Accurate Synchrophasor Estimation to Support the Islanding Maneuver of Active Distribution Networks

Similar documents
ISO Rules Part 500 Facilities Division 502 Technical Requirements Section Wind Aggregated Generating Facilities Technical Requirements

A P + M Phasor Measurement Unit

EH2741 Communication and Control in Electric Power Systems Lecture 2

ISO Rules Part 500 Facilities Division 502 Technical Requirements Section Aggregated Generating Facilities Technical Requirements

Use of Synchrophasors to Detect Control System and Circuit Breaker Reclosing Issues

Measurement tools at heart of Smart Grid need calibration to ensure reliability

Microgrid Islanding with a Battery Energy Storage System (BESS) Gabriel Haines

Wind Power Facility Technical Requirements CHANGE HISTORY

Use of the Power System Outlook (PSO) and SMART 1 Programs to View PSLF Dynamic Simulation Data Files

SDG&E Transmission Synchrophasor Project Update

Under-Frequency Load Shedding based on PMU Estimates of Frequency and ROCOF

Adamantios Marinakis, Scientist, 12 th IEEE SB Power Engineering Symposium, Leuven, Enhancing Power System Operation with WAMS

THE ROLE OF SYNCHROPHASORS IN THE INTEGRATION OF DISTRIBUTED ENERGY RESOURCES

Wide Area Monitoring with Phasor Measurement Data

Experiences on using gapless waveform data & synchronized harmonic phasors

BED INTERCONNECTION TECHNICAL REQUIREMENTS

Experiences of Using Synchrophasors at Duke Energy

New Methods to Mitigate Distribution System Harmonics

A New Approach Applied to Adaptive Centralized Load Shedding Scheme

Sarma (NDR) Nuthalapati, PhD

Evaluation of Steady-State and Dynamic Performance of a Synchronized Phasor Measurement Unit

Generation and Load Interconnection Standard

ISSUES OF SYSTEM AND CONTROL INTERACTIONS IN ELECTRIC POWER SYSTEMS

Generation Interconnection Requirements at Voltages 34.5 kv and Below

Synchrophasor Technology PMU Use Case Examples

Fault Location Using Sparse Wide Area Measurements

Anti-IslandingStrategyforaPVPowerPlant

E N G I N E E R I N G M A N U A L

Synchrophasors for Distribution Applications

Fuel cell power system connection. Dynamics and Control of Distributed Power Systems. DC storage. DC/DC boost converter (1)

Wide-Area Measurements to Improve System Models and System Operation

Application of Synchrophasors in Power Plants Incorporated with Condition Monitoring Systems K P C L

Connection Impact Assessment Application

Overvoltage Phenomena in Offshore Wind Farms Following Blocking of the HVDC Converter

CAPRICA: A Testbed Demonstrating a Cyber-Secure Synchronous Power Island. Dr Kieran McLaughlin, Dr David Laverty, Prof Sakir Sezer

SynchroPhasor use at OG&E. Austin D. White P.E. Steven E. Chisholm Oklahoma Gas & Electric

each time the Frequency is above 51Hz. Continuous operation is required

Intermittent Renewable Resources (Wind and PV) Distribution Connection Code (DCC) At Medium Voltage (MV)

Application Example Document ID: SA Rev. - September 24, 2004

Tasmanian Networks Pty Ltd Guideline. Technical Requirements for the Connection of Embedded Generation

Study and Simulation of Phasor Measurement Unit for Wide Area Measurement System

Wide Area Control Systems (1.4) Mani V. Venkatasubramanian Washington State University (

Resonances in Collection Grids of Offshore Wind Farms

APPENDIX B: Generation Interconnection Application Form

Capacitive Voltage Substations Ferroresonance Prevention Using Power Electronic Devices

Protective Relaying for DER

INTERIM ARRANGEMENTS FOR GRID TIED DISTRIBUTED ENERGY RESOURCES. Technical Requirements for Grid-Tied DERs

The Effect of Delays on Wide-Area Damping Control of Electromechanical Oscillations

Hybrid Anti-Islanding Algorithm for Utility Interconnection of Distributed Generation

Comparative Testing of Synchronized Phasor Measurement Units

Generation and Load Interconnection Standard

A New Subsynchronous Oscillation (SSO) Relay for Renewable Generation and Series Compensated Transmission Systems

Massive Transient Stability Based Cascading Analysis and On-line Identification of Critical Cascades

ENGINEERING DATA SUBMITTAL For the Interconnection of Generation System

Application for A Sub-harmonic Protection Relay. ERLPhase Power Technologies

GRID RELIABILITY MONITORING

Online Oscillation Management at ISO New England

SYNCHRONIZED PHASOR MEASUREMENT TECHNIQUES. A.G. Phadke

State of North Dakota Engineering data submittal Page 1 For interconnection of distributed generation to Otter Tail Power Company

Testing and Implementation of a Source Locating method at ISO New England

Real-time Monitoring of Power Oscillations and Modal Damping in the European ENTSO-E System

Do Capacitor Switching Transients Still Cause Problems?

Frequency Analysis for Planned Islanding Operation in the Danish Distribution System Bornholm

Southern Company Interconnection Requirements for Inverter-Based Generation

Low Frequency Demand Disconnection Summary

Parallel tap-changer controllers under varying load conditions (Part 1)

PMU Implementation Issues

SYNCHROPHASOR TECHNOLOGY GLOSSARY Revision Date: April 24, 2011

EE 742 Power System Components. Y. Baghzouz ECE Department UNLV

RECENT developments have seen lot of power system

How Full-Converter Wind Turbine Generators Satisfy Interconnection Requirements

Low Frequency Local mode Oscillations in NER Grid, Validation using Model based analysis and Mitigation

- 1 - NEUTRAL CONNECTION TO EARTH IN MEDIUM VOLTAGE NETWORKS: OPERATION EXPERIENCE IN ENEL

ECE 422/522 Power System Operations & Planning/Power Systems Analysis II 5 - Reactive Power and Voltage Control

A Software Tool for Real-Time Prediction of Potential Transient Instabilities using Synchrophasors

Section L5: PRE-ENERGIZATION TEST PROCEDURES FOR LOAD-ONLY ENTITIES AND TRANSMISSION-ONLY ENTITIES

Synchrophasor Solutions Deployment at PG&E Off-Line Analysis

Control of Power Converters for Distributed Generation

Fault Localization using Wavelet Transforms in 132kV Transmission Lines

Micro-synchrophasors (µpmus) in Electric Power Distribution Systems 5/29/15 SF PES Chapter Workshop

Phasor Measurements in the WECC

Postprint. This is the accepted version of a paper presented at IEEE PES General Meeting 2016, Boston.

Digital Fault Recorder Deployment at HVDC Converter Stations

APPLICATION FOR INTERCONNECTION & OPERATIONS OF MEMBER-OWNED GENERATION

Introduction to micropmu. PSL Australasian Symposium 2017 September 29 Thomas Pua Product Engineer

Synchrophasor Applications for Distribution Networks Enhancing T&D Operation and Information Exchange

Progress Report on Failures of High Voltage Bushings with Draw Leads By Jim McBride and Larry Coffeen, JMX Services / NEETRAC 7/26/2010

Analysis of Effect on Transient Stability of Interconnected Power System by Introduction of HVDC Link.

Enabling Tomorrow s Technology Today

Voltage Support and Reactive Power Control in Micro-grid using DG

ELECTRICAL POWER ENGINEERING

Protection of Microgrids Using Differential Relays

Jean-Pierre Braun obtained the B.E. degree from the Ecole d'ingénieurs de Genève, Switzerland, in 1980; the M.E.M. degree from the University of

Fault Induced Delayed Voltage Recovery (FIDVR) Advisory

COMPARATIVE PERFORMANCE OF SMART WIRES SMARTVALVE WITH EHV SERIES CAPACITOR: IMPLICATIONS FOR SUB-SYNCHRONOUS RESONANCE (SSR)

Interconnection-Wide Oscillation Analysis: Baselining Oscillation Modes in the North American Power System Objective Purpose

LOSS OF MAINS DETECTION AND AMELIORATION ON ELECTRICAL DISTRIBUTION NETWORKS

ECE 528 Understanding Power Quality

Qualitrol s PMU Technologies

Wide Area Visualization & SynchroPhasors

Transcription:

Working Group Meeting June 5-6, 2012 Accurate Synchrophasor Estimation to Support the Islanding Maneuver of Active Distribution Networks Prof. Mario Paolone EPFL, Switzerland - Distributed Electrical Systems Laboratory Prof. Carlo Alberto Nucci and Prof. Alberto Borghetti University of Bologna, Italy Power Systems Laboratory Owen Golden National Instruments, USA - Global Energy Segment

Outline The challenge of using PMUs in active distribution networks Configuration of the network Goals of the PMU monitoring system Conclusions

The challenge of using PMUs in active distribution networks Peculiarities of electrical distribution networks lower p.u.l. inductances with non-negligible p.u.l resistance; low power flows values; high harmonic distortion levels; higher dynamics compared to transmission networks (electromechanical transients). Peculiarities of the developed PMU TVE, phase and amplitude accuracies in the order of PPM; Accuracies not influenced by the harmonic distortion of the analyzed signals; Accuracies not influenced by large frequency transients (1 Hz/s). PMU prototype based on the National Instruments crio platform

Configuration of the network External transmission network 80 MW power plant (PP): two aeroderivative gas turbine (GT) units and a steam turbine unit (ST) in combined cycle; PMU2 2 PMU3 BR1 3 PP substation is linked, by means of a cable line, to a local 132 kv substation that supply 15 feeders of the local medium voltage (15 kv) distribution network. The substation also provides the connection with the external transmission network throughout circuit breaker BR1. BR2-GT1 1 PMU1 800 m cable line BR-ST BR2-GT2 Three PMUs were installed in correspondence of the PP and before/after BR1 BR1-GT1 BR1-GT2

Configuration of the network PP is equipped with a power management system that, after network disconnection (remote ctrl of breaker BR1), performs the following operations External transmission network PMU3 BR1 PMU2 communicates the load droop anticipator command to the ST control system in case of islanding maneuvers; 800 m cable line disconnects MV feeders to guarantee the load balance; BR2-GT1 PMU1 BR-ST BR2-GT2 selects the operation control mode of the two gas turbines for the frequency regulation of the network in islanded conditions; controls PP units to allow a reliable reconnection maneuver. BR1-GT1 BR1-GT2

Goals of the PMU monitoring system Support the system operators during the islanding maneuver and reconnection to the external network; Monitor possible network instabilities subsequent to the islanding maneuver; Provide help to the PMS action with the synchro-check relay in order to support the reconnection maneuver.

External transmission network Islanding maneuver description: PMU2 PMU3 BR1 GT1 unit was in operation at an output level equal to 29.4 MW, with a positive export to the external network equal to 1.9 MW; GT2 and ST units were in standby. BR2-GT1 PMU1 800 m cable line BR-ST BR2-GT2 Intentional opening of circuit breaker BR1. BR1-GT1 BR1-GT2

PMU measured frequency transient The islanding maneuver in presence of a positive PP power export to the external network, has resulted in a decrease of the PP power production and a consequent large frequency transient. Frequency transient characterized by a rate of rise in the order of 1Hz/s. Good match between the SCADA machine speed and the PMU measured frequency.

Voltage phasors angle differences Angle difference between positive-sequence components of PMU2 and PMU3 phasors ( ) 12000 10000 8000 6000 4000 2000 0 PMU2-PMU3 PMU1-PMU2 0 10 20 30 40 50 60 Time (s) 0.21 0.2 0.19 0.18 0.17 0.16 0.15 Angle difference between positive-sequence components of PMU1 and PMU2 phasors ( ) Clear identification of the separation between the two networks (continuous line PMU2-PMU3). Identification of an oscillation (0.3 Hz) between the PP and the rest of the network. Measurement of the post-islanding reduction of the phasors angle deviation between PMU1-PMU2 associated to the reduced power flow between the PP and the rest of the network.

Phasor-based estimated power injections into the cable link Estimation of the power flows between the PP and the primary substation and related amplitude of the active power flow oscillation.

External transmission network Reconnection maneuver description: PMU2 PMU3 BR1 A feedback of the PMU measurements was given to the PP operator. The synchro-check relay and the synchronizing PMS action permitted the smooth reconnection maneuver. BR2-GT1 PMU1 800 m cable line BR-ST BR2-GT2 BR1-GT1 BR1-GT2

PMU measured frequency transient Frequency (Hz) 50.15 50.1 50.05 PMU1 PMU2 PMU3 Monitoring of the frequency difference (positive) between the islanded network (PMU1 and PMU2) and the external network (PMU3). 50 49.95 0 10 20 30 40 50 60 Time (s)

Voltage phasors angle differences Angle difference between positive-sequence components of PMU2 and PMU3 phasors ( ) 200 0-200 -400-600 -800-1000 -1200-1400 -1600 PMU2-PMU3 PMU1-PMU2 0.21 0.2 0.19 0.18 0.17 0.16 Angle difference between positive-sequence components of PMU1 and PMU2 phasors ( ) Identification of the correct phase difference between islanded and external network to trigger the reconnection maneuver. 0 10 20 30 40 50 60 Time (s)

Conclusions Requirements of PMU use in active distribution networks could call for more specific indications in the available standards (IEEE C37.118). The information provided by PMUs appear to be of great help for the development of improved control and management systems aimed at supporting islanding and reconnection maneuvers more straightforward and reliable. The information coming from PMUs may represent a useful support to distribution system operator decisions during critical instances experienced by the system, such as islanding/reconnection operation.