Bulletin L NEMA AC Electrically Held Lighting Contactors Product Selection Top Wiring for Non-Motor and Lighting Loads Tungsten Lamp Loads (Max. V Line, V Load) Maximum Continuous Ampere Ratings [A] General Use Resistive Heating Ballast Lighting (Fluorescent) Discharge Lighting (Mercury Vapor High Pressure Sodium and Metal Halide) Open Type Without Enclosure Type General Purpose Enclosure Type /X Watertight, Corrosion- Resistant Enclosure Stainless Steel Power Poles V AC Maximum Hz Type R// Rainproof, Dusttight Industrial Use Enclosure Cat. No. Cat. No. Cat. No. Cat. No. L-TO L-TA L-AO L-AA L-AC L-AJ L-BO L-BA L-BC L-BJ L-CO L-CA L-CC L-CJ L-DO L-DA L-DC L-DJ L-EO L-EA L-EC L-EJ L-FO L-FA L-FC L-FJ L-GO L-GA L-GC L-GJ L-HO L-HA L-HC L-HJ L-JO L-JA L-KO L-KA General Use Resistive Heating Tungsten Lamp Loads (Max. V Line, V Load) Ballast Lighting (Fluorescent) Discharge Lighting (Mercury Vapor High Pressure Sodium and Metal Halide) Cat. No. Cat. No. Cat. No. Cat. No. Power Poles V AC Maximum Hz L-TO L-TA L-AO L-AA L-AC L-AJ L-BO L-BA L-BC L-BJ L-CO L-CA L-CC L-CJ L-DO L-DA L-DC L-DJ L-EO L-EA L-EC L-EJ L-FO L-FA L-FC L-FJ Coil Voltage Code The cat. no. as listed is incomplete. Select a coil voltage code from the table below to complete the cat. no. Example: Cat. No. L-AO becomes Cat. No. L-AOD. For other voltages, consult your local Rockwell Automation sales office or Allen-Bradley distributor. [V] - - - - - - - - - AC, Hz K S P T N KN I Q M R AC, Hz J D H A F U B C Fiberglass-reinforced polyester hubs are included with each starter. Does not include line and load lugs, see page - for kits. Feed-through wiring only. Only available on sizes. When using V coils on size or, an interposing relay may be required. See coil VA values on page -. This coil is optimized for V, Hz applications, but can be used at V, Hz nominal. This coil is optimized for V, Hz applications, but can be used at V, Hz nominal. This coil is optimized for V, Hz applications, but can be used at V, Hz nominal. This coil is optimized for V, Hz applications, but can be used at V, Hz nominal. Special Purpose Bolted Enclosures Hazardous Location Contactor Type & ; Class I, Groups C & D; Class II, Groups E, F & G Type R, & ; Class I, Groups C & D; Class II, Groups E, F & G Size Poles Divisions & Enclosure Code (E) Divisions & Enclosure Code (H) Available Available - www.ab.com/catalogs Preferred availability cat. nos. are bold. Publication A-CAA-EN-P
Bulletin Line Approximate Dimensions NEMA AC Contactors Approximate dimensions are shown in inches (millimeters). Dimensions are not intended to be used for manufacturing purposes. Open Type without Enclosure for Bulletin FL, L, and LP and for NEMA sizes, for Bulletin and F Contactors Note: Top mounting hole on Size is / in. (. mm) to the left of centerline on Open Type. Mounting screws: # for sizes, / #, or / # for sizes. NEMA Size /A /A A A A A A Bulletin F-FL Number of Switching Poles Bulletin L-LP -- A Width -/ () -/ (.) -/ () -/ () -/ () -/ () -/ () -/ (.) -/ (.) -/ (.) () -/ (.) -/ (.) () For Feed-Through Wiring this dimension is -/ in. ( mm). For Feed-Through Wiring this dimension is -/ in. ( mm). For Feed-Through Wiring this dimension is -/ in. ( mm). B Height -/ () () -/ () -/ () -/ () -/ () Dimensions in Inches (Millimeters) C Depth D E -/ (.) -/ () -/ () -/ (.) -/ (.) -/ () -/ () -/ () -/ () -/ () -/ () -/ () -/ () -/ () -/ () -/ () -/ () -/ () Approximate Shipping Weight [lb (kg)] (.) (.) -/ (.) -/ (.) (.) -/ (.) -/ (.). (.) (.) () (). (.). () (.) - Publication A-CAA-EN-P
Bulletin Line Mechanical Ratings NEMA Size Mechanical Life (Millions of Operations) Maximum Number of Auxiliary Contacts Operating Time [ms] Pick-up (Average) Drop-out (Average) Construction NEMA Size Wire Size for Power Terminals Required Torque on Power Terminal Wire Clamps and Pressure Connectors or Lugs Type of Power Terminal # AWG lb in Pressure terminals # AWG lb in # AWG lb in Saddle or wire clamps # AWG lb in Pressure terminals # / AWG lb in # / AWG lb in # AWG MCM lb in Lugs sold separately. See page -. Direct bus connections only. Environmental Power Contacts Silver alloy Contact Material Auxiliary Contacts Silver Requirements for Sizing of Wire All wire rated F ( C) or higher must be sized per the local Electrical Code for F ( C) wire. NEMA Size Operating Position Operating Temperature Range Altitude Corrosion-Resistance Horizontal Starters with eutectic alloy Overload relay + F ( + C) Vertical Horizontal Vertical Starters with SMP Overload relay + F ( + C) (provided condensation is prevented) feet before derating All metal parts are treated for corrosion-resistance Publication A-CAA-EN-P -
Bulletin Line Short Circuit Rating Combination contactors and starters with disconnect switch: Bulletin,,, E, F, G, and X NEMA Size Combination Contactors and Starters with Disconnect Switch: Bulletin,,, E, F, G, and X Fuse Type Available Short Circuit Amperes RMS Symmetrical [A] H, K Maximum Voltage [V] H, K J, R L L Combination Lighting Contactors with Disconnect Switch: Bulletin L Available Short Circuit Amperes RMS Lighting Contactor Rating [A] Fuse Type Symmetrical [A] Maximum Voltage [V] H, K H, K J, R Combination Contactors and Starters with Circuit Breaker: Bulletin,,, E, F, G, and X Available Short Circuit Amperes RMS Enclosure Type NEMA Size Symmetrical [A] Maximum Voltage [V], R, R//, /X (stainless) Unilock R,, & Bolted R,, &, R, R//, /X (stainless) Unilock R,, & Unilock R,, & Bolted R,, & R, R// Combination Lighting Contactors with Circuit Breaker: Bulletin L Available Short Circuit Amperes RMS Enclosure Type Lighting Contactor Rating [A] Symmetrical [A] Maximum Voltage [V], R, R//, /X (stainless) Unilock R,, & Bolted R,, &, R, R//, /X (stainless) Unilock R,, & Unilock R,, & Bolted R,, & For the most up-to-date SCCRs, please see the on-line Industrial Controls catalog at www.ab.com/catalogs. - Publication A-CAA-EN-P
Bulletin Line AC Coil Data NEMA Size Operating Volt Amperes Burden [VA] Inrush Hz Coils Sealed Heat Dissipation [W].. & P. ( poles). ( poles). ( poles) ( poles) ( poles). ( poles). (Series L).. (Interposing relay).. Economized DC Coil (Interposing relay).. Economized DC Coil (Interposing relay).. Economized DC Coil (Interposing relay). Coil Operating Limits % This rating is for the size contactor coil only. All starters are shipped with an interposing relay as standard. Size starters are shipped with a VA control circuit transformer and an interposing relay with a V coil. Voltage is then rectified to DC for the contactor coil. Size starters are shipped with a VA control circuit transformer and an interposing relay with a V coil. Voltage is then rectified to DC for the contactor coil. Size starters are shipped with a VA control circuit transformer and an interposing relay with a V coil. Voltage is then rectified to DC for the contactor coil. Auxiliary Contacts (NEMA A and P) Bulletin, AC Rating Designation A Maximum AC Contact Rating Per Pole [A] Continuous [VA] Maximum Voltage Carrying Current or Hz Make Break [A] Make Break.. Maximum DC Contact Rating Per Pole for, Auxiliary Contacts (Maximum Continuous Carrying Current is A) DC Rating Designation V DC V DC V DC P. A. A (Requires Contacts in Series). A (Requires Contacts in Series) Publication A-CAA-EN-P -
Bulletin Line Load-Life Curves Bulletin Line contactors and starters are designed to provide superior performance in a variety of applications. These load-life curves are based on Rockwell Automation tests according to the requirements defined in IEC -. Actual contact life may vary based on the application, duty cycle, and environmental conditions from that indicated by the curves. To find the contactor s estimated electrical life, follow these guidelines: Choose the appropriate graph that most closely approximates the utilization category of the application. Locate the intersection of the life-load curve of the appropriate contactor with the application s operational current (I e ) found on the horizontal axis. Read the estimated contact life in millions of operations along the vertical axis. Contact Life for Mixed Utilization Categories AC and AC In many applications, the utilization category cannot be defined as either purely AC or AC. In those applications, the electrical life of the contactor can be estimated from the following equation: L = mixed L AC L AC AC + P ( ) L AC Where: L mixed = Approximate contact life for a mixed AC/AC utilization category application L AC = Approximate contact life in operations for AC utilization category (from AC life-load curves below) L AC = Approximate contact life in operations for AC utilization category (from AC life-load curves below) P AC = Percentage of AC operations Utilization Categories CategoryTypical Duty ACStarting of squirrel cage motors and switching off only after the motor is up to speed. ACStarting of squirrel cage motors with inching and plugging duty. Bulletin Load/ Life Curves AC and AC M M M M M NEMA SIZE AC NEMA SIZE M M M M M AC M OPERATING CYCLES M K K K K OPERATING CYCLES K K K K K K K K K K K K K K K K OPERATIONAL CURRENT le (APMERES) OPERATIONAL CURRENT le (APMERES) - Publication A-CAA-EN-P
Bulletin Line Group Motor Ratings for NEMA Contactors/Starters Manual Starters FLA Range (Amps) Group Rating (V) Contactors w/o Limiter with Limiter Size Size Size Size Size -MN-.. ka ka -TO -AO -BO -MN-.. ka ka -TO -AO -BO -MN-.. ka ka -TO -AO -BO -MN-.. ka ka -TO -AO -BO -MN-.. ka ka -TO -AO -BO -MN-.. ka ka -TO -AO -BO -MN-.. ka ka -TO -AO -BO -MN-.. ka ka -TO -AO -BO -MN-.. ka ka -TO -AO -BO -MN-.. ka ka -TO -AO -BO -MN-.. ka ka -AO -BO -CO -MN-.. ka ka -AO -BO -CO -MN-.. ka ka -BO -CO -MN+- P -MN+- P.. ka -CO -DO.. ka -CO -DO Group Rating (V) Starters FLA Range Manual Starters (Amps) w/o Limiter with Limiter Size Size Size Size Size -MN-.. ka ka -TO -AO -BO -MN-.. ka ka -TO -AO -BO -MN-.. ka ka -TO -AO -BO -MN-.. ka ka -TO -AO -BO -MN-.. ka ka -TO -AO -BO -MN-.. ka ka -TO -AO -BO -MN-.. ka ka -TO -AO -BO -MN-.. ka ka -TO -AO -BO -MN-.. ka ka -TO -AO -BO -MN-.. ka ka -TO -AO -BO -MN-.. ka ka -AO -BO -CO -MN-.. ka ka -AO -BO -CO -MN-.. ka ka -BO -CO -MN+- P.. ka -CO -DO -MN+- P.. ka -CO -DO Cat. No. is incomplete. Refer to page -. Cat. No. is incomplete. Refer to page -. Publication A-CAA-EN-P -
Bulletin Line Full Load Currents of -Phase, Hertz AC Induction Motors The full load currents listed below are average values for horsepower rated motors of several manufacturers at the more common rated voltages and speeds. These average values, along with the similar values listed in the U. S. National Electrical Code (NEC), should be used only as a guide for selecting suitable components for the Motor Branch Circuit. The rated full load current, shown on the motor nameplate, may vary considerably from the listed value depending on the specific motor design. ATTENTION: The motor nameplate full load current should always be used in determining the rating of the devices used for Motor Running Overcurrent Protection. HP / / / / -/ -/ RPM Full Load Current [A] V V V V V V........................................................................................................................................................................................... Synchronous speed nameplate is usually less due to slip..................................... HP RPM Full Load Current [A] V V V V V V..................................................................................................................... - Publication A-CAA-EN-P