CASE STUDY. Implementation of Active Harmonic Filters at Ford Motor Company SA Silverton Plant

Similar documents
HARMONICS THE BASICS H A R M O N I C M I T I G A T I O N A N D D I S P L A C E M E N T P O W E R F A C T O R C O R R E C T I O N

CHAPTER 5 POWER QUALITY IMPROVEMENT BY USING POWER ACTIVE FILTERS

Harmonic Solutions in Electrical Systems. Raed Odeh Application Specialist - Power Quality & Electrical Distribution

Active Harmonic Filter (AF3)

Low Pass Harmonic Filters

22.0 Harmonics in Industrial Power Systems

Welcome to the rd. Annual Northern Ohio. 3 rd Energy Management Conference September 30, 2008

Technical Paper. Harmonic Distortion in Data Centers

Effective Harmonic Mitigation with Active Filters

APQline Active Harmonic Filters. N52 W13670 NORTHPARK DR. MENOMONEE FALLS, WI P. (262) F. (262)

ARE HARMONICS STILL A PROBLEM IN DATA CENTERS? by Mohammad Al Rawashdeh, Lead Consultant, Data Center Engineering Services

3/29/2012 MAIN TOPICS DISCUSSED ELECTRICAL SYSTEMS AND ELECTRIC ENERGY MANAGEMENT SECTION K ELECTRIC RATES POWER COMPUTATION FORMULAS.

Electromagnetic Harmonic Filters Technical Guide

THE COMPREHENSIVE APPROACH TO FACILITY POWER QUALITY

A PQ Case Study CS 36 HOSP 14. A Case Study OF Harmonics Mitigation in a Hospital and its Benefits

Active Harmonic Filter (AHF)

Reliable power onboard and offshore

Technical News. Part 2: Harmonics. The link between harmonics and power factor. Industrial Electrical and Automation Products, Systems and Solutions

Harmonic Filters for Power Conversion Equipment (Drives, rectifiers, etc) Effects of Harmonics IEEE Solutions

World Academy of Science, Engineering and Technology International Journal of Electrical and Computer Engineering Vol:7, No:6, 2013

Emicon Engineering Consultants L.L.C.

Harmonics Reduction using 4-Leg Shunt Active Power Filters

Harmonic Distortion and Variable Frequency Drives

McGill Power Sales & Engineering, INC.

Alternator winding pitch and power system design

Motors and drives. Module B- Introduction to input measurements

AccuSine PCS Active Harmonic Filter. Cruise through rough waves in your electrical network

Fluke 40/41 Power Harmonics Analysers

Harmonics, its Mitigation & Result of Case study of Spinning Mill

Enhancement of Power Quality Using Advanced Series Active Power Filters

Active Harmonic Filters IPC150 AHF Series

Analysis of Harmonic Distortion in Non-linear Loads

Thyristorised Automatic Power Factor

AccuSine PCS Active Harmonic Filter. Cruising through rough waves in your electrical network

Reducing Total Harmonic Distortion with Variable Frequency Drives

Power Quality implications of new residential appliances. EEA Conference & Exhibition 2010, June 2010, Christchurch

Harmonic Filters for Single Phase Equipment

Presents. Harmonics Years

A Thyristor Controlled Three Winding Transformer as a Static Var Compensator

Harmonic Filters and Reactors

PQ01. Harmonic Solutions for VFD s. Review of Power Control Harmonics, Power Factor, Distortion & Displacement

UNBALANCED CURRENT BASED TARRIF

Guide to Harmonics. Reactive Power and Harmonic Compensation POWER QUALITY. The Basics of Harmonics

Dynamic Harmonic Mitigation and Power Factor Correction

Power IT LV Active Filters PQFA - PQFL - PQFT

Study of Power Factor Correction in Single Phase AC-DC Converter

Power Factor. Power Factor Correction.

Tripping of circuit breakers in PV installations due to zero sequence field impedance

Harmonics Issues that Limit Solar Photovoltaic Generation on Distribution Circuits

ZENER ELECTRIC PTY LTD

Harmonic Mitigation for Variable Frequency Drives. HWEA Conference February 15, Kelvin J. Hurdle Rockwell Bus. Dev. Mgr.

ECET Modern Power

An easy-to-use Precision Power Analyser. The touch of a button gives direct readout of true power and a host of other useful measurements.

Improvement of Power System Distribution Quality Due to Using Dc-Converter Loads and Electric Arc Furnaces. H.A. Khalik, M. A. Aziz, and E. Farouk.

Harmonics I Harmonics White Paper. Power Protection Products, Inc. by Dan Maxcy l 2018 Update

Chapter M Harmonic management

PF Correction Techniques in highly varying load

Multi-Pulse Rectifier Solutions for Input Harmonics Mitigation Applicable Product: F7, G7, P7 and E7

NJWA - Harmonics and Drives Proper System Design

Power Conditioning Equipment for Improvement of Power Quality in Distribution Systems M. Weinhold R. Zurowski T. Mangold L. Voss

Section 11: Power Quality Considerations Bill Brown, P.E., Square D Engineering Services

Introduction to Harmonics and Power Quality

Understanding Power Quality

Liebert AF2 Next Generation Active Harmonic Filter. Power Protection for Business-Critical Continuity TM

Welcome SUMMARY SERVICE AND SUPPORT WHEN IT REALLY MATTERS. n Introduction. n Service and Support when it really matters

Power Factor improved by Variable Speed AC Drives By Mauri Peltola, ABB Oy, Drives

Power IT LV Active Filters PQFI PQFM PQFK. The ABB comprehensive solution for active filtering of harmonics

1C.4.1 Harmonic Distortion

ABB DRIVES Technical guide No. 6 Guide to harmonics with AC drives

How adjustable speed drives affect power distribution

P2 Power Solutions Pvt. Ltd.

Generator Advanced Concepts

Do You Have a Harmonic Problem?

VARIABLE FREQUENCY DRIVE OPERATION AND APPLICATION OF VARIABLE FREQUENCY DRIVE (VFD) TECHNOLOGY

APPLICATION GUIDE. Harmonics in HVAC applications

THE FIRST STEP IN THE RESOLUTION OF VOLTAGE DISTORTION FOR SHARED GENERATORS AND MV UNDERSEA RING MAIN IN AN OFFSHORE OIL FIELD

CHAPTER 4 HARMONICS AND POWER FACTOR

POWER FACTOR CORRECTION USING BOOST CONVERTER

7/15/2002 PP.AFD.08 1 of 28

Reduction Of Harmonics By Using Active Harmonic Filter

HARMONIC MITIGATIONCASE STUDY

LV PFC Basics. Power Factor Correction - Basics FK PC PM PFC Januar 07 Page: 1

An Introduction to Power Quality

Improving the Power Factor Correction in the Presence of Harmonics by Reducing the Effect of Resonance and Harmonics

2.10. Adjustable Frequency Drives. Clean Power Drives. Clean Power Drives

p. 1 p. 6 p. 22 p. 46 p. 58

Harmonics Elimination Using Shunt Active Filter

Power Quality improvement of a three phase four wire system using UPQC

POWER FACTOR CORRECTION AND ITS PITFALLS

Harmonic Reduction using Thyristor 12-Pulse Converters

UNIVERSAL MEASURING INSTRUMENTS. TNM 34xx. TNM 3410 / 3420 / 3430 / 3440 Universal measuring instrument 1/49

Active Harmonic Filter

Production power on a budget: How to generate clean reliable power, Part 1 By Guy Holt

Variable Frequency Drive Packages with Harmonic Mitigation. Low Harmonic Drive Packages Engineered by Rockwell Automation

ENERGY SAVINGS THROUGH POWER CONDITIONING WITH THE PowerGUARD SYSTEM

Effects of Harmonic Distortion I

Harmonic Mitigating Transformer - Technical Guide

Harmonics and Their Impact on Power Quality. Wayne Walcott Application Engineering Manager June, 2017

DSP-BASED CURRENT SHARING OF AVERAGE CURRENT CONTROLLED TWO-CELL INTERLEAVED BOOST POWER FACTOR CORRECTION CONVERTER

Voltage-controlled active filter gives standby generator power quality

Transcription:

CASE STUDY Implementation of Ford Motor Company SA Silverton Plant 1 SCENARIO Ford Motor Company is a global automotive and mobility company based in Dearborn, Michigan. Ford Motor Company of Southern Africa (FMCSA) has been an active participant in the South African motor industry since 1923 when they began assembling Model T cars in a disused wool shed in Port Elizabeth. FMCSA has become one of Southern Africa s leading automotive companies. The Silverton Assembly Plant in Pretoria assembles light commercial vehicles that are supplemented with passenger vehicle imports from a number of different countries. The Struandale Engine Plant in Port Elizabeth has significantly upgraded and expanded its machining and assembly capabilities for this programme, and now has an annual production capacity of 250,000 machined component kits, comprising of engine heads, blocks and crankshafts for the Duratorq TDCi engine. Approximately 75,000 of these are used for local engine assembly to power the new Ranger built at the Silverton Assembly Plant. The remaining 175,000 component sets are destined for export to Ford engine assembly plants in Thailand and Argentina. FMCSA recently invested ± US$272 million into South Africa, which has transformed both plants into world class facilities to produce the new Ford Ranger and Duratorq TDCi engine for local consumption and export to 148 countries worldwide. Annual capacity has been increased at the Silverton Assembly Plant to 110,000 units. Cost saving initiatives are always high on the agenda in any business, and with Ford it is no exception. This case study describes the implementation of new technology, Active Harmonic Filters, at the Ford Silverton Plant in order to reduce direct and indirect costs that are caused by harmonic pollution on the electrical power system. 2 HARMONIC PROBLEM Various unplanned plant shutdowns as a result of circuit breaker trips, equipment failures and malfunction of certain equipment occurred in the Ford Silverton Plant in recent times, some of which are believed to be a result of poor Power Quality on the electrical distribution networks feeding to the plant equipment. Power Quality (PQ) audits that were conducted since 2015 have indicated high levels of harmonic distortion on most of the transformers LV outputs in the three Substations that feed to the Bodyshop, Paintshop and Assembly Line. The current harmonics that are caused by the non-linear loads, which include Robot Controllers, Welders, Variable Speed Drives on motors (pumps, compressors), UPSs, Fluorescent Lights, and other loads that have some kind of AC/DC rectifier on the input, cause distortion on the voltage waveforms on the LV output of the transformers. As transformers also have impedance, voltage distortion appears at the transformer s secondary terminals when harmonic currents flow through it. File: Ford AHF.docx Page 1 of 11

Distorted voltage waveforms on the transformer s LV output is not ideal, since other sensitive equipment that may be supplied from the transformer s LV output will receive the distorted voltage waveforms, which can have a detrimental impact on the performance and reliability of these equipment. Common symptoms of problematic harmonic levels include overheating of motors, drives, cables, thermal tripping of protective devices and logic faults of digital devices, all of which can result in downtime. In order to reduce voltage distortion on a transformer s output, two factors can be modified: the transformer impedance can be reduced, or the level of harmonic currents through the transformer can be reduced. The former is neither practical nor economical to implement. Energy Insight proposed an engineering solution to reduce the high harmonic current levels through the transformers in the three Substations in order to reduce voltage distortion levels on the LV distribution networks. 3 SOLUTION By comparing the pros and cons of Passive versus Active Harmonic Filters, Energy Insight proposed to implement an Active Harmonic Filter solution on the transformer outputs in the three Substations. The product that was proposed is the Accusine PCS+ Active Harmonic Filter (AHF) of Schneider-Electric. The AHF employs current transformers to measure the source current to determine the content of harmonic current present. By injecting the synthesized current, harmonic currents through the transformers are greatly mitigated, thus reducing the harmful effects of harmonic current and reducing voltage distortion in order to permit other equipment to operate properly and enjoy a long product life span. Apart from mitigating current harmonics that are generated by the non-linear loads, the AccuSine PCS+ can also be configured to improve the load s power factor by injecting the corrective fundamental (50Hz) component of reactive current into the network. This is commonly known as Power Factor Corection (PFC). A third function can also be enabled, which is the balancing of unbalanced load currents. This is done by injecting the negative sequence reactive component of unbalanced load currents into the network, thereby improving the balancing of three-phase currents drawn from the source. A total of 19 x AHF units was proposed, to be installed on the LV (400V) output of 14 x distribution transformers in the three Substations. The rating of the AHF units range from 60A to 300A. On some of the transfomers where the current distortion levels were high, the use of two AccuSine units in parallel was proposed. For this project, the goal of the AHF solution will be to largely cancel out the whole spectrum of current harmonics (3 rd to 51 st ), to reduce the Current Total Harmonic Distortion (THD) to levels below 5% of fundamental, and as a result to reduce the Voltage THD to levels below 3%. File: Ford AHF.docx Page 2 of 11

Figure 1 shows a single line diagram of a typical installation where two AccuSine AHF units are connected in parallel on the LV output of a distribution transformer. Figure 1: Single Line Diagram of a Typical AccuSine PCS+ AHF Installation 4 BENEFITS Benefits that FMCSA can expect by implementing the Active Harmonic Filter Solution at the three Substations include the following: 1. Reduced Peak RMS Currents through the 14 x Transformers due to the reduction of harmonic currents and fundamental reactive currents (Power Factor Correction). 2. Reduced losses (copper and core) in the 14 x Transformers in the Substations. 3. Reduced kva demand on the transformers due to the reduction of the RMS current through the transformers. This will contribute to the reduction of the kva Demand cost component in the monthly electricity bill. This is a direct cost reduction. 4. Extending the life of transformers. Transformers will run at lower temperatures due to reduced losses. 5. Reduced indirect cost due to unplanned plant downtime in the various Plants, some of which is believed to be caused by poor Power Quality on the LV distribution networks. 6. Source balancing of unbalanced load currents, which can improve the balancing of the supply voltage on the Main LV bus bars, feeding to other sensitive equipment. File: Ford AHF.docx Page 3 of 11

5 RESULTS In the Substation that feeds to Paintshop, a total of 10 x 300A AHF units were installed and commissioned in April 2018 on the LV outputs of 6 x 2,000kVA transformers. The total installed capacity of these ten AHF units is 3,000 Amp @ 400V = 2,078kVA. The units were configured to mitigate the odd current harmonic orders from the 3 rd to the 29 th, to correct the power factor on each transformer to at least 0.98 (lagging), and to perform source current balancing using the remaining capacity of the AHF units. Most units were configured to control the Current Total Harmonic Distortion THDi on 1%. Figure 2 shows some of these AHF units that were installed in this Substation. Figure 2: AccuSine PCS+ AHF Units in Paintshop Substation Figure 3 shows a snapshot that was taken of the current waveforms that are measured and displayed on the HMI Controller of one of two AccuSine AHF units in parallel. The waveforms shown are I out (output of the AHF unit), I load (distorted load current), and I src (transformer current), all for phase 1. The sum of the load current and two times the AHF output current (because of two units in parallel) results in the almost sinusoidal source current (blue line). Figure 3: Screenshot from an HMI Controller on one AccuSine AHF Unit File: Ford AHF.docx Page 4 of 11

RMS VOLT The table below shows a summary of the results obtained on one of the transformers (TRX- 3) in the Paintshop Substation (Sub-10). Of note is the reduction of THDi from 14.6% to 1.06%, the reduction of THDv from 4.78% to 2.02%, the reduction of the transformer current by 9.6%, and the reduction of the kva demand through the transformer by 5.9%. Measurement Unit Without With AccuSine % Compensation PCS+ Change Voltage (average line-line) V 394 396 +0.5 Current (average phase) A 1,425 1,288-9.6 Current Unbalance Factor % of Average Current 4.28 2.58-39.7 Real Power kw 893 886-0.8 Reactive Power kvar 318 70-78.0 Apparent Power kva 948 892-5.9 Displacement Power Factor PU 0.94 0.997 +6.1 True Power Factor PU 0.929 0.997 +7.3 THDv % of Fundamental 4.78 2.02-57.7 THDi % of Fundamental 14.6 1.06-92.7 Vh5 (5 th order voltage) % of Fundamental 4.03 1.03-74.4 Vh7 (7 th order voltage) % of Fundamental 2.20 0.66-70.0 Ih5 (5 th order current) % of Fundamental 14.85 0.26-98.2 Ih7 (7 th order current) % of Fundamental 5.55 0.18-96.8 Table 1: Paintshop Substation Results Summary:TRX-3 Figure 4 shows the Transformer Output Voltage with and without the AccuSines activated. There was no significant impact on the RMS Output Voltage. The average line-line voltage slighlty increased by 0.5%, as a result of the stabilizing effect that the AccuSine units provide through leading reactive current injection into the network. FORD SUB-10 TFR-3 OUTPUT VOLTAGE PROFILES (10-minute data) Voltage A-B Mean [V] Voltage B-C Mean [V] Voltage C-A Mean [V] Low Limit [V] High Limit [V] 450 440 430 420 410 400 390 380 370 360 350 Figure 4: Paintshop Substation Transformer Output Voltage File: Ford AHF.docx Page 5 of 11

PERCENTAGE OF AVERAGE CURRENT RMS AMPERE Figure 5 shows the Transformer Output Current with and without the AccuSines activated. There was a significant reduction in the RMS Output Current on all three phases. On average the RMS value of the phase currents reduced by 9.6%. FORD SUB-10 TFR-3 OUTPUT CURRENT PROFILES (10-minute data) 1,600 Current A Mean [Amp] Current B Mean [Amp] Current C Mean [Amp] 1,400 1,200 1,000 800 600 400 200 0 Figure 5: Paintshop Substation Transformer Output Current Figure 6 shows the Transformer Output Current Unbalance Factor with and without the AccuSines activated. There was an almost 40% reduction in the Current Unbalance factor. FORD SUB-10 TFR-3 OUTPUT CURRENT UNBALANCE PROFILE (10-minute data) 6.0 Current Unbalance Mean [%] 5.0 4.0 3.0 2.0 1.0 0.0 Figure 6: Paintshop Substation Transformer Output Current Unbalance Factor File: Ford AHF.docx Page 6 of 11

POWER FACTOR [LAGGING] POWER [kw, kvar, kva] Figure 7 shows the Transformer Output Power with and without the AccuSines activated. There was a 78% reduction in the Reactive Power due to the leading reactive current injection of the AccuSine units. The Apparent Power was reduced by 5.6%. FORD SUB-10 TFR-3 OUTPUT LOAD PROFILES (10-minute data) 1,200 Real Power Mean [kw] Reactive Power Mean [kvar] Apparent Power Mean [kva] 1,000 800 600 400 200 0 Figure 7: Paintshop Substation Transformer Output Power Figure 8 shows the Transformer Displacement Power Factor with and without the AccuSines activated. There was a significant improvement in the Power Factor from 0.94 (lagging) to 0.997 (lagging). FORD SUB-10 TFR-3 OUTPUT POWER FACTOR PROFILE (10-minute data) 1.02 Power Factor Mean 1.00 0.98 0.96 0.94 0.92 0.90 0.88 Figure 8: Paintshop Substation Transformer Displacement Power Factor File: Ford AHF.docx Page 7 of 11

PERCENTAGE OF FUNDAMENTAL PERCENTAGE OF FUNDAMENTAL Figure 9 shows the Voltage Total Harmonic Distortion with and without the AccuSines activated. There was a reduction of 58% in the THDv, which is significant. FORD SUB-10 TFR-3 OUTPUT VOLTAGE THD PROFILES (10-minute data) 6.0 THD Voltage V1 Mean [%] THD Voltage V2 Mean [%] THD Voltage V3 Mean [%] 5.0 4.0 3.0 2.0 1.0 0.0 Figure 9: Paintshop Substation Transformer THDv Figure 10 shows the Current Total Harmonic Distortion with and without the AccuSines activated. There was a reduction of almost 93% in the THDi, which is an outstanding result. The THDi setpoint is set on 1%, and the AccuSine units controls the THDi on this value under all loading conditions. FORD SUB-10 TFR-3 OUTPUT CURRENT THD PROFILES (10-minute data) 30 THD Current A Mean [%] THD Current B Mean [%] THD Current C Mean [%] 25 20 15 10 5 0 Figure 10: Paintshop Substation Transformer THDi File: Ford AHF.docx Page 8 of 11

PERCENTAGE OF FUNDAMENTAL Figure 11 shows the Voltage Harmonic Spectrum with and without the AccuSines activated. There was a significant reduction in the magnitude of all the individual voltage harmonics orders, the most significant being the reduction of the 5 th and 7 th orders. The 5 th order was reduced by 74%, and the 7 th order by 70%. FORD SUB-10 TFR-3 OUTPUT VOLTAGE HARMONICS Before Active Filter After Active Filter 5.0 4.5 4.0 3.5 3.0 2.5 2.0 1.5 1.0 0.5 0.0 THD Vh3 Vh5 Vh7 Vh9 Vh11 Vh13 Vh15 Vh17 Vh19 Vh21 Vh23 Vh25 Vh27 Vh29 Vh31 HARMONIC ORDER Figure 11: Paintshop Substation Transformer Voltage Harmonic Spectrum Figure 12 shows the three-phase Voltage waveforms with and without the AccuSines activated. Without the AccuSine units activated, the presence of waveform distortion is evident in the top graph on each phase. The waveforms in the bottom graph, with the AccuSine units activated, are almost purely sinusoidal. THDv is down to 2%. Figure 12: Paintshop Substation Transformer Voltage Waveforms File: Ford AHF.docx Page 9 of 11

PERCENTAGE OF FUNDAMENTAL Figure 13 shows the Transformer Output Current Harmonic Spectrum with and without the AccuSines activated. There was a huge reduction in the magnitude of all the individual current harmonics orders, the most significant being the reduction of the 5 th and 7 th orders. The 5 th order was reduced by 98%, and the 7 th by 97%, which is an outstanding result. FORD SUB-10 TFR-3 OUTPUT CURRENT HARMONICS Before Active Filter After Active Filter 18 16 14 12 10 8 6 4 2 0 THD Ih3 Ih5 Ih7 Ih9 Ih11 Ih13 Ih15 Ih17 Ih19 Ih21 Ih23 Ih25 Ih27 Ih29 HARMONIC ORDER Figure 13: Paintshop Substation Transformer Current Harmonic Spectrum Figure 14 shows the Transformer Output Current waveforms with and without the AccuSines activated. Without the AccuSine units activated, the presence of the 5 th and 7 th orders is evident in the top graph on each phase. The waveforms in the bottom graph, with the AccuSine units activated, show much less distortion. THDi is down to 1%. Figure 14: Paintshop Substation Transformer Current Waveforms File: Ford AHF.docx Page 10 of 11

6 CONCLUSIONS The AccuSine PCS+ Active Harmonic Filter Solution was successfully implemented in the Paintshop Substation at Ford Silverton Plant. Results for the other two substations where the other nine Active Filter units are installed, are pending since those units still need to be connected to the Transformers, and be commissioned. This is expected to be done by end of June 2018. The current harmonic distortion through all six transformers in the Paintshop substation were reduced to very low levels, resulting in a Current Total Harmonic Distortion of 1% on most transformers. The reduced current distortion through the transformers resulted in a significant reduction in the distortion of the transformers output voltage waveforms. This will benefit other sensitive loads that are connected on the transformers outputs, and should result in a reduction of nuisance trips and equipment malfunction that were previously experienced. Furthermore, the reduced current harmonics through the transformers will result in a reduction of transformer core losses. The RMS current through the transformers were significantly reduced, resulting in a reduction of kva demand on the primary side of the transformers, and a reduction of transformer winding losses. Due to the reduction of winding and core losses in the transformers, they will operate at lower temperatures, thereby extending their live span. Compiled by Johan Roos +27 82 894 6825 E-mail: johanr@energyinsight.co.za Web: www.energyinsight.co.za File: Ford AHF.docx Page 11 of 11