Modeling and Analysis of a 3-Phase 132kv Gas Insulated Substation

Similar documents
Calculation of Transient Overvoltages by using EMTP software in a 2-Phase 132KV GIS

Estimation of Re-striking Transient Over voltages in a 132KV Gas insulated Substation

Calculation of Transients at Different Distances in a Single Phase 220KV Gas insulated Substation

Estimation of Re-striking Transient Overvoltages in a 3-Phase 132KV Gas insulated Substation

GIS Disconnector Switching Operation VFTO Study

A Simple Simulation Model for Analyzing Very Fast Transient Overvoltage in Gas Insulated Switchgear

VFTO STUDIES DUO TO THE SWITCHING OPERATION IN GIS 132KV SUBSTATION AND EFFECTIVE FACTORS IN REDUCING THESE OVER VOLTAGES

The various factors influencing the VFTO levels in 500kV and. 750kV GIS have been discussed by developing the simulink models which

Effect of Shielded Distribution Cables on Lightning-Induced Overvoltages in a Distribution System

INTERNATIONAL JOURNAL OF ENGINEERING SCIENCES & RESEARCH TECHNOLOGY. Approach for Fault Detection in GIS.

Tab 2 Voltage Stresses Switching Transients

SUPPRESSION METHODS FOR VERY FAST TRANSIENT OVER- VOLTAGES ON EQUIPMENT OF GIS

Effect of High Frequency Cable Attenuation on Lightning-Induced Overvoltages at Transformers

Analysis of Very Fast Transient over Voltages of Transformer in Gas Insulated Substation (GIS) using Wavelet Technique

Research Article Survey of Induced Voltage and Current Phenomena in GIS Substation

Research Article A Simplified High Frequency Model of Interleaved Transformer Winding

Session Four: Practical Insulation Co-ordination for Lightning Induced Overvoltages

DIFFERENCE BETWEEN SWITCHING OF MOTORS & GENERATORS WITH VACUUM TECHNOLOGY

Modelling of Sf6 Circuit Breaker Arc Quenching Phenomena In Pscad

Electromagnetic Disturbances of the Secondary Circuits in Gas Insulated Substation due to Disconnector Switching

A3-308 HIGH SPEED GROUNDING SWITCH FOR EXTRA-HIGH VOLTAGE LINES

CHAPTER 2. v-t CHARACTERISTICS FOR STANDARD IMPULSE VOLTAGES

Effect of Shielded Distribution Cable on Very Fast Transients

Modeling insulation in high-voltage substations

THE PROPAGATION OF PARTIAL DISCHARGE PULSES IN A HIGH VOLTAGE CABLE

ANALYSIS OF VERY FAST TRANSIENT OVER VOLTAGES IN GAS INSULATED SUBSTATION

Lightning transient analysis in wind turbine blades

CONTENTS. 1. Introduction Generating Stations 9 40

Key words: Lightning overvoltage s, GIS (gas insulated substations), AIS (air insulated substations), GIB (gas insulated bus duct) 1.

TRANSMISSION ENGINEERING STANDARD TES-P , Rev. 0 TABLE OF CONTENTS 1.0 SCOPE 2.0 BONDING METHODS

Power Frequency Withstand Voltage On-site testing of 400 kv GIS

EMC Philosophy applied to Design the Grounding Systems for Gas Insulation Switchgear (GIS) Indoor Substation

ANALYSIS OF A FLASHOVER OPERATION ON TWO 138KV TRANSMISSION LINES

A Study on Ferroresonance Mitigation Techniques for Power Transformer

TECHNICAL REPORT. Insulation co-ordination

7P Series - Surge Protection Device (SPD) Features 7P P P

Testing 320 kv HVDC XLPE Cable System

High voltage engineering

Switching and Fault Transient Analysis of 765 kv Transmission Systems

G. KOEPPL Koeppl Power Experts Switzerland

FGJTCFWP"KPUVKVWVG"QH"VGEJPQNQI[" FGRCTVOGPV"QH"GNGEVTKECN"GPIKPGGTKPI" VGG"246"JKIJ"XQNVCIG"GPIKPGGTKPI

Simulation Study of Voltage Surge Distribution in a Transformer Winding

DEPARTMENT OF ELECTRICAL AND ELECTRONICS ENGINEERING QUESTION BANK SUBJECT CODE & NAME : EE 1402 HIGH VOLTAGE ENGINEERING UNIT I

Lightning overvoltage and protection of power substations

ROEVER ENGINEERING COLLEGE ELAMBALUR, PERAMBALUR DEPARTMENT OF ELECTRICAL & ELECTRONICS ENGINEERING

In power system, transients have bad impact on its

Basics of Partial Discharge. Prepared for 2015 Phenix RSM Meeting January 2015

Substation Preventive Maintenance

Lightning performance of a HV/MV substation

Condition Assessment of High Voltage Insulation in Power System Equipment. R.E. James and Q. Su. The Institution of Engineering and Technology

LIGHTNING OVERVOLTAGES AND THE QUALITY OF SUPPLY: A CASE STUDY OF A SUBSTATION

When surge arres t ers are installed close to a power transformer, overvoltage TRANSFORMER IN GRID ABSTRACT KEYWORDS

Simulation and Analysis of Lightning on 345-kV Arrester Platform Ground-Leading Line Models

Switching Induced Transients:

EE 1402 HIGH VOLTAGE ENGINEERING

Generation of Sub-nanosecond Pulses

Chapter 1. Overvoltage Surges and their Effects

10. DISTURBANCE VOLTAGE WITHSTAND CAPABILITY

Comparison of switching surges and basic lightning impulse surges at transformer in MV cable grids

GIS Instrument Transformers: EMC Conformity Tests for a Reliable Operation in an Upgraded Substation

Electric Stresses on Surge Arrester Insulation under Standard and

Effect of Surge Arrester on Overhead Transmission Lines as Shield against Over Voltage

Investigation into Transient SFO, FFO, VFTO Overvoltage Characteristics for Typical Gas Insulated Substations

Investigation of Inter-turn Fault in Transformer Winding under Impulse Excitation

IJSRD - International Journal for Scientific Research & Development Vol. 2, Issue 04, 2014 ISSN (online):

Progress Report on Failures of High Voltage Bushings with Draw Leads By Jim McBride and Larry Coffeen, JMX Services / NEETRAC 7/26/2010

A Guide to the DC Decay of Fault Current and X/R Ratios

Utility System Lightning Protection

A Case Study on Selection and Application of Lightning Arrester and Designing its Suitable Grounding Grid

Prevention of transformers damage in HPP with double generating units connected to GIS via HV cables

Parameters Affecting the Back Flashover across the Overhead Transmission Line Insulator Caused by Lightning

VOLTAGE OSCILLATION TRANSIENTS CAUSED BY CAPACITOR BANKING ENERGIZING FOR POWER FACTOR CORRECTION IN THE POWER SYSTEM

Investigation of Transmission Line Overvoltages and their Deduction Approach

PREVENTING FLASHOVER NEAR A SUBSTATION BY INSTALLING LINE SURGE ARRESTERS

Switching Restrikes in HVAC Cable Lines and Hybrid HVAC Cable/OHL Lines

Advancements in online partial discharge monitoring and assessment of MV through EHV Substation assets

The Analysis Results of Lightning Overvoltages by EMTP for Lightning Protection Design of 500 kv Substation

Insulation Co-ordination For HVDC Station

A Special Ferro-resonance Phenomena on 3-phase 66kV VT-generation of 20Hz zero sequence continuous voltage

Influence Of Lightning Strike Location On The Induced Voltage On a Nearby Overhead Line

Prediction of Transient Transfer Functions at Cable-Transformer Interfaces

Computer Based Model for Design Selection of Lightning Arrester for 132/33kV Substation

Overview of Grounding for Industrial and Commercial Power Systems Presented By Robert Schuerger, P.E.

Appendix B to Working on Exposed Energized Parts

The Application of Partial Discharge Measurement and Location on CGIS

Gas-Insulated Medium-Voltage Switchgear siemens.com/8dab12

AORC Technical meeting 2014

Short-circuits in ES Short-circuit: cross fault, quick emergency change in ES the most often fault in ES transient events occur during short-circuits

Investigation on the Performance of Different Lightning Protection System Designs

Lightning Protection of Distribution Substations by Using Metal Oxide Gapless Surge Arresters Connected in Parallel

The Many Uses of Transmission Line Arresters

Study of Power Transformer Abnormalities and IT Applications in Power Systems

Ferroresonance Experience in UK: Simulations and Measurements

Sources of transient electromagnetic disturbance in medium voltage switchgear

International Journal of Advance Engineering and Research Development. Analysis of Surge Arrester using FEM

Simulation of characteristics of impulse voltage generator for testing of equipment using MATLAB Simulink

Underground System Design TADP 547

Specialists in HV and MV test and diagnostics. Testing in Substations

Measurement Of Partial Discharge (PD) In High Voltage Power Equipment

Analysis of Electromagnetic Transients in Secondary Circuits due to Disconnector Switching in 400 kv Air-Insulated Substation

Transcription:

Modeling and Analysis of a 3-Phase 132kv Gas Insulated Substation M. Kondalu1, Dr. P.S. Subramanyam2 Electrical & Electronics Engineering, JNT University. Hyderabad. Joginpally B.R. Engineering College, Moinabad, Hyderabad Abstract: -- This paper introduces Modeling of a 3- Phase 132kv Gas Insulated Substation. Such over voltages can cause mal functioning of protection circuits and control circuits and also initiates faults and influence on other components such as transformers. For designing a substation it is essential to know the maximum value of FTO. Hence studies are carried out on estimation of the FTO levels. For this purpose MATLAB 7.8 can be used. In MATLAB 7.8 simulation a suitable equivalent circuit is necessary for each component of the substation. Analysis of ery Fast Transient Overvoltage has been carried out using MATLAB7.8 for various switching conditions in a 3- phase 132k gas insulated substation. Keywords, MATLAB 7.8 software and Control circuitry, Gas Insulated Substation (GIS), ery Fast Transient overvoltages, Switching operations, 3 phase fault I. INTRODUCTION Gas Insulated Substations (GIS) have found a broad range of applications in power systems over the last three decades because of their high reliability, easy maintenance, small ground space requirement etc.. In our country also, a few GIS units have been in operation and a large number of units are under various stages of installation[1]. GIS is based on the principle of operation of complete enclosure of all energized or live parts in a metallic encapsulation, which shields them from the external environment[2]. Compressed SF6 gas, which has excellent electrical insulating properties, is employed as the insulating medium between the encapsulation and the energized parts. Gas Insulated Substations have a grounded outer sheath enclosing the high voltage inner conductor unlike conventional equipment whose closest ground is the earth surface[3][4]. The Basic Insulation Level (BIL) required for a Gas Insulated Substation (GIS) is different from that of the conventional substation because of certain unique properties of the former[5]. Gas insulated bus has a surge impedance (70 Ohm) more than that of the conventional oil filled cables, but much less than that of a over head line (300 400 Ohms)[6]. In addition, the GIS is totally enclosed and therefore is free from any atmospheric contamination. Hence, in general the GIS permit lower BIL rating than the conventional one. A GIS requires less number of lightning arresters than a conventional one[7]. The representation of bushing is important for simulating the fast transients. Generally, the transit time through a bushing is comparable to or greater than the rise time of GIS generated transients. For this reason, bushings cannot be considered as a lumped element in estimating the FTO level. The generation of fast transients can be classified into two types. They are due to the following: a) Dis-connector switch operation b) Faults between Bus bar and Enclosure In case of 3-phase fault, the voltage collapse at the fault location occurs in a similar way as in dis-connector gap during re-striking. By this event, step shape traveling surges are injected. For such a surge source inside GIS, two surges traveling in opposite directions are generated. However, if voltage collapse occurs at the open end of GIS, only single surge propagates on the bus[8]. During recent field tests on a 132K substation, measurements were made of the trapped charge left when a DS was opened onto a floating section of switchgear. Numerous measurements led to the conclusion that for this switch, a potential of 0.1 0.2p.u is left on the floating section and that this result is consistent [9][10]. II. ESTIMATION OF 132K GAS INSULATED SUBSTATION During the switching operation of the circuit, the transients are developed. By the calculated values of the circuit parameters in previous chapter, the equivalent circuits are constructed by using MATLAB 7.8 software. By using the circuits the transients are calculated for different lengths of 12

Gas insulated substation. The transients are also calculated during the faults with and without load at different distances. During the current operation of dis-connector switch in a GIS, re-strikes(pre-strikes) occur because of low speed of the dis-connector switch moving contact, hence ery fast Transient Over voltage are developed. These FTO s are caused by switching operations and 3-phase fault in 132Kv GIS. Using MATLAB of the equivalent models is developed. A. Spacers capacitance The spacer existed with finite thickness and develops some amount of capacitance in addition with existed capacitance. Spacers are used for supporting the inner conductor with reference to the outer enclosure. They are made with Alumina filled epoxy material whose relative permittivity (εr) is 4. B. Calculation of short circuit inductance & Resistance: Assuming a short circuit fault level of 1000 MA for 220K system voltage, inductance and resistance are calculated as follows: S I And ph But ph % Z X %Z* I X 2* *f X*I * L X L 2* *f C. Calculation of Inductance due to Load (Transformer): For 600MA,, 220K transformer with 10% impedance and 0.8 power factor the inductance is calculated as follows: 3 **I*Cos I P P 3 * *Cos And X*I % Z X %Z* I But X 2* *f * L D. Inductance calculation X L 2* *f The inductance of the bus duct can be calculated by using the formula [8] given below, where r1, r2, r3, r4, are the radii of the conductors in the order of decreasing magnitude and l is the length of the section. = 0.001 l ln r1 r3 2 r2 + ln r2 2 r1 1 r2 r1 r1 r4 + ln + r3 2 ln r1 r2 1 Calculation of variable arc resistance: The ariable arc resistance is calculated using the formula: R = K T l t q 0 + 0 i t dt Where, K T = Toepler s constant = 0.005 volt.sec/mt for SF6 under uniform field conditions L = spark length in meters q 0 = Initial charge or charge at the instant of breakdown T = spark collapse time in sec. The value of time varying spark resistance R(t) is calculated until it reaches a value of 1 to 3 ohms. The integral in the denominator sums up the absolute value of current i through the resistance R(t) over the time beginning at breakdown inception. Thus, it corresponds to the charge conducted through the spark channel up to time t. Initial charge q o is an important parameter while considering the non-uniform fields. But the field between the disconnector contacts is almost uniform. Therefore q o is very small. 13

Fig 1. Equivalent circuit of GIS Fig. 2. Equivalent circuit for 10mtrs. Length in a 3 -phase to132kv GIS Fig. 3. MATLAB circuit for 10mtrs length in a 3-phase to 132K GIS Fig. 4. Sub Circuit of 132 k GIS 14

III. EQUIALENT CIRCUIT FOR 132K GIS SYSTEM This circuit is divided into three sections of 1mtr, 4mtrs and 5mtrs respectively from load side and by using the circuit shown below figure 1 & 2. The Fast transient over voltages are generated not only due to switching operations but also due to 3-phase fault in 132Kv GIS.The bus duct is dividing into three sections of length from load side. The GIS bushing is represented by a capacitance of 200pf. The resistance of 1 ohm spark channel is connected in series with circuit breaker. MATLAB Circuit for 10 mtrs. length in a 3-phase 132Kv GIS shown in the fig. 3 and Sub Circuit of 132 k GIS fig.4. The proposed method implemented on MATLAB 7.8. the voltage before and after circuit breaker is taken to be 1.0 p.u and -1.0pu as the most enormous condition but depending on the time of closing of circuit breaker the magnitude of the voltage on the load side changes. For different values of voltages on the load side the magnitudes and rise time of the voltage wave are calculated keeping source side voltages as constant as 1.0p.u the values are tabulated in table I. Similarly by changing the magnitudes of the voltage on the source side, keeping voltage on load side constant at 1.0p.u. Then the transient due to variation of voltage on source side obtained. The values are tabulated in Table II. S.no TABLE I TRANSIENT DUE TO ARIATION OF OLTAGE ON LODE SIDE Load side oltage (p.u) Magnitude of the voltages (p.u) Rise Time (Nano secs) R Y B tr ty tb phase phase phase 1-1.0 2.42 2.40 2.43 11 12 11 2-0.9 2.34 2.33 2.34 13 14 12 3-0.8 2.22 2.22 2.23 09 10 11 4-0.7 2.12 2.15 2.18 11 12 11 5-0.6 1.87 1.84 1.86 12 11 11 6-0.5 1.84 1.82 1.82 11 10 10 7-0.4 1.70 1.71 1.70 12 10 11 8-0.3 1.63 1.64 1.62 10 11 10 9-0.2 1.45 1.43 1.42 11 10 11 10-0.1 1.39 1.40 1.39 09 10 09 S.no Load side oltage (p.u) Magnitude of the voltages (p.u) Rise Time (Nano secs) R Y B phase phase Phase tr ty tb 1 1.0 2.41 2.40 2.42 10 09 10 2 0.9 2.36 2.36 2.33 11 12 11 3 0.8 2.23 2.22 2.21 12 11 12 4 0.7 2.03 2.04 2.03 11 10 11 5 0.6 2.04 2.05 2.02 13 12 13 6 0.5 1.79 1.78 1.77 12 11 11 7 0.4 1.71 1.70 1.69 11 10 12 8 0.3 1.61 1.60 1.62 12 11 11 9 0.2 1.48 1.47 1.46 10 11 10 10 0.1 1.36 1.35 1.36 09 10 11 I. RESULTS AND DISCUSSION The various current and transient voltage at different positions in a 3 -phase 132kv GIS for the first switching operation presented in results. The variable arc resistance is calculated by using the Toepler s formula. The inductance of the bus bar is found out from the diameters of conductors and enclosure. The bus capacitance is calculated using formula for concentric cylinders. The transients due to switching operations and line to enclosure faults with fixed arc resistance for different lengths of GIS are found. Transients are calculated along with load and it was observed that the transients obtained in 5mts length GIS will effect the system more than that obtained in 10mts length GIS. As the distance between the fault point and load increases during fault analysis the magnitudes and rise times of the transients also increases. The maximum values of FTO, the MATLAB7.8 software is used and a simulation is carried out by designing suitable equipment circuits and its models are developed. The main advantages of such models are used to enable the transient analysis in GIS. During closed operation, the current through the resistance of the circuit breaker is shown in fig.5 From the graph it was found the maximum current is 35A at a rise time of 14ns. TABLE II TRANSIENTS DUE TO ARIATION OF OLTAGE ON SOURCE SIDE Fig. 5 Current waveform during closing operation of CB for 10mts length in a 3-phase 132kv GIS 15

The transients due to closing of the circuit breaker are calculated as shown in fig 6. From this graph, the peak voltages obtained are 2.44, 2.43 and 2.44p.u at rise times of 69, 68.69ns respectively. From the graph, the maximum voltages obtained is 2.51, 2.52 and 2.54 p.u at arise time of 122,121 and 123ns respectively. The magnitudes and rise times of 10mts length GIS are tabulated in the table III. Fig 6 Transient voltage wave from during closing operation of CB for 10mts length in a 3-phase 132kv GIS To introduce current chopping the circuit breaker is opened. The transients obtained during opening operation are shown in Fig 6.4. From the graph, the maximum voltages obtained are 1.23, 1.22 and 1.21p.u. at rise times of 61,60,and 61ns respectively. MATLAB Circuit for 10mtrs. Length in a 3- phase 220kv GIS shown in the fig 3. Fig. 7 Transient voltage waveform during opening operation of CB for 10mts length in a 3-phase 132kv GIS Assuming a second re-strike occurs the transients are calculated by closing another switch at the time maximum voltage difference occurs across the circuit breaker. The transients obtained due to second re-strike are shown in Fig 8 Fig.8 Transient voltage waveform during second re-strikes for 10mts length in a 3-phase 132kv GIS Mode of operation During closing operation During opening operation During second re-strike TABLE III THE ANALYSIS ALUES ARE TABULATED AS FOLLOWS: R phase Magnitude of voltages(p.u) Y phase B phase Rise time (Nano sec) tr ty tb 2.44 2.43 2.44 69 68 69 1.23 1.22 1.21 61 60 61 2.51 2.52 2.54 122 121 123. CONCLUSION The fast transient over voltages that are obtained due to switching operations in GIS are simulated.. It is observed that the peak magnitudes are 26% to 30% higher in case of disconnector switch closing operation. With effective design and use of the same can effectively reduce the steepness and maximum peak of FTO generated. The fast transient over voltages are obtained due to switching operations and short-circuit faults are studied. The transients are calculated initially with fixed arc resistance and then variable arc resistance. The variable arc resistance is calculated by using Toepler s formulae. Transients along with load and without load are also estimated. 16

I. REFERENCES: [1] S. Nishiwaki, Y. Kanno, S. Sato, E. Haginomori, S. Yamashita, and S. Yanabu, Ground Fault by Re-striking Surge of SF6 Gas insulated Disconnecting Switch and Its Synthetic Tests, Transactions on Power Apparatus and Systems, vol. PAS-102, No. 1, pp. 219-227, 1983. [2] N. Fujimoto and S. A. Boggs, Characteristics of GIS Disconnector-induced Short Rise time Transients Incident on Externally Connected Power System Components, IEEE 87 WM 185-2,New Orleans, Feb. 1987. [3] W. Boeck and W. Taschner, Insulating Behavior of SF6 with and without Solid Insulation in Case of Fast Transients, CIGRE Paper No.1547, Aug. 1986. Transactions on Power Systems, vol. PWRD- 1, No. 2, pp. 95-101, 1983. [4] R. Witzman, Fast Transients in Gas Insulated Substations (GIS) Modeling Of Different GIS Components, Fifth International Symposium on High oltage Engineering, No. 12.06, 1987. [5] J. Lewis, B. M. Pryor, C. J. Jones, T. Irwin, Disconnector Operations in Gas Insulated Substations Over voltage Studies and Tests Associated with a 420 k Installation, CIGRE,ol. 11, 1988, paper 33.09, pages 1-8 [6] M.kondalu, G.Sreekanthreddy, Dr. P.S. subramanyam, Analysis and Calculation of very fast transient over voltages in 220kv gas insulated Substation International Journal of Engineering &techsciencevol 2(4) 2011 [7] M.kondalu,, Dr. P.S. subramanyam Estimation of Re-striking Transient Over voltages in a 3-phase 132kv Gas Insulated substation published in International journal of Advanced Research in Computer Engineering & Technology Issue4-olume1-series1,pages 22-27,June- 2012 [8] M.kondalu,, Dr. P.S. subramanyam Calculation of Transients at Different Distances in a single phase 220kv Gas Insulated substation published in International journal of Advanced Research in Computer Engineering & Technology Issue4-olume1pages 28-33 June-2012 [9] H. Hiesinger,RWitzmann. ery fast Transient Breakdown at a needle Shaped Protrusion, IX Int. Conf. on Gas Dis. and Their Appli. Sep 1988. [10] M.kondalu, G.Sreekanthreddy, Dr. P.S. subramanyam, Estimation Transient overvoltages in gas insulated bus duct from 220kv gas insulated substation, International journal of Computer applications, (0975-8887) volume 20-no.8 april 2011. 17