TECHNICAL NOTE 2.0. Overvoltages origin and magnitudes Overvoltage protection

Similar documents
Transformers connected via a cable Overvoltage protection

Selection of MO surge arresters Overvoltage protection

High voltage engineering

Protection against unacceptable voltages in railway systems

Modeling insulation in high-voltage substations

LIGHTNING OVERVOLTAGES AND THE QUALITY OF SUPPLY: A CASE STUDY OF A SUBSTATION

PREVENTING FLASHOVER NEAR A SUBSTATION BY INSTALLING LINE SURGE ARRESTERS

10. DISTURBANCE VOLTAGE WITHSTAND CAPABILITY

INTERNATIONAL STANDARD

Utility System Lightning Protection

When surge arres t ers are installed close to a power transformer, overvoltage TRANSFORMER IN GRID ABSTRACT KEYWORDS

Lightning performance of a HV/MV substation

CHAPTER 2. v-t CHARACTERISTICS FOR STANDARD IMPULSE VOLTAGES

Session Four: Practical Insulation Co-ordination for Lightning Induced Overvoltages

Analysis of lightning performance of 132KV transmission line by application of surge arresters

Insulation Coordination Fundamentals Where Arrester and Insulator Characteristics Meet

Electric Stresses on Surge Arrester Insulation under Standard and

GIS Disconnector Switching Operation VFTO Study

Insulation Co-ordination For HVDC Station

Effect of High Frequency Cable Attenuation on Lightning-Induced Overvoltages at Transformers

Earthing of Electrical Devices and Safety

ROEVER ENGINEERING COLLEGE ELAMBALUR, PERAMBALUR DEPARTMENT OF ELECTRICAL & ELECTRONICS ENGINEERING

The Many Uses of Transmission Line Arresters

HIGH VOLTAGE Insulation Coordination

Type DMX-N Surge Arresters Maximum System Voltage 2 to 36 kv

Tab 2 Voltage Stresses Switching Transients

ABSTRACT 1.0 INTRODUCTION LIST OF SYMBOLS

DEPARTMENT OF ELECTRICAL AND ELECTRONICS ENGINEERING QUESTION BANK SUBJECT CODE & NAME : EE 1402 HIGH VOLTAGE ENGINEERING UNIT I

ABSTRACTS of SESSION 6

Maximum Lightning Overvoltage along a Cable due to Shielding Failure

INSTALLATION OF LSA ON A 400 KV DOUBLE-CIRCUIT LINE IN RUSSIA

Low voltage products in high altitudes

Lightning Flashover Rate of an Overhead Transmission Line Protected by Surge Arresters

A Case Study on Selection and Application of Lightning Arrester and Designing its Suitable Grounding Grid

Lightning overvoltage and protection of power substations

MEDIUM VOLTAGE PRODUCT. TJP 6.1, TJP 6.2 Indoor voltage transformers

Chapter 1. Overvoltage Surges and their Effects

ANALYSIS OF VOLTAGE TRANSIENTS IN A MEDIUM VOLTAGE SYSTEM

MODIFICATION OF THE ARRESTER ARRANGEMENT WHEN CONVERTING THE METHOD OF NEUTRAL TREATMENT

TECHNICAL REPORT. Insulation co-ordination

Calculation of Transient Overvoltages by using EMTP software in a 2-Phase 132KV GIS

Substation Insulation Coordination Study

2000 Mathematics Subject Classification: 68Uxx/Subject Classification for Computer Science. 281, 242.2

MEDIUM VOLTAGE PRODUCT. PARAMETERS GUIDE How to specify the indoor instrument transformers correctly

Disclosure to Promote the Right To Information

Modeling of overhead transmission lines with line surge arresters for lightning overvoltages. Poland

University of Zagreb Faculty of Electrical Engineering and Computing

OVERVOLTAGE PROTECTION. Dimensioning, testing and application of metal oxide surge arresters in low-voltage power distribution systems

Metal-Oxide Surge Arresters Integrated in High-Voltage AIS Disconnectors An Economical Solution for Overvoltage Protection in Substations

Computation of Lightning Impulse Backflashover Outages Rates on High Voltage Transmission Lines

APPLICATION GUIDELINES. Overvoltage protection Metal-oxide surge arresters in medium-voltage systems

Parameters Affecting the Back Flashover across the Overhead Transmission Line Insulator Caused by Lightning

Insulation Test System

The Lightning Event. White Paper

GIS Instrument Transformers: EMC Conformity Tests for a Reliable Operation in an Upgraded Substation

TECHNICAL SPECIFICATION

MEDIUM VOLTAGE PRODUCT. TJP 5.x Indoor voltage transformers

Current monitoring relays CM-SRS.2 for single-phase AC/DC currents

Lightning Protection of Distribution Substations by Using Metal Oxide Gapless Surge Arresters Connected in Parallel

Power Quality and Reliablity Centre

DIFFERENCE BETWEEN SWITCHING OF MOTORS & GENERATORS WITH VACUUM TECHNOLOGY

Fixed Series Compensation

A TECHNICAL REVIEW ON CAPACITOR BANK SWITCHING WITH VACUUM CIRCUIT BREAKERS

Analysis of MOV Surge Arrester Models by using Alternative Transient Program ATP/EMTP

Voltage monitoring relays CM-ESS.1 for single-phase AC/DC voltages

Electronic timer CT-YDE Star-delta change-over with 1 c/o (SPDT) contact

7P Series - Surge Protection Device (SPD) Features 7P P P

Comparison of switching surges and basic lightning impulse surges at transformer in MV cable grids

Relion 605 series Self-Powered Feeder Protection REJ603 Product Guide

Shunt Reactor Switching

Lumped Network Model of a Resistive Type High T c fault current limiter for transient investigations

ABB 1. Multifunctional three-phase monitoring relays. CM-MPS.11, CM-MPS-21, CM-MPS.31 and CM-MPS.41 Data sheet. Features. Approvals. Marks.

Current monitoring relays CM-SRS.1 for single-phase AC/DC currents

Analysis of Major Changes to Arrester Standards IEC STEVE BREWER

Three-phase monitoring relay CM-PVE

Hazard of Induced Overvoltage to Power Distribution Lines Jiang Jun, Zhao Rui, Chen Jingyang, Tian Hua, Han Lin

ABB 1. Multifunctional three-phase monitoring relays. CM-MPN.52, CM-MPN.62 and CM-MPN.72 Data sheet. Features. Approvals. Marks.

Coordination of surge arresters in DC 3 kv railway traction system field tests

What is the Value of a Distribution Arrester

Effect of Surge Arrester on Overhead Transmission Lines as Shield against Over Voltage

OVERVOLTAGE PROTECTION OF POLE MOUNTED DISTRIBUTION TRANSFORMERS

CHOICE OF MV FEEDER BIL TO MAXIMIZE QOS AND MINIMIZE EQUIPMENT FAILURE

A Study on Lightning Overvoltage Characteristics of Grounding Systems in Underground Distribution Power Cables

SURGE PROPAGATION AND PROTECTION OF UNDERGROUND DISTRIBUTION CABLES

Lightning Overvoltage Performance of 110 kv Air-Insulated Substation

Three-phase monitoring relay CM-PBE

Electronic timer CT-EBE Flasher starting with OFF, 1 c/o (SPDT) contact

Investigation of Transmission Line Overvoltages and their Deduction Approach

2. Current interruption transients

Simplified Approach to Calculate the Back Flashover Voltage of Shielded H.V. Transmission Line Towers

A Review Comprehension: Guideline for Testing of HV, EHV and UHV Substation Equipment

The line-lightning performance and mitigation studies of shielded steelstructure

Effect of Shielded Distribution Cables on Lightning-Induced Overvoltages in a Distribution System

This document is a preview generated by EVS

Computer Based Model for Design Selection of Lightning Arrester for 132/33kV Substation

Lightning phenomena and its effect on transmission line

DEPARTMENT OF EEE QUESTION BANK

Research Article A Simplified High Frequency Model of Interleaved Transformer Winding

Insulation Test System

Simulation of Short Circuit and Lightning Transients on 110 kv Overhead and Cable Transmission Lines Using ATP-EMTP

Transcription:

ECHNICAL NOE 2.0 Overvoltages origin and magnitudes Overvoltage protection

he ECHNICAL NOES (N) are intended to be used in conjunction with the APPLICAION GIDELINES Overvoltage protection Metaloxide surge arresters in mediumvoltage systems. Each ECHNICAL NOE gives in a concentrated form additional and more detailed inforion about various topics of MO surge arrester and their application under normal and special service conditions. First published March 2019

ARICLE OVERVOLAGE OR CHAPER PROECION ILE 3 Overvoltages in electrical power systems Overvoltages in electrical supply systems result from lightning and switching actions and endanger electrical equipment. hey can lead to electrical breakdown or a reduction of the lifetime of equipment. 1 Introduction An overvoltage is per definition any voltage between phase and earth or between phases having a peak value exceeding the peak of the highest voltage of the system divided by 3 or exceeding the amplitude of the highest voltage of the system, respectively. Ongrid overvoltages (OV) are due to short circuits or earth faults in the system, load rejections or resonances. hese overvoltages with power frequency generally do not endanger the insulation of equipment and are therefore not discussed in the following. 2 Origin of overvoltages Figure 1: Illustration of the global electric circuit (adapted from Rakov and man). Overvoltage values are expressed in p.u., 1 p.u. = s 2/ 3 (IEC 600711) his means that overvoltages are in any case related to the system voltage. Voltages and overvoltages are classified according their shape and duration. We must distinguish between continuous voltage and temporary overvoltage (OV) with power frequency, and transient overvoltages due to lightning effects and switching operations in the time range of microseconds to milliseconds. Electrosphere 2.1 From lightning to overvoltage Figure 1 shows the principle of the global electric circuit. It is assumed that the earth is charged negatively and the atmosphere in a height of about 50 km is charged positively. he electrosphere as indicated in Figure 1 is conducting. Due to the electric field between the electrosphere and the earth a fairweather current flows between the electrosphere and the earth. If a lightning strike occurs the thundercloud will be discharged to earth. At the same time a charge equalization will take place due to the fairweather current. With this very simplified model of a closed current circuit the phenomenon of lightning can be illustrated. Shown scheically under the thundercloud are precipitation, lightning, and corona. Lightning can be defined as a transient, highcurrent (typically tens of kiloamperes) electrical discharge in air whose length is measured in kilometers. he lightning discharge in its entirety is usually termed a lightning flash or a flash. Fairweather current

4 ECHNICAL NOE OVERVOLAGES Figure 2: Cloudtoground lightning categorization according to Berger. op left: downward negative; top right: upward positive; bottom left: downward positive; bottom right: upward negative. A lightning discharge that involves an object on ground or in the atmosphere is referred to as a lightning strike. he terms stroke or component stroke apply only to components of cloudtoground discharges. Cloudtoground discharges constitute about 25% of global lightning activity. It is believed that downward negative lightning flashes account for about 90% or more of global cloudtoground lightning, and that 10% or less of cloudtoground discharges are downward positive lightning flashes. pward lightning discharges are thought to occur only from tall objects (higher than 100 m or so) or from objects of moderate height located on mountain tops. he types of lightning are shown in Figure 2 (Cigré B 549). A lightning flash consists of one or more discharges. For downward negative lightnings 3 to 4 discharges (strokes) per flash are typically. he time duration of a stroke is in the range of some ten microseconds, the time duration between the strokes is in the range of 30 to 40 milliseconds. he lightning current parameters are taken from lightning statistics. Figure 3 shows a statistical evaluation of worldwide measured lightning currents. he curve of the mean value shows the probability of the occurred lightning current peak values. he mostly negative cloudtoground lightning strikes that occur have current peak values between app. 14 ka (95% probability) and 80 ka (5% probability). With a probability of 50% the following values are reached or exceeded: Current peak value: 30 ka Rise time: 5.5 µs ime to half value: 75 µs A peak value of 20 ka with a probability of 80% is often used in standardization work, and for test and coordination purposes of MO surge arresters. Lightning currents with peak values above 100 ka are very rare. Figure 3: Statistical evaluation of lightning measurements all over the world. Described is the probability of occurrence above the lightning current s peak values (adapted from Cigré survey). 99.0 P% 90.0 70.0 50.0 20.0 10.0 2.0 0.2 0 10.0 100.0 I ka

OVERVOLAGE PROECION 5 However, in geographical regions where winter thunderstorms occur, extreme lightning strikes can reach peak values above 250 ka, with halftime values of 2,000 µs. hese are typically downward positive discharges. Assuming that in mediumvoltage systems a lightning current of 30 ka diverts in the case of a fardistance direct lightning strike, and that flashovers between phases and at insulators occur, one can get a nominal discharge current of I n = 5 ka. A wave shape of approxiely 8/20 µs results for the lightning current if a flashover occurred at one or more insulators. 2.1.1 Possible points of lightning strike Overvoltages in distribution systems occur due to direct lightning strikes to a phase wire, lightning strikes to a pole, or lightning strikes to earth or earthed objects near an overhead line. Figure 4 gives an overview about the possible points of lightning strikes. It is worth to mention that the earthing of the poles and substations is of high importance and must be in all cases as low as possible. he lower the footing resistance of the poles and the earth of substations is, the better will be the protection. An earth resistance of less than 10 Ω is generally recommended. In some special cases earth resistance values of 1 Ω or 2 Ω are requested. A worst case to be considered is a direct lightning strike in a phase wire in front of a substation without an insulator between the point of strike and the substation. In this case it can be assumed that a lightning current of e.g. 20 ka diverts in both directions of the line and half of the lightning current (10 ka) travels undamped into the substation. Figure 4: Points of lightning strikes to an overhead line. Fardistance lightning to the phase wire Lightning to the top of a pole Lightning to the phase wire close to the substation Direct lightning to a substation or the phase Nearby lightning into the earth Lightning protection system resistance of the pole resistance of the substation

6 ECHNICAL NOE OVERVOLAGES 2.1.1.1 Direct lightning to a substation or to the phase wire in front of a substation A substation must be protected by a lightning protection structure () to avoid any direct lightning to equipment in the substation. his can be done by Franklin Rods or earth shielding wires above the substation. he total lightning current must be diverted directly to earth, see the right part of Figure 5. he earth resistance of the substation has to be as low as possible. MO surge arresters can protect only against surges travelling along the line into the substation. he worst case of a lightning strike is the direct strike to the phase wire in front of the substation without any insulator between the point of strike and the equipment to be protected. In Figure 5 the principle is shown. Assuming the lightning strike has a lightning current = 20 ka. he lightning current will be divided, so that a current impulse with a peak value of 10 ka appears on both sides of the point of strike, travelling along the line in both directions. he current is coupled with the surge impedance Z and this results in a lightning overvoltage u travelling with the speed of light along the line. Assuming a surge impedance of Z = 450 Ω a voltage with a peak value of u = 4,500 kv will occur. his is too high and will destroy the transformer. herefore, MO surge arresters at the entrance of the substation are a must. 2.1.1.2 Lightning to the phase wire close to the substation and fardistance lightning strike Figure 6a shows the case that a lightning strikes the phase wire and only one pole is between the point of strike and the transformer. he same values as in the case shown in Figure 5 are assumed. he voltage u travels along the line in direction of the substation. In the moment when the voltage arrives at the insulator of the pole and becomes higher than the flashover voltage of the insulator the insulator will flash over and a part of the lightning current will be diverted via the pole to the earth, which results to a breakdown of the voltage. As long as the earth resistance is not zero the voltage will rise again and travel with a wave shape as indicated in Figure 6a in direction of the transformer. Figure 6b shows again a lightning strike in the phase wire, in this case some spans away from the substation. he same will happen as explained in the example above: in the moment the voltage wave reaches the flashover voltage of the insulator, a flashover occurs and the voltage will break down and rise again, depending on the earth resistor. his happens at each insulator, as indicated in Figure 6b. Finally, a voltage wave shape limited to the flashover value of the insulators, will arrive at the substation. Depending on the distance between the point of strike and the substation a considerable damping of the voltage wave will occur, which results in a reduction of the steepness of the overvoltage.

OVERVOLAGE PROECION 7 Figure 5: Principle of lightning strike to a substation Z 2 2 Z Figure 6a: Lightning strike to the phase wire close to the substation i Figure 6b: Fardistance lightning to the phase wire

8 ECHNICAL NOE OVERVOLAGES Figure 7: Direct lightning to the top of a pole ib ib RE,P pole Figure 8: Principle of nearby lightning i i H max,i Peak value of induced voltage Z 0 Mutual impedance between point of strike and overhead line h Height of overhead phase wire x Shortest distance between point ofstrike and line Lightning current Figure 9: Principle of switching overvoltages swsw RE,P RE,P sw Switching overvoltage

OVERVOLAGE PROECION 9 2.1.1.3 Lightning strike to the top of the pole Figure 7 shows the case of a direct lightning to the top of a pole (or an earthed shielding wire). If the earth resistance of the pole is assumed to be zero the whole lightning current would go directly into the earth. Because the earth resistance of a pole is never zero, a potential rise pole will occur due to the lightning current, as indicated in Figure 7. Assuming again a lightning current of = 20 ka and an unfavorable high earth resistance of = 100 Ω, an overvoltage of pole = 2,000 kv will arise on the pole. his voltage exceeds by far the voltage withstand value of the insulators, and a backflash from the pole to the phase wire will occur. Consequently, an overvoltage travels along the line in direction of the substation, as shown. 2.2 Switching overvoltages Switching overvoltages occur due to circuit breaker operations, disconnector operations, restrikes of circuit breakers and operation of fuses, to mention the main reasons. Switching actions may be intended or unintended. hey depend strongly on the circuit breaker characteristics and the line configuration and can be estied by system simulations. In mediumvoltage systems switching overvoltages are not so critical. hey can reach values up to 3.5 p.u. in a worst case. For a 24 kvsystem it would result to app. 68 kv. his value is normally not critical for the insulation. However, vacuum breakers can produce very steep overvoltages. In this case, and due to reflections critical overvoltages may occur. 2.1.1.4 Nearby lightning into the earth he principle of overvoltages induced in an overhead line is shown in Figure 8. If a lightning current hits the earth, or an earthed object close to the line, a voltage i will be induced into the phase wire because of the magnetic field H around the lightning current. he magnitude of the induced voltage can be approxied with the equation from Rusck: h max,i = Z 0 x x x Assuming a lightning current of = 20 ka, a mutual impedance of Z 0 = 30 Ω, a height of h = 5 m and a distance of x = 100 m, an induced overvoltage of max,i = 30 kv will appear on the phase wire.

10 ECHNICAL NOE OVERVOLAGES 3 Standardized voltage wave shapes he voltages and the overvoltages that stress the insulation are determined in amplitude, shape and time duration. For each class of voltages and overvoltages standard voltage shapes are determined that represent the effects of the original voltages with respect to test purposes and insulation coordination, see able 1. It must be understood that the wave shapes and magnitudes of the overvoltages occurring in the system due to lightning incidents and switching operations are never known. he standardized voltage wave shapes represent the critical parameters and are used for test purposes. Standardized voltages and overvoltages with power frequency (OV) are used in labs for insulation withstand tests of the arrester housings, and for evaluation of the OV performance of MO surge arresters. Lightning overvoltages with the wave shape 1.2/50 µs are used for voltage withstand tests of insulators, and therefore also for tests of the arrester housing. It is worth to mention that a very critical test for transformers is a voltage withstand test with a chopped lightning voltage impulse. his is because of the voltage breakdown (high d/dt) that stresses the windings of the transformer and may lead to unacceptable high voltage resonances in the transformer. Switching overvoltages with the wave shape of 250/2500 µs are not used for testing medium voltage equipment. 4 Summary Overvoltages in electrical systems result from lightning flashes and switching operations. hey can be power frequency overvoltages (OV) or transient overvoltages. Power frequency overvoltages (OV) generally do not endanger the insulation of electrical equipment. Most critical in mediumvoltage systems are transient overvoltages due to lightning flashes. heir magnitude depends only on the lightning current and can be extremely high. Depending on the point of strike of the lightning different wave shapes and magnitudes may occur. Switching overvoltages and induced overvoltages can occur quite frequently in mediumvoltage systems, but their magnitude is generally not so high to lead to a flashover or to endanger the insulation of equipment. However, due to the high occurrence rate they may weaken liquid and solid insulation (aging), which results finally in a reduction of the lifetime of the insulation. able 1: Classes and shapes of overvoltages, Standard voltage shapes and Standard withstand voltage tests (IEC 600711). Class Low frequency ransient Voltage or overvoltage shapes Continuous emporary Slow front Fastfront Veryfastfront 1/f 1/f f p 1 1/f1 1/f2 t t 2 2 Range of voltage or overvoltage shapes Standard voltage shapes f = 50 Hz or 60 Hz t 3600 s 1/f 10 Hz < f < 500 Hz 0,02 s t 3600 s 1/f 20 µs < p 500 µs 2 20 ms 0.1 µs < 1 20 µs 2 300 µs t 100 ns 0.3 MHz < f 1 < 100 MHz 30 khz < f 2 < 300 khz p 1 t t 2 2 Standard withstand voltage test f = 50 Hz or 60 Hz t a a 48 Hz f 62 Hz t = 60 s Shortduration power frequency test p = 250 µs 2 = 2500 µs Switching impulse test 1 = 1.2 µs 2 = 50 µs Lightning impulse test a a a o be specified by the relevant apparatus committees.

ABB Switzerland Ltd. PGHV Surge Arresters Jurastrasse 45 CH5430 Wettingen/Switzerland el. 41 58585 2911 Fax 41 58585 5570 Email: sales.sa@ch.abb.com abb.com/arrestersonline Additional inforion We reserve the right to make technical changes or modify the content of this document without prior notice. With regard to purchase orders, the agreed particulars shall prevail. ABB AG does not accept any responsibility whatsoever for potential errors or possible lack of inforion in this document. We reserve all rights in this document and in the subject ter and illustrations contained therein. Any reproduction, disclosure to third parties or utilization of its contents in whole or in parts is forbidden without prior written consent of ABB AG. Copyright 2019 ABB. All rights reserved Specifications subject to change without notice 1HC0138870 EN AA