Doing It Right. Phasor Labs. March voice fax

Similar documents
Test 1: What is the effect on cattle drinking water from an insulated water trough if an electric fence is within inches of the water tank?

The newer Fluke 199C recording scope meters are GREAT instruments if used properly.

Evaluating Electrical Events on the Dairy Farm

I. Introduction to Animal Sensitivity and Response

Measuring Stray Voltage. Steady state

Scopes for Stray Voltage. February

I. Introduction to Animal Sensitivity and Response

AE Agricultural Customer Services Play-by-Play Tekscope Manual


Mr. Pulsartm. Specialized Function Generator

OAH No , MPUC Dkt No. IP6701/WS STATE OF MINNESOTA OFFICE OF ADMINISTRATIVE HEARINGS

Oscilloscope Applications MREC Rural Energy Conference 2012 Prepared by Paul Ortmann, P.E. /

Transformer Waveforms

Grounding for Power Quality

Course 11 Distribution Transformer Applications Instructor: David R. Smith, PE Due: April 24, 2017 (EV), April 25, 2017 (LC)

The Variable Threshold Neutral Isolator (VTNI)

General Description & Features Selection Charts Definition of Terms... 42

ARC FLASH PPE GUIDELINES FOR INDUSTRIAL POWER SYSTEMS

New Methods to Mitigate Distribution System Harmonics

EXAMPLE. Use this jack for the red test lead when measuring. current from 0 to 200mA. Figure P-1

Contact Voltage Detection

Stray Electricity. Occurs as small voltage differences between

Subject: Drive isolation transformers. VFD definition: History the short version. February 2012

148 Electric Machines

thepower to protect the power to protect i-gard LITERATURE Low and medium voltage

The Confusion Surrounding Stray Voltage

Topic 6 Quiz, February 2017 Impedance and Fault Current Calculations For Radial Systems TLC ONLY!!!!! DUE DATE FOR TLC- February 14, 2017

A Simple Notch Type Harmonic Distortion Analyzer

Guide for Conducting a Stray Voltage Evaluation Under the MPSC Stray Voltage Rule 1

Load Isolation Transformers

NON-TRADITIONAL STRAY VOLTAGE: AS LEARNED IN THE FIELD

Do You Have a Harmonic Problem?

MILWAUKEE SCHOOL OF ENGINEERING LABORATORY SESSION 4 THREE PHASE TRANSFORMERS

Unit 3 Magnetism...21 Introduction The Natural Magnet Magnetic Polarities Magnetic Compass...21

Preface...x Chapter 1 Electrical Fundamentals

EA16, EB16, EA17, EA19

Instrument Usage in Circuits Lab

Straight Isolation - Plug In (171 Series)

MV ELECTRICAL TRANSMISSION DESIGN AND CONSTRUCTION STANDARD. PART 1: GENERAL 1.01 Transformer

Single Supply, Rail to Rail Low Power FET-Input Op Amp AD820

VOLTAGE AND CURRENT RELATIONS AND POWER PART1: THREE PHASE VOLTAGE AND CURRENT RELATIONSHIPS

2 : AC signals, the signal generator and the Oscilloscope

Hours / 100 Marks Seat No.

Power Quality Basics. Presented by. Scott Peele PE

201AP Charge Amplifier User Manual

When you have completed this exercise, you will be able to determine the frequency response of an

MOVING-IRON METERS EA16, EB16, EA17, EA19, EA12 TYPES

AC Power Instructor Notes

Stray Voltage and Swimming Pools

Thermal Imaging, Power Quality and Harmonics

Short Circuit Current Calculations

POWER FACTOR CORRECTION. HARMONIC FILTERING. MEDIUM AND HIGH VOLTAGE SOLUTIONS.

Power System Neutral/Ground Voltages Causes, Safety Concerns and Mitigation

Unit 29 Three-Phase Transformers

Model 4402B. Ultra-Pure Sinewave Oscillator 1Hz to 110kHz Typical Distortion of % Serial No. Operating Manual

GENERATOR INTERCONNECTION APPLICATION Category 5 For All Projects with Aggregate Generator Output of More Than 2 MW

FIELD INTENSITY METER MODEL FIM-41 OPERATING INSTRUCTIONS

Complimentary Reference Material

QUESTIONNAIRE for Wind Farm Power Stations only

Experiences on using gapless waveform data & synchronized harmonic phasors

+ 24V 3.3K - 1.5M. figure 01

Solving Customer Power Quality Problems Due to Voltage Magnification

DP&L s Technical Requirements for Interconnection and Parallel Operation of Distributed Generation

SDCS-03 DISTRIBUTION NETWORK GROUNDING CONSTRUCTION STANDARD (PART-I) UNDERGROUND NETWORK GROUNDING. Rev. 01

Distributed Generation Application Form (Generation of Greater than 20 kw to 15 MW)

To Float or Not to Float? Analysis of a floating vs. grounded output Associated Power Technologies

Single Supply, Rail to Rail Low Power FET-Input Op Amp AD820

5320A. Multifunction Electrical Tester Calibrator. Extended Specifications

Reliable Power Meters Multipoint Power Recorder

500 kva Dry-type Isolation Transformer V-Delta to 208Y/120V 3PH - NEMA 1/Indoor

Notes on DYNALYZER HVU Usage

Industrial Electricity. Answer questions and/or record measurements in the spaces provided.

SDCS-03 DISTRIBUTION NETWORK GROUNDING CONSTRUCTION STANDARD (PART-II) OVERHEAD NETWORK GROUNDING. Rev. 01

CEC VIBRATION TRANSMITTER

Capstone Turbine Corporation Nordhoff Street Chatsworth CA USA Phone: (818) Fax: (818) Web:

EVALUATION OF DIFFERENT SOLUTIONS OF FAULTED PHASE EARTHING TECHNIQUE FOR AN EARTH FAULT CURRENT LIMITATION

GROUND-FAULT PROTECTION ON RESISTANCE-GROUNDED POWER-DISTRIBUTION SYSTEMS WITH ADJUSTABLE-SPEED DRIVES 1. Modified_103007

3Ø Short-Circuit Calculations

The University of Jordan Mechatronics Engineering Department Electronics Lab.( ) Experiment 1: Lab Equipment Familiarization

Phase-phase/phase-neutral: 24/13.8 kv star, 13.8 kv delta, 12/6.9 kv star.

Name: Period: Date: 2. In the circuit below, n charge carriers pass the point P in a time t. Each charge carrier has charge q.

AVO CT 160 Meter Protection

Compliant to DOE 10, CFR Part 431 (effective as of January 1 st, 2016)

GEA DairyRotor T8900. High performance in unique design

Sept 13 Pre-lab due Sept 12; Lab memo due Sept 19 at the START of lab time, 1:10pm

ELECTRONICS Practical work 2 APPLICATIONS OF OPERATIONAL AMPLIFIERS V EE. Fig. 1 Schematic of the inverting OA.

CHAPTER 4 FULL WAVE RECTIFIER. AC DC Conversion

Single-Phase Transformation Review

Predicting the Voltage Sag Performance of Electricity Distribution Networks

Power Voltage Transformers for Air Insulated Substations. THE PROVEN POWER.

MICROPROCESSOR-BASED METERING EQUIPMENT SECTION 16901C PART 2

Short-Circuit Current Calculations

FERRORESONANCE SIMULATION STUDIES USING EMTP

Electric Circuit Fall 2017 Lab3 LABORATORY 3. Diode. Guide

Appendix 6-F: Electric and Magnetic Field Study Report

Lab 04. Basic Oscilloscope Operation Capacitor Time Constant. 1. The Oscilloscope.

These true on-line inverters incorporate pulse width modulation (PWM) control combined with high frequency igbt power transistors.

Chapter 24. Alternating Current Circuits

Introduction to the Laboratory

Single Earthed Neutral and Multi Earthed Neutral. Single Earthed Neutral and Multi Earthed Neutral: Multi Grounded Neutral System (MEN):

Transcription:

Doing It Right Phasor Labs 5420 Glenway Circle Oregon, Wisconsin 53575 608-835-9605 voice 608-835-9039 fax cforster@phasorlabs.com March 2004 cforster@phasorlabs.com 1

Doing It Right March 2004 cforster@phasorlabs.com 2

What stray electricity do you find on a farm that is served and wired electrically correct? In November of 2003 I performed a survey of four farms for a farm owner with a total of 11,000 diary cows being milked three times a day. March 2004 cforster@phasorlabs.com 3

One of the farms is served from an investor owned substation along with other utility customers. The remaining three farms are served by a dedicated substation with three 12 kv feeders, one to each farm. March 2004 cforster@phasorlabs.com 4

Distribution lines are 12.47 kv multi-grounded with the neutral grounded at each pole. Each farm has a 750 or 1000 kva pad mounted transformer. Transformers are grounded wye primary and grounded wye secondary. March 2004 cforster@phasorlabs.com 5

All farm services are 480 volt three phase. q 120/208 volt loads are served by dry type step-down transformers. q HID Lighting is 208 volt phase to phase. q Watering unit heaters are 120 volt. March 2004 cforster@phasorlabs.com 6

All grounding on and off farm is to Code and remains connected. March 2004 cforster@phasorlabs.com 7

The first tests performed were Cow Contact Profiles. A Fluke 189 meter, a 500 ohm resistor and C. Forster s Many Point tester were used. March 2004 cforster@phasorlabs.com 8

Measurements were made at each watering unit Approximately 180 electric watering units required 4 miles of walking to measure all cow contact points. Points between watering units measured lower CC voltages. (Weather was warm, heaters were energized but not heating.) March 2004 cforster@phasorlabs.com 9

Four 72 cow rotary units were Measurements were made from parlor steel platform to floor and bump rail to floor. used for milking. March 2004 cforster@phasorlabs.com 10

Record your steady state measurements If there is a pattern to the measurements, you might investigate for on farm sources. March 2004 cforster@phasorlabs.com 11

46 50 55 95 20 18 39 25 41 52 63 45 48 76 34 54 127 28 36 35 49 70 47 58 42 44 40 25 32 22 20 5 26 Step potential measurements are from water unit metallic housing to floor. All values are in millivolts (mv) 57 41 19 270 35 12 28 true 23 rms 23 16 and 114 using 34 a 500 ohm cow resistor. Meter was a Fluke 189 digital voltmeter.4 March 2004 cforster@phasorlabs.com 12

CC voltages recorded at the watering units in free stall areas: Minimum CC voltage was 5 millivolts rms. Average CC voltage was 70 millivolts rms. Maximum CC voltage was 270 millivolts rms. (These values are with a 500 ohm cow resistor) March 2004 cforster@phasorlabs.com 13

CC voltages recorded in the milking parlor areas: Minimum CC voltage was 2 millivolts rms. Average CC voltage was 25 millivolts rms. Maximum CC voltage was 83 millivolts rms. (These values are with a 500 ohm cow resistor) March 2004 cforster@phasorlabs.com 14

Good science would tell us: The steady state voltage would have to reach 1,400 millivolts rms (for steady state conditions) to have 5% of the most sensitive cows even detect the presence of stray electricity. March 2004 cforster@phasorlabs.com 15

Some SV advisors selling solutions might say The above voltages would certainly prevent good production March 2004 cforster@phasorlabs.com 16

You may want to check for fencer, cow trainer, ID system or VFD on farm source influence in the cow contact area. March 2004 cforster@phasorlabs.com 17

Cow ID System Influence March 2004 cforster@phasorlabs.com 18

Is it significant??? 10,000 V Behavioral response for 5% of the most sensitive cows using sine waves from muzzle to hooves exposure Typ. Fencer 1,000 V 100 V 1 Cycle, Biphasic 1 Cycle, Monophasic Multiple Cycle 5 2 10 V 1 V (1,000 mv) Worst Case ID Loop USDA LOC PSCW LOC 0.1 V Higher Frequency Lower Frequency 0.01 V (10 mv) 0.001 V (1 mv) 1000 on your AM radio dial 300 Hz (5th Harmonic) 1 millisecond 60 Hz 0.1 1 10 100 1,000 10,000 Phase Duration (microseconds) = Time between voltage zero crossings Reprinted with permission C. Forster 7/5/00, 6/2003 March 2004 cforster@phasorlabs.com 19

VFD System Influence March 2004 cforster@phasorlabs.com 20

March 2004 cforster@phasorlabs.com 21

March 2004 cforster@phasorlabs.com 22

Significant? Behavioral response for 5% of the most sensitive cows using sine waves from muzzle to hooves exposure 10,000 V Typ. Fencer 1,000 V 100 V 1 Cycle, Biphasic 1 Cycle, Monophasic Multiple Cycle 5 2 10 V 1 V (1,000 mv) VFD influence USDA LOC PSCW LOC 0.1 V Higher Frequency Lower Frequency 0.01 V (10 mv) 0.001 V (1 mv) 1000 on your AM radio dial 300 Hz (5th Harmonic) 1 millisecond 60 Hz 0.1 1 10 100 1,000 10,000 Phase Duration (microseconds) = Time between voltage zero crossings Reprinted with permission C. Forster 7/5/00, 6/2003 March 2004 cforster@phasorlabs.com 23

So, what myths have been debunked? Myth #1 - You cannot use a multigrounded distribution system to serve farms. March 2004 cforster@phasorlabs.com 24

More myths.. Myth #2 - Grounding the neutral creates too many earth currents. Myth #3 - All farms must be isolated. Myth #4 - All farms should be wired with an ungrounded electrical system. March 2004 cforster@phasorlabs.com 25

More myths.. Behavioral response for 5% of the most sensitive cows using sine waves from muzzle to hooves exposure Myth #5 - Voltage levels below the sensitivity curve for the most sensitive cows will affect milk production. 10,000 V 1,000 V 100 V 5 2 10 V 1 V (1,000 mv) 0.1 V 0.01 V (10 mv) 0.001 V (1 mv) Higher Frequency 0.1 1 10 100 1,000 10,000 Reprinted with permission C. Forster 7/5/00, 6/2003 1000 on your AM radio dial Typ. Fencer Lower Frequency Phase Duration (microseconds) = Time between voltage zero crossings Vertical scale is in volts (Zero to Peak) across a 500 ohm "Cow" resistor 300 Hz (5th Harmonic) 1 millisecond 1 Cycle, Biphasic 1 Cycle, Monophasic Multiple Cycle 60 Hz USDA LOC PSCW LOC March 2004 cforster@phasorlabs.com 26

Behavioral response for 5% of the most sensitive cows using sine waves from muzzle to hooves exposure 10,000 V Typ. Fencer 1,000 V 100 V 1 Cycle, Biphasic 1 Cycle, Monophasic Multiple Cycle 5 10 V 2 1 V (1,000 mv) USDA LOC PSCW LOC 0.1 V Higher Frequency Lower Frequency 0.01 V (10 mv) 0.001 V (1 mv) 1000 on your AM radio dial 300 Hz (5th Harmonic) 1 millisecond 60 Hz 0.1 1 10 100 1,000 10,000 Phase Duration (microseconds) = Time between voltage zero crossings Reprinted with permission C. Forster 7/5/00, 6/2003 Vertical scale is in volts (Zero to Peak) across a 500 ohm "Cow" resistor March 2004 cforster@phasorlabs.com 27

Just do it right! -End- March 2004 cforster@phasorlabs.com 28