SECTION 10520: FIRE EXTINGUISHERS AND CABINETS PART 1 GENERAL 1.01 GENERAL REQUIREMENTS: A. This section specifies fire extinguishers, cabinets for fire extinguishers, fire and other accessories. Their location is shown on the drawings. 1.02 RELATED REQUIREMENTS: A. Document A20 1: General Conditions of the Contract for Construction. B. Section 01340: Shop Drawings, Product Data and Samples. C. Section 06100: Rough Carpentry. D. Section 07920: Sealants and Caulking. 1.03 SUBMITTALS: A. Manufacturer's catalog cuts and data sheets, and installation requirements for each item specified. B. Submit complete color choice for Architect's selection. PART 2 PRODUCTS 2.01 FIRE EXTINGUISHER CABINETS: A. Larsen's Architectural Series. Model 2409 6R (or equivalent J.L. Industries) 1. Semi-recessed; 4" wall recess. 2. Door: 5/8 in. hollow steel. DS glazed panel, Vertical Duo 3. Finish: Factory finished color as selected by Architect or Color Schedule. 4. Installation: Top of cabinet ( 4'-8" A.F.F. 2.02 FIRE EXTINGUISHER BRACKETS: A. Provide a bracket for each fire extinguisher not in a cabinet, but designated on the drawings as F.E.. B. Larsen's, B-2 Series 2.03 FIRE EXTINGUISHERS: (Shown on drawings as F.E.) A. Larsen's MP Series. 1. 10-lb. capacity. 2. Cabinet or bracket mounted. 3. Fire class 4A-60BC. Sec. 10520 Fire Extinguishers page 1
PART 3 EXECUTION 3.01 INSTALLATION: A. Comply with manufacturer's installation instruction. Install where indicated on drawings. B. Place one extinguisher, fully charged and certified in each cabinet or bracket location. END OF SECTION Sec. 10520 Fire Extinguishers page 2
SECTION 10800: TOILET ACCESSORIES PART 1 GENERAL 1.01 RELATED WORK SPECIFIED ELSEWHERE: A. Document A20 1: General Conditions of the Contract for Construction. B. Section 01340: Shop Drawings, Product Data and Samples. C. Section 06100: Rough Carpentry. D. Section 09107: Metal Stud System. E. Section 09250: Gypsum Wallboard. 1.02 QUALITY ASSURANCE: A. Approved Manufacturers: 1. Unless otherwise indicated, model numbers specified for washroom accessories are items manufactured by American Specialties Inc. and are listed as a standard of quality. 2. Equivalent items of the following manufacturers are acceptable: a. Bradley Corporation. b. Bobrick. c. American Specialties, Inc. (Specified herein) 1.03 SUBMITTALS: A. Manufacturer's catalog cuts and data sheets, complete parts list, and installation requirements for each accessory item specified. B. Maintenance data, operating instructions, and keys required for each type of equipment and lock. 1.04 JOB CONDITIONS: A. Prior to closing of walls, inspect to ensure that all anchor plates have been installed in framing. B. Coordinate with other trades as required. PART 2 PRODUCTS 2.01 MATERIALS: A. Stainless Steel: 1. Type: 302/304, ASTMA 167. 2. Finish: No.4 satin. B. Brass: Cast or forged quality alloy, FS WW-P-54LB. Sec. 10800 ToiletAccessories page 1
C. Mounting Devices: Vandal-proof, concealed galvanized steel, ASTM A3 86. 2.03 FABRICATION: A. Brand names not permitted on face of unit. B. Locked Dispensing Units: Key alike for all accessories. C. Coin Operated Dispensing Units: Key coin boxes separately from dispensing unit. D. Weld corners, leaving no open miters. E. Stainless Steel, 18 gauge minimum, satin finish. F. Coin mechanism, door mounted. PART 3 EXECUTION 3.01 INSPECTION: A. Check framing prior to closing of same for required anchor plates. Check opening scheduled to receive recessed units for correct dimensions, plumb blocking or frames, preparation that would affect installation of accessories. B. Check areas to receive surface mounted units for conditions that would affect quality and execution of work. C. Verify spacing of plumbing fixtures and toilet partitions that affect installation of accessories. D. Do not begin installation of washroom accessories until openings and surfaces are acceptable. 3.02 INSTALLATION: A. All mounting devices vandal-proof B. Drill holes to correct size and application that is concealed by item, with 1/4 in. tolerance. C. Mount recessed accessories into wall openings with wood screws through cabinet side into wood blocking, or sheet metal screws into metal frames. D. Mount surface mounted accessories with toggle bolts. E. If not otherwise indicated, mount units in locations per Architect's directions. 3.03 SCHEDULE: A. Soap Dispensers: 0342. 1. One at: Women 108, Men 109, Lounge 105. Sec. 10800 Toilet Accessories page 2
B. Paper Towel Holders: 0210 (Surface). 1. One at: Women 108, Men 109, Lounge 105. C. Mirrors: 24" x 36" #0600 1. One at: Women 108, Men 109. D. Toilet Paper Holders: #0030. 1. One each at each water closet in Women 10.8, Men 109. E. Grab Bars are #3200P, 1 1/2 o.d., stainless steel, peened, non-slip surface, and are shown on drawings. END OF SECTION Sec. 10800 Toilet Accessories page 3