Customer Requirements Commercial Secondary Service

Similar documents
SPECIFICATIONS FOR THE INSTALLATION OF CONDUIT SYSTEMS IN RESIDENTIAL SUBDIVISIONS. Notification of Completed Conduit Sections

SPECIFICATIONS FOR THE INSTALLATION OF CONDUIT SYSTEM(S) FOR STREETLIGHTS. 1 Definitions. 2 Scope of Work. 3 Extent of Work

Page Electric Utility Service Specifications

Section. DEVELOPMENT STANDARDS City of Ellensburg ILLUMINATION STANDARDS

SECTION 5 TRANSFORMERS

Customer Connection Guide Updates Effective May 2017

Customer Requirements RF Antenna Installations

2' x 3' Polymer Pull Box Cover 4'-0" 7'-0" 24" x 76" Access Opening 3'-6"

SECTION UNDERGROUND POWER DUCT AND SUB-STRUCTURES. A. Section : Trenching, Backfilling, and Compacting

Electric Service Guide. Residential Subdivision

Utility Structures. Utility vaults, trenches, transformer pads Electrical Pole Bases and switching cubicles

SAUSALITO-MARIN CITY SANITARY DISTRICT MISCELLANEOUS UPGRADES PROJECT. Addendum No. 2

MH Table of Contents Standard Title/Scope Page Table of Contents SCE Public

EXCAVATION AND BACKFILL

SECTION 58 PRECAST CONCRETE BOX CULVERT. This work consists of furnishing and installing Pre-cast Concrete Box Culverts.

Manholes Table of Contents

Work Type Definition and Submittal Requirements Work Type: Subsurface Utility Engineering (SUE)

CITY OF LA MARQUE CHAPTER GRAPHIC REQUIREMENTS CONSTRUCTION PLAN AND MISCELLANEOUS REQUIREMENTS

A. Deviation from this standard must be approved by the Project Architect.

NEW OR UPGRADED ELECTRICAL SERVICE

SECTION 39 - MANHOLES TABLE OF CONTENTS

.1 Applicability: These criteria shall be applied as follows:

Delivering Reliability. Services. Strength You Can Count On. oldcastleprecast.com/services

CONTINUING EDUC ATION

Existing and proposed contours at 1-foot intervals. The fill and/or excavation quantities in cubic yards.

Precast Concrete. Installation Guide V GR-WI-599. Page 1

CONSTRUCTION SPECIFICATION FOR PRECAST REINFORCED CONCRETE BOX CULVERTS AND BOX SEWERS

Plastibeton Trench System. Installation Packet

SECTION MANHOLES

3.1 Overview of ATCO Electric s URD System Design

TECHNICAL SPECIAL PROVISIONS

PROPOSED FIBER OPTIC CONDUIT INSTALLATION E. 50TH ST. AND S. COTTAGE GROVE AV. CHICAGO, ILLINOIS

PART 4 STANDARD DRAWINGS FOR CONSTRUCTION

NORTH HARRIS COUNTY REGIONAL WATER AUTHORITY. Section ELECTRICAL IDENTIFICATION

MECKLENBURG COUNTY. Land Use and Environmental Service Agency Code Enforcement 2/9/11 ELECTRICAL CONSISTENCY MEETING. Code Consistency Questions

HDD Training. HDD Construction Process. Mark Miller, PE Jon Robison, PE

CITY OF LOMPOC DEVELOPMENT ASSISTANCE BROCHURE ENCROACHMENT PERMITS AND PUBLIC IMPROVEMENT PLANS

Guidelines for the Preparation of Traffic Signal & Intelligent Transportation System Plans on Design-Build Projects August 2007

TAXIWAY B NORTH ROAD RUNWAY TAXIWAY C NORTH ROAD VICINITY MAP. Plans Prepared By:

LA DOTD s Nighttime Standards for Construction Operations. Presented by: Tom Ervin Traffic Solutions, Inc.

SECTION PRECAST CONCRETE SECTIONAL MANHOLES

STATE UNIVERSITY CONSTRUCTION FUND

CHAPTER 29 PROJECT COMPLETION DOCUMENTS

CITY OF BEVERLY HILLS Department of Public Works and Transportation Civil Engineering Division STREET/ALLEY IMPROVEMENT PLAN REVIEW CHECKLIST

SECTION ELECTRICAL IDENTIFICATION

Plastibeton Trench System. Installation Packet

MANHOLES PART I: GENERAL. A. Precast Concrete Manholes

STANDARD BID ITEM NUMBERS

VILLAGE OF VILLA PARK CENTRAL BOULEVARD IMPROVEMENTS LOCATION MAP (NOT TO SCALE) CORTESI AVE. MYRTLE AVE. CENTRAL BLVD.

SECTION III SUBMITTALS AND APPROVALS

DIVISION APPROVED MATERIAL LIST AND STANDARD DETAILS

City/County Design Guidelines for Wireless Communication Facility in the Right of Way. Acquire Agreement with City of Knoxville/Knox County

SECTION CABLE TRAYS

For crossing under a railroad, contact the specific railroad company's engineering department.

UNDERGROUND UTILITY VAULTS

Journeyman's Practice Exam

Product Dimensions (Width x Length x Height) (inches)

POWER SERVICE DETAILS

CITY OF PINE CITY SMALL WIRELESS FACILITY DESIGN GUIDELINES

TABLE OF CONTENTS 7.0 CABLE INSTALLATION IN UNDERGROUND STRUCTURES

SPECIAL SPECIFICATION LIGHTNING PROTECTION SYSTEM

Minor Site Plan Application and Checklist Land Disturbing Activities

Guidelines for the Preparation of ITS & Signal Plans by Private Engineering Firms

BRASELTON WATER AND WASTEWATER DEPARTMENT CONSTRUCTION PLAN REVIEW CHECKLIST May 2006

SURVEYING THE UNDERGROUND

AWOS A Site Preparation Manual

PRO-RIB FENCE PANELS INSTALLATION GUIDELINES. Virtually Maintenance Free Available in 24 Colors Custom Heights Available by the Inch

Building a Hoop Barn: Setting posts and constructing knee wall

MERALCO Standards: Electrical Design. Engr. Eduard Mercado Electrical Design Team

SECTION III STANDARD DRAWINGS ROYSE CITY GENERAL CONSTRUCTION NOTES & DETAILS

SELF-ALIGNING PLASTIC INCLINOMETER CASING IN BOREHOLES. Model GEO-LOK. Roctest Limited, All rights reserved.

ACSA PLAN REVIEW CHECKLIST (Guideline Only) (4) Standard water and sewer general plan notes (attached).

EPG. by Chris C. Kleronomos

Grease Interceptor Design Checklist

SECTION WIREWAYS FOR RADIOLOGY EQUIPMENT

SECTION 3 IMPROVEMENT PLAN REQUIREMENTS

INSTRUCTIONS: 1. Record the transmittal letter number, date, and subject on the transmittal record sheet located in the front of the manual.

HP 2 SERIES Integral Driver - Solid State LED

SUBSTATION SECURITY WALL INSTALLATION MANUAL

High-Tensile Coated Wire Fence Installation Guide

MSD STANDARD DRAWINGS LOUISVILLE AND JEFFERSON COUNTY METROPOLITAN SEWER DISTRICT 700 WEST LIBERTY STREET LOUISVILLE, KENTUCKY

SECTION STEEL LIGHTING STANDARDS. 1. Electrical conduit and fittings; Section

City of Massillon Site Plan Checklist

ADDENDUM NO. 3 PROJECT: COURTLAND PUMP STATION CONTRACT: IFB NO COM.00030

FieldSmart Fiber Scalability Center (FSC) Installation Manual

Appendix C Construction Details

CITY OF TUMWATER 555 ISRAEL RD. SW, TUMWATER, WA (360)

SURVEYING THE UNDERGROUND

Diamond Knowledge Base. Inductive Loop Guide. Introduction

Standard Specifications

Driveway Alarm INSTALLATION MANUAL

PORT OF ST. HELENS SCAPPOOSE INDUSTRIAL AIRPARK PARALLEL TAXIWAY B RELOCATON AIP PROJECT ADDENDUM NO. 1

SOUTH DUBLIN COUNTY COUNCIL Traffic Management Centre Roads (Traffic and Transportation) Department

Application for Site Plan Review

MULTIPLE-FAMILY DESIGN REVIEW SUBMITTAL CHECKLIST

CITY OF MUSKEGO DRAFTING STANDARDS

RESIDENTIAL DEMOLITION PERMIT APPLICANT CHECKLIST

CONTINUOUS COUNTERPOISE ON POLES

GCG ASSOCIATES, INC. February 8, Mr. Nathaniel Strosberg, Town Planner 101 Main Street Town of Ashland Ashland, MA 01721

MILL HILL ARTS VILLAGE

Transcription:

Application Installation requirements for commercial services from Tacoma Power overhead or underground facilities. It applies to new construction or upgrades of older services. Electrical service may be provided in the following three methods: In This Standard I. Overhead Service II. Underground Service from Padmount Transformer III. Underground Service from Polemount Transformer (UGP) Topic See Page Terms 1 Responsibilities & Inspections 2 I Overhead Service 3 II Underground Service from Padmount Transformer 3 III Underground Service from Polemount Transformer (UGP) 3-11 Limitations 3 Selection of Conduit from Pole to SSB 4 Selection of SSB 5 SSB (Bottomless Plastic Enclosure) 6-7 SSB (Precast Concrete Vault) 8-11 Conduit Entry 11 Terms Term Construction Inspector Electrical Inspector Electrical Secondary Electrical Service New Services Engineer Secondary Service Box (SSB) Definition Representative from Tacoma Power T&D Construction Staff. A preconstruction meeting with the Construction Inspector must happen prior to any construction. Call 253-381-3023. Tacoma Power electrical inspection staff that inspect for compliance to the Tacoma Power standards, Tacoma Electrical Code, NEC, WAC and Electric Service Handbook requirements. Conduit and cables (less than 600 volts) that connect from the transformer to the SSB. Utility owned. Conduit and cables from the transformer to the service entrance or from the SSB to the service entrance. Customer owned. Tacoma Power engineering staff that provide design, cost estimates, and coordination of the commercial secondary service project. A plastic or concrete vault designed to contain the point of connection for the electrical service which connects the electrical secondary cables to the electrical service cables. Transmission & Distribution Standards Page 1 of 11

Responsibilities and Inspections Construction Area Location of SSB SSB Work in Road Right-of-Way Electrical Secondary Conduit and Pole Conduit Riser Completion of the Pole Conduit Riser Electrical Secondary Cables & Connections Electrical Service Responsibility The New Services Engineer will work with the customer s electrical contractor to determine the location of the SSB on the customer s property. The customer s electrical contractor will install the SSB per this standard under the direction of the New Services Engineer. The customer s electrical contractor will be responsible for installing conduit in the road right-ofway per the requirements of the permitting agency. Permits to cut and restore the road and any other work in the road right-of-way must be obtained before work in the right-of-way can begin. A copy of the approved permit must be on site while the road work is being done. The customer s electrical contractor will install conduit from the SSB to the pole and a portion of the conduit riser on the pole according to Customer Requirements Standard C-UG-1200, Pole Conduit Riser. Tacoma Power T&D Construction Staff Tacoma Power T&D Construction Staff will: install the electrical secondary cables from the pole to the SSB or from the padmount transformer to the SSB, and make all connections at the SSB, at the pole and/or at the padmount transformer. The customer s electrical contractor will install the electrical service. Inspection by Construction Inspector Construction Inspector Construction Inspector Construction Inspector Not needed Not needed Electrical Inspector Transmission & Distribution Standards Page 2 of 11

I Overhead Service An overhead service drop may be provided for services of up to 400A (the New Services Engineer will determine if a 600A service can be furnished) provided that it meets all criteria of the overhead service drop. Contact New Services Engineer for information. II Underground Service from Padmount Transformer Underground service from a padmount transformer requires the installation of a primary underground system. Contact New Services Engineer. Pre-construction meeting with the Construction Inspector must happen prior to any construction. If the New Services Engineer determines an SSB is to be installed, see section Selection of SSB with Table 1 and Table 2 to help determine the size of SSB necessary per the size of electrical service. III Underground Service from Polemount Transformer (UGP) In areas with an existing overhead electrical system, an underground service from a polemount transformer (UGP) may be provided for services in accordance with the limitations in the table below. Contact New Services Engineer Pre-construction meeting with the Construction Inspector must happen prior to any construction. Limitations UGP s have the following limitations: Issue Maximum Service Panel Size Maximum Cable Size Minimum Wire Size Maximum Distance from Pole to SSB Maximum Number of Conduit Bends from Pole to SSB Single Phase: 400A Requirements Three Phase: Contact New Services Engineer See section Selection of SSB with Table 1 and Table 2, unless approved by New Services Engineer #10 AWG 200 feet 270 o (degrees) of bends / elbows, including the 90 o pole conduit riser elbow on the pole and the 90 o conduit elbow into a bottomless plastic SSB (if applicable) Transmission & Distribution Standards Page 3 of 11

Figure 1 Typical UGP SSB 10' max. 8' min. Pole Quadrants 2 & 3 are reserved for utility equipment. Quadrants 1 & 4 are reserved for climbing by utility personnel. In any case, pole quadrant to be used will be determined by the Construction Inspector at the pre-construction meeting. 4" min. To customer service entrance Pole Conduit Riser per C-UG-1200 36" Electrical Service Roadway Electrical Secondary Selection of Conduit From Pole to SSB The size and number of conduits required for the electrical secondary are listed below: Size of Service Panel Single Phase Service Conduit (Quantity and Size) up to 200A 1 2.5 300A to 400A 2 2.5 Three Phase Service Contact New Services Engineer Transmission & Distribution Standards Page 4 of 11

Selection of SSB The following tables will provide guidelines on how to select the type and size of SSB. In any case the customer s electrical contractor shall coordinate with the New Services Engineer on the type and size of the SSB to be used on the project. Bottomless plastic enclosure SSBs shall not be located in driveways, areas subject to vehicular loading, or in the public right-of-way. All precast concrete SSBs can be located in areas not subject to any vehicular loading, off-street or incidental traffic areas, or in the public rightof-way. All precast concrete SSBs shall have a non-skid type cover (see standard C-UG-2000 Customer Requirements, Precast Concrete Vaults Approved Vendors. All conduit quantities in Tables 1 and 2 are the sum total of electrical service and electrical secondary cables from customer and Tacoma Power respectively. Table 1 SSB Selection for Bottomless Plastic Enclosures (No Vehicular Loading) Tacoma Power Description Total Conduit (Quantity and Size) Cables (Max. Size) SSB (Small) 2 2.5 only 250 kcmil SSB (Large) 6 2.5 max or 4 4 max 350 kcmil Manufacturer and Model # PenCell #PE-20GS-2X PenCell #PE-20PL-2X-TAC PenCell #PE-30GS PenCell #PE-30PLX-TAC Tacoma Power MID # Base #19118 Cover #19437 Base #37920 Cover #37921 Table 2 SSB Selection for Precast Concrete Vaults (Off-Street, Incidental Traffic) Tacoma Power Description 233 Vault Total Conduit (Quantity and Size) 6 2.5 max or 4 4 max Cables (Maximum Size) 350 kcmil Manufacturer and Model # Tacoma Power MID # 554 Vault 8 4 max 500 kcmil 774 Vault 8 conduit max 750 kcmil If electrical service size exceeds 8 runs of 750 kcmil, New Services Engineer will determine quantity and size of SSBs or the use of a secondary service cabinet (see standard A-UG-1600 Secondary Service Cabinet ) See C-UG-2000 Customer Requirements, Precast Concrete Vaults Approved Vendors Transmission & Distribution Standards Page 5 of 11

SSB (Bottomless Plastic Enclosure) Step 1 2 3 4 5 Procedure Call Construction Inspector for pre-construction meeting prior to any construction. Establish location and final grade for the SSB and install SSB. Select size of SSB per Table 1. o SSB covers shall have Tacoma Power embossed on them for identification purposes. Bottomless SSBs shall not be located in driveways, areas subject to vehicular loading, or in the public right-of-way. SSBs shall not be placed in a depression or in low areas that would tend to fill with water or silt. Ensure there are no rocks between SSB base and cover to avoid damage to the cover. The top of the SSB cover shall be: o 2 inches above final grade in landscaped areas. o flush with final grade in paved areas. Establish location of and install pole conduit riser per standard C-UG- 1200 Customer Requirements, Pole Conduit Riser. Dig trench from the SSB to the service entrance and to the pole. Dig service and secondary trenches to the same side of the SSB, property side of SSB preferred. On private property, the trench shall be deep enough to maintain a minimum of 24 inches of cover over the conduit. In road right-of-way, the trench shall be deep enough to maintain a minimum of 36 inches of cover over the conduit. Permits from local governmental agency must be obtained before any work in the road right-of-way can begin and a copy of the approved permit on site while the road work is being done. The trench must be deep enough at the SSB so the conduit elbow(s) can be terminated vertically within the SSB. The trench should be dug as straight as possible and the trench bed leveled and free of rocks larger than 2 inches diameter. Install conduit from SSB to the service entrance and to the pole. From pole to SSB, conduit shall be 2.5 or 4 Sch. 40 gray PVC. Excavate beneath the SSB and insert the 90 conduit elbows. All conduit must be at the same end of the SSB and grouped closely together (property side of the SSB preferred). Conduit ends shall extend vertically 2 inches above the bottom of the SSB. Identify conduit ends with customer building address. Install bell ends on the conduit ends. Do not glue bell ends inside SSB. Transmission & Distribution Standards Page 6 of 11

SSB (Bottomless Plastic Enclosure) (continued) 6 7 8 9 10 Inspections for conduit (BEFORE Backfill) are as follows: From the service entrance to the SSB inspection and approval by the Electrical Inspector. From the pole to the SSB, including the SSB inspection and approval by the Construction Inspector. Backfill the trench. Per the requirements of any permits and site requirements of Tacoma Power and others. Use available clean material. Pieces of scrap cable and other construction items must not be buried in the trench. Large rocks must be removed and if native soil is rock, sand bedding may be required. Tamp the soil, leaving a slight mound to allow for settling. Pull in electrical service cables from the service entrance to the SSB. Leave 4 feet minimum of cable, measured from the top of the SSB, inside the SSB. Ensure any parallel cables have matching phase tapes. Identify cables with customer building address. Ensure the following has been done: All applicable fees are paid. All right-of-way and easement issues are resolved (if any). All inspections have been passed. Tacoma Power T&D Construction Staff will: complete the pole conduit riser. pull in electrical secondary cables from the pole to the SSB. energize the service. Transmission & Distribution Standards Page 7 of 11

Figure 2 Typical SSB (Bottomless Plastic Enclosure) SSB (Precast Concrete Vault) Step 1 2 Procedure Call Construction Inspector for pre-construction meeting prior to any construction. Establish location and final grade for the SSB and install the SSB. Select size of SSB per Table 2. o SSB covers shall have Tacoma Power embossed on them for identification purposes. Concrete SSBs can be located in areas not subject to any vehicular loading, off-street or incidental traffic areas, or in the public right-of-way. SSBs shall not be placed in a depression or in low areas that would tend to fill with water or silt. The top of the SSB cover shall be: o 6 inches above final grade in landscaped areas. o flush with final grade in paved areas. Transmission & Distribution Standards Page 8 of 11

SSB (Precast Concrete Vault) (continued) 3 4 5 6 Establish location of and install pole conduit riser per standard C-UG-1200 Customer Requirements, Pole Conduit Riser. Dig trench from the SSB to the service entrance and to the pole. On private property, the trench shall be deep enough to maintain a minimum of 24 inches of cover over the conduit. In road right-of-way, the trench shall be deep enough to maintain a minimum of 36 inches of cover over the conduit. Permits from local governmental agency must be obtained before any work in the road right-of-way can begin and a copy of the approved permit on site while the road work is being done. The trench should be dug as straight as possible and the trench bed leveled and free of rocks larger than 2 inches diameter. Install conduit from SSB to the service entrance and to the pole (see Figure 3). From pole to SSB, conduit shall be 2.5 or 4 Sch. 40 gray PVC. Install conduit 4 inches minimum into the SSB perpendicular to the vault wall. Identify conduit ends with customer building address. Install bell ends on the conduit ends. Do not glue bell ends inside SSB. Grout around knockouts. Inspections for conduit (BEFORE Backfill) are as follows: From the service entrance to the SSB inspection and approval by the Electrical Inspector. From the pole to the SSB, including the SSB inspection and approval by the Construction Inspector. Transmission & Distribution Standards Page 9 of 11

SSB (Precast Concrete Vault) (continued) Backfill the SSB excavation as shown below: 7 Clean fill as directed by the Construction Inspector Vault base 9 min. of 5/8 minus crushed rock well compacted and extending 12 min. beyond the edge of the vault in all directions. 8 9 10 12 Backfill the trench. Per the requirements of any permits and site requirements of Tacoma Power and others. Use available clean material. Pieces of scrap cable and other construction items must not be buried in the trench. Large rocks must be removed and if native soil is rock, sand bedding may be required. Tamp the soil, leaving a slight mound to allow for settling. Pull in electrical service cables from the SSB to the service entrance. Leave the following minimum length of each service cable, measured from the top of the SSB, inside the SSB: o 233 or 554 vault 10 feet of cable o 774 vault 15 feet of cable Ensure any parallel cables have matching phase tapes. Identify cables with customer building address. Ensure the following has been done: All applicable fees are paid. All right-of-way and easement issues are resolved (if any). All inspections have been passed. Tacoma Power T&D Construction Staff will: complete the pole conduit riser. pull in electrical secondary cables from the pole to the vault. energize the service. Transmission & Distribution Standards Page 10 of 11

Figure 3 Typical SSB (Precast Concrete Vault) Conduit Entry Conduit entering the vault shall consistently enter the left side knockouts on all sides. This is for the training of cable in the vault in the same direction. The Construction Inspector may approve exceptions on a site-by-site basis only. In any case, the service conduit entry and the secondary conduit entry shall allow all cables to be trained in the same clockwise or counter-clockwise direction (See Figure 3). Transmission & Distribution Standards Page 11 of 11