Babak Enayati National Grid Thursday, April 17

Similar documents
Impacts of the Renewable Energy Resources on the Power System Protection by: Brent M. Fedele, P.E., National Grid for: 11 th Annual CNY Engineering

Focused Directional Overcurrent Elements (67P, Q and N) for DER Interconnection Protection

Protective Relaying for DER

ECE 528 Understanding Power Quality

2012 Grid of the Future Symposium. Impacts of the Decentralized Photovoltaic Energy Resources on the Grid

BED INTERCONNECTION TECHNICAL REQUIREMENTS

Power System Protection Part VII Dr.Prof.Mohammed Tawfeeq Al-Zuhairi. Differential Protection (Unit protection)

This document covers common questions concerning the design of an effectively grounded system.

Connection Impact Assessment Application

Phase-phase/phase-neutral: 24/13.8 kv star, 13.8 kv delta, 12/6.9 kv star.

GENERATOR INTERCONNECTION APPLICATION Category 5 For All Projects with Aggregate Generator Output of More Than 2 MW

Table of Contents. Introduction... 1

E N G I N E E R I N G M A N U A L

Experiences in Integrating PV and Other DG to the Power System

DP&L s Technical Requirements for Interconnection and Parallel Operation of Distributed Generation

The Effect of Various Types of DG Interconnection Transformer on Ferroresonance

Protection of distributed generation interfaced networks

Utility Interconnection and System Protection

Appendix C-1. Protection Requirements & Guidelines Non-Utility Generator Connection to Okanogan PUD

The Connecticut Light and Power Company

Microgrid Protection

Embedded Generation Connection Application Form

Protection of Microgrids Using Differential Relays

Appendix S: PROTECTION ALTERNATIVES FOR VARIOUS GENERATOR CONFIGURATIONS

Protecting Large Machines for Arcing Faults

Generation Interconnection Requirements at Voltages 34.5 kv and Below

GENERATOR INTERCONNECTION APPLICATION Category 3 For All Projects with Aggregate Generator Output of More Than 150 kw but Less Than or Equal to 550 kw

ADVANCED VECTOR SHIFT ALGORITHM FOR ISLANDING DETECTION

Modelling Parameters. Affect on DER Impact Study Results

Sequence Networks p. 26 Sequence Network Connections and Voltages p. 27 Network Connections for Fault and General Unbalances p. 28 Sequence Network

ISO Rules Part 500 Facilities Division 502 Technical Requirements Section Aggregated Generating Facilities Technical Requirements

Remotes Case 2&3 Form REINDEER Cases 2&3 -Connection Impact Assessment (CIA) Application

Issued: September 2, 2014 Effective: October 3, 2014 WN U-60 Attachment C to Schedule 152, Page 1 PUGET SOUND ENERGY

POWER FACTOR CORRECTION. HARMONIC FILTERING. MEDIUM AND HIGH VOLTAGE SOLUTIONS.

TECHNICAL GUIDELINE FOR THE INTERCONNECTION OF DISTRIBUTED ENERGY RESOURCES TO EPCOR DISTRIBUTION AND TRANSMISSION INC. S DISTRIBUTION SYSTEM

Distributed Solar Integration Experiences

GRID CODE COMPATIBLE PROTECTION SCHEME FOR SMART GRIDS

Voltage Sag Mitigation by Neutral Grounding Resistance Application in Distribution System of Provincial Electricity Authority

New Methods for Detecting Unintentional Islanding for a Distributed-Generation Inverter

Catastrophic Relay Misoperations and Successful Relay Operation

Notes 1: Introduction to Distribution Systems

UProtection Requirements. Ufor a Large scale Wind Park. Shyam Musunuri Siemens Energy

System Protection and Control Subcommittee

Transmission Interconnection Requirements for Inverter-Based Generation

THE ROLE OF SYNCHROPHASORS IN THE INTEGRATION OF DISTRIBUTED ENERGY RESOURCES

Topic 6 Quiz, February 2017 Impedance and Fault Current Calculations For Radial Systems TLC ONLY!!!!! DUE DATE FOR TLC- February 14, 2017

Embedded Generation Connection Application Form

Protection Basics Presented by John S. Levine, P.E. Levine Lectronics and Lectric, Inc GE Consumer & Industrial Multilin

Information and Technical Requirements For the Interconnection of Distributed Energy Resources (DER)

EE Lecture 14 Wed Feb 8, 2017

Section 6: System Grounding Bill Brown, P.E., Square D Engineering Services

Embedded Generation Connection Application Form

NERC Protection Coordination Webinar Series July 15, Jon Gardell

ANALYSIS OF LIGHTNING ARRESTER OVERLOADING IN FUTURE DISTRIBUTION SYSTEMS WITH DISTRIBUTED GENERATION. A Thesis JONATHAN MICHAEL SNODGRASS

Connection Impact Assessment Application Form

Section G2: PROTECTION AND CONTROL REQUIREMENTS FOR TRANSMISSION GENERATION ENTITIES

Texas Reliability Entity Event Analysis. Event: May 8, 2011 Loss of Multiple Elements Category 1a Event

Impact Assessment Generator Form

Power Quality Basics. Presented by. Scott Peele PE

Design, Control and Application of Modular Multilevel Converters for HVDC Transmission Systems by Kamran Sharifabadi, Lennart Harnefors, Hans-Peter

Informative (*Customer to review then remove this page from submitted witness test procedure)

Protecting Feeders With Distributed Resource Scott Elling HDR Inc HDR, all rights reserved.

Education & Training

BUS2000 Busbar Differential Protection System

NERC Protection Coordination Webinar Series June 9, Phil Tatro Jon Gardell

IEEE 1547: Standard for Interconnection and Interoperability of Distributed Energy Resources with Associated Electric Power Systems Interfaces

PJM Manual 07:: PJM Protection Standards Revision: 2 Effective Date: July 1, 2016

OPERATING, METERING, AND EQUIPMENT PROTECTION REQUIREMENTS FOR PARALLEL OPERATION OF LARGE-SIZE GENERATING FACILITIES GREATER THAN 2,000 KILOWATTS

Fuseless Capacitor Bank Protection

Detecting and Managing Geomagnetically Induced Currents With Relays

Earth Fault Protection

Overcurrent Elements

Distance Protection in Distribution Systems: How It Assists With Integrating Distributed Resources

GUIDE FOR GENERATOR INTERCONNECTION THE WIRES OWNER DISTRIBUTION SYSTEM

Numbering System for Protective Devices, Control and Indication Devices for Power Systems

COPYRIGHTED MATERIAL. Index

ARC FLASH PPE GUIDELINES FOR INDUSTRIAL POWER SYSTEMS

Section G2: PROTECTION AND CONTROL REQUIREMENTS FOR TRANSMISSION GENERATION ENTITIES

NORTH CAROLINA INTERCONNECTION REQUEST. Utility: Designated Contact Person: Address: Telephone Number: Address:

Feeder Protection Challenges with High Penetration of Inverter Based Distributed Generation

IDAHO PURPA GENERATOR INTERCONNECTION REQUEST (Application Form)

Southern Company Interconnection Requirements for Inverter-Based Generation

ENOSERV 2014 Relay & Protection Training Conference Course Descriptions

EARTH FAULT PROTECTION VIS-A-VIS GENERATOR GROUNDING SYSTEM

Differential Protection for Microgrids with Embedded Generations

Our Brands. Where we are?

APPLICATION FOR INTERCONNECTION & OPERATIONS OF MEMBER-OWNED GENERATION

Protection & Control Challenges with Distributed Generation

Application for A Sub-harmonic Protection Relay. ERLPhase Power Technologies

A Tutorial on the Application and Setting of Collector Feeder Overcurrent Relays at Wind Electric Plants

Sizing of and Ground Potential Rise Calculations for Grounding Transformers for Photovoltaic Plants

Power System Protection Where Are We Today?

Evaluating the Response of Surge Arresters

ReliabilityFirst Regional Criteria 1. Disturbance Monitoring and Reporting Criteria

TABLE OF CONTENT

PROTECTION of electricity distribution networks

Need for grounding Codes and Standards for grounding Wind Turbine Generator grounding design Foundation + Horizontal Electrode grounding design

NEW DESIGN OF GROUND FAULT PROTECTION

INTERCONNECTION REQUIREMENTS FOR PARALLEL OPERATION OF GENERATION GREATER THAN 50 KW CONNECTED TO THE PECO DISTRIBUTION SYSTEM

Generator Protection GENERATOR CONTROL AND PROTECTION

Transcription:

2014 IEEE PES Transmission & Distribution Conference & Exposition Impacts of the Distribution System Renewable Energy Resources on the Power System Protection Babak Enayati National Grid Thursday, April 17

Index Normal Distribution System Distributed Generation What Utilities Generally Specify Interconnection Transformer Winding Arrangements Impact Protection Islanding Power Back-feed into Transmission System

Normal Distribution Power Flows from Substation to Load Fault Currents flow in only one direction Protection typically based on series overcurrent device coordinated in time Often employ reclosing since many faults are temporary

Distributed Generation Change Feeder Voltage Profile May affect capacitor & voltage regulator control Will effect magnitude and distribution of fault currents Will Impact Overcurrent Device Coordination

What Utilities Generally Specify Utility-Grade interconnection relays - Pass all pertinent ANSI standards - C37.90-1,2,3 CT and VT requirements (quantities sensed) Winding configuration of interconnection transformers Functional protection - 81U/O, 27, 59, etc. - Settings of some interconnection functions Pick ups Trip times

Distributed Generation Transformer Connections Charles (Chuck) Mozina Beckwith Electric http://www.beckwithelectric.com/docs/tech-papers/impact-of-green-power- Generation-on-Distribution-Systems.pdf

Interconnection Transformer Winding Arrangements Impact Protection The winding arrangements facing the Utility and the Facility have an impact on protection Interconnection Transformer convention: Utility = Primary Facility = Secondary

Distribution System Design Considerations Primary Distribution System o Grounding V A Gnd=0 V LG =1 pu V A V LG 1.2 pu V C Unfaulted System V B Effectively Grounded System V C ØA Grnd Fault V B

Distribution System Design Considerations Primary Distribution System o Grounding V A Gnd=0 V LG =1 pu V A V LG 1.7 pu V C V B Unfaulted System V C V B Ungrounded System ØA Grnd Fault

Distributed Generation Provides No Ground Current for Faults at F1 and F2 Feeder Ground Fault Relaying will not Respond to Fault at F3 F2 Can supply feeder from an ungrounded source if Feeder Breaker Opens, potentially causing overvoltages for other customers particularly under ground fault conditions. F1 Protection Install Zero Sequence PT s (Grounded Wye-Open Delta) Detect Ground Faults with 59G (Ground Overvoltage) Relay F3

Distributed Generation Provides No Ground Current for Faults at F1 and F2 Feeder Ground Fault Relaying will not Respond to Fault at F3 F2 Can supply feeder from an ungrounded source if Feeder Breaker Opens, potentially causing overvoltages for other customers particularly under ground fault conditions. High ground Fault current into DG F1 Protection Install Zero Sequence PT s (Grounded Wye-Open Delta) Detect Ground Faults with 59G (Ground Overvoltage) Relay F3

Distributed Generation F2 F3 F1 No Overvoltages for L-G ground Fault at F1 due to neutral shift Can relay transformer neutral to detect fault current and clear ground fault contributions for Fault at F1 Ground Current Source for Faults at F1 and F2, weak infeed even when DG is off-line effects ground relay coordination on all substation breakers DG high side relaying will see unbalanced currents on the utility system Circulating currents in delta due to unbalanced utility circuit Protection Install CT in transformer neutral with overcurrent relay Install 59N relay on the delta side of the interconnection transformer Neutral grounding reactor may be needed to limit the fault current contribution The interrupting device must be installed on the high side

F2 F3 F1 Distributed Generation With a grounded source No Overvoltages for L-G Fault at F1 due to neutral shift Can relay transformer neutral to detect fault current and clear ground fault contributions for Fault at F1 Ground Current Source for Faults at F1 and F2 DG relaying will see unbalanced currents from the utility system Feeder Protection will see faults at F3 Protection Install CT in transformer neutral with overcurrent relay Voltage controlled OC relay may be used for inverter generation (maximum fault current is limited to ~120-130% of nominal current)

Distribution System Design Considerations Transformer Connections Many utilities like to see effectively grounded sources at the PCC to limit overvoltages on feeder/system ground faults. Need to consider criteria for effective grounding: X0/X1 3 and R0/X1 1

Islanding Utility Substation Feeder Island If DG creates a feeder island, reclosing requires synchronizing at the utility substation DG Islanded Operation of DG with Utility Load Is Generally Not Allowed SmartGrid and Microgrid may allow islanding in the future Anti-islanding protection: Direct Transfer Trip (DTT), Power Line Carrier, etc

Islanding Utility Substation DG can create its own island, and synchronize to the utility DG DG Island DG Facility Islanding to the Utility is normally Allowed Restoration responsibility on the DG - Requires synchronizing to Utility

Power Back-feed into Transmission System Normally the Transmission side of the utility substation transformer is Delta 59N relay may be used to detect the L-G faults on the Transmission system Directional OC relay may be used to detect the ungrounded faults on the Transmission system. The impact of DG infeed on the Transmission system Distance Protection must be carefully reviewed.

Thank you Questions?