Simplified Approach to Calculate the Back Flashover Voltage of Shielded H.V. Transmission Line Towers

Similar documents
Parameters Affecting the Back Flashover across the Overhead Transmission Line Insulator Caused by Lightning

Analysis of lightning performance of 132KV transmission line by application of surge arresters

Back-flashover Investigation of HV Transmission Lines Using Transient Modeling of the Grounding Systems

Study of Tower Grounding Resistance Effected Back Flashover to 500 kv Transmission Line in Thailand by using ATP/EMTP

Effective Elimination Factors to the Generated Lightning Flashover in High Voltage Transmission Network

Lightning transient analysis in wind turbine blades

Simulation and Analysis of Lightning on 345-kV Arrester Platform Ground-Leading Line Models

2000 Mathematics Subject Classification: 68Uxx/Subject Classification for Computer Science. 281, 242.2

PREVENTING FLASHOVER NEAR A SUBSTATION BY INSTALLING LINE SURGE ARRESTERS

Maximum Lightning Overvoltage along a Cable due to Shielding Failure

X International Symposium on Lightning Protection

Lightning Performance Improvement of 115 kv and 24 kv Circuits by External Ground in MEA s Distribution System

Lightning performance of a HV/MV substation

Analysis of MOV Surge Arrester Models by using Alternative Transient Program ATP/EMTP

ABSTRACTS of SESSION 6

Modeling insulation in high-voltage substations

When surge arres t ers are installed close to a power transformer, overvoltage TRANSFORMER IN GRID ABSTRACT KEYWORDS

Lightning overvoltage and protection of power substations

SCIENCE & TECHNOLOGY

Simulation of Lightning Transients on 110 kv overhead-cable transmission line using ATP-EMTP

Lightning Flashover Rate of an Overhead Transmission Line Protected by Surge Arresters

The relationship between operating maintenance and lightning overvoltage in distribution networks based on PSCAD/EMTDC

Effect of Shielded Distribution Cables on Lightning-Induced Overvoltages in a Distribution System

MODIFICATION OF THE ARRESTER ARRANGEMENT WHEN CONVERTING THE METHOD OF NEUTRAL TREATMENT

The Simulation Experiments on Impulse Characteristics of Tower Grounding Devices in Layered Soil

EMC Philosophy applied to Design the Grounding Systems for Gas Insulation Switchgear (GIS) Indoor Substation

OVERVOLTAGE MEASUREMENTS RELATED TO LIGHTNING- DETECTION SYSTEMS IN NORWAY

Analyzing and Modeling the Lightning Transient Effects of 400 KV Single Circuit Transmission Lines

Towards an Accurate Modeling of Frequency-dependent Wind Farm Components under Transient Conditions

Accurate Modeling of Core-Type Distribution Transformers for Electromagnetic Transient Studies

Computation of Lightning Impulse Backflashover Outages Rates on High Voltage Transmission Lines

The Effect of Lightning Parameters on Induced Voltages Caused by Nearby Lightning on Overhead Distribution Conducting Line.

Electric Power Systems Research

Including Surge Arresters in the Lightning Performance Analysis of 132kV Transmission Line

Transmission of Electrical Energy

A Study on Lightning Overvoltage Characteristics of Grounding Systems in Underground Distribution Power Cables

Simulation Study on Transient Performance of Lightning Over-voltage of Transmission Lines

Investigation on the Performance of Different Lightning Protection System Designs

ATP SIMULATION OF FARADAY CAGE FOR THE ANALYSIS OF LIGHTNING SURGES

EXPERIMENTAL INVESTIGATION OF A TRANSIENT INDUCED VOLTAGE TO AN OVERHEAD CONTROL CABLE FROM A GROUNDING CIRCUIT

Lightning Overvoltage Performance of 110 kv Air-Insulated Substation

ABSTRACT 1 INTRODUCTION

Effect of High Frequency Cable Attenuation on Lightning-Induced Overvoltages at Transformers

Lightning Overvoltages on Low Voltage Circuit Caused by Ground Potential Rise

Protection against unacceptable voltages in railway systems

ABSTRACT 1.0 INTRODUCTION LIST OF SYMBOLS

Influence Of Lightning Strike Location On The Induced Voltage On a Nearby Overhead Line

TRIGGERED by energy transition towards sustainability,

Estimating BFOR on HV Transmission Lines Using EMTP and Curve of Limiting Parameters

Accuracy of Lightning Surge Analysis of Tower Surge Response

An Approximate Formula for Estimating the Peak Value of Lightning-Induced Overvoltage Considering the Stratified Conducting Ground

Research on Lightning Over-voltage and Lightning Protection of 500kV. HGIS Substation

Modeling of substation grounding for fast front overvoltage studies

ACCURATE SIMULATION OF AC INTERFERENCE CAUSED BY ELECTRICAL POWER LINES: A PARAMETRIC ANALYSIS

The Influences of Soil Ionization in the Grounding System and Corona Phenomena on the Injection Lightning Current of 1000 KV UHV Transmission Line

Fig.1. Railway signal system

Lightning Protection of Distribution Substations by Using Metal Oxide Gapless Surge Arresters Connected in Parallel

Modeling for the Calculation of Overvoltages Stressing the Electronic Equipment of High Voltage Substations due to Lightning

A Case Study on Selection and Application of Lightning Arrester and Designing its Suitable Grounding Grid

The Use of a Special Grounding Arrangement to Improve the Lightning Performance of Transmission Line

Lightning current field measurement on a transmission line, comparison with electromagnetic transient calculations

FDTD-Based Lightning Surge Simulation of a Microwave Relay Station

Lightning Performance of Transmission Lines with Tall Sections

Modeling of overhead transmission lines with line surge arresters for lightning overvoltages. Poland

TECHNICAL NOTE 2.0. Overvoltages origin and magnitudes Overvoltage protection

INTEGRATED METHOD IN ELECTROMAGNETIC INTERFERENCE STUDIES

Analysis of the Electromagnetic Interferences between Overhead Power Lines and Buried Pipelines

Hazard of Induced Overvoltage to Power Distribution Lines Jiang Jun, Zhao Rui, Chen Jingyang, Tian Hua, Han Lin

The Lightning Event. White Paper

GIS Disconnector Switching Operation VFTO Study

ARTICLE IN PRESS. Lightning effects in the vicinity of elevated structures. F.H. Silveira, S. Visacro

Calculation of Transient Overvoltages by using EMTP software in a 2-Phase 132KV GIS

The line-lightning performance and mitigation studies of shielded steelstructure

LIGHTNING OVERVOLTAGES AND THE QUALITY OF SUPPLY: A CASE STUDY OF A SUBSTATION

Electric Stresses on Surge Arrester Insulation under Standard and

10. DISTURBANCE VOLTAGE WITHSTAND CAPABILITY

A Reflectometer for Cable Fault Location with Multiple Pulse Reflection Method

SURGES TRANSFERRED TO THE LOW-VOLTAGE NETWORK VIA TRANSFORMER THE INFLUENCE OF THE LOAD CONNECTED TO THE SECONDARY

Sensitivity Analysis of Maximum Overvoltage on Cables with Considering Forward and Backward Waves

University of Zagreb Faculty of Electrical Engineering and Computing

Effect of Surge Arrester on Overhead Transmission Lines as Shield against Over Voltage

Session Four: Practical Insulation Co-ordination for Lightning Induced Overvoltages

Visualization of the Ionization Phenomenon in Porous Materials under Lightning Impulse

EVALUATION OF LIGHTNING-INDUCED VOLTAGES ON LOW-VOLTAGE DISTRIBUTION NETWORKS

A Simple Simulation Model for Analyzing Very Fast Transient Overvoltage in Gas Insulated Switchgear

Cable Protection against Earth Potential Rise due to Lightning on a Nearby Tall Object

INSTALLATION OF LSA ON A 400 KV DOUBLE-CIRCUIT LINE IN RUSSIA

Mitigation of Back-Flashovers for 110-kV Lines at Multi-Circuit Overhead Line Towers

New Modeling of Metal Oxide Surge Arresters

Grounding and Lightning 1

Mitigation Methods to Improve the Lightning Performance of Hybrid Transmission Line

EXPLOTING THE IMPULSE RESPONSE OF GROUNDING SYSTEMS FOR AUTOMATIC CLASSIFICATION OF GROUNDING TOPOLOGIES

Investigation of Transmission Line Overvoltages and their Deduction Approach

APPLICATION OF THE ELECTROMAGNETIC FIELD METHOD TO STUDY A COMMUNICATION SATELLITE SITE DAMAGED BY LIGHTNING

AC Voltage- Pipeline Safety and Corrosion MEA 2015

Fast Front Transients in Transformer Connected to Gas Insulated Substations: (White+Black) Box Models and TDSF Monitoring

The Many Uses of Transmission Line Arresters

HIGH VOLTAGE Insulation Coordination

Generation of Sub-nanosecond Pulses

Power Quality and Reliablity Centre

Transcription:

Proceedings of the 14 th International Middle East Power Systems Conference (MEPCON 1), Cairo University, Egypt, December 19-1, 1, Paper ID 1. Simplified Approach to Calculate the Back Flashover Voltage of Shielded H.V. Transmission Line Towers Ghada M. Amer Abstract over voltages due to switching or lightning may cause damage for the transmission line insulators, transformers and switchgear. The flow of overvoltage to earth through transmission system towers causes an increase in the potential of metal structure and the earth potential and may create back flashover voltage causing failure to transmission system insulators in which transmission line outages occur. In this paper the effect of tower grounding surge impedance on the back flashover is investigated. The coupling factors between the and the healthy conductors are considered. Index Terms Back flashover voltage, H.V.T.L., Shielded, Towers F I. INTRODUCTION or properly designed lines having shield, lightning strikes to the lines will terminate on the shield and it will be conducted into the ground towers and grounding system. It is possible under certain circumstances due to the high energy of lightning to generate sufficient voltage across insulators to cause them to flashover [1]. The grounding system is never perfect (i.e. zero footing resistance) and the structure itself possesses a surge impedance. The surge flowing through the tower structure and the footing impedance cause a voltage rise of the structure above ground voltage []. The surge voltage appears across a phase insulator may be in many cases sufficiently high to cause a back flashover voltage over the transmission line insulators. The back flashover voltage depends on the coupling factor which is a function of the relative spacing of conductors to ground and conductors to shield, the tower structure impedance and ground system impedance [3, 4]. In this paper investigations are carried out to study the back flashover voltages of 5 kv transmission lines. The effect of grounding system surge impedance, the tower structure surge impedance and coupling factor between phases and on the back flashover voltages magnitude are studied. II. MODELS OF SYSTEM A. Lightning Current The properties of lightning and switching surges have been well summarized in [5]. Usually, the discharge increases from zero to a maximum in few μs (from.1 to 1 μs), then declines to half the peak value in about to 1 μs. The typical value of the peak derivative di/dt is about 11 ka/μs. The peak value of the stroke is about 15-3 ka, and some stroke s could be about (probability of occurrence less than.1%) [5].The peak value of ka has 5% probability or 75% probability. Also it is found that 14 ka is about 87.5% probability correlation [-1]. The lightning stroke impulse source which will be used as an input for the transient analysis of grounding system in the present study equation is [5]: (1) B. Modeling of ground and tower system for transient studies: B.1 Grounding System Modeling The ground rod impedance is represented by a lumped R-L-C circuit Fig. 1 [1]. In Fig. 1 the impinges on the rod electrode and enters the ground, which in addition to its resistivity has a dielectric constantε. Thus the ground electrode will have a capacitance, as reciprocal to the resistance and inductance [11, 1]. () (3) The inductance of such a rod is (4) Ghada M. Amer, Author was with Benha University, Benha, Egypt. He is now with the Department of Electrical engineering, High Institute of Technology, (e-mail:dr_ghada11@hotmail.com, dr_ghada@benhauniv.edu.eg). Where l is the rod length in meter, a is the radius of the driven rod and ρ is the soil resistivity in. The capacitance of a driven rod of moderate length plays no significant part even 8

with rapid lightning phenomena. Transient behavior of grounding systems can be calculated using ATP program [13]. C. Coupling Factor Calculations The coupling factor (F) between the two and each phase conductors can be calculated by the relation [15]: Fig.1. models of a vertical ground rod The voltage drop on the electrode inductance L will be: (1) Where a and b are the distances between each wire to conductor and its reflection, h is height of ground wire and r is the radius of ground wire. In case of one wire the coupling factor can be calculated as follows [1]: ] (5) For the tower grounding system having n vertical ground rods the total impedance equals () Where Z (t) is the transient impedance of one rod and, n is number of rods, M is the mutual impedance factor between rods. The transient voltage across the grounding system can be obtained by: V (t) =Z T (t).i(t) (7) B. Tower Modeling Tower can be represented as surge impedance. It has inductance and resistance. The voltage across the tower structure can be represented by the equation: (8) Where i is the amplitude of the lightning, L tower is the inductance of the tower structure. Its value for carrying conductors is approximately 1.7 μh/m, di/dt is the average steepness of the front of lightning (ka/μs) and R tower is the tower structure surge, its value can be calculated according to the formula given by Cigré [14]: (9) Where h is the tower height and x is the tower equivalent radius [14]. For 5 kv two shield transmission line R tower = 87.8Ω, and for 5 kv single shield wire transmission line R tower =84.9485 Ω.As it is observed in the above equation that the increasing of tower height increases the surge tower resistance. (11) Table I gives the parameters of single and double circuits 5 kv transmission systems and the calculated coupling factor conductors TABLE I COUPLING FACTOR FOR 5 KV T.L. SYSTEM h 1 5.4 58. Phase a b A a= 8.884 b=97.3175.394 B a=18.93 b=88.1.155 C a=.911 b=78.4533.17 A a 1 = 1.4 b1=14.459 a = 3.377 b= 1.5137.3131 B a 1 =3.198 b1=93.44 a =34.7131 b=9.9513.7 C a 1 =34.34 b1=8.584 a =39.93 b=84.18.139 From table I it is noticed that conductors close to the shield have higher coupling coefficients (i.e. higher induced voltages) and consequently have lower voltages appearing across their supporting insulators. The induced voltage is calculated from the relation given in equation 1. Table II shows the induced voltage appears on the transmission line during transient over voltages on the for phases A, B and C when grounding system contains 4 rods, m length and. m radius, the soil resistivity ρ=1, the mutual impedance factor M is taken 1% of one rod grounding resistance and the soil permittivity ε r =9. The impulse peak is varied as given in the table II. From this table it is noticed that the induced voltages on phases close to wire are higher than the other phases. Also using two increases the induced voltages and this will reduce the voltage appear across the tower insulators. (1) F 81

TABLE II THE INDUCED VOLTAGE APPEARS ON THE TRANSMISSION LINE DURING TRANSIENT OVER VOLTAGES Tower peak V A (kv) V B (kv) V C (kv) Single line 8.93 44.35 35.9 3 ka 918.8.48 48.5 Single line 1.7 1377.5 95.9 1 ka 8.7 189.3 174. Single line 3157.9 45.4 1411.7 15 ka 458.1 81.7 1893.3 Single line 5.4 3381.3 333.7 74.9 447. 313. III. BACK FLASH VOLTAGE () The back flashover voltage for 5 kv transmission line systems can be calculated by the relation. (13) Fig. shows simulation of back flashover voltage appears across the tower grounding system and tower structure and the induced voltage appears on the transmission conductors. Fig. 3 shows the. as a function of time across 5 kv transmission system phases A, B, and C in case of two and single shield respectively. In case of tower grounding system has 4 rods, soil resistivity ρ=1 and impulse =3 ka. As shown in Figs. 3 phase A has lower. across its insulator string and phase C has the highest. across its insulators. Back flash over voltage Induced voltage As shown also in this figure the voltage appears on the grounding system is small compared with the voltage of tower surge impedance. It is approximately about.7% of the voltage appears on the tower surge impedance. A. Effect of Soil Resistivity on the Back Flashover Voltage To study the effect of soil resistivity variation on the ground surge impedance and back flashover voltage, the soil resistivity is changed between 5, 1, and 3. The ground system parameters are the rod length equals m, number of rods are changed 4, 8 and 1 respectively, the radius of the driven rod is a=. m and the soil permittivity ε r =9. The peak value of the stroke is 3 ka. Fig. 4 shows the relation between the soil resistivity and surge impedance of grounding system for two shield transmission line. In these calculations the effect of soil ionization is neglected according to IEEE guide lines [17, 19]. (Volt) 3.5 1.5 1.5 3.5 x 1 5 kv T.L. two shielded V tower V B V A V ground.1..3.4.5..7.8.9 1 Time (s) x 1-4 V C 3 x 1 5 kv T.L. single shielded Insulator 1-F Conductor (Volt).5 1.5 V tower V B V A V C 1.5 V ground Back Voltage Fig. Induced and back flashover voltages appears on the transmission line towers.1..3.4.5..7.8.9 1 Time (s) x 1-4 Fig. 3 the. appears across 5 kv transmission system phases A, B, and C in case of two and single shield respectively. The amplitude 8

Grounding surge impedance Ω Fig. 4 the relation between the soil resistivity and surge impedance of grounding system for various numbers of rods Table III gives the relation between. and the soil resistivity ρ for the two types of 5 kv transmission lines towers when the impulse peak s are 3kA and, the grounding system contains 4 rods. 3 ka 1 1 8 4 TABLE III THE RELATION BETWEEN. AND SOIL RESISTIVITY KV T.L. FOR PHASES A, B AND C. Soil resistivity ρ for two kv phase 5 1 3 A 4.7 15.7 37. 59.5 B 315.3 38. 353.3 378. C 51. 5. 553.4 58.9 for A 158.1 17. 194.5 18.8 single B 397.3 41.8 437.8 44.7 kv C 533. 547.9 57.4 4.9 for two kv n=4 n=8 n=1 5 1 15 5 3 Soil Resistivity ρ A 15355 15447 159 1581 B 17734 1784 1851 18 C 194 19357 1958 19815 for A 1488 1589 179 1994 single B 1831 1848 1853 18878 kv C 19357 1947 19714 19951 B. Influence of Grounding Rods Number on the. and Surge Impedance The number of rods of the tower grounding system is changed to be 4, 8, 1, 1 and respectively. The soil resistivity is kept constant at, each rod length is m, radius of the driven rod is. m and the permittivity of the soil is ε r = 9. The relation between the surge impedance versus the number of tower grounding system when impulse peak = 3 ka is given in Fig. 5., Table IV gives the relation between. and the number of grounding rods 4, 8, 1, 1 and for the two types of 5 kv transmission lines towers for impulse peak 3kA and. C. Effect of earth wire radius on the. In this section the earth wire radius is change and the is calculated. The soil resistivity is kept constant at, 4 rods are used in earthling system each rod length is m, radius of the driven rod is. m and the permittivity of the soil is ε r = 9. Table 5 shows the relation between. and the radius of earth wire when impulse peak takes the values of 3 ka and respectively From table V it s noticed that when the earth wire radius increases the. decrease IV. CONCLUSION The main conclusions of this paper are: 1. Simplified approach is suggested to calculate. of shielded high voltage transmission line tower and it is in agreement with the calculations done by ATP, given in reference [].. The simplified method is used to investigate different factors affecting the transient. such as earth radius, grounding system and soil resistivity. 3. From results it is noticed that: a) the coupling factor for the conductors close to the shielded have higher coupling coefficients (i.e. higher induced voltages) b) Grounding resistance has little effect on. comparing with the surge impedance of the tower structure. c) Using two reduces. comparing with using single shielded wire. Grounding surge impedance Ω 1 1 8 4 ρ= ρ=1 ρ=5 ρ=3 4 8 1 1 14 1 18 Number of rods Fig. 5 relation between the surge impedance versus the number of tower grounding rods 83

TABLE IV THE RELATION BETWEEN. AND THE NUMBER OF GROUNDING RODS FOR 5 KV TRANSMISSION LINE FOR IMPULSE PEAK CURRENT 3KA and. 3 ka phase Number of rods 4 8 1 for A 37. 13.5 5.5 two B 353.3 35.5 31. kv C 553.4 53. 513. for A 194.5 17.8 158.9 single B 437.8 48.1 398.3 kv C 57.4 545.1 17.8 for A 159 1548 153 two B 1851 17819 1774 kv C 1958 19334 195 for A 179 159 1495 single B 1853 184 1834 kv C 19714 19453 193 TABLE 5 THE RELATION BETWEEN. AND THE EARTH WIRE RADIUS FOR 5 KV TRANSMISSION LINE FOR IMPULSE PEAK CURRENT 3KA and. 3 ka phase Earth wire radius (cm).47.5.55.5 for two A 37. 19.3 11.7 4. B 353.3 334.1 39.1 34.4 kv C 553.4 533. 53. 57.1 for single A 194.5 191.1 184.4 178. B 437.8 435. 431. 47. kv C 57.4 574.9 571.9.591 for two A 159 15479 1541 1537 B 1851 1789 17854 1537 kv C 1958 194 1939 1937 A 179 17 1714 17 for single B 1853 183 183 1857 kv C 19714 197 1979 1958 ACKNOWLEDGMENT The author is grateful to Prof. Dr. Osama Gouda for his skillful guidance through preparing this paper. References [1] IEEE Working Group on Lightning Performance of Transmission Lines., IEEE Guide for Improving The lightning Performance of Transmission Lines, IEEE Standard 143-1997, June 1997. [] P. Yadee and S. Premrudeepreechacharn, Analysis of Tower Footing Resistance Effected Back Flashover Across Insulator in a Transmission System, www.ipst.org/techpapers/7/ipst_7/paper./9.pdf [3] P. Chowdhuri, Parameters of lightning strokes and their effects on power systems, IEEE Transmission and Distribution Conference and Exposition, Nov. 1, pp. 147-151. [4] G. Lucca, Mutual impedance between an overhead and a buried line with earth-return, in Proc. 1994 of the IEE, 9th International Conference on Electromagnetic Compatibility, pp. 8-8. [5] Thottappillil R., Electromagnetic pulse environment of cloud-to ground lightning for EMC studies, IEEE transactions on EMC, Vol. 44, No. 1, Feb., p. 3-13. [] Marcus O. Durham and Robert Durham, "Lightning, Grounding, and Protection for Control Systems", IEEE Transactions on Industry Applications, Vol. 31, No.1, Jan-Feb 1995, pp. 45, New York. [7] Bazelyan, E. M. and Y. P. Raiser, : Lightning Physics and Lightning Protection, Institute of Physics Publishing, Bristol, p. 175. [8] Matsuo, N.M.; Zanetta, L.C., Jr., Frequency of occurrence of lightning over voltages on distribution lines CIRED. 14th International Conference and Exhibition on (IEE Conf. Publ. No. 438) Volume 1, Issue, -5 June 1997 Page(s): 18/1-18/5 vol. [9] P. Hasse and J. Wiesinger, Handbook for Lightning and Grounding (in German), 4th ed. Munich, Germany: Pflaum, 1993. [1] Fujiang Mo, Yunping Chen, Jiangjun Ruan, Analysis on coupling mechanism and calculation method of the lightning induced surge on overhead transmission lines, Power System Technology,5,9():7-77. [11] N. M. Nor, S. Srisakot, H. Griffiths, and A. Haddad, Characterization of soil ionization under fast impulse, in Proc. 5th Int. Conf. Lightning Protection, Rhodes, Greece, Sep. 18,, pp. 417 4.. [1] S. Bourg, B. Sacepe, and T. Debu, Deep earth electrodes in highly resistive ground: Frequency behavior, in Proc. IEEE Int. Symp. Electromagnetic Compatibility, 1995, pp. 584 589. [13] ATP rule book, Can/Am EMTP User Group, 1995. [14] Cigré WG 33-1, Guide to Procedures for Estimating the Lightning Performance of Transmission Lines, Cigré Monograph No. 3, October 1991. [15] Eko Yudo Pramono, Reynaldo Zoro, Deny Hamdani, Hadi Parmono, Evaluation of Lightning Performance of Extra High Voltage 5 kv Transmission Lines Using Lightning Current Characteristic International Conference on Electrical Engineering and Informatics Institute Technology Bandung, Indonesia June 17-19, 7 [1] R. J. Mohr, coupling between open and shielded wire lines over a ground plane, IEEE Tans. Electromagnetic Compatibility, Vol. EMC-9, September 197, pp. 34-45. [17] A.M. Mousa, The soil ionization gradient associated with discharge of high s into concentrated electrodes, IEEE Trans. on Power Delivery, vol. 9, no. 3, pp. 19-177, July 1994. [18] G. Ala, P. L. Buccheri, P. Romano, F. Viola, Finite Difference Time Domain Simulation of Earth Electrodes Soil Ionization Under Lightning Surge Condition, IET Sci. Meas. Technol., Vol., No. 3, pp. 134-145, 8. [19] P. Yadee and S. Premrudeepreechacharn, Analysis of Tower Footing Resistance Effected Back Flashover Across Insulator in a Transmission System, Proc. of Int. Conf. on Power Systems Transients (IPST 7), Lyon, France, June 4-7, 7. [] B. Marungsri, S. Boonpoke, A. Rawangpai, A. Oonsivilai, and C. Kritayakornupong Study of Tower Grounding Resistance Effected Back Flashover to 5 kv Transmission Line in Thailand by using ATP/EMTP, International Journal of Electrical Power and Energy Systems Engineering : 9. 84