System and equipment for measurement, registration of parameters and analyse of the quality of the electric energy

Similar documents
MEASUREMENT OF THE PARAMETERS FOR ELECTRIC ENERGY QUALITY. (1) Gabriel VLADUT, (2) Petre-Marian NICOLAE

Simulation Results on the Currents Harmonics Mitigation on the Railway Station Line Feed

UNIT-4 POWER QUALITY MONITORING

ELECTROMAGNETIC POLLUTION PRODUCED BY THE INDUSTRIAL FREQUENCY CRUCIBLE INDUCTION FURNACES IN THE POWER SUPPLY NETWORK

2) APRV detects and records low frequency events (voltage drop, over-voltages, wave distortion) with a sampling frequency of 6400 Hz.

Case Study Survey of Harmonic Pollution Generated by Railway Systems and Filtering Solutions

Multimeter 500CVD21 RTU500 series

MT 560/UMT TRANSDUCER & ANALYZER

Digital Fault Recorder Deployment at HVDC Converter Stations

Harmonic Distortions Analyzer for Power Rectifiers

FACULTATEA DE INGINERIE ELECTRICĂ. Ing. Lucian Diodiu. PHD Thesis ABSTRACT

MODELING THE ELECTROMAGNETIC POLLUTION OF THE ELECTRIC ARC FURNACES

Power Quality Measurements the Importance of Traceable Calibration

Experimental Analysis of Advanced System for Reducing the Energy Consumption of Public Street Lighting Systems

Power Conditioning Equipment for Improvement of Power Quality in Distribution Systems M. Weinhold R. Zurowski T. Mangold L. Voss

Power Quality Control on The Romanian Energy Market

Harmonics Elimination Using Shunt Active Filter

Fundamentals of Power Quality

OPERATING MANUAL POWER QUALITY ANALYZER PQM-707

MICROPROCESSOR-BASED METERING EQUIPMENT SECTION 16901C PART 2

C.A 8332 C.A Display your network analysis all in picture format! OBSERVE, DIAGNOSE, MONITOR... Three Phase Power Quality Analysers

Distorting and Unbalanced Operating Regime A Possible Diagnosis Method?

Power factor correction and harmonic filtering. Automatic power factor regulators R.1

Chapter -3 ANALYSIS OF HVDC SYSTEM MODEL. Basically the HVDC transmission consists in the basic case of two

A New Fault Detection Tool for Single Phasing of a Three Phase Induction Motor. S.H.Haggag, Ali M. El-Rifaie,and Hala M.

Power factor improvement in three-phase networks with unbalanced inductive loads using the Roederstein ESTAmat RPR power factor controller

p. 1 p. 6 p. 22 p. 46 p. 58

Power Quality of a Battery Energy Storage System (BESS) with Nonlinear Load Gabriel Haines

Power Quality Analysers

Doãn Văn Đông, College of technology _ Danang University. 2. Local Techniques a. Passive Techniques

SIEMOS PQ The Multi-Functional Power Quality Analyzer for Low and Medium-Voltage Networks

Electrical Network Analyzers

Power quality Harmonics up to 40th harmonic Rotary field components Distortion factor THD-U / THD-I

LOW LEVEL CURRENTS AND VOLTAGES MEASUREMENTS

Modern Techniques for Power Quality Analysis Using LabVIEW Environment

RISH Master Digital Multifunction Instrument with onsite pluggable output options. Application : Product Features:

INTERIM ARRANGEMENTS FOR GRID TIED DISTRIBUTED ENERGY RESOURCES. Technical Requirements for Grid-Tied DERs

UNBALANCED CURRENT BASED TARRIF

An Introduction to Power Quality

Power Quality Permanent Monitoring Systems in Romania

ALPHA 50 MULTIFUNCTION METER (ALPHA SERIES)

Supervision and analyse of the electrical network EN50160 & POWER QUALITY

Measuring centers MC7x0 series Multifunction Meter MC740

Moving Test - MT3000

Effects of Harmonic Pollution on Three-Phase Electrical Motors

Končar TMS - Bushing monitoring

Smart Energy & Power Quality Solutions. Portable energy measurement devices COMPACT FLEXIBLE PRECISE

Functioning Analysis of a High Frequency Electro Thermal Installation with Electromagnetic Induction Using PSCAD-EMTDC Tool

Excitation Systems RG3 - T4. Transistorized Excitation Systems for Synchronous Generators. Power Generation

Implementation of a Numerical Distance Relay for the 110kV Electric Lines

The experience of the Qualistar, ensuring high performance

3 Phase Power Quality Analy er

Scope of functions 32R

Induction Machine Test Case for the 34-Bus Test Feeder -Distribution Feeders Steady State and Dynamic Solutions

The experience of the Qualistar ensuring high performance

Line Impedance Estimation Using SCADA Data

Energy Explorer PROFESSIONAL POWER & HARMONICS ANALYSER

PQ-Box 100 Network Analyzer for Low-, Medium- and High-Voltage Networks

Enhancement of Power Quality in Distribution System Using D-Statcom for Different Faults

IN ELECTRICAL ENGINEERING - I C M E T CRAIOVA

POWER QUALITY REPORT

A Controversial Issue: Power Components in Nonsinusoidal Single-Phase Systems

PowerMonitor 5000 Family Advanced Metering Functionality

FAULT IDENTIFICATION IN TRANSFORMER WINDING

Improving the Shunt Active Power Filter Control Methods under Distorted and Unbalanced Grid Voltages

ENA33LCD. Power line analyzer. User and service manual. Obrezija 5 SI-1411 Izlake

NEURAL NETWORKS USED IN THE EVALUATION OF POWER QUALITY

Automatic capacitor banks with detuned filters

PQube 3 Specifications

Multimeter 560CVD11 Data sheet

ZTEC Instruments. Oscilloscope Measurement Fundamentals: Avoiding Common Pitfalls Creston Kuenzi, Applications Engineer

Three Phase Power Calibrator and Tester of Power Engineering Devices

Virtual Instrumentation Applied to Calculation of Electrical Power Quantities in Single-Phase Systems

IEEE sion/1547revision_index.html

SYSTEM OF CONTROLLING THE PROCESS OF STEEL ELABORATION IN DC ELECTRIC ARC FURNACES

A New Subsynchronous Oscillation (SSO) Relay for Renewable Generation and Series Compensated Transmission Systems

Realization and characterization of a smart meter for smart grid application

Simultaneous amplitude and frequency noise analysis in Chua s circuit

A Power Quality Interface for Low and Medium Voltage Smart Grids

Excitation Systems THYRIPART. Compound-Excitation System for Synchronous Generators. Power Generation

A POWER QUALITY INSTRUMENT FOR HARMONICS INTERHARMONICS AND AMPLITUDE DISTURBANCES MEASUREMENTS

MULTICHANNEL ACQUISITION SYSTEM

T 1000 PLUS Secondary Injection Relay Test Set

Power Quality Analysis for Connecting a PV Park to the Power Network in Order to Obtain the Certificate of Conformity

Energy Management Modular Smart Power Transducer Type SPT-90

T 1000 PLUS. Secondary Injection Relay Test Set. Designed for testing relays and transducers

DRTS 66 The new generation of advanced test equipments for Relays, Energy meters, Transducers and Power quality meters

With any other power quality analyzer you re just wasting energy.

Energy Management Power Analyzer with plug-in Output Modules Type W M22-DIN

MILWAUKEE SCHOOL OF ENGINEERING LABORATORY SESSION 4 THREE PHASE TRANSFORMERS

Extended analysis versus frequency of partial discharges phenomena, in support of quality assessment of insulating systems

LV Compensation & Filtering Products

C.A Complete electrical network analysis at the tips of your fingers! Power Quality Monitor. Keeping up with the standards

sw rev. 55B DEVICE FOR THE PERMANENT CONTROL OF INSULATION ON THE SUPPLY LINES IN MEDICAL PRACTICE PLACES INSTALLATIONS

Technical Requirements for Connecting Small Scale PV (sspv) Systems to Low Voltage Distribution Networks

Data Sheet. RISH Master Record %THD

IEEE 1547: Standard for Interconnection and Interoperability of Distributed Energy Resources with Associated Electric Power Systems Interfaces

C.A 8332 C.A Advanced Test Equipment Rentals ATEC (2832) Display your network analysis all in picture format!

Reliable Power Meters Multipoint Power Recorder

Ferroresonance Signal Analysis with Wavelet Transform on 500 kv Transmission Lines Capacitive Voltage Transformers

Transcription:

System and equipment for measurement, registration of parameters and analyse of the quality of the electric energy Gabriel VLADUT*, Ion PURCARU **, Petre-Marian NICOLAE,*** Camelia COJOCARU* * IPA, Craiova, office@ipacv.ro, ** VIG IMPEX srl, purcaruion@yahoo.com, ***University of Craiova Abstract The paper presents the equipment used to measure some parameters that characterize the electric energy quality. The equipment performs test and acquisition of analogue data (U and I) and numerical data. The sampled data are recorded when preset thresholds are exceeded by the analogical inputs or when the digital inputs states change. The fixed variant is supplementary provided with 2 analogue outputs and 8 numerical outputs. The operation of equipment is simulated and the corresponding software are exemplified for the case of a highly distorting consumer, a set of electric energy quality parameters being determined for this case. 1. INTRODUCTION The recent implementations based on power electronics provide a lot of advantages related to the designing of some high power electrical drives with variable speed, such as the increase of driving system performances. Unfortunately this kind of equipment added new quality problems to the existing ones. The new problems are related to the electric nature waveforms distortions, with direct impact over the consumers supplying. The energetic effects that affect the electric energy quality must be precisely evaluated in order to their consecutive limitation. The quality parameters measurement is related to the existing voltage level, to the data acquisition time speed, to the employed numeric algorithms. Test and isolated implementations were recently performed in our country and abroad, but none became a market leader. 2. GENERAL DESCRIPTION OF THE EQUIPMENT In order to determine some of the electric energy quality parameters and also to achieve a complex equipment that should be able to determine some other quantities and unpleasant phenomena, a modular portable system was conceived. The main functions provided by it are: - determination of electric energy quality parameters that should consequently result in measures for improving of qualitative and quantitative efficiency of energetic consumptions; - events recording, in order to detect the faults causes and the repeated connections and disconnections over electric lines. The equipment modular designing makes possible the realization of a family of fixed and portable systems for tests and data acquisitions. Due to its modular conceiving, the system provides: - acquisition of 9/16 analogue inputs and 6/32 numerical inputs by means of circuits that perform the conditioning of analogue signals compatible to the electric quantities supplied by the electro-energetic systems; - portable variant are supplementary equipped with 2 analogue outputs and 8 numeric outputs for simulations, tunings and tests; - non-volatile recording of finite number of records; - connection through a serial line of a PC compatible computing system for data loading corresponding to the recordings that present interest. 3. EQUIPMENT FUNCTIONS The equipment provides the following functions: - test and acquisition of analogue data (voltages, currents and powers) and respectively of numeric data (switching apparatus state) for nodes of the electro-energetic system where the distorting regimes occur; - numeric processing of data, in order to determine the energetic parameters, the performance indices concerning the electric energy quality; - recording, evaluation, administering and displaying along periods of the consumptions and events concerning the deviations from the quality of the used electric energy;

- permanent monitoring of the energetic parameters; faults detection and localization; - signalization when some quality indices standardized values are exceeded. A series of facilities are provided, as follows: - determination of data corresponding to the voltages and currents for phases and neutral wire. The input voltages are supplied either by voltage transformers secondary windings with a rated value of 1Vac, or by instant values transducers. The input currents are supplied either by current transformers secondary windings with a rated value of 1Aac, or by instant values transducers. - consumptions evaluation; - evaluation of analogue quantities, separately for each phase (RMS values, initial phases of currents and voltages harmonics, spectral analysis); - displaying of time variations for quantities (currents, voltages), state of switches from the distribution utilities; - real time clock, non-volatile memory, graphical display of extended sizes 75 x 14 mm; - analysis and determination in the three phase network of the following parameters: - phases and neutral impedances; - direct, reversed and homopolar components of the unbalanced systems of voltages/currents; - determination of the survived element operation regime (load, idle, voltage missing, fault, etc). The estimated and recorded data are processed by means of a soft package that allows: - harmonic analysis of measured quantities (voltages and currents) ; - computation of electric energy quality indices; - displaying, on request, of electric parameters: active/reactive electric energies, active/reactive and distorting powers, power factor, currents, voltages, frequency; - displaying on request of superior harmonics weights for voltages and/or currents; - detection of normal rapid variations and of accidental unbalancies from the three phase systems of voltages and currents; - recording, evaluation and displaying for a month of the events corresponding to the electric energy quality deviations; - prescription of thresholds both for the quantities estimated in the system and respectively for the estimated quantities; when the respective thresholds are reached, sound and optic alarms are generated; - obtaining of the main energetic parameters situation. The considered standards are: PE 143/94, IEC 6664, ANSI-IEEE 519, CEI 1-2-4 [9]. 4. TECHNICAL FEATURES The equipment presents the following characteristics: - Number of monitored and evaluated lines: 3 (test variant 3 voltages and 2 currents) ; 2 (test variant 3 voltages and 3 currents) ; - Analogue outputs (fixed variant): 2; - Tests accuracy: - U, I..,5% - P, Q, S, D 1% - Frequency,5% - Active/reactive energy cf class 2 IEC1268 - Distortion coefficient I/U 2% - Storing capacity: 1MO... 16MO; - Period of recording: 3 sec 4 hours, the records are non volatile; triggering facility - Supplying: 23 V c.a / 5 Hz; -15%...+15%; and battery 12V. 5. EQUIPMENT S UTILIZATION FOR THE DETERMINATION OF ELECTRIC ENERGY QUALITY PARAMETERS The equipment was tested under normal operation conditions, taking data from a connection point of a major distorting three phase consumer. The sampling frequency was 3,6 khz. For the beginning the distorting three phase receiver voltages and currents waveforms were recorded. Based on an original processing algorithm, the harmonics analysis was performed, considering the EU standards (in order to obey the European standards while considering the specific of Romanian consumers and networks) [6]. The recorded three phase voltages waveforms are depicted by fig,1(a) and those corresponding to currents are depicted by fig. 1(b). Using the decomposition algorithm mentioned above, the first 4 harmonics of current and voltage were determined. The signals recomposed from the first 4 harmonics of the first phase voltage together with the significant harmonics from the u1 waveform and their initial phases are depicted by fig. 2. In fig.3 we represented the signal recomposed from the current through phase 1, compared to the initial signal (Fig. 3(a)), along with the harmonics magnitudes from the i1 waveform (Fig,3(b)) and their initial phases (Fig.3(c)). Based on the harmonic decomposition we could determine coefficients related to the electric energy quality corresponding to phase 1 [3]: - for u1: RMS value: 3.8984e+2 V; peak factor: 1.424e+; shape factor: 1.988e+; VTHD 1: 1.264e+; - for i1: RMS value 7.2715e+ A; peak factor : 1.389e+; shape factor: 1.1534e+; ITHD 1: 1.3631e+1

1 u1, u2, u3 (u) [V] 5 u1 u2 u3-5 (a) -1.1.2.3.4.5.6.7 2 i1, i2, i3 (i) [A] 1 i1 I2 I3 (b) -1-2.1.2.3.4.5.6.7 Time [secs] Fig. 1. Three-phase voltages and currents from system 1 - Mag. [%].....1.1.1.1.1 Time 15 1 Mag.(1)=1% 5 Phase 1 2 3 4 5 6 7 8 9 1 11 12 13 14 15 16 17 18 19 2 4 2-2 1 2 3 4 5 6 7 8 9 1 11 12 13 14 15 16 17 18 19 2 Harmonic order Fig. 2 Voltage u1 Signal reconstructed from 4 harmonics superposed over the original signal

2 Mag [%] Phase -2.....1.1.1.1.1 Time(sec) 15 1 Mag.(1)=1% 5 1 2 3 4 5 6 7 8 9 1 11 12 13 14 15 16 17 18 19 2 4 2-1 2 3 4 5 6 7 8 9 1 11 12 13 14 15 16 17 18 19 2 Harmonic order The harmonic analysis for the phases 2 and 3 revealed an evolution similar to that of the first phase. The analysis also proved that the three-phase system is symmetric, so that for the analyzed consumer the problems related to the electric energy quality are actually those related to the distorting regime. Fig. 3. Current i1 signal reconstructed from 4 harmonics superposed over the original signal In Fig 4 we present the monitoring, registration and analyse of parameters at one defalt of an 11kV grid Monitoring of a event on an 11kV grid, we calculate default parameters, including the phazorial diagramme Configuration of calculate parameters at one defalt analyse Armonic analyse Analyse of one default; configuration of paramethers that caracterize the electric grid affect by the default Fig 4: Monitoring and analyse of parameters at one defalt of an 11kV grid

4. CONCLUSIONS As far as we are awared, in Romania there is no equipment similar to the one presented in this paper (as stationary equipment). Famous manufacturers as Chauvin Arnoux/ Enerdis France, Siemens Germany, Schneider France, General Electric SUA, Circutor Spain produce equipment that provide only partial similarities to it. The manufacturers we analyzed make efforts to modernize the test principles, to use small size transducers, provided with local intelligence and respectively to increase the number of facilities provided by the equipment: functions for rapid electric events recording, simultaneously with the recording of electric parameters along long periods, SCADA compatibility, electric energy quality analysis, etc.. This test principle results in an increase of test accuracy, operation safeness and improved reliability. 5. REFERENCES [1] Budeanu, C., Rolul fizic al marimilor instantanee in fenomenele de conservare, Energetica, 86, p.277-281 [2] Depenbrock, M., The FDB-Method a Generally Applicable Tool for Analyzing Power Relations, IEEE Trans. on Power Systems, vol.8, no.2/93, p.38-386 [3] Emanuel, A.E., a.o., New Concepts of Instantaneous Active and Reactive Powers in Electrical Systems with Generic Loads, IEEE Tr. on Power Del., no.3/93, p.697-73 [4 Nicolae, P.M., Calitatea energiei electrice in sisteme electroenergetice de putere limitatá, Ed. Tehnicá, Buc. 1998 [5] Nicolae, P.M., Mandache, L., Nicolae, I.D., About The Correlation Between The Power Quality Parameters and Th e Number of Fourier Series Terms, ATEE 22, Politehnica University, Bucuresti, 22 [6] Tugulea, A., Consideratii privind efectele energetice in regimuri deformante, Energetica, no. 1/ 86, p.27-31 [7] Tugulea, A., Factorul de putere in regim deformant si nesimetric, Energetica, no. 9/ 86, p.47-414 [8] Tugulea, A., Criteria for the Definitions of the Electric Power Quality and its Measurement Systems, ETEP, [9] Mircea, I., Ciontu, M., Ruşinaru, D., Aspects about abnormal operation of the fast overcurent protections in the short-circuit conditions, the 7-th International Symposium on Short-circuit Currents in Power Systems, Warszawa, Poland, 1996; [1] IEEE Working Group on Nesinusoidal Situations Practical Definitions for Powers in Systems with Nonsinusoidal Waveforms and Unbalanced Loads, IEEE Tr. on Power Del., no.1/96, p. 79-11 [11] G. Vladut, P.M. Nicolae, L. Mandache, C. Cojocaru, I. Purcaru Equipment for measuring of parameters that characterize the electric energy quality, ICATE 24, Baile Herculane International Conference.