POWER TRANSFORMER SPECIFICATION, DESIGN, QUALITY CONTROL AND TESTING 18 MARCH 2009

Similar documents
Transformer Technology Seminar What to consider at Design Reviews

10. DISTURBANCE VOLTAGE WITHSTAND CAPABILITY

Transformer Winding Design. The Design and Performance of Circular Disc, Helical and Layer Windings for Power Transformer Applications

Electrical Design Process

Basic Principles and Operation of Transformer

Pomona, CA May 24 & 25, LTC Applications - Location, Series & Preventative Auto Transformers

A Review Comprehension: Guideline for Testing of HV, EHV and UHV Substation Equipment

Transformers handling and transport

ISSN: [IDSTM-18] Impact Factor: 5.164

Transformer Factory Testing

7. INSPECTION AND TEST PROCEDURES

36kV VOLTAGE TRANSFORMERS (OUTDOOR TYPE)

Tertiary Winding Design in wye-wye Connected Transformers Restricted Siemens Energy 2013 All rights reserved.

RESIDUAL LIFE ASSESSMENT OF GENERATOR TRANSFORMERS IN OLD HYDRO POWER PLANTS

SPECIFICATION FOR STEP UP TRANSFORMER 0.415/11Kv and (630KVA & 1000KVA)

TRANSFORMER TECHNOLOGY GPT

EE 1402 HIGH VOLTAGE ENGINEERING

Technical Questionnaire 9.101/6 Transformer Test System. Personal Data. Application. Test of. Delivery scope

Discipline Electrical Testing Issue Date Certificate Number T-2837 Valid Until Last Amended on - Page 1 of 6 LOCATION 1

POWER TRANSFORMER. Failure Analysis & Troubleshooting. H.H. Sheik Sultan Tower (0) Floor Corniche Street Abu Dhabi U.A.E

FGJTCFWP"KPUVKVWVG"QH"VGEJPQNQI[" FGRCTVOGPV"QH"GNGEVTKECN"GPIKPGGTKPI" VGG"246"JKIJ"XQNVCIG"GPIKPGGTKPI

Power transformers for Network, Rectifiers, Furnace

Commissioning Manual Distribution Transformers - Three-phase Oil Filled

Transformer Technology Seminar Winding Selection

KNOW MORE ABOUT THE TRANSFORMERS. Glossary Transformers

Insulation Co-ordination For HVDC Station

Energy Division. Bowthorpe LV/MV Surge Arresters

DEFERRING REPLACEMENT OF A 600 MVA, 345GRD Y/138GRD Y/ 13.8 kv SHELL TYPE WESTINGHOUSE AUTOTRANSFORMER

Tab 8 Surge Arresters

Understanding the Value of Electrical Testing for Power Transformers. Charles Sweetser, OMICRON electronics Corp. USA

Regional Technical Seminar SHORT CIRCUIT FORCES

Group F : Sl. No. - 1) 33/0.403 KV, 100 KVA Station Transformer GUARANTEED & OTHER TECHNICAL PARTICULARS. Table : A

Chapter 7 Conclusion 7.1 General

(2) New Standard IEEE P (3) Core : (4) Windings :

TRANSFORMER OPERATIONAL. Principles, Selection & Troubleshooting

EE059: Transformer Operation, Maintenance, Diagnosis & Testing

Insulation Level and Test Technology of. 1000kV Power Transformer

TesTIng of Power. Transformers are the largest, most. feature. By brandon dupuis

Benefits of SFRA - Case Studies

TRANSFORMER OPERATIONAL PRINCIPLES, SELECTION & TROUBLESHOOTING

Substation Preventive Maintenance

Schedule of Accreditation issued by United Kingdom Accreditation Service 2 Pine Trees, Chertsey Lane, Staines-upon-Thames, TW18 3HR, UK

Reactor and inductor are names used interchangeably for this circuit device.

Power Voltage Transformers for Air Insulated Substations. THE PROVEN POWER.

ECP HV INSULATION TESTING

Testing of 400 kv GIS

شركة الوقت للكهرباء والمقاوالت ذ.م.م.

Shunt Reactors. Global Top Energy, Machinery & Plant Solution Provider

ECP HV INSULATION TESTING

ESB National Grid Transmission Planning Criteria

HOW TO SAFE GUARD THE TRANSFORMER..???

Shortcomings of the Low impedance Restricted Earth Fault function as applied to an Auto Transformer. Anura Perera, Paul Keller

Specialists in HV and MV test and diagnostics. Testing in Substations

PES & IAS NY Chapter And NY LMAG June 23 rd, 2015

TRANSMISSION ENGINEERING STANDARD TES-P , Rev. 0 TABLE OF CONTENTS 1.0 SCOPE 2.0 BONDING METHODS

WESTERN UNDERGROUND COMMITTEE GUIDE 2.6 (2.6/00/0868)

Title Substation Auxiliary Transformer from Rectifier Transformer Secondary. Reference Number PDS 01 (RIC Standard: EP SP)

Siemens Transformer Technology Seminar Insulation & Thermal Design

Power Transformer Condition Assessment Based on Standard Diagnosis

Australian Standard. Instrument transformers. Part 1: Current transformers (IEC Ed.1.2 (2003) MOD) AS AS

MGM Transformer. Vacuum Pressure Impregnated (VPI) Dry-Type Substation Transformer Specification Guide

Diagnostic testing of cast resin transformers

High voltage engineering

AC/DC Current Probe GCP-100 QUICK START GUIDE ISO-9001 CERTIFIED MANUFACTURER

Understanding the Value of Electrical Testing for Power Transformers. Charles Sweetser - OMICRON

APDRP SCHEME, WESCO. Technical Specification for Distribution Transformers ( 11/0.4KV ) PART 1: GENERAL

Variation in SFRA plot due to design and external parameter

DETECTING SHORTED TURNS

VI 3 - i TABLE OF CONTENTS

CONTENTS. 1. Introduction Generating Stations 9 40

Understanding and Extracting Valuable Information from Basic and Advanced Power Transformer Testing Techniques

HVDC Transmission. Michael Muhr. Institute of High Voltage Engineering and System Performance Graz University of Technology Austria P A S S I O N

Back to the Basics Current Transformer (CT) Testing

Coil Products Beginnings 1960 State of the Art. Customer partnership around the globe. Continuous innovation since 1900

CHAPTER 2 ELECTROMAGNETIC FORCE AND DEFORMATION

TMC Transformers TMC

Innovative Test Techniques and Diagnostic Measurements to Improve the Performance and Reliability of Power System Transformers

FIELD ELECTRICAL TESTING SPX TRANSFORMER SOLUTIONS, INC.

Western Mining Electric Association San Antonio TX Layer vs. Disk Windings Discussion NOVEMBER 15, SPX Transformer Solutions, Inc.

TRANSFORMERS FAULT ANALYSIS - A MULTIDISCIPLINARY APPROACH

Test description for dry-type transformers chapter for special tests

HIGH VOLTAGE ENGINEERING(FEEE6402) LECTURER-24

TIGHTENING TORQUE ON WOODEN CORE CLAMP (Nm) (STEEL FASTENER) 1 M M M M M

POSI-BREAK Metal Oxide Varistor Elbow (M.O.V.E.) Surge Arrester

Electrical Description

ABB Power Products Service

MODIFICATION OF THE ARRESTER ARRANGEMENT WHEN CONVERTING THE METHOD OF NEUTRAL TREATMENT

G. KOBET, I. GRANT, G. GOZA Tennessee Valley Authority USA. R. GIRGIS, M. ESPINDOLA ABB Corporation USA SUMMARY

COMBINED METERING TRANSFORMERS (OUT DOOR TYPE) FOR 11kV & 33kV SYSTEMS

EI HIGH VOLTAGE INSULATION TESTING POLICY

MEDIUM & HIGH VOLTAGE

IJSRD - International Journal for Scientific Research & Development Vol. 2, Issue 04, 2014 ISSN (online):

Transformer Design: Economics & Reliability

DEPARTMENT OF ELECTRICAL AND ELECTRONICS ENGINEERING QUESTION BANK SUBJECT CODE & NAME : EE 1402 HIGH VOLTAGE ENGINEERING UNIT I

SPTS 1 - Ratings and General Requirements for Plant, Equipment and Apparatus for The ScottishPower System and Connection Points to it.

PREVENTING FLASHOVER NEAR A SUBSTATION BY INSTALLING LINE SURGE ARRESTERS

Transformer Protection

About us. Vision. To lead our field in innovation, quality and customer service.

DMRC ELECTRICAL STANDARDS & DESIGN WING (DESDW)

Transcription:

POWER TRANSFORMER SPECIFICATION, DESIGN, QUALITY CONTROL AND TESTING 18 MARCH 2009 Nkosinathi Buthelezi Senior Consultant: Power Transformers and Reactors

Presentation Content Standardization of Power Transformers in the network Design and design reviews Quality Control Testing

Interchangeability and standardization Philosophy All transformers are specified, designed, tested, maintained and operated to meet at least the expected operational life span of approximately 40 years when used in normal operation.

Interchangeability and standardization New transformers are specified to be designed for minimum maintenance requirements and oil leaks i.e. vacutapminimum 300000 operation, and welded top covers All the units are easily interchangeable in terms of their electrical & physical parameters and must work optimally when connected in parallel.

Interchangeability and standardization Eskom Transmission has standardized on all transformers and is reaping practical and economic benefits. All units are interchangeable, spares are common, less time is needed to check designs, performing design reviews, approval of drawings, test certificate and time is saved in preparing specifications & drawings for new Capital projects. Field maintenance staff have fewer different types of equipment to deal with

Interchangeability and standardization Power transformers are required to interconnect the system voltages of 765, 400, 275 and 220kV step down from these voltages to 132 and 88kV to give supplies to distribution or other end users. Selecting these transformers generally involves deciding on the number of type of units i.e. MVA ratings, insulation, winding Connection, vector grouping and voltage ratio. Furthermore, impedance, type of tapchanger and tapping range plays a crucial role

Table of Standard Transformers Table 1 Main parameters of standard system transformers Nominal Voltage (kv) Ratings Main/Tertiary (MVA/MVA) Impedance Standard Number HV MV Tertiary /LV 1 2 3 4 Min (%) Ratio Max/Min Vector Group A13 765 400 33 2000/* 12 1.3 A12 400 275 22 1000/* 110 1.35 A11 400 275 22 800/40 400/40 10 1.35 A10 400 220 22 630/40 215/40 11 1.30 A9 400 132 22 500/40 250/40 125/20 13 1.25 A8 275 132 22 500/40 250/40 125/20 11 1.30 A7 275 88 22 315/40 160/20 80/10 12 1.25 YNa0d1 A6 220 132 22 500/40 250/40 125/20 9 1.30 A5 220 66 22 160/20 80/10 40/10 11 1.25 A4 132 88 22 315/40 160/20 80/10 8 1.35 A3 132 66 22 160/20 80/10 40/10 9 1.30 A2 132 44 22 80/10 40/10 20/5 10 1.25 A1 88 44 22 80/10 40/10 20/5 8 1.30 B11 132 33 80 40 20 10 1.25 B10 132 22 40 20 10 10 1.25 B9 132 11 20 10 10 1.25 B8 88 33 80 40 20 10 9 1.25 B7 88 22 40 20 10 5 9 1.25 B6 88 11 20 10 5 9 1.25 Ynd1 B5 88 6.6 10 5 9 1.25 B4 66 22 40 20 10 5 8 1.25 B3 66 11 20 10 5 2.5 8 1.25 B2 44 11 20 10 5 2.5 7 1.25 B1 44 6.6 100 5 2.5 7 1.25 C2 33 11 20 10 5 2.5 7 1.25 YNyn0 C1 22 11 20 10 5 2.5 5 1.25

Interchangeability and standardization Tapping Ranges +5% to -15% of HV voltage has been adopted as the standard for transformers based on the following; The electricity act states that supply voltages shall not vary by more than ±5% from the nominal. Thus sending end busbar voltages shall not exceed 105% while receiving end voltages shall not be less than 95%, assuming loads connected to both busbars.

Interchangeability and standardization Tapping Ranges cont. Allowing for a 5% volt drop through the transformer at the receiving end and assuming that the voltage of the LV busbar associated with this transformer is required to be boosted to 105%, an 85% tap is required on the HV side together with an ability to withstand for at least a limited period of 10% over-fluxing condition. At light load a 5% voltage rise in the line due to the Ferranti effect with 100% sending voltage requires a maximum tap of 105% on the receiving end transformer

Interchangeability and standardization Tapping Ranges cont. 16 steps each of 1.25% is chosen as the standard to provide reasonably fine control without excessive operations due to minor fluctuations. For the 400kV system transformers the tapping range is reduced to 0% to -15%, firstly because U max for this system is only 105% and, secondly, because a 20% tapping range introduces problems with the insulation of the tapping winding

Interchangeability and standardization Insulation and connection For economic reasons all auto-transformers and all star-connected windings of 132kV and above have graded insulation and must be solidly earthed. All transformers must be either auto-connected or Star/star so that there is no phase shift between primary and secondary voltages. Where voltage ratio(n) is 3:1 or less, economics dictate an auto-transformer

Weakness identified in the current Specification Internal Faults : Failure Root Cause Insulation breakdown, collapse of the Tap windings as a results of an number of through faults and lightning strikes occurring in the network. Design reviews Conducted by an Independent Consultant revealed some shortcoming on the existing winding arrangement Over fluxing could be observed on the 400kV transformers with no plus tolerance due to the limitations on maximum system voltages These failures had exceeded the international limit of 2.5% per annum.

TRANSMISSION TRANSFORMERS REVIEW UPDATE Severe failures transformers 12mmi 8 N u m b e r 6 4 2 Value(s) Target 0 2000 2001 2002 2003 2004-April Year

Existing winding arrangement 3A2 11 3 a2 A13 CORE Tertiary Winding Tapping Winding MV Winding HV Winding 12

Adoption of this arrangement This winding arrangement was originally adopted to ensure almost constant impedance throughout the tapping range in order to achieve the full rated power across the whole tapping range. Furthermore, it ensured maximum impedance occurring in the minimum tap-position, which is advantageous for LV fault MVA consideration. This is due to the fact that previously Eskom had a policy to supply the rural and farm communities from the tertiary terminals of the main autotransformer.

Adoption of this arrangement, Cont This policy has been abolished in the recent past due to the line faults failures experienced from the tertiary feeders which is a dangerous practice as a direct short-circuit fault on the tertiary winding can lead to very high forces on that winding, resulting in the destruction of the whole transformer.

Investigation findings on the windings

Investigation findings on the windings, cont The tap winding is located between the LV and MV both being more or less on ground potential Tapping winding acts like a sharp electrode between the adjacent windings and is exposed to high axial short-circuit stresses (Voltage Knife condition). This condition requires a tap winding to be insulated from LV and MV windings. Disadvantages: more paper insulation, less mechanical stability, it becomes more spongy under through fault condition.

Investigation findings on the tap-changes

ZnO Varistors

Protection against transients ZnO offer protection because as the voltage tries to rise above the threshold level, the resistance plummets and a large amount of current is passed. This action keeps the voltage between taps to below the threshold level as the power is shunted through the discs. They are made to operate only during very short time voltage transients due to lightning strikes and switching transients. These are types of transients which produce the highest internal voltage stresses in the transformer, as well as the highest possibility of exciting winding damaging resonances.

Studies for Transients stress suppression 300 200 1050 kv Full Wave at X Voltage across RW VRW (kv) 100 0-100 -200-300 0 20 40 60 80 100 120 140 160 180 200 without with MOV's t (mys)

Investigation for a new solution Because of such high failure rate of these Transmission transformers windings and tap changers on the Eskom Transmission National Grid. These failures reached an unprecedented high levels in the early 2000. These failures were the highest in such that they exceeded annual failure rate stipulated by international standards. The extent of failures has been quantified and was the major driving motivation behind the upgrading of the specification.

Changes and adoption of the new Specification 3A2 a2 3 11 A13 CORE Tertiary Winding MV Winding Tap Winding HV Winding 12

Challenges Tertiary impedance dropped due to the relocation of the tapping winding into the main field. Tertiary reactor was introduced to increase the impedance thereby dropping the fault level to < 20kA. Impedance slope differed due to the different winding arrangement.

Challenges Tertiary Reactors

Challenges Paralleling of units 500 MVA, 275 / 132 kv Impedance characteristic 20 18 16 I m p e d a n c e ( % ) 14 12 10 8 6 4 2 old design new design 0 1 3 5 7 9 11 13 15 17 Tap position

The new Specification SERVICE CONDITIONS The rated nominal frequency shall be 50Hz. Temperature Rise. Temperature rises must be in accordance with IEC 60076 standards. It has to be considered that the annual average rated ambient temperature has been changed from 25 C to 30 C. Winding Rise. The average winding rise above ambient at nameplate MVA rating shall not exceed 55 C for oil natural flow through the windings, and shall not exceed 60 C for oil forced directed flow through the winding.

Temperature Rise of Metallic Parts at Rated MVA. The hot spot temperature rise above ambient of metallic parts in contact with cellulose material outside the winding block shall not exceed 68 C. The rise above ambient of other metallic parts in contact with oil including core and tank shall not exceed 75 C for the surface in contact with the oil.

The new Specification Winding Hottest Spot Temperature Rise. The winding hot spot temperature rises above ambient at nameplate MVA rating has been changed from 73 C to 68 C. The top oil temperature rise above ambient has been changed from 55 to 50 C. If forced oil flow through the winding is applied (ODAF/ODWF) the oil flow through the core must also be forced so that the oil at top of the core does not exceed a 50 C temperature rise above ambient.

The new Specification Temperature Rise of Metallic Parts at Rated MVA. The hot spot temperature rise above ambient of metallic parts in contact with cellulose material outside the winding block shall not exceed 68 C. The rise above ambient of other metallic parts in contact with oil including core and tank shall not exceed 75 C for the surface in contact with the oil. Flux density to be limited to 1.7 Tesla at 50Hz at rated voltage.

Changes and adoption of the new Specification 20% Insulation safety margin as per international standard as demonstrated by field plots. Increase the radial build of tap winding, reducing paper insulation within limits Fitting ZnO varistors across the tap winding to limit voltage transients that causes oscillation Using low chip epoxy to improve mech. strength of the tap Wdg s.

Design reviews international Consultant is engaged Design Review is performed on every new design and the ff: is verified as per Cigre Guideline Focus area is on conformity and performance data with both ordering specification and IEC/IEEE Standards. Reliability aspects such as design safety margins crosschecks calculations, material quality, and quality assurance in terms of designs and manufacturing. Lifetime expectancy aspects such as thermal aspects focussing on hot spots in the windings and metal parts, Dissolved Gas Analysing limits, short circuit behaviour, overload condition behaviour as per IEC 60076-7 Loading guide.

Factors considered during the design reviews ELECTRICAL DESIGN Winding Arrangement Arrangement of windings. Describe type of windings to be used. Conductor configuration in each winding. Location and type of tap windings or tap sections to be used.

Factors considered during the design reviews Insulation Clearances and Configuration of Insulation. Insulation clearances between windings and between windings and ground. Electrostatic shielding around the core, at ends of windings, and adjacent to line coils or disks. Insulation spaces between disks. Calculated impulse voltages between disks. Conductor insulation on each winding. Calculated turn to turn voltage in each winding. Drawing of the insulation assembly between and around windings. Transient voltage distribution

Factors considered during the design reviews Describe method used to calculate transient voltage distribution Calculated capacitances between windings. This must include induced voltages in adjacent windings. Acceptable voltages for the spaces across which the voltage appears. the voltages with and without the metal oxide varistors. Study of oil spaces and creepage stresses

Factors considered during the design reviews Leakage Flux Heating in Cores and Mechanical Parts Calculation methods used to determine the field magnitudes. Determination of losses in the various elements. Cores and core supports. Frame and tank wall heating. Shielding used to reduce losses and prevent heating.

Factors considered during the design reviews MECHANICAL DESIGN Tanks Construction Joint design and welding to prevent leaks.

Factors considered during the design reviews TEST PROGRAM Review requirements in the specifications and standards. Review test plans for the transformer. Accuracy of loss measurement methods. Temperature tests including review of allowed gas in oil increases during temperature tests. Impulse and partial discharge testing. Discuss acceptance criteria. Check points during testing.

Workshop Inspection- Individual windings

Workshop Inspection- Assembly line

Workshop Inspection-Top Lining up

Workshop Inspection- Winding inspection

Workshop Inspection- Winding assembly

Workshop Inspection- Core section

Workshop Inspection- Active part before tanking

Workshop Inspection

Quality control Focus area is on Tests to prove that the transformer has been built correctly: This include ratio, polarity, resistance and taphange operation. Tests to prove the guarantees: These are the losses, impedance, and temperature rise and noise level. Test to prove that the transformer will be satisfactory in service for at least 35 years. The tests in this category are the most important and the most difficult to frame. These tests are performed as per IEC 60076-3

Transformer testing Main test required as per IEC: Temperature rise test (only on the first unit) Short time duration heat run test Type Routine, on subsequent units Short circuit test Calculation for the short circuit withstand capability should be submitted Lightning impulse test Switching impulse test Routine Induced over voltage test Routine Routine Routine Chopped impulse test Routine Routine Acoustic noise level measurement Overload test Dielectric loss angle test and capacitance (Doble instrument) Vibration test SFRA Fully assembled filled with oil. (Doble instrument) SFRA Fitted with test bushing and gas filled. (Doble instrument) Type Type Routine Routine Routine Routine

Transformer testing

Thank You