESTINGHOUSE AUTOTRANSFORMER

RESIDUAL LIFE ASSESSMENT OF GENERATOR TRANSFORMERS IN OLD HYDRO POWER PLANTS

TRANSFORMER OPERATIONAL PRINCIPLES, SELECTION & TROUBLESHOOTING

Transformer Testing & Maintenance Fundamentals. AVO Training Institute, Inc. 2018

ABB Power Products Service

TABLE OF CONTENT

CASE STUDY- FAULT IN POWER TRANSFORMER AT LOKTAK POWER STATION. - S K Mishra & S K Das NHPC Ltd O&M Division

Training Fees 3,300$ per participant including Materials/Handouts, Tea/Coffee Refreshments & International Buffet Lunch.

Substation Preventive Maintenance

Chapter 7 Conclusion 7.1 General

Martin Stoessl R&D Manager Siemens Transformers Austria - Weiz

Monitoring Solutions For Power Transformers, Reactors, Bushings and Instrument Transformers

Transformer Protection Principles

EE 1402 HIGH VOLTAGE ENGINEERING

Transformer Thermal Impact Assessment White Paper Project (Geomagnetic Disturbance Mitigation)

Transformer Thermal Impact Assessment White Paper TPL Transmission System Planned Performance for Geomagnetic Disturbance Events

Transformer Thermal Impact Assessment White Paper (Draft) Project (Geomagnetic Disturbance Mitigation)

Phase Shifting Transformers. Presented by

Coil Products Beginnings 1960 State of the Art. Customer partnership around the globe. Continuous innovation since 1900

Benefits of SFRA - Case Studies

COPYRIGHTED MATERIAL. Index

Transformer Thermal Impact Assessment White Paper TPL Transmission System Planned Performance for Geomagnetic Disturbance Events

Protecting power transformers from common adverse conditions

Transformer Protection

Regional Technical Seminar

Effective maintenance test techniques for power transformers

Innovative Test Techniques and Diagnostic Measurements to Improve the Performance and Reliability of Power System Transformers

EFFECETIVE TRANSFORMER CONDITION ASSESSMENT

UBC Technical Guidelines Section Edition Medium-Voltage Transformers Page 1 of 5

Insulation Level and Test Technology of. 1000kV Power Transformer

Diagnostic testing of cast resin transformers

Schedule of Accreditation issued by United Kingdom Accreditation Service 2 Pine Trees, Chertsey Lane, Staines-upon-Thames, TW18 3HR, UK

Shunt Reactors. Global Top Energy, Machinery & Plant Solution Provider

Effective Maintenance Test Techniques and Diagnostic Measurements to Improve the Performance and Reliability of Power System Transformers

CHAPTER 3 REVIEW OF POWER TRANSFORMER PROTECTION SCHEMES

TPL is a new Reliability Standard to specifically address the Stage 2 directives in Order No. 779.

Power transformers for Network, Rectifiers, Furnace

HVDC Transmission. Michael Muhr. Institute of High Voltage Engineering and System Performance Graz University of Technology Austria P A S S I O N

Power System Protection. Dr. Lionel R. Orama Exclusa, PE Week 3

HIGH VOLTAGE CIRCUIT BREAKERS

Medium voltage circuit breaker technical guide

The NOVA Recloser shall be designed and tested in accordance with the following standards as applicable:

SERVICE OFFERINGS FOR POWER SYSTEM STUDY & CONDITION MONITORING FOR STATIC EQUIPMENT

DEVELOPMENT OF A TEST PROTOCOL FOR A 15 KV CLASS SOLID-STATE CURRENT LIMITER

Discipline Electrical Testing Issue Date Certificate Number T-2837 Valid Until Last Amended on - Page 1 of 6 LOCATION 1

The Reflective Wave Phenomena

TesTIng of Power. Transformers are the largest, most. feature. By brandon dupuis

ACS 1000 Transformer Failure Investigation. Nathan Schachter, Peng

TECHIMP Technologies & Services for Diagnostics and Monitoring of High Voltage Assets

MV ELECTRICAL TRANSMISSION DESIGN AND CONSTRUCTION STANDARD. PART 1: GENERAL 1.01 Transformer

IJSRD - International Journal for Scientific Research & Development Vol. 2, Issue 04, 2014 ISSN (online):

Effects of Harmonic Distortion I

Cholla T809 Condition Assessment Report Provided by students of Northern Arizona University with the support of Arizona Public Service

Insulation Co-ordination For HVDC Station

Problems connected with Commissioning of Power Transformers

WESTERN UNDERGROUND COMMITTEE GUIDE 2.6 (2.6/00/0868)

DATA SHEET FOR LIGHTING TRANSFORMER APPD. BY VDV PROJECT NO

Power Transformer Products & Services INCREASED PERFORMANCE & UPTIME

Arild Furnes,ATPA OGP/Petrobras workshop, Dry type transformers-ideal for FPSO - Transformers for electrical and drive systems

Evaluating the Response of Surge Arresters

Index. b back-flashover 245 biomass 207 breakers 74 buchholz protection 235 busbar sectionalizer 193 business enterprises 18

System Protection and Control Subcommittee

Modern transformer relays include a comprehensive set of protective elements to protect transformers from faults and abnormal operating conditions

FGJTCFWP"KPUVKVWVG"QH"VGEJPQNQI[" FGRCTVOGPV"QH"GNGEVTKECN"GPIKPGGTKPI" VGG"246"JKIJ"XQNVCIG"GPIKPGGTKPI

Mechanical Design. Brian Brinson Mechanical Design Manager.

Transformer Installation, Assembly & Testing

10. DISTURBANCE VOLTAGE WITHSTAND CAPABILITY

VariSTAR Type AZL heavy-duty distribution-class MOV arrester

UNIVERSITY OF MISSOURI Liquid-Filled Utility Transformers 2016 Q1

SPECIFICATION FOR STEP UP TRANSFORMER 0.415/11Kv and (630KVA & 1000KVA)

Transcription:

Transformer Design: Economics & Reliability Weidmann-ACTI Inc. Technical Conference New Diagnostic Concepts for Better Asset Management November 8 10, 2004 Holiday Inn Capitol Plaza, Sacramento, CA H. Jin Sim Waukesha Electric Systems

A lot of good information is provided for your information. We will cover just highlights today. Let s make this interactive! Please stop me and ask questions during the presentation if you have them.

Failure Survey Information From ANSI/IEEE C37.91, Table 1 Table 1 summarizes failure statistics for a broad range of transformer failure causes reported by a group of U.S. utilities over a period of years. Failures 1955-1965 1965-1982 1983-1988 Number % of Total Number % of Total Number % of Total Winding 134 51 615 55 144 37 Tap changer 49 19 231 21 85 22 Bushing 41 15 114 10 42 11 Terminal board 19 7 71 6 13 3 Core 7 3 24 2 4 1 Miscellaneous 12 5 72 6 101 26 Total 262 100 1127 100 389 100

Thermal Dielectric Mechanical Operation Issues for Reliability

Thermal Cooling Internal Cooling determines Watts/Sq. In Gradient Losses within the winding Surface area of windings exposed to the cooling oil Flow of the oil within the winding (Guided or natural) External Cooling determines Oil Temperature Rise Radiators Fans Pumps Other heat exchangers Ambient temperature Gradient plus Average Oil Temperature rise = Wdg. Temp. Rise Accurate Calculation and Proper Execution determines the ability of the Equipment s reliable operation

Thermal Hot-Spot Temperatures are calculated by using; Loss distribution Heat transfer Hot-Spot Temperatures determine; Rate of insulation aging Bubble formation (along with moisture content and gas saturation level) Maximum safe loading level

Example of Leakage Field Plot for Hot-spot Temperature Calc. 28 kv, 175.5 kv 28 kv, 195.5 kv 28 kv, 255.5 kv 28 kv, 235.5 kv

Result of the analysis indicating specific needs for improvements Hot-Spot Temperature @ 175.5 kv @ 195.5 kv @ 255.5 kv @ 235.5 kv Hottest Inner Winding 84.1 83.9 88.4 86.1 88.4 Winding 2 77.0 76.9 79.8 78.4 79.8 Winding 3 80.9 77.0 71.2 72.7 80.9 Winding 4 65.7 65.7 70.0 69.8 70.0 Outer Winding 65.4 65.6 69.5 66.2 69.5

Thermal (Cont.) Insulation Life (Based on Tensile Strength of Paper) 9.80 x 10-18 x EXP [15000/(θ H + 273)] Follows an adaptation of the Arrhenius reaction rate theory 6 C and 8 C rule (doubling of aging rates)

Thermal (Cont.) Normal Insulation Life for well-dried and oxygen-free insulation systems with the Hot-spot temperature maintained at 110 C (See table below) Many transformers last much longer than Normal life since the temperature does not stay this high constantly Basis 50 % retained Tensile Strength of Insulation (Former C57.92 Criterion) 25 % retained Tensile Strength of Insulation 200 retained DP in insulation Interpretation of Distribution Transformer Functional Life test data (Former C57.91 Criterion) Normal Insulation Life Hours Years 65,000 7.42 135,000 15.41 150,000 17.12 180,000 20.55

Thermal (Cont.) Standards and Specifications ONAN/ONAF/ONAF offers at least the base MVA with all external coolers out of service OFAF (Formerly FOA) does not have base rating If the unit is expected to be loaded beyond the maximum rating, specify the capability required with as much information as available Familiarize with the loading guide (such as IEEE C57.91) and manufacturer s instruction manual Specify maximum loading parameters (Top Oil and Hot-spot temperatures) if the industry guide is not suitable for your applications

Dielectric Tools used to analyze stresses and design margin FEA field plots Stressed oil volume theory Cumulative creep curve Volt-time curve Oil Duct theory

Dielectric (Cont.) FEA field plots used to develop minimum clearances Minimum Design Margin is acceptable!

Dielectric (Cont.) Major insulation design

Dielectric (Cont.) Stressed Oil Volume v.s. Breakdown Stress

Dielectric (Cont.) Creep Curve

Dielectric (Cont.) Volt Time curve Relative strength 3 2 1 C B A Insulation Coordination 1 10 10 2 10 3 10 4 10 5 10 6 10 7 time (µs) Oil or pressboard breakdown relative strength vs time - schematic

Dielectric (Cont.) Oil Duct Theory E d The narrower the duct, the higher the average breakdown stress Must be manufacturable Barriers must stay in place through all mechanical stresses (Shipping, operational forces, maintenance, etc.)

Dielectric (Cont.) Minimum Design margin is based on process capabilities to remove moisture from the insulation and free of contaminants in the total insulation system Vapor Phase drying is the current state-of-the-art process to achieve consistently uniform dryness Proper application of the insulation theories and consistent execution provides maximum design margins

Dielectric (Cont.) Partial Discharge and Design Rules Limit the design stress (E) below the PD inception EHV Weidmann - Partial Discharge-Inception 100 E (kv/mm) 10 1 0.1 1 10 100 Oil Duct Width (mm) Non-Insulated Electrodes Gas-Saturated Oil

Dielectric (Cont.) Partial Discharge and Design Rules (creep breakdown curve d c = creep distance in mm)

Dielectric (Cont.) Typical requirements for Power Transformers beyond the current industry standards Dissolved Gas in Oil before and after tests Particle counts in oil Moisture content of oil and paper Partial Discharge in µv and pico Coulomb (Some of these will become IEEE requirements soon.)

Dielectric (Cont.) Standards and Specification Standards for Class I power transformers do NOT require Impulse testing and one hour long Induced test with RIV and PD measurements Specify if the user feels these are necessary Some manufacturers treat them same as Class II and perform tests Specifying Reduced BIL may lower the initial cost Must do the Insulation Coordination carefully Consider higher steady-state stresses during normal operation Some designers will design what s considered minimum level

Mechanical Short-Circuit Force Calculation and Management Tools used for the analysis Leakage Flux Field Classical Force calculations Classical Material strength analysis Failure Mode and Design Margin analysis Model testing to verify Design Margins

Leakage Flux Field and Resultant Forces in a Core Form Transformer: Text book (Next slide shows a real life example.) Lorentz force law f = J X B J = current density (SI units are used) B = magnetic field (leakage field) surrounding the coils

Failure Modes Studied Radial Forces Inner Winding Forced buckling (Beam bending) Free buckling (Hoop buckling) Outer Winding Hoop tension (Stretching) Relaxation buckling Axial Forces (All windings) Conductor tipping Conductor beam bending Clamping system Vibration HV @ Tap 3 LTC @ N HV @ Tap 1 LTC @ 8R HV@ Tap 5 LTC @ 16L Combined Forces Spiral motion Telescoping Examples of Leakage Field Plots

Short-Circuit Force Calculation and Management The maximum radial short circuit forces (Fr) is calculated using Fr 6.274* π *( r Fr = maximum radial short circuit force (N). r Lm = medium radius of the LV winding (m). r Hm = medium radius of the HV winding (m). I * N = Ampere*Turn value of the transformer. I SC /I R = ratio of symmetrical short circuit current to rated current defined by (1). K = asymmetrical short circuit factor defined by (3). α = length of leakage path (m) = 0.5 * (L + H) + (a + b + c)/3. The maximum axial short circuit forces (Fa) is calculated using Fa = = 4* Fr * X X Lm + rhm) * 1000 * α [ I * N * ( ISC / IR) * K] Fa = maximum axial short circuit force (N). X = displacement of winding electrical centers (m) = (H + L)/4 + (G H + G L )/4 + Tolerance D = a/2 + b + c/2 2 + D 2 2

Mechanical Short-Circuit Force Calculation and Management (Cont.) Classical Material strength specification and analysis

Mechanical Short-Circuit Force Calculation and Management (Cont.) Critical Buckling Stress

Mechanical Short-Circuit Force Calculation and Management (Cont.) Critical Tipping Stress Conductor Modulus of Elasticity E = 16,000 ksi for Annealed Copper E = 18,000 ksi for Hard Copper E = 9,500 ksi for EC Aluminum Key Spacer Embedding Constant C = 9,000 ksi

Mechanical Short-Circuit Force Calculation and Management (Cont.) Model testing to verify Design Margins

Mechanical Short-Circuit Force Calculation and Management (Cont.) Failure Mode and Design Margin analysis (Example) We calculate and manage all failure modes DETC Tap 5 LTC Tap 8R HV winding 0.1 DETC Tap 5 LTC Tap 16L HV winding 0.1 Stress DETC Tap 5 LTC Tap 16L DETC Tap 1 LTC Tap 8R HV winding 0.1 Failure Mode Allowable HV Radial Hoop 3,854 13,000 psi Beam Bending 7,110 13,000 psi Axial Tipping 164,676 232,830 lb LV Radial Buckling 4,655 7,800 psi Beam Bending 20,412 26,000 psi Axial Tipping 155,254 >1,000,000 lb Clamping Structure 139,975 256,000 lb

Mechanical (Cont.) Structural Design Tanks for full vacuum and pressure Corners are formed rather than welded Braces are box-beam style rather than angles Welding both inside and outside Flanged openings are raised bosses Full pressure and leak tested Core clamps Designed to withstand full short-circuit forces Supports all internal components and assemblies

Transf. Operational Considerations Transformer Operation Issues for Reliability Loading Switching Protection/Coordination Service Environment Monitoring Maintenance Life Extension

Transf. Operational Considerations Transformer Operation Issues for Reliability Loading Limits used for loading? Hot-Spot Temperature? Top Oil Temp.? Other? How are these monitored? Alarm and Trip settings IEEE C57.91 Loading guide for transformers Harmonics Potential overheating of windings and leads IEEE 519 Causes, limits, mitigation IEEE C57.110 Recommended Practice for transformers Impact (High magnitude, short duration) loading Needs to be properly designed for thermal and mechanical stress Connected directly to generator? UT/UAT/SST application guide IEEE C57.116

Transf. Operational Considerations Transformer Operation Issues for Reliability Loading Summer/Winter Ambient Temperature Profiles Max Top Oil Temp Max Hot Spot Temp Max Loss of Life Higher Current Rating Components

Transf. Operational Considerations Transformer Operation Issues for Reliability Loading Harmonics Higher than Normal (<0.05 per unit) User must specify entire harmonic profile Affects temperature rise, eddy and stray losses Larger equivalent KVA

Transf. Operational Considerations Transformer Operation Issues for Reliability Loading Impact Loading Mechanical and Thermal Performance Considerations Full Voltage Start Reduced Voltage Start How many starts per hour? Bumpless Transmission with Variable Frequency Drives

Transf. Operational Considerations Transformer Operation Issues for Reliability Loading Impact (High current for short duration) loading Transformer MVA > Full Load MVA Transformer MVA > RMS MVA or Combined Starting and Load Cycle Transformer MVA > Starting MVA // C 1000 N Pulse Per Hour 100 10 1 0 1 2 3 4 5 C Per Unit Pulse

Transf. Operational Considerations Transformer Operation Issues for Reliability Loading GSU Good reference C57.116 Guide Wye Delta for UT Delta-Wye for UAT and SST Overexcitation Voltage Regulation considerations Breaker Protection

Transf. Operational Considerations Transformer Operation Issues for Reliability Switching Break / Transformer Interaction TRV frequency close to Transformer s natural resonance frequency System parameters (largely the Capacitance) are different today Cables v.s. Overhead wires High series capacitance built into the transformers The industry lacks Understanding of the problem Standards and guides What should we do? IEEE working on the Guide Users and equipment manufacturers work together to mitigate the problem for existing installations Users and manufacturers work together to PREVENT the problem for new installations

ENGINEERING ANALYSIS for Br. / Tr. Interaction Circuit Breaker Transformer Lightning Arrester Load Lg Circuit Breaker e3 Recovery Voltage Transients L R Contact e2 Reignition Cg C l L l e1 V bd Lg = Generator Inductance System Equivalent circuit Cg = Generator Capacitance L = Stray Inductance R = Resistance L l = Load Inductance C l = Load Capacitance V bd = Min. Breakdown voltage for Breaker contacts Rignition Current Cycles Arc Interruption Time

Transf. Operational Considerations Transformer Operation Issues for Reliability Protection/Coordination ; Voltage Insulation coordination Volt-time characteristics of equipment Surge arrester characteristics Fast-front transient surges in GIS installations Capacitor switching up or down the system Installation of coordinated devices How close are the surge arresters from the equipment being protected? Devices to avoid resonance? Snubber, Reactor, Capacitor, etc System study? EMTP, SPICE, TNA, etc

Transf. Operational Considerations Transformer Operation Issues for Reliability Protection/Coordination ; Current Proper selection and setting of the relay protection (C37.91) Directional relays Differential relays Overcurrent relays Impedance relays Proper implementation of protection scheme Trip v.s. Alarm Reclosure settings (Time delay and number of reclosings) Protection Zone and combination of electrical/mechanical/thermal protective relays to determine appropriate action Training operators for newer relays Connections Settings Testing Maintenance

Transf. Operational Considerations Transformer Operation Issues for Reliability Protection/Coordination ; Others Mechanical Gas accumulation Gas detection Pressure (Sudden gas, Sudden gas/oil, Sudden oil, Static) Thermal Winding temperature Top oil temperature Fuses or Overcurrent relays Excellent material for system engineers: IEEE C37.91, Guide for Protective Relay Applications to Power Transformers

Transf. Operational Considerations Transformer Operation Issues for Reliability Service Environment High altitude Thermal Dielectric Ambient temperatures Below 20 C or above 40 C Many other Unusual service conditions (Next slide)

Other unusual service conditions: a) Damaging fumes or vapors, excessive or abrasive dust, explosive mixtures of dust or gases, steam, salt spray, excessive moisture, or dripping water, etc. b) Abnormal vibration, tilting, shock, or seismic conditions. c) Ambient temperatures outside of normal range. d) Unusual transportation or storage conditions. e) Unusual space limitations. f) Unusual maintenance problems. g) Unusual duty or frequency of operation, impact loading. h) Unbalanced ac voltages, or departure of ac system voltages from a substantially sinusoidal waveform. i) Loads involving abnormal harmonic currents such as those that may result where appreciable load currents are controlled by solidstate or similar devices. Such harmonic currents may cause excessive losses and abnormal heating. j) Specified loading conditions (kva outputs, winding load power actors, and winding voltages) associated with multiwinding transformers or autotransformers. k) Excitation exceeding either 110% rated voltage or 110% rated volts per hertz. l) Planned short circuits as a part of regular operating or relaying practice. IEEE/ANSI C57.12.00, Clause 4.3.3. m) Unusual short-circuit application conditions differing from those described as usual in Clause 7. n) Unusual voltage conditions including transient overvoltages, resonance, switching surges, etc., which may require special consideration in insulation design. o) Unusually strong magnetic felds. It should be noted that solar magnetic disturbances may result in the flow of telluric currents in transformer neutrals. p) Large transformers with high-current isolated-phase bus ducts. It should be noted that high-current isolated-phase bus ducts with accompanying strong magnetic fields may cause unanticipated circulating currents in transformer tanks and covers, and in the bus ducts. The losses resulting from these unanticipated currents may result in excessive temperatures when corrective measures are not included in the design. q) Parallel operation. It should be noted that while parallel operation is not unusual, it is desirable that users advise the manufacturer when paralleling with other transformers is planned and identify the transformers involved.

Transf. Operational Considerations Transformer Operation Issues for Reliability Monitoring What to monitor? How to monitor? What to do with these information? This is a subject for another two-day long seminar!

Transf. Operational Considerations Transformer Operation Issues for Reliability Maintenance Periodic schedule? Preventive? Predictive? Condition-based? User s experience with specific equipment History of specific equipment performance OEM s recommendations (Instruction Manuals)

Transf. Operational Considerations Transformer Operation Issues for Reliability Life Extension Evaluation of the Condition Risk Assessment Reconditioning

Transf. Operational Considerations Transformer Operation Issues for Reliability Life Extension Evaluation of the Condition External DGA, Oil Quality, Furan Analysis Electrical measurements (PF, TTR, Megger, FRA, Doble Excitation, etc.) Components (Bushings, Arresters, Tap Changers, Conservator, etc.) Monitoring devices (Gages, Relays, Detectors, etc.) Leaks / Rusts Internal Core & Coil inspection Leads Components (BCT s, Tap Changers, Bushing connections, etc.) Insulation materials (Degree of Polymerization)

Transf. Operational Considerations Transformer Operation Issues for Reliability Life Extension Risk Assessment Value to User Vintage of the equipment Operational history (Loading and Through faults) Operational environment Availability of Spares (Transformer or parts) Forced or Planned outage?

Transf. Operational Considerations Transformer Operation Issues for Reliability Life Extension Reconditioning External Arrester Replacement (old style? MOV?) Auxiliary Cooling replacement (Fans, pumps) Test and replace defective devices (Gauges, PRD, pressure relays) Gaskets Components in control box Oil (Dry out / Recirculation) Internal Core and Coil reclamping Tap Changer maintenance / upgrade Leads (positions, clamping) Electrical and mechanical connections General cleanliness

Summary & Conclusions Specifications, Design, Execution of these at OEM, and Verification testing build in robustness Monitoring, Maintenance, Proper implementation of the Operating strategy, and taking appropriate actions in time protect your investment and provide maximum return on that investment

Questions?