modu420: Automation station

Similar documents
Fan-coil intelligent unitary controller

LONMARK Certified 14-Point Programmable Controller. Overview

LONMARK Certified 10-Point Programmable Controller. Overview

DDC volume flow controller

ECP-103 Series. ECP-103 Series. 10-Point Free Programmable Controller. Applications. Features

EY-EM 527: Remote I/O module, ecolink527

ECP-400 Series. ECP-400 Series. 24-Point Free Programmable Controller. Applications. Features

EY-EM 522, 523: Remote I/O module, ecolink522, 523

EYL225: nova225, Compact automation station

ECL-VAV-N. Features & Benefits

ECB-103 BACnet B-ASC 10-Point Programmable Controllers

NRT 105: Electronic fan-coil controller, equiflex

EYK220: nova220, Compact automation station with BACnet interface

Control solutions Biofloor

Lonbox PIO4014 Users Manual

SRC-110 Series Zone Controllers with Modbus RTU

Electrical data Nominal voltage AC/DC 24 V Nominal voltage frequency

CONTA-ELECTRONICS. Converter Units

NRT 300: Electronic air-conditioning controller, heating/cooling, equiflex

DUAL 4-20 MA NETWORK BRIDGE. Voltage. Regulator. Neuron CPU. Ohm Sense Resistor. Model 1400A Block

XIOC technology and networking modules

92.450/1. EYK 220: nova220, Compact automation station with BACnet interface. Sauter Systems

FX10 Standard Programmable Electronic controller for HVAC and refrigeration applications. Features and Benefits

Sensor Plug-In Description / Documentation

VFSC9 ELECTRONIC SPEED CONTROLLER. Mounting and operating instructions

Power amplifier for thermic valve actuators

Electro Controls. Input-Output Modules WattsIndustries.co.uk

High-quality digital indicator for panel mounting Model DI35-M, with multi-function input Model DI35-D, with two inputs for standard signals

Analogue temperature controllers

PolyGard Digital Transmitter DGC DT-02

Viconics VT76x7 Series Rooftop Unit Controllers Engineering Guide Specification

EQJW145. Content: 1 General. 2. Indicators and operating controls 3. Putting into service (by a technician) 4. How to operate (user)

43.019/1. NRT 300: Electronic controller for air-conditioning (heating/cooling) Sauter Components

Electronic Step Controller

Radiocontrol F. Floor Heating Controller Radio control system for floor heating

LON I/O Module DR-N MCU4-AC Art. no.: MTN881811

QFM21... Duct sensors. Symaro. for relative humidity and temperature

Thermostat P. Thermostats Electronic room thermostat with clock for thermal actuators

Data Acquisition Modules/ Distributed IO Modules

Electrical data Nominal voltage AC/DC 24 V Nominal voltage frequency

Electrical data Nominal voltage AC/DC 24 V Nominal voltage frequency

Functional description "BIU-2ILT"

Compact room automation stations, BACnet MS/TP, AC 24 V

Gateway EnOcean/LonWorks

Electrical data Nominal voltage AC/DC 24 V Nominal voltage frequency

FTT-10A Free Topology Twisted Pair Transceiver Model 50051

Electrical data Nominal voltage AC/DC 24 V Nominal voltage frequency

NetBiter I/O Extender 4RO 6RTD 8DIO - DAIO User Manual Revision 1.00

Electrical data Nominal voltage AC/DC 24 V Nominal voltage frequency

ELECTRONIC THERMOSTAT: T920

Sauter Components

21 VA (l max 20 5 ms) Connection Cable 1 m, 4 x 0.75 mm 2 Functional data Factory settings Variable Setting Torque Inhibiting torque

Excel 10 W7761A Remote Input/Output Device

PLC-K506 Series FEATURES DESCRIPTION FEATURES

Manual triggering of the adaption by pressing the «Adaption» button or with the PC-Tool

Functional data Factory settings Variable Settings

11 VA Connection Cable 1 m, 4 x 0.75 mm 2 Functional data Factory settings Variable Setting Torque (nominal torque) Motor Spring return

Electrical data Nominal voltage AC/DC 24 V Nominal voltage frequency

Intelligent Compact Controller

Outside Temperature Sensors

Wireless multizone receiver RDE-MZ6

SRA 2250/6 RESISTOR ARS-01 RESISTOR AUTOMATICS

R7L-YV2. DC VOLTAGE OUTPUT MODULE, 2 points MODEL BEFORE USE... POINTS OF CAUTION COMPONENT IDENTIFICATION INSTRUCTION MANUAL R7L-YV2

Technical Information itemp TMT180

High-quality digital indicator for panel mounting Model DI35-M, with multi-function input Model DI35-D, with two inputs for standard signals

n FRONT PANEL CONFIGURATIONS

KNC-PLC-K506 Series FEATURES DESCRIPTION FEATURES

control & display PROGRAMMABLE SENSOR CONTROLLER COMPLETE VERSATILITY OF SENSOR MANAGEMENT & DATA COMMUNICATIONS

US2, US4, US6 Electronic step controllers

Gateway EnOcean/LonWorks

HV / MV / LV electrical network quality analyzers Class A. Communication port: local, modem, integrated Ethernet, multi-point

ERV-M ELECTRONIC FAN SPEED CONTROLLER. Mounting and operating instructions

The universal input/output device is a DIN rail mounted device. It is connected to the EIB via a bus connecting terminal.

Room Temperature Controllers. for heating and cooling systems

Room Sensors. for relative humidity and temperature

Room Sensors. In ventilating and air conditioning plants to acquire relative humidity and temperature in rooms. Humidity measuring range

R7420B. MicroniK 100 HONEYWELL TEMPERATURE CONTROLLER PRODUCT DATA GENERAL FEATURES

Controller for the Implementation of a Central or Decentralized Electrohydraulic System

Room Temperature Controllers. for heating and cooling systems

Technical data. Safety notes. T3-LR24A-SR en v Subject to changes 1 / 2

Netbiter IO Extender 4RO 6RTD 8DIO DAIO 8AIV 8AIIS

NRT 107: Room- and supply-temperature controller, equiflex

Room sensors. In ventilating and air conditioning plants to acquire relative humidity and temperature in rooms. Humidity measuring range

STR-LCF. Security Advice Caution. Notes on Disposal. Electronic Fan Coil Thermostat (Flush mounting) Datasheet. Application

Overview of types. Technical data

Self-learning Room Temperature Controller Receiver

PHOENIX CONTACT - 03/2007

Differential pressure sensors

em4 local - Robust Specific characteristics Part number

LX Scheduler. Installation Instructions LX-SCHEDL-0. Mounting. Applications. North American Emissions Compliance. Installation

QUINT-PS/ 3AC/24DC/10

J IPC IGBT power converter

UniStream Uni-I/O Modules

Electronic Air / Fuel Ratio Control System

PROMUX Distributed MODBUS I/O Modules Catalog and Design Guide

Compact room automation stations, BACnet/IP, AC 24 V

Software Description SRCN_HWL_9_1_03 for SRC 04 FTT and SRC 65 FTT

DIN 22.5/17.5 Size Lineup of A Wide Range of Measuring and Monitoring Relays. Model Number Structure

ADC5000 SERIES. AC/DC Switch Mode Power Supplies and Rectifiers for Industrial and Telecom Applications. 60W, 125W and 250 W

Electrical data Nominal voltage AC/DC 24 V Nominal voltage frequency

Transcription:

SAUTER EY-modulo 4 PDS 92.285 en Product Data Sheet EY-AS420 modu420: Automation station How energy efficiency is improved Integrated pulse counter to measure and optimise energy consumption. Integrated calendar function enables operation of the plant to be adapted to usage with minimal energy consumption. Areas of application Can be used for a wide variety of applications such as fan-coil, control of chilled beams, heating pumps, multispeed ventilation plants, energy measurement, cooling and heating systems, or roof-top units. Features Compact, freely programmable LON automation station Supports LonMark object types #0, #1, #3, #20020, #3300 and #20100 LonMark -certified as per Interoperability Guideline, Version 3.4 Lower housing can be separated so that terminals and electronics can be installed separately. Audio jack plug for rapid access to the LON network. LNS plug-in for rapid programming of the automation station Technical description 24 V~/= power supply Universal inputs and outputs can be configured via software 6 universal inputs 3 fuse-protected universal outputs 5 Triac outputs 2 scheduler objects TP/FT 10, 78 kbps Neuron 3150 processor Products Type EY-AS420F001 Description Compact automation station Technical data Electrical supply Permitted ambient conditions Power supply 24 V~ (50/60 Hz) ± 15% Operating temperature 0 70 C 24 V= (20.4 27.6 V) Transport and storage temperature 20 70 C Power consumption 12 VA max. Humidity 0 90% rh no condensation Inputs, outputs Universal inputs 6 Standards, guidelines and directives Resolution 16 bit analogue/digital Degree of protection IP 10 (EN 60529) Can be used as: Protection class III (EN 60730-1) Counters Potential-free contact Environmental class 3K3 (IEC 60721) Analogue input U/I/R CE conformity as per Temperature measurement NI1000, NTC, PT100, PT1000 EMC Directive 2004/108/EC EN 61000-6-1 Potentiometer R EN 61000-6-3 Universal outputs 3 Resolution 10 bit digital/analogue Installation Can be used as: Dimensions W H D (mm) 145 120 51 Analogue output U/I Weight (kg) 0.35 Digital output 0-I Housing ABS PA-765A PWM max. 60 ma at 12 V= Triac outputs 5 Additional information up to 1 A Fitting instructions MV P100002802 Material declaration MD 92.285 Dimension drawing Wiring diagram M11424 M11425 A10589 Accessories Type Description Manual operating panel EY-RU482F001 EY-RU481F001 EY-RU481F002 EY-RU481F003 ecos4 sensor FCU, display ecos4 sensor ecos4 sensor, occupancy ecos4 sensor, occupancy, setpoint www.sauter-controls.com 1/6

SAUTER EY-modulo 4 General functioning of the automation station The modu420 automation station (AS) is a microprocessorassisted, freely programmable controller used to control and regulate a varied range of HVAC applications on the basis of LON technology. The modu420 automation station uses the LonTalk communication protocol and is LonMark -certified if the sensor profile (number 1) is used for the relevant input objects and if the actuator profile (number 3) is used for the relevant output objects. The integrated operating programme can be programmed freely; it reads in the hardware and software addresses, processes the user programme, updates the outputs and handles the necessary communication with other stations in the network or with the management level. The user program can be loaded from any point in the LON network using SAUTER CASE LON Engine. The plugins can be used to programme or parameterize the controllers with the SAUTER CASE LON Engine network management tool or via any LNS-based software, according to choice. Engineering notes Installation and wiring The modu420 automation station can be fitted in an MCC using a top-hat rail (EN 60715). Wall-mounting is possible, using the fitting holes in the lower housing. It is possible to separate the upper and lower sections of the housing in order to install and connect the automation station. The plant devices are connected via screw terminals. The following conditions must be met: Cross-section conductors: LON network: of min. 0.82 mm² (AWG 18), max. 2 mm² (AWG 13), compliant with standards and national installation regulations. min. 0.65 mm² (AWG 22), twisted and unscreened Suitable network terminations (terminators) must be used for different network topologies. Failure to comply with the specified requirements may cause transmission errors between the controllers. The use of different cable cross-sections in one network section is not permitted. Detailed guidelines on planning and installing twisted-pair LonWorks networks have been published by the Echolon Corporation. Connections: LON network: 2 jack plugs, mono, 1/8" (3.5 mm) Earth terminals: 19 I/O terminals: 24 LS-MM terminals: 24 V~/= Room operating unit: 2 (SMRT +/- ) Hardware: The modu420 automation station comprises: Processor: Neuron 3150 ; 8 bit; 10 MHz Memory: Non-volatile 64 kb flash memory (APB application) Non-volatile 128 kb flash-chip (programme) Communication: LonTalk protocol Channel: TP/FT-10; 78 kbit/s Status indicators: Green LED: Power supply status and LON-TX Description of inputs and outputs The modu420 automation station has 6 universal inputs, 5 Triac outputs and 3 universal outputs on the hardware side. All the inputs and outputs must be configured via software. The input resolution is 16 bits and the output resolution is 10 bits. The inputs and outputs may be used as follows: Input: Temperature sensor: Potentiometer: Current: Digital: Pulse: Ni1000, NTC, Pt 10 k, 100 k 0 20 ma (4 20 ma) Dry contact Dry contact 500 ms min. ON/OFF Output: Current: 0 20 ma Voltage: 0 10 V= Digital: 0/12 V=, (I/O) PWM Triac: PWM, on/off, floating 1 A max The sampling period for the inputs is 1 s if they are configured as current, voltage, potentiometer or temperature inputs, and 500 ms for configuration as digital or pulse inputs. The UIx inputs can take a maximum load of 24 V. www.sauter-controls.com 2/6

EY-AS420 Technical specifications of inputs and outputs Temperature measurement (Ni1000, NTC, Pt) The Ni/Pt1000 sensors are connected using the two-wire method between one of the input terminals for a universal input (UI01 UI06) and an earth terminal. In case of an Ni/NTC/Pt connection, the inputs do not require calibration and can be used directly. The connected sensor type and the desired offset input are chosen in the software. Ni1000 Accuracy: ± 0.5 C Circuit: Period duration Value Short-circuit/ override *) < 5 s > 5 s > 15 s Override = on Override = off Input = +199.9 Open: - -199.9 NTC type 2, 10 k Accuracy: ± 0.5 C NTC type 3, 10 k Accuracy: ± 0.5 C Circuit: Period duration Value Short-circuit/ override *) < 5 s > 5 s > 15 s Override = on Override = off Input = +199.9 Open: - -199.9 PT1000, 1 k Accuracy: ± 1 C PT100, 100 k Range: -40 135 C Accuracy: ± 1 C Circuit: Period duration Value Short-circuit/ override *) < 5 s > 5 s > 15 s Override = on Override = off Input = +199.9 Open: - -199.9 *) If the input is short-circuited, this may be interpreted as an override, i.e. the relevant control loop is switched from "unoccupied" status to the "occupied/override" operating mode. Potentiometer measurement (Pot) It is possible to use the input in combination with a potentiometer if a 10 k or 100 k resistance is used. For configuration purposes, the resistance value can be limited and scaled to any desired value range in C. A potentiometer is connected between an input terminal of a universal input (UI01 UI06) and the associated earth terminal. The measurement accuracy is ± 0.5%. Current measurement (I) The current to be measured is connected to the input terminals of the universal inputs (UI01 UI06) between UIx and earth. The signal must be potential-free. In order to use the current input on the modu420 automation station, either a supply of current to the sensor or a parallel input-sensor supply is required. A 249 resistance must also be connected in parallel with the input. The input is defined as a 0 20 ma input by default. To adapt the input to 4 20 ma, the minimum value must be configured as 4 ma in the software. Voltage measurement (U) The universal inputs (UI01 UI06) are used to measure voltage. The voltage input has a range of 0 10 V. The connection is made to an input and the associated earth terminal. The voltage signal must be potential-free. The input can be adapted to different ranges via software. Parameters "min.", "max." or "offset" are available for this purpose. Digital inputs All universal inputs (UI01 UI06) can be used as digital inputs and must be connected to earth. Type of inputs: Pulse counters: Potential-free contacts, connected to earth Opto-coupler Transistor (open collector) 500 ms on/off Digital inputs (DI) Digital information is connected between the input terminals (UI01 UI06) and earth. The station applies a voltage of approx. 13 V to the terminal. In normal cases (NORMAL) this corresponds to INACTIVE (bit=0) for an open contact. When a contact is closed it is ACTIVE (bit=1) and 0 V is applied, whereby the current flow equates to approx. 1 ma. For each input, it is possible to define the "on" and "off" values individually, as well as the direction of operation (normal or reverse). Pulse counter at digital input (CI with DI) Counter inputs for potential-free contacts, opto-couplers or transistors with an open collector can be connected to the digital inputs. The maximum time that can be measured between the ON and OFF values for the input must be at least 500 ms. Pulses are measured on the rising and falling flanks. The values for this purpose can be adjusted individually. The combination of the two values is evaluated as a pulse. Digital output (DO) All the universal outputs (UO01 UO03) can be configured as digital outputs. A discrete output signal is issued: 0 V= for OFF and 12 V= for ON. If a relay is triggered via the universal output, a diode (1N400x family) must be connected to the connection terminals in parallel. This protects the output against voltage peaks when the relay cuts out. If the universal outputs are configured as PWM outputs, the period duration can be set between 2 s and 15 min. The period duration can be set between 0 and 100% of the "on" duration. Loading capacity of the output: max. 60 ma at 12 V= Max. load 200 The output is fitted with a self-resetting fuse. Maximum power load: 60 ma at 60 C 100 ma at 100 C The output is written immediately if the programmed value changes. However, this does not take place more quickly than the programme cycle time. It is not advisable to connect a relay to the output in PWM mode. www.sauter-controls.com 3/6

EY-AS420 Voltage output (U) The universal outputs (UO01 UO03) can be configured as voltage outputs, via the software. The output voltage is measured between the relevant output terminal and an earth terminal (UOx, Com). Type of output: 0(2)...10 V= approx. 60 ma to earth Triac outputs 5 x digital Triac max. 1.0 A for 24 V~ at Tmax 40 C Triac max. 0.75 A for 24 V~ at Tmax 70 C One earth per output The Triac outputs can be configured as PWM, digital (on/off) or 3- point outputs, according to choice. For use as a 3-point output, it is mandatory to use two adjacent outputs. Time programme and calendar A maximum of two independent time programmes can be configured in the AS programme. This is done via a plug-in. Each time programme supports up to 6 events per day of the week. In addition, 4 special days with up to 6 events each can be configured per time programme. Behaviour on switching off or in case of a mains failure All the programme parameters are stored in the flash memory to secure them against failures. When the station is reconnected to the power supply, the user programme is started as normal. LED displays The automation station has 3 LED displays on the front to signal operating statuses and network communication. The three LEDs on the left, arranged vertically, indicate the following statuses: LED name Display Description Permanently on Normal mode Permanently off APB file missing (AS has no application loaded) SERVICE Flashing AS in operation; LED flashes depending on execution of the programme Flashing slowly (1 s on/1 s off) AS is not configured Flashing quickly (0.3 s on/1 s off) Watchdog time-out; application is faulty. RX/TX Flickers irregularly AS is sending and/or receiving data LEDs O01 O08 signal the operating status of the universal outputs depending on the specific configuration. Output configuration Analogue output (0 10 V) Digital output PWM Display 0 V = off 10 V = on 0 V = off 10 V = on 0V = off 12 V = on Programming and parameterisation of the automation station Commissioning the automation station To commission the automation station, it must be connected to the LON network. Sauter CASE LON Engine can be used to commission the automation station. To do this, call up the Commission Device function, select the appropriate image (.abp file) and then press the Service Pin on the automation station. If an incorrect.apb file is loaded, the neuron chip may be destroyed and the automation station will become unusable. Network variables The controller software supports all structured SNVTs and UNVTs of 1 and 2 bytes in length. 17 NVIs and 17 NVOs (with changeable types and lengths) are available. 5 additional NVIs are available as possible bindings, as fan inputs. In this case, 3 NVIs can be used (supporting up to 80 NVs) in combined minimum, maximum, total or average function, and 2 NVIs in maximum or minimum function. User programme To create the user programme, a graphic programming interface is available in which individual function blocks are combined to form complex programmes. For this purpose, the modu420 automation station supports the use of up to 16 independent PID loops and 2 schedules. Once functions have been created within the programming environment, it is possible to store them for further use in the form of one's own user modules. The software supports the following types of function block (functions): Comparators (=,, <, >, ) constant and variable (types: numerical and enumeration), customer-specific function blocks, function blocks of a general nature (min, max, limit, etc.), HVAC (optimum start/stop, enthalpy calculation, dew-point calculation, etc.), logic functions (and, or, switch, multiplexer, etc.), mathematical functions (+, -, *, /, sum, root, etc.), SNVT conversion, time functions (timer, schedule, etc.) and VAV functions. A value range of 24 bits (±83886.07) is available for integers. Up to 10 values can be stored permanently so that they are not lost after a reset. The two schedulers have simply configurable weekly, daily and vacation planners. Special events can quickly be added or deleted. Seven weekly templates and six configurable events can be set per day for each scheduler. 4/6 www.sauter-controls.com

EY-AS420 Functional profile nvirequest SNVT_obj_request nvifilereq SNVT_file_req nvifilepos SNVT_file_pos Mandatory Network Variables Node Object #0 nvostatus SNVT_obj_status Optional Network Variables nvofilestat SNVT_file_status nvifp_xx (xx=09-12) Manufacturer Network Variables Manufacturer Network Variables Fan-In Support nvifp_xx (xx=13-14) (Hisel & Lowsel) nvofp_xx (xx=07-17) 6x Optional Configuration Properties Device Major Version (SCPTdevMajVer) Device Minor Version (SCPTdevMinVer) Location (SCPTlocation) Manufacturer Configuration Properties Hardware Information (UCPThardwareInfo) Mandatory Network Variables Hardware Input Open-Loop Sensor #1 Optional Configuration Properties Maximum Send Time (SCPTMaxSendTime) Minimum Send Time (SCPTMinSendTime) Manufacturer Configuration Properties nvofp_xx nvifp_xx (xx=15-17) nvimodify UNVT_modify_internal_val (Hisel, Lowsel, Sum & Average) Free Programmable Internal Points FreeProg Object Type #20100 nvovn1_7 UNVT_Internal_var_1to7 nvovn8_14 UNVT_Internal_var_8to14 nvovn15_21 UNVT_Internal_var_15to21 nvovn22_28 UNVT_Internal_var_22to28 nvovn29_35 UNVT_Internal_var_29to35 nvove1_27 UNVT_Internal_var_1to27 nvohwi1_6 UNVT_hardware_input_1to6 nvosmi1_5 UNVT_sm_Input_1to5 nvowri1_14 UNVT_wr_Input_1to14 nvohwo1_8 UNVT_hardware_output_1to8 8x nvifp_xx xx=01to06 Mandatory Network Variables Hardware Output Open-Loop Actuator #3 Optional Configuration Properties Maximum Receive Time (SCPTmaxRcvTime) Manufacturer Configuration Properties Valid Output Signal Type (UCPTvalidOutputSignalType) Configuration Properties nvofp Configuration Properties: Update Rate (SCPTupdateRate) Default Output (SNVT_tod_event) nvifp Configuration Properties: Maximum Receive Time (SCPTmaxRcvTime) Manufacturer Configuration Properties: Object Major Version (SCPTobjMajVer) Object Minor Version (SCPTobjMinVer) Minimum Send Time (SCPTminSendTime) Maximum Send Time (SCPTmaxSendTime) Associated File Index (UCPTassociatedFileIndex) ncicn1_7 (UNVT_Internal_const_1to7) ncicn8_14 (UNVT_Internal_const_8to14) ncicn15_21 (UNVT_Internal_const_15to21) ncicn22_28 (UNVT_Internal_const_22to28) ncicn29_35 (UNVT_Internal_const_29to35) ncice1_31 (UNVT_Internal_const_1to31) xx=01to08 2x Scheduler Object Type #20020 Manufacturer Network Variables nvischedulex SNVT_tod_event nvoschedulex SNVT_tod_event Configuration Properties nvoschedule Configuration Properties: Update Rate (SCPTupdateRate) Default Output (SNVT_tod_event) nvischedule Configuration Properties: Maximum Receive Time (SCPTmaxRcvTime) Manufacturer Configuration Properties: Object Major Version (SCPTobjMajVer) Object Minor Version (SCPTobjMinVer) Associated File Index (UCPTassociatedFileIndex) x=1to2 www.sauter-controls.com 5/6

Dimension drawing 144,8 50,8 108,0 12VDC Relay M11424 M11425 119,4 57,2 Wiring diagram Triac DOx x-x Fuse AXT111F202 + Ext. Trafo 230 / 24 V 18 17 16 15 14 13 12 11 10 09 08 07 06 05 04 03 02 01 Ls MM 24 V modu420 Outputs (Triac) Outputs (Universal) Service Power Inputs (Universal) ecounit 482 TX RX 01 02 03 04 05 06 07 08 09 10 11 12 13 14 15 16 17 18 19 A10589a Fr. Sauter Ltd Im Surinam 55 CH-4016 Basle Tel. +41 61-695 55 55 Fax +41 61-695 55 10 www.sauter-controls.com info@sauter-controls.com 6/6 www.sauter-controls.com 7192285003 02 Printed in Switzerland