Lumped Network Model of a Resistive Type High T c fault current limiter for transient investigations

Similar documents
MATEFU Insulation co-ordination and high voltage testing of fusion magnets

FIELD DEMONSTRATION OF WORLD WIDE LARGEST SUPERCONDUCTING FAULT CURRENT LIMITER AND NOVEL CONCEPTS

GIS Disconnector Switching Operation VFTO Study

ABSTRACT 1 INTRODUCTION

2000 Mathematics Subject Classification: 68Uxx/Subject Classification for Computer Science. 281, 242.2

Simulation and Analysis of Lightning on 345-kV Arrester Platform Ground-Leading Line Models

Design and Construction of a150kv/300a/1µs Blumlein Pulser

IJSRD - International Journal for Scientific Research & Development Vol. 2, Issue 04, 2014 ISSN (online):

Ferroresonance Experience in UK: Simulations and Measurements

Use of inductive heating for superconducting magnet protection*

Lightning transient analysis in wind turbine blades

Electric Stresses on Surge Arrester Insulation under Standard and

10. DISTURBANCE VOLTAGE WITHSTAND CAPABILITY

Research Article A Simplified High Frequency Model of Interleaved Transformer Winding

Analysis of MOV Surge Arrester Models by using Alternative Transient Program ATP/EMTP

A Novel 110KV Fault Current Limiter for Improving The Reliability of A Substation

CHAPTER 2 ELECTROMAGNETIC FORCE AND DEFORMATION

Session Four: Practical Insulation Co-ordination for Lightning Induced Overvoltages

A Simple Simulation Model for Analyzing Very Fast Transient Overvoltage in Gas Insulated Switchgear

ANALYSIS OF VOLTAGE TRANSIENTS IN A MEDIUM VOLTAGE SYSTEM

Over-voltage Trigger Device for Marx Generators

FGJTCFWP"KPUVKVWVG"QH"VGEJPQNQI[" FGRCTVOGPV"QH"GNGEVTKECN"GPIKPGGTKPI" VGG"246"JKIJ"XQNVCIG"GPIKPGGTKPI

Efficient HF Modeling and Model Parameterization of Induction Machines for Time and Frequency Domain Simulations

Understanding and Optimizing Electromagnetic Compatibility in Switchmode Power Supplies

Single-turn and multi-turn coil domains in 3D COMSOL. All rights reserved.

Diagnostic testing of cast resin transformers

THE PROPAGATION OF PARTIAL DISCHARGE PULSES IN A HIGH VOLTAGE CABLE

A new hybrid protection system for high-field superconducting magnets

Study of Design of Superconducting Magnetic Energy Storage Coil for Power System Applications

HV AC TESTING OF SUPER-LONG CABLES

Transformer Engineering

Power Electronics. Exercise: Circuit Feedback

ISSN: X Impact factor: (Volume 3, Issue 6) Available online at Modeling and Analysis of Transformer

MODIFICATION OF THE ARRESTER ARRANGEMENT WHEN CONVERTING THE METHOD OF NEUTRAL TREATMENT

Recent Development of SFCL in the USA

International Journal of Science and Engineering Investigations vol. 2, issue 15, April 2013

Conventional Paper-II-2011 Part-1A

Insulation Co-ordination For HVDC Station

Simulations of W7-X magnet system fault scenarios involving short circuits

TECHNICAL NOTE 2.0. Overvoltages origin and magnitudes Overvoltage protection

Alternative Coupling Method for Immunity Testing of Power Grid Protection Equipment

PREVENTING FLASHOVER NEAR A SUBSTATION BY INSTALLING LINE SURGE ARRESTERS

Modeling and electromagnetic transients study of two 1800MVA phase shifting transformers in the Italian transmission network

The Role of the Grounding System in Electronics Lightning Protection

3.7 Grounding Design for EAST Superconducting Tokamak

6. du/dt-effects in inverter-fed machines

(2) New Standard IEEE P (3) Core : (4) Windings :

Pulse Cable for TESLA Modulators Hans-Jörg Eckoldt DESY TESLA

Comprehensive modeling of Dry type foil winding transformer to analyse inter turn insulation under Lightning Impulse Voltage

When surge arres t ers are installed close to a power transformer, overvoltage TRANSFORMER IN GRID ABSTRACT KEYWORDS

High Frequency Modeling of Two Limb Series Loop Winding for Partial Discharge Localization

LIGHTNING IMPULSE MODELING AND SIMULATION OF DRY-TYPE AND OIL-IMMERSED POWER- AND DISTRIBUTION TRANSFORMERS

A Study on Lightning Overvoltage Characteristics of Grounding Systems in Underground Distribution Power Cables

DIFFERENCE BETWEEN SWITCHING OF MOTORS & GENERATORS WITH VACUUM TECHNOLOGY

Calculation of Transients at Different Distances in a Single Phase 220KV Gas insulated Substation

Power Quality and Reliablity Centre

Improved Method for Winding Deformation Detection Sensitivity in Transformer

SWITCHING OVERVOLTAGES IN A 400-KV CABLE SYSTEM

EXPERIMENTAL INVESTIGATION OF A TRANSIENT INDUCED VOLTAGE TO AN OVERHEAD CONTROL CABLE FROM A GROUNDING CIRCUIT

Effect of High Frequency Cable Attenuation on Lightning-Induced Overvoltages at Transformers

Radio Frequency Electronics

Prevention of transformers damage in HPP with double generating units connected to GIS via HV cables

POWER TRANSFORMER SPECIFICATION, DESIGN, QUALITY CONTROL AND TESTING 18 MARCH 2009

EFFECT OF INTEGRATION ERROR ON PARTIAL DISCHARGE MEASUREMENTS ON CAST RESIN TRANSFORMERS. C. Ceretta, R. Gobbo, G. Pesavento

TRANSFORMER TECHNOLOGY GPT

The practicalities of measuring fast switching currents in power electronics using Rogowski probes

Resistive and Inductive Fault Current Limiters: Kinetics of Quenching and Recovery

Lecture 36 Measurements of High Voltages (cont) (Refer Slide Time: 00:14)

Investigation of Inter-turn Fault in Transformer Winding under Impulse Excitation

LIGHTNING OVERVOLTAGES AND THE QUALITY OF SUPPLY: A CASE STUDY OF A SUBSTATION

DEPARTMENT OF ELECTRICAL AND ELECTRONICS ENGINEERING QUESTION BANK SUBJECT CODE & NAME : EE 1402 HIGH VOLTAGE ENGINEERING UNIT I

CHAPTER 2. v-t CHARACTERISTICS FOR STANDARD IMPULSE VOLTAGES

Modeling insulation in high-voltage substations

Efficient Electromagnetic Analysis of Spiral Inductor Patterned Ground Shields

Pre location: Impulse-Current-Method (ICE)

Fault Current Limiter Selection Considerations for Utility Engineers

Simulation Study of Voltage Surge Distribution in a Transformer Winding

USING DAMPED AC VOLTAGES

Relay Protection of EHV Shunt Reactors Based on the Traveling Wave Principle

Sub-cooled SFCL Device and Modules for Power Transmission / Distribution

High voltage engineering

Effect of Shielded Distribution Cables on Lightning-Induced Overvoltages in a Distribution System

Maximum Lightning Overvoltage along a Cable due to Shielding Failure

Shunt Reactors. Global Top Energy, Machinery & Plant Solution Provider

SHORT CIRCUIT ANALYSIS OF 220/132 KV SUBSTATION BY USING ETAP

Transmission Line Transient Overvoltages (Travelling Waves on Power Systems)

HVDC Transmission. Michael Muhr. Institute of High Voltage Engineering and System Performance Graz University of Technology Austria P A S S I O N

Enhancement of Fault Current and Overvoltage by Active Type superconducting fault current limiter (SFCL) in Renewable Distributed Generation (DG)

Discipline Electrical Testing Issue Date Certificate Number T-2837 Valid Until Last Amended on - Page 1 of 6 LOCATION 1

TRANSMISSION ENGINEERING STANDARD TES-P , Rev. 0 TABLE OF CONTENTS 1.0 SCOPE 2.0 BONDING METHODS

Tab 2 Voltage Stresses Switching Transients

HIGH VOLTAGE ENGINEERING(FEEE6402) LECTURER-24

INNOVATIVE PERSPECTIVES FOR ELECTRICITY TRANSPORT

IEEE Power Engineering Society 2001 Winter Meeting Columbus, OH. Panel Session. Data for Modeling System Transients

Modeling for the Calculation of Overvoltages Stressing the Electronic Equipment of High Voltage Substations due to Lightning

High Voltage Engineering

EMC Philosophy applied to Design the Grounding Systems for Gas Insulation Switchgear (GIS) Indoor Substation

Chapter 2. Inductor Design for RFIC Applications

Analysis of lightning performance of 132KV transmission line by application of surge arresters

High-Voltage Test Techniques

Transcription:

Lumped Network Model of a Resistive Type High T c fault current limiter for transient investigations Ricard Petranovic and Amir M. Miri Universität Karlsruhe, Institut für Elektroenergiesysteme und Hochspannungstechnik, Engesserstrasse, D-768 Karlsruhe, Germany (email: ricard@ieh.uni-karlsruhe.de) Abstract In general, simulations of superconducting fault current limiters (SFCL) include the thermal- and electricalbehaviour of the limiter. Thermal properties deal with resistive heating caused by AC losses, increasing resistivity, etc. Electrical behaviour includes the U-I or E-J characteristics which are specific for every type of superconductor. This type of simulations is mainly made to predict the performance of the limiter in the electric power system if a short circuit occurs. The rise time of this signals is in the region of milliseconds. Signals with a smaller rise time can cause high voltage stresses if the frequency of the signal corresponds to the natural frequencies of the winding system. In this case resonance excitations are caused in the windings of the limiter, which can lead to insulation faults and therefore have to be considered during the design. High voltage stresses in electric power systems can be caused by lightning strikes, disconnecting operations or system disturbances. The rise times of the initiated travelling waves are in the range of ms to ns and correspond to frequencies in the range of khz to several MHz. In this paper the transient behaviour of a high T c resistive SFCL made of BSCCO tubes is modelled and evaluated. A lumped network model of a 5 MVA limiter is established and simulations in both, time- and frequency-domain are performed. The model includes the frequency dependence of the resistance R, being caused by the skineffect and the frequency dependence of the inductance L. resonant oscillations are excited. These cause high voltage stresses in the windings of the limiter, which can lead to insulation faults, and therefore have to be considered in the design of the limiter. If electrical equipment is deployed in electric power networks in Europe, it has to withstand the demands of the European standard IEC 600056. This standard includes for equipment used in the 0 kv voltage level the test with a./50 µs lightning impulse voltage with 75 kv peak value, a power-frequency withstand voltage with 8 kv r.m.s. value and a 30/300 µs lightning stroke current with 30 ka peak value. To investigate the transient behaviour of the limiter a lumped network model has been developed, allowing us to calculate voltages and currents in all windings. II. LIMITER There are two main types of superconducting fault current limiters being used for current limitation. One is the inductive- or shielded core type and the other a resistive type []. The limiter being modelled in this work is a resistivetype limiter made of melt cast processed BSCCO tubes which have already been tested successfully [3]. Fig.. shows the design of one module. Keywords Transient Analysis, Modeling, Superconducting Fault Current Limiter, PSpice I. INTRODUCTION The design of superconducting equipment, such as the SFCL, includes thermal and electrical properties of the material []. Thermal properties deal with the resistive heating due to AC losses during normal operation and especially for the SFCL an increasing resistance due to fault current limitation. Electrical properties often deal with critical current density J c and critical electrical field strength E c. An important fact being not considered sufficiently is the coordination of insulation to withstand overvoltages caused by resonance excitations. Electrical equipment can be subject to various kinds of high voltage stresses caused by lightning strikes, disconnecting operations or system disturbances. The rise times of the initiated travelling waves are in the range of ms to ns and correspond to frequencies in the range of khz to several MHz. If the dominating frequency of a signal corresponds to the natural frequency of the winding system, Fig. Construction of a tube of the limiter. To prevent an overheating during limitation, the superconductor (SC) has a Copper Nickel shunt parallel, which will carry the current as soon as the superconductor be-

comes normal conducting. To increase the mechanical stability epoxy-glass resin (ER) has been added to the inside of a module. The superconductor is a high T C superconductor and is operated at 65 K to increase the critical current density J C. To reduce the magnetic field B and the forces due to the high currents during limitation the limiter is made as a bifilar wound coil. The main parameters of one module of the limiter are shown in Table. Table I Parameters of BSCCO limiter at T=65K Critical temperature T c 9K Critical current density 3600A/cm Conductor length 5.4 m Cross section 0.4 cm For the application of the limiter in the 0 kv grid, thirty modules per phase will have to be connected in series. Thus, one phase of the complete SFCL will have a length of 6 m approximately. III. LUMPED NETWORK MODEL OF THE SFCL To simulate the resonant behaviour of the limiter, electric and magnetic fields are assigned to an electric network consisting of lumped elements, Fig.. To use lumped elements, the conductor has to be considered as electrically short [4]. The distinction between electrically short and electrically long lines is possible either in the time- or in the frequency domain. In the time domain, the rise time of a signal has to be smaller than the travelling time τ. Otherwise the currents and voltages have to be described with partial differential equations, since they are both, time- and location dependent. Each winding turn of a module was modeled by a single discrete inductance L in series with a resistance R, representing the magnetic self-field and the ohmic-losses. The mutual inductance M represents the coupling between each single winding of the limiter. The two branches in parallel in each winding correspond to the superconductor and the copper-nickel-shunt. The conductance G between superconductor and shunt represents the contact resistance of the solder. Capacitance elements C account for the electric field between adjoining windings and between windings and the grounded cryostat walls. IV. REDUCED MODEL To enable a computation of the complete limiter with 30 modules in series, several windings of a module have been combined to one branch in the model. Therefore, the inductances, resistances, capacitances and couplings had to be summarized. An appropriate number of windings has to be found as a compromise between computation time and accuracy of the model. In our case five windings have been combined to one branch. The amount of parts with and without reduction is shown in Table Table II Number of elements for regular and reduced model Parts Regular Model Reduced Model Capacitances 470 39 Inductances 60 480 Resistances 430 960 Couplings 76680 3600 V. DETERMINING THE LUMPED ELEMENTS Fig. Section of a limiter winding with the complete electricand magnetic coupling. A. Resistance The DC-impedance (R DC ) for the CuNi shunt R sh was calculated with the resistivity of CuNi for 65K. However, for transient investigations the AC resistance of the CuNi shunt differs from the DC value because of the skin effect. With increasing frequency the resistance will increase since the current is displaced towards the outer border of the conductor. The resistance of the superconductor R SC of the lumped network model is set to the normal state resistance near T c to investigate the behaviour of a already quenched conductor. An analytical solution is feasible only for simple wires with circular cross-section. Since the conductor in this work has a rectangular surface, a two dimensional axissymmetric FE model of one winding was created and Fig. 3 shows the distribution of the current density for various frequencies. Based on P = UI and R = P/I the resistance of the CuNi shunt can be calculated with the formula J dv σ () V R = JdA A

where σ stands for the conductivity, J for the current density, V for the Volume and A for the surface of the conductor from Fig. 3. Fig. 4 shows the frequency dependence of the resistance caused by the self-field of the current. It can be seen that the AC resistance is twelve times the DC value for a frequency of 8 MHz. Fig. 5 Frequency dependence of the Inductance L of one winding. Fig. 3 Distribution of current density for khz (left), MHz (middle) and 9 MHz (right), showing the current density increasing on the conductor border as the frequency increases. The values for the mutual inductance M ik of two coils i and k close together have been calculated with EFFI [5], which is based on Biot-Savart s Law. The general formula to calculate the mutual inductance of two coils is M µ = 4π I I ik r VV J ( r) J ( r' ) r' dv dv, () where I and I are the currents through coil and coil, respectively. J and J are the corresponding current densities and r r' is the distance between the two coils with volumes V and V, respectively. The mutual inductance of more distant windings has been calculated with [6] Fig. 4 Frequency dependence of the Copper-Nickel shunt resistance. B. Self- and Mutual Inductance The DC value for the self inductance of a single winding was also calculated with a two dimensional axisymmetric FE model. The inductance can be devided in an inner inductance L i coming from the component of the magnetic field strength H in the conductor and an outer conductance L o from H outside of the conductor. Because of the above mentioned skin effect, L i will be also frequency dependent. Fig. 5 shows the frequency dependence of the inner inductance L i, the constant value for the outer conductance L o and the total conductance L total. C. Capacitances All capacitances of the lumped network were considered to be constant for the investigated frequency range. The capacitances between single windings of a module were obtained with simple analytical formulae. The coupling capacitances between adjacent windings of different modules and the grounded cryostat were obtained with a two dimensional FE model of the limiter, Fig. 6. One can see one phase of the limiter with the thirty modules and the grounded cryostat. Brighter regions have a higher magnitude of electrical field strength. The capacitance was determined with the following formulae W = and Volume E D dv (3) 3

CU W =, (4) where W denotes the electric energy of the field, E the electric field, D the displacement current density, C the capacity and U the voltage. V peak voltage and a frequency range from Hz to 00 MHz was performed with a circuit without cables and resistance and the results are shown in Fig. 8. One can see the simulated per unit voltage between two windings of module. The results show a 5.5 times higher voltage between the windings at 0 MHz as compared to the DC value U 0. Fig. 6 D FE model with field distribution of the limiter VI. MODEL AND SIMULATION To investigate the transient behaviour of the limiter, a PSpice model, consisting of thirty modules in series, with the values from section IV has been developed. Fig. 7 shows the block diagram of the limiter. Fig. 8 P.U. Voltage between windings of module one. As mentioned in the introduction, the limiter has to withstand certain tests defined by the European standard IEC 600056. In this work the model is tested with the./50 µs lightning impulse voltage. To test the insulation a impulse of 40 kv peak and a rise time of 0. µs is applied. Since the frequency of 50 Hz leads to a homogeneous distribution, the effects of the power-frequency withstand voltage are not investigated. Fig. 9 shows the results of the simulation with the./50 µs lightning impulse voltage with 50 kv crest value. Fig. 7 Block diagram of the limiter. The equivalent network, shown in Fig., is implemented in each module with the reductions from chapter IV. The circuit consists of a voltage source with a 30 Ω impedance, a cable with a characteristic impedance of 30 Ω, the limiter with thirty modules followed by another 30 Ω cable. The circuit was used for time domain analysis. The 30 Ω impedance is used to terminate the cable and thus not to obtain reflections of the signal. The following simulations have been performed with a quenched superconductor with a resistivity near T C. This case represents the worst case scenario where a surge propagates into the SFCL after a limitation. In general, a circuit with capacitances and inductances represents a resonant circuit. High overvoltages can occur, if natural frequencies of the circuit are excited. To determine these frequencies, a frequency domain analysis with Fig. 9 Voltages between windings of module one. The voltage is then divided between R source and the cable to the desired withstand voltage of 75 kv. One can see on 4

Fig. 9 that no overvoltages occur due to resonant excitations. The voltage is distributed homogeneously over the thirty modules, hence approximately. kv are between in- and output of one module. The dotted- and dashed lines represent the voltage between windings 4 and 5 and between 7 and 8 of the same module. The first harmonic of this impulse is 08 khz and according to Fig. 6 no resonance is expected for this frequency. A second simulation was performed with a impulse of 40 kv peak and a rise time of 0. µs. The results are shown in Fig. 0. According to the number of modules a peak voltage of.33 kv has to be expected. However, a peak of kv can be observed being caused by resonance excitations. Since the value does not exceed the breakdown strength of the liquid Nitrogen between two windings, no counteractive measures have to be taken into account. ACKNOWLEDGMENTS This work has been supported by the Graduate Research Center Applications of Superconductivity of the German national science foundation DFG. The authors would like to thank C.Meinecke for valuable discussions. REFERENCES [] R. Petranovic; A.M. Miri; F. Breuer; S. Elschner, Simulation Of Short Circuit Tests With A Resistive Type Superconducting Fault Current Limiter Proceedings of the 0th International Symposium on Short-Circuit Currents in Power Systems SCC 00, pp. 09-3. [] P. Komarek, Hochstromanwendung der Supraleitung, B.G.Teubner, 995, pp. 74-85 [3] S. Elschner, F. Breuer, A. Wolf, M. Noe, L. Cowey, J. Bock, Characterization of MCP BSCCO bulk material for resistive current limiters.ieee Trans. Applied Superconductivity, vol., issue, March 00, pp. 507-50. [4] A.Schwab, Field Theory Concepts, st ed., Springer Verlag, 988, pp. 39-49. [5] S. J. Sacket. EFFI-A code for calculating the electromagnetic field, force and inductance in coil systems for arbitrary geometry. UCRL-540, 978. [6] F. Grover, Inductance calculations. Working formulas and tables. Dover Publications, 973. Fig. 0 Voltages between windings of module one VII. CONCLUSIONS The transient behaviour of a high T c resistive superconducting 0 MVA limiter (SFCL) made of 30 series connected Bi- tubes was investigated. Therefore a lumped network model of the limiter was implemented in Pspice. The parameters of the model (R, L, C) are obtained with both, analytical formulae and FE models. Frequency dependence of the resistance R and the inner inductance L i is determined and included in the model. To enable a computation of the model the number of elements is reduced. To determine the resonance frequencies of the limiter a frequency domain analysis is performed. After frequency domain analysis a time domain analysis is performed with voltages required from the European standard IEC 600056. No overvoltages due to resonance excitations can be observed. 5