Energy System Protection for Grid Resilience. Xianyong Feng, PhD, PE Center for Electromechanics The University of Texas at Austin October 31, 2017

Similar documents
Experiences of a microgrid research laboratory and lessons learned for future smart grids

Medium Voltage DC Solid State Circuit Protection

Under-Frequency Load Shedding based on PMU Estimates of Frequency and ROCOF

Model Description Document Notional Four Zone MVDC Shipboard Power System Model ONR GRANT # N

Synchrophasor Applications for Distribution Networks Enhancing T&D Operation and Information Exchange

Highgate Converter Overview. Prepared by Joshua Burroughs & Jeff Carrara IEEE PES

Investigation and Correction of Phase Shift Delays in Power Hardware in Loop Real-Time Digital Simulation Testing of Power Electronic Converters

Texas Reliability Entity Event Analysis. Event: May 8, 2011 Loss of Multiple Elements Category 1a Event

Electric Grid Modernization Enabled by SiC Device based Solid State Transformers and Innovations in Medium Frequency Magnetics

DC 4Q POWER AMPLIFIER 200kW 2 RANGES HIGH POWER RS232

The HIL Based Model Validation Paradigm - Tools, Challenges, and Application Examples

EH2741 Communication and Control in Electric Power Systems Lecture 2

AORC Technical meeting 2014

Effects of Phase-Shifting Transformers, and Synchronous Condensers on Breaker Transient Recovery Voltages

22 kw 4Q POWER AMPLIFIER RS232

How Full-Converter Wind Turbine Generators Satisfy Interconnection Requirements

MMC (Modular Multilevel Converter)

ENOSERV 2014 Relay & Protection Training Conference Course Descriptions

MITIGATION OF VOLTAGE SAGS/SWELLS USING DYNAMIC VOLTAGE RESTORER (DVR)

Automated Fault Detection With PQ Monitors

ISLANDING DETECTION USING DEMODULATION BASED FFT

Control of Power Converters for Distributed Generation

Chapter -3 ANALYSIS OF HVDC SYSTEM MODEL. Basically the HVDC transmission consists in the basic case of two

Validation of Frequency- and Time-domain Fidelity of an Ultra-low Latency Hardware-in-the-Loop (HIL) Emulator

A Novel Islanding Detection Technique for Distributed Generation (DG) Units in Power System

CHAPTER 4 POWER QUALITY AND VAR COMPENSATION IN DISTRIBUTION SYSTEMS

Z-Source Circuit Breaker Utilizing Ultra-Fast Mechanical Switch for High Efficiency DC Circuit Protection

Fixed Series Compensation

Hamdy Faramawy Senior Application Specialist ABB Sweden

Analysis and modeling of thyristor controlled series capacitor for the reduction of voltage sag Manisha Chadar

Arizona Public Service Company and the Transmission Partnership for National Electric Power Company of Jordan

Power Quality Basics. Presented by. Scott Peele PE

Past CIGRE and Emerging IEEE Guide Documents on FCLs

POWER AMPLIFIERS 4 QUADRANTS 3x500 VA to 3x1500 VA - THREE-PHASES

Development and testing of an experimental power system fault demonstrator

Mitigation of the Statcom with Energy Storage for Power Quality Improvement

Z-Source Circuit breaker design and protection schemes for DC micro grid systems

2015 Relay School Bus Protection Mike Kockott March, 2015

Inverter-Based Resource Disturbance Analysis

RT- HIL Implementation of Hybrid Synchrophasor and GOOSE- based Passive Islanding Schemes

COMPARATIVE PERFORMANCE OF SMART WIRES SMARTVALVE WITH EHV SERIES CAPACITOR: IMPLICATIONS FOR SUB-SYNCHRONOUS RESONANCE (SSR)

A New Fault Detection Tool for Single Phasing of a Three Phase Induction Motor. S.H.Haggag, Ali M. El-Rifaie,and Hala M.

ALP-UDR Universal Detection Relay user-defined protection, automation, and monitoring

Power Hardware-in-the-Loop testing for the Inverterbased Distributed Power Source

Power systems Protection course

Study on Voltage Controller of Self-Excited Induction Generator Using Controlled Shunt Capacitor, SVC Magnetic Energy Recovery Switch

WP4-Hardware in the Loop Validation of the EFCC Scheme

A Pyrotechnic Fault Current Limiter Model for Transient Calculations in Industrial Power Systems

EFCC Academia dissemination event

Grounding and Fault Location in Power Electronic based MVDC Shipboard Power and Energy Systems

200 kw 4Q POWER AMPLIFIER RS232

A Demonstrator for Experimental Testing Integration of Offshore Wind Farms With HVDC Connection. S.D'Arco, A. Endegnanew, SINTEF Energi

Non-detection zone of LOM protection for converter connected wind turbines

Analysis, Modeling and Simulation of Dynamic Voltage Restorer (DVR)for Compensation of Voltage for sag-swell Disturbances

Short-Circuit Analysis IEC Standard Operation Technology, Inc. Workshop Notes: Short-Circuit IEC

Fault Location Using Sparse Wide Area Measurements

UPGRADING SUBSTATION RELAYS TO DIGITAL RECLOSERS AND THEIR COORDINATION WITH SECTIONALIZERS

Poornima G P. IJECS Volume 3 Issue 6 June, 2014 Page No Page 6453

Design and Simulation of superconducting fault current limiter

Investigation and Correction of Phase Shift Delays in Power Hardware in Loop Real-Time Digital Simulation Testing of Power Electronic Converters

Investigation of Inter-turn Fault in Transformer Winding under Impulse Excitation

Sarma (NDR) Nuthalapati, PhD

Application for A Sub-harmonic Protection Relay. ERLPhase Power Technologies

CHAPTER 3 APPLICATION OF THE CIRCUIT MODEL FOR PHOTOVOLTAIC ENERGY CONVERSION SYSTEM

Comparison Of DC-DC Boost Converters Using SIMULINK

No. SSIEC-SEW SHINSUNG. Solid Insulation Eco Load Break Switch (SILO) SILO SERIES 15kV, 27kV 400A, 630A

ABB AG - EPDS. I S -limiter The worldʼs fastest limiting and switching device

CHAPTER-IV EXPERIMENTAL AND SIMULATION PROGRAM

Protect and survive. Fault protection analysis in low-voltage DC microgrids with photovoltaic generators

In power system, transients have bad impact on its

ECE 528 Understanding Power Quality. Paul Ortmann (voice) Lecture 6

A Novel H Bridge based Active inductor as DC link Reactor for ASD Systems

IMPLEMENTATION OF FM-ZCS-QUASI RESONANT CONVERTER FED DC SERVO DRIVE

FAULT PROTECTION OF A LOOP TYPE LOW VOLTAGE DC BUS BASED MICROGRIDS

WILEY CONTROL OF POWER INVERTERS IN RENEWABLE ENERGY AND SMART GRID INTEGRATION. Qing-Chang Zhong. Tomas Hornik IEEE PRESS

Success Story. 1. Context

DC Interfaces for Naval Applications

Real-time Visualization, Monitoring and Controlling of Electrical Distribution System using MATLAB

ISSN Vol.07,Issue.11, August-2015, Pages:

Christopher S. Edrington, PhD, PE. Energy Conversion and Integration Thrust. Electrical and Computer Engineering/Center for Advanced Power Systems

Chapter 3 : Closed Loop Current Mode DC\DC Boost Converter

Design and Implementation of Modern Digital Controller for DC-DC Converters

p. 1 p. 6 p. 22 p. 46 p. 58

Mitigation of voltage disturbances (Sag/Swell) utilizing dynamic voltage restorer (DVR)

DESIGN OF A MODE DECOUPLING FOR VOLTAGE CONTROL OF WIND-DRIVEN IG SYSTEM

PAPER-II (Subjective)

ETAP PowerStation. Electrical Transient Analyzer Program. ETAP PowerStation. Short Circuit Analysis. ANSI Standard 3-Phase Fault Currents

Real-time Volt/Var Optimization Scheme for Distribution Systems with PV Integration

Fault Current Limiter Selection Considerations for Utility Engineers

Differential Current Sensor acc. to the standard UL2231 Ed.2.0. Customer: Standard type Page 1 of 7. Electrical data Ratings min. typ. max.

CHAPTER-5 DESIGN OF DIRECT TORQUE CONTROLLED INDUCTION MOTOR DRIVE

Protective Relaying for DER

Mitigation of Power Quality Problems Using DVR in Distribution Network for Welding Load

CHAPTER 6 DEVELOPMENT OF A CONTROL ALGORITHM FOR BUCK AND BOOST DC-DC CONVERTERS USING DSP

Renewable Interconnection Standard & Experimental Tests. Yahia Baghzouz UNLV Las Vegas, NV, USA

A Three-Phase AC-AC Buck-Boost Converter using Impedance Network

Optimizing HV Capacitor-Bank Design Protection & Testing

THE RTDS SIMULATION AND ANALYSIS ON CSG OPERATION CHARACTERS

Response of Grid Interconnected Solar PV inverters to Transmission System Faults

II. RESEARCH METHODOLOGY

Transcription:

Energy System Protection for Grid Resilience Xianyong Feng, PhD, PE Center for Electromechanics The University of Texas at Austin October 31, 1

Presentation Outline Overview Mission Critical Energy Systems Energy System Fault Mgmt. CEM Approach Ctrl. & Prot. Energy System Protection (3 cases) Conclusion 2

Overview Resilience is different from reliability A resilient system 1. Acknowledges that power outages can occur 2. Be prepared and minimizes their impact 3. Quickly restores service 4. Draws lessons from experience to improve robustness * page 3 * Flynn, S.E. 2008. America the resilient: Defying terrorism and mitigating natural disasters. Foreign Affairs 87: 2 8.

Mission Critical Energy System All-electric ship DC datacenter Wind collection system PV farm Electric aircraft Oil & gas platform page 4

Energy System Fault Management Detection Real-time monitoring Detect electrical abnormal Fault type identification (permanent or temporary) PREPARE Location Isolation Quickly and accurately locate fault Minimize system impact Open protective device Minimize load interruption AMELIORATE Restoration Restart interrupted power equipments Restore interrupted loads to normal QUICK RECOVERY page 5

CEM Approach - Control & Protection Simulation Test: New control and protection strategies are initially implemented in modeling software and verified in numerical simulation. The tools include but not limited to: 1. Matlab / Simulink 2. PSCAD 3. ETAP 4. OpenDSS Simulated control block 1 Simulated control block N Numerical simulation environment Control signal Measured signal Simulated circuit The control or protection strategies are implemented as software blocks in simulation tools; the control system performance can be evaluated and controller parameters can be optimally selected in off-line simulations. i Power Hardware-in-the-Loop (PHIL) Simulation Test: Design the interface between HIL simulator and real power systems such as hardware microgrid system at CEM. Power amplifiers (power converters and emulators) are the interfaces between real-time simulator and real power system. Key features: 1. Complicated network model is implemented in HIL simulator 2. Power electronics converters and active sources serve as the interface between software simulator and the real system 3. NI FPGA simulator enables the fast response of PE devices Real Hardware Microgrid System MV bus HIL simulator Controlled voltage source ~ Voltage signal Hardware Interface Current measurement I/Os Simulated network Power Amplifier Current signal Active Source iii Control Hardware-in-the-Loop (CHIL) Simulation Test: New control and protection strategies are implemented in hardware controllers. The controller is validated and tested in the HIL simulation environment to de-risk field test and demonstration. Main procedures include: 1. Model the circuit 2. Implement control strategy in hardware 3. Configure the communication interface between real-time simulator and hardware controllers 4. Perform real-time HIL tests Distributed control Advanced protection strategies Simulated switching devices in NI PXI simulator PXIe Real-Time/FPGA HIL System Sensors High speed communication link Control and Protection Hardware Control Center Simulated Distribution Network in Opal-RT Opal-RT Simulator I/O or other comm. Interfaces NI controllers Tertiary Controls SCADA System IED Real Hardware Test and Field Demonstration: The control and protection strategies are ultimately implemented in the control platform of real hardware power system for final testing and validation. Main benefits include: 1. Obtain validated engineering data 2. Demonstrate the control system performance in the real operation environment MW-scale Microgrid page 6 ii iv

LVDC Distribution System Protection DC fault current DC Protection Challenges No zero-crossing in fault current Lower line impedance in tightly coupled system High di/dt Power electrics device can not tolerate high fault current Extremely fast capacitor discharge AC fault current DC distribution system example DC Power Supply Fault 1 Fault 2 ~ = = = L Fault 3 L L L page 7

LVDC Distribution System Protection Inductance-based dc fault location* Estimate fault inductance with local measured v(t) and i(t) Use estimated L to locate fault Equivalent inductance L 1 Line inductance distribution L 2 L 3 Distance + - v Equivalent fault circuit i R *X. Feng, L. Qi, and J. Pan, A novel fault location method for dc distribution protection, IEEE Trans. Industrial Applications, vol. 53, no. 3, May-June,. L RF DC UPS 380 VDC ~ = = = level 1 level 2 level 3 Fault 1 Fault 2 Zone 1 (20 m) Zone 2 (65 m) Zone 3 (10.2 m) L L L L L L Fault 3 page 8 Zone 4 (1.5 m)

LVDC Distribution System Protection Protection Scheme Implementation Online moving-window least square method Algorithm on embedded controller Fault detection v i di/dt and location routine ADC ADC ADC v (1) i (1) di/dt (1) PRUs read data sequentially and store them in memory 7 analog inputs with A/D converters k = k + 1 Yes di ( k M 1) dt di A ( k M 2) dt di ( k) dt Start Fault detected? Yes k = 0 Read in measurements v(k), i(k), and di/dt(k) if k < M No No i( k M 1) v ( k M 1) i( k M 2) v ( k M 2 ) B i( k) v ( k ) Go to next time interval Yes di (0) dt di A (1) dt di ( k) dt i(0) v(0) i(1) v(1) B i( k) v( k ) Request new data once finishing the previous cycle N Main program executes the fault detection and location routine Locate fault? Y Send tripping PRUs 65 digital I/Os Processor (AM3358) if t < T max No No L R R F T 1 T A A A B if 0 < L < L th Yes Send tripping signal End page 9

Inductance (H) Inductance (H) LVDC Distribution System Protection Numerical Simulation Fault 1 15 m from breaker 1 Fault R: 2 mω Fault 2 50 m from breaker 2 Fault R: 2 mω 10 x 10-7 8 6 4 2 0-2 3 x 10-5 1 ms Zone 2 Zone 1 Estimated inductance Threshold 0.04 0.042 0.044 0.046 0.048 0.05 time (sec) DC UPS 380 VDC ~ = = = Fault 1 Fault 2 Zone 1 (20 m) 0.77 mf 0.159 mω 0.053 mω 4.5 mω 0.333 µh 0.111 µh 13.8 µh Zone 2 (65 m) 1.35 mω 4.15 µh Zone 3 (10.2 m) L L L L L L Fault 3 Zone 4 (1.5 m) 2.5 2 1.5 1 0.5 0 1 ms Zone 3 Zone 2 0.04 0.042 0.044 0.046 0.048 0.05 time (sec) 10

LVDC Distribution System Protection User interface Control-HIL Test Opal-RT simulator Ethernet Opal-RT simulator Simulated DC network Simulated a 380 V dc system Convert v(t)/i(t) to analog Read in breaker status through D in Embedded controller Read in v(t)/i(t) signals Execute prot. algorithm Send a trip signal for internal fault Analog outputs: current/voltage signal Microcontroller A/D converters Breaker status wired back to Opal-RT simulator Fault detection and location algorithm Trip command 24 V 47uF Breaker page 11

LVDC Distribution System Protection Control-HIL Test Results Estimated error < 8.4% Fault location time < 0.7 ms current signal tripping signal ID Actual L (µh) / fault R (mω) Estimated L (µh) Error (%) Fault location time (ms) 1 18 / 20 18.152 +0.84 ~0.5 2 18 / 20 16.831-6.49 ~0.35 3 18 / 20 16.680-7.33 ~0.25 4 30 / 2 29.461-1.80 ~0.3 5 30 / 2 28.524-4.92 ~0.35 6 30 / 2 27.695-7.68 ~0.55 7 30 / 20 29.461-1.80 ~0.3 8 30 / 20 28.524-4.92 ~0.35 9 30 / 20 27.695-7.68 ~0.55 current signal voltage signal page 12

Estimated L (H) Estimated L (H) Estimated L (H) LVDC Distribution System Protection Sensitivity Analysis* Voltage error: 0.025% - 1.25% * V rated (380 V) Current error: 0.005% - 1.5% * I max (2000 A) Improve accuracy using digital filter x 10-5 3.4 Original method (L) Improved method (L) 3.2 Level 6 Lower lower Boundary boundary Inductance (H) 2.5 x 10-5 2 1.5 1 0.5 0 2.5 x 10-5 2 Voltage sensitivity Voltage error: 0.025% Voltage error: 0.125% Voltage error: 0.25% Voltage error: 0.5% Voltage error: 1.25% Base Scenario 1 Scenario 2 Scenario 3 Scenario 4 0.04 0.042 0.044 0.046 0.048 0.05 time (sec) Current sensitivity Inductance (H) 3 2.8 2.6 2.4 2.2 0.04 0.045 0.05 0.055 0.06 time (sec) *X. Feng, L. Qi, and J. Pan, Fault inductance based protection for DC distribution systems, Proc. of the 13th International Conference on Developments in Power System Protection, Edinburgh, Scotland, March 2016. Inductance (H) 1.5 1 0.5 0 Current error: 0.005% Current error: 0.01% Current error: 0.025% Current error: 0.05% Current error: 0.25% Current error: 0.5% Current error: 1% Current error: 1.5% Base case Scenario 1 Scenario 2 Scenario 3 Scenario 4 Scenario 5 Scenario 6 Scenario 7 Level 4 boundary 0.04 0.042 0.044 0.046 0.048 0.05 time (sec) page 13

Voltage Current LVDC Distribution System Protection Hardware Test Low voltage circuit 7.07 mf capacitor is charged to 12 V Inductors are used to emulate lines Short-circuit fault is created by closing a breaker Embedded controller Read in v(t), i(t), di/dt Execute prot. algorithm Send a trip signal for internal fault + 12 V DC - Switch Capacitor (7.07 mf) Inductor (6 µh) SLD diagram Current sensor Analog circuit of di/dt calculation Real circuit Line (6-12 µh) BeagleBone Black board with Tripping fault detection & signal location Emax page 14

Time (ms) Time (ms) LVDC Distribution System Protection Hardware Test Results L estimation error < 20% Detection/location time < 0.7 ms 0.65 0.6 0.55 0.5 0.45 0.4 0.35 L = 18 µh and R = 20 mω 0.65 0.6 0.55 0.5 0.45 0.4 0.35 L = 30 µh and R = 2 mω ID Actual L (µh) / fault R (mω) Estimated L (µh) Error (%) Fault location time (ms) 1 18 / 20 18.152 +0.84 0.5 2 18 / 20 16.831-6.49 0.35 3 18 / 20 16.680-7.33 0.25 4 30 / 2 29.461-1.80 0.3 5 30 / 2 28.524-4.92 0.35 6 30 / 2 27.695-7.68 0.55 7 30 / 20 29.461-1.80 0.3 8 30 / 20 28.524-4.92 0.35 9 30 / 20 27.695-7.68 0.55 0.3 0.25 5 10 15 20 Error (%) 0.3 0.25-10 -5 0 5 10 15 20 Error (%) page 15

LVDC Distribution System Protection Improvement Level 1 Level 2 Level 3 No boundary inductor Equivalent inductance distribution Zonal boundary inductors Equivalent inductance ΔL 1 ΔL 2 ΔL 3 Level 4 L 4 Equivalent inductance L 2 L 3 Inserted ΔL 3 L 3 L 1 Distance L 2 Inserted ΔL 2 level 1 level 2 level 3 L 1 Inserted ΔL 1 level 1 level 2 level 3 level 4 Distance DC UPS 380 VDC ~ = = = Fault 1 Fault 2 Zone 1 (20 m) Zone 2 (65 m) Zone 3 (10.2 m) L L L L L L Fault 3 Zone 4 (1.5 m) page 16

LVDC Distribution System Protection Summary The prot. method uses local measurements only to locate fault 1. Detection and location time < 0.7 ms 2. L estimation error in HIL test < 8.4% 3. L estimation error in hardware test < 20% The prot. method can accurately locate short-circuit faults if: 1. Voltage measurement error < 0.5% 2. Current measurement error < 1% Boundary inductors improve prot. selectivity Next Step More test on real MW-level dc microgrid page 17

MVDC Shipboard Power System Protection MVDC Prot. Challenges Multiple sources Distributed capacitors Mesh network Low line impedance Fast fault isolation Convert FCL Pulse load (high di/dt) 1.1 kv 2 MW 200 Hz M PMM PROPULSON LOAD PGM 850 V 0.8 MW 60 Hz 3-ph 850 V 1.2 MW 60 Hz 3-ph PCM PGM PFN Railgun MISSION LOAD 1.15 kvdc/ 1.0 kvdc = = 60 Hz Loads IPNC 1.15 kvdc PCM1-A = = 60 Hz AC Distribution 400 Hz Loads 60 Hz Loads 1.15 kvdc 60 Hz Loads 60 Hz AC Distribution IPNC = = = = 1.15 kvdc/ 1.0 kvdc PCM1-A 400 Hz Loads page 18

MVDC Shipboard Power System Protection Two power generation modules FCL in dc-dc converters One propulsion load One pulse load High di/dt Two dc circuit breakers Isolate fault on main dc bus Protection strategy* FCL + differential protection PMM M 1.1 kv 2 MW 200 Hz 3 NC PROPULSON LOAD Toshiba 1 & 4 NC = Normally closed CL = Current Limit 1 = Capacitor 2 = Mechanical Circuit Breakers 3 = Contactors 4 = Line Reactor 3 1.15 kv main dc bus 2 2 NC NC 850 V, 0.8 MW 60 Hz, 3-phase Lab Power CL = = PGM CL = = 1 & 4 NC NC PGM 850 V, 1.2 MW 60 Hz, 3-phase Lab Power 3 3 3 NC NC Equivalent DC zonal Load PCM MISSION LOAD PFN Railgun *S. Strank, X. Feng, A. Gattozzi, D. Wardell, S. Pish, J. Herbst, and R. Hebner, Experimental test bed to de-risk the navy advanced development model, Proc. of Electric Ship Technology Symposium, Arlington, VA, Aug., pp. 352-358. page 19

Voltage (V) Current (A) MVDC Shipboard Power System Protection Main results Fault: 10-25 ms, 20 mω, on dc bus Prot. strategy: FCL + diff. prot. 2000 1500 1000 500 PGM 1 950 V 60 Hz 3-Ph ac Current differential: i 1 (t) + i 2 (t) = = Reactor 1 CB1 0.39 mh 0.39 mh 5 mf 0.5 mf Load 1 0.6 MW Diff. prot. zone i 1 (t) 80 µh 9 mω 0-500 0 5 10 15 20 25 30 35 40 time (ms) 2000 1500 1000 500 PGM 2 950 V 60 Hz 3-Ph ac = = 5 mf Reactor 2 0.39 mh 0.39 mh 0.5 mf 1 MW Load 2 CB2 i 2 (t) 80 µh 9 mω Main dc bus 1150 V dc 0 0 5 10 15 20 25 30 35 40 time (ms) page 20

Current (A) Current (A) MVDC Shipboard Power System Protection Sensitivity analysis Current diff. with different fault R Current diff. with measurement time differences 5000 4000 3000 2000 1000 0 Internal fault Current differential: i 1 (t) + i 2 (t) Fault R = 1 mohm Fault R = 10 mohm Fault R = 20 mohm Fault R = 50 mohm Fault R = 200 mohm -1000 0 5 10 15 20 25 30 35 40 time (ms) Next step work Test the prot. strategy on a MWlevel MVDC test bed 400 300 200 External fault delta t = 2 us delta t = 5 us delta t = 10 us delta t = 20 us delta t = 50 us 100 0 9.9 10 10.1 10.2 10.3 10.4 10.5 time (ms) page 21

Current (p.u.) (p.u.) Current (p.u.) (p.u.) AC Distribution System Fault Location Fault type identification Permanent or temporary Impedance-based Fault Location Use impedance model and fault waveform Currents for a permanent fault Currents for a permanent fault 50 50 0 0-50 -50-100 -100 100 100 50 50 0 0-50 -50-100 -100 0.05 0.1 0.15 0.2 0.25 0.05 0.1 0.15 0.2 0.25 Time (Seconds) Time (Seconds) Currents for a transient fault Currents for a transient fault 0.05 0.1 0.15 0.2 0.25 0.05 0.1 0.15 0.2 0.25 Time (Seconds) Time (Seconds) page 22

AC Distribution System Fault Location Traveling Wave Method Requirement GPS synchronization High sampling rate sensors Fast processing speed Benefit Incipient fault location (sub-cycle fault) Simple algorithm Extra-fast fault location Proposed intelligent sensors GPS signals Traveling wave s 2 s 1 s 3 fault Intelligent sensor page 23

Conclusion 1. Reliable and fast prot. strategy improves grid reliability and resilience 2. DC prot. is enabling tech. for large-scale deployment of dc systems 3. Extra-fast fault location and restoration are keys for grid resilience 4. Control/power-HIL tests effectively evaluate new prot. technology page 24

Thanks Contact information: Xianyong Feng Center for Electromechanics The University of Texas at Austin Email: x.feng@cem.utexas.edu Phone: 1-512-232-1623 page 25