Transformers handling and transport

Similar documents
KNOW MORE ABOUT THE TRANSFORMERS. Glossary Transformers

TesTIng of Power. Transformers are the largest, most. feature. By brandon dupuis

POWER TRANSFORMER SPECIFICATION, DESIGN, QUALITY CONTROL AND TESTING 18 MARCH 2009

Benefits of SFRA - Case Studies

Chapter 7 Conclusion 7.1 General

RESIDUAL LIFE ASSESSMENT OF GENERATOR TRANSFORMERS IN OLD HYDRO POWER PLANTS

TECHNIQUES AND STANDARD

Understanding the Value of Electrical Testing for Power Transformers. Charles Sweetser, OMICRON electronics Corp. USA

Understanding the Value of Electrical Testing for Power Transformers. Charles Sweetser - OMICRON

Effective Maintenance Test Techniques and Diagnostic Measurements to Improve the Performance and Reliability of Power System Transformers

Understanding and Extracting Valuable Information from Basic and Advanced Power Transformer Testing Techniques

SPECIFICATION FOR STEP UP TRANSFORMER 0.415/11Kv and (630KVA & 1000KVA)

Effective maintenance test techniques for power transformers

Vallabh Vidyanagar, Anand, INDIA

Innovative Test Techniques and Diagnostic Measurements to Improve the Performance and Reliability of Power System Transformers

EFFECETIVE TRANSFORMER CONDITION ASSESSMENT

FIELD ELECTRICAL TESTING SPX TRANSFORMER SOLUTIONS, INC.

Test description for dry-type transformers chapter for special tests

Transformer condition assessment with an integrated test van

(2) New Standard IEEE P (3) Core : (4) Windings :

7. INSPECTION AND TEST PROCEDURES

MGM Transformer. Vacuum Pressure Impregnated (VPI) Dry-Type Substation Transformer Specification Guide

Hands-On Transformer Testing and Maintenance

Demagnetization of Power Transformers Following a DC Resistance Testing

Transformer Factory Testing

Variation in SFRA plot due to design and external parameter

ISSN: [IDSTM-18] Impact Factor: 5.164

nical catalogue Tech

Matz Ohlen Director Transformer Test Systems. Megger Sweden

TIGHTENING TORQUE ON WOODEN CORE CLAMP (Nm) (STEEL FASTENER) 1 M M M M M

Application of Polarisation Depolarisation Current (PDC) technique on fault and trouble analysis of stator insulation

Importance of Transformer Demagnetization

OIL-IMMERSED ARC-SUPPRESSION COILS

HIGH VOLTAGE ENGINEERING(FEEE6402) LECTURER-24

The importance of partial discharge testing throughout the development and operation of power transformers

WESTERN UNDERGROUND COMMITTEE GUIDE 2.6 (2.6/00/0868)

RESONANT TRANSFORMER

OMICRON Seminar on Substation Testing and Diagnosis. October 23, 2017 Dubai, United Arab Emirates. October 24, 2017 Abu Dhabi, United Arab Emirates

Operational Management of Grid Transformers An Experience of POWERGRID

EEE3441 Electrical Machines Department of Electrical Engineering. Lecture. Basic Operating Principles of Transformers

Transformer Winding Design. The Design and Performance of Circular Disc, Helical and Layer Windings for Power Transformer Applications

Diagnostic testing of cast resin transformers

Testing and Diagnostic of Power Transformers & Distribution Transformers

Advanced Diagnostic Testing Services. Provides detailed and reliable results

Performing reliable and reproducible frequency response measurements on power transformers

FRAX Series Sweep Frequency Response Analyzers

GE Ventilated Dry-Type Transformers. Secondary Substation Transformers - 5 and 15kV Class

CASE STUDY- FAULT IN POWER TRANSFORMER AT LOKTAK POWER STATION. - S K Mishra & S K Das NHPC Ltd O&M Division

IMPORTANCE OF INSULATION RESISTANCE

The measurement and normalisation of dielectric dissipation factor for diagnostics of transformer insulation

CONDITIONS FOR A TENTATIVE APROVAL FOR CONNECTION OF TRANSFORMERS

Training Fees 3,300$ per participant including Materials/Handouts, Tea/Coffee Refreshments & International Buffet Lunch.

Comparative study of the derating of distribution transformers

Basic Principles and Operation of Transformer

Power Transformer Condition Assessment Based on Standard Diagnosis

Arild Furnes,ATPA OGP/Petrobras workshop, Dry type transformers-ideal for FPSO - Transformers for electrical and drive systems

Case Studies of Electric Power Equipment Diagnostics Using Acoustic Emission

Transformer Testing & Maintenance Fundamentals. AVO Training Institute, Inc. 2018

10. DISTURBANCE VOLTAGE WITHSTAND CAPABILITY

HOW TO SAFE GUARD THE TRANSFORMER..???

INSTALLATION & TESTING OF UNDERGROUND PRIMARY AND SECONDARY POWER CABLES PRIOR TO ENERGIZATION

Practical Transformer on Load

IJSRD - International Journal for Scientific Research & Development Vol. 2, Issue 04, 2014 ISSN (online):

Neutral Earthing. For permanent or temporary neutral earthing in HV systems

Ior DIGITAL LEAKAGE CLAMP TESTER MCL-400IR INSTRUCTION MANUAL

Power Transformers Basics

Transformer Protection Principles

A New Approach for Transformer Bushing Monitoring. Emilio Morales Technical Application Specialist Qualitrol

Field Experience with Sweep Frequency Response Analysis for Power Transformer Diagnosis

Power Factor Insulation Diagnosis: Demystifying Standard Practices

Regional Technical Seminar SHORT CIRCUIT FORCES

Power transformers for Network, Rectifiers, Furnace

Efacec work every day to anticipate solutions for a sustainable world in the new energy era.

SPECIFICATION FOR 11 KV CLASS, 24/15.7, 30/19.7 & 45/29.5 AMPS SPECIAL DESIGN TRANSFORMERS.

Automatic Transformer Winding Analyser

TMS 580. Transformer Loss Measuring System FEATURES BENEFITS APPLICATIONS

Single-Phase Mini Pad-Mounted Transformer Specification: Energy+ MPDL

Distribution Equipments - Technology and Applications. Training Module for DISTRIBUTION TRANSFORMER

SERVICE OFFERINGS FOR POWER SYSTEM STUDY & CONDITION MONITORING FOR STATIC EQUIPMENT

FRAX Series Sweep Frequency Response Analyzers

STRAY FLUX AND ITS INFLUENCE ON PROTECTION RELAYS

Improved Method for Winding Deformation Detection Sensitivity in Transformer

Power Measurements and Basic Electrical Diagnostic Tests

Transformer Protection

3. Contact Form A: SPST-NO

SAMPLE. Determining the health of your power transformer begins with Transformer Clinic s SAMPLE testing programs.

Specialists in HV and MV test and diagnostics. Testing in Substations

USING DAMPED AC VOLTAGES

36kV VOLTAGE TRANSFORMERS (OUTDOOR TYPE)

Fault Detection in Transformer Using Frequency (Sweep) Response Analysis

51-SDMS-04 SPECIFICATIONS FOR. DISTRIBUTION TRANSFORMERS UP TO 36 kv WITH ALUMINUM WINDINGS FOR DUAL SECONDARY 400/230 V AND 230/133 V

Generator Users Group Annual Conference Core testing, low and high flux, tap. Mladen Sasic, IRIS Power

S. C. Electric Cooperative s Specification for a Single-Phase, Single Bushing Overhead Distribution Transformer (Revised 10/2013)

TEST VOLTAGES INFLUENCE ON TURN RATIO TESTING ndb Technologies model ART-3D

Metallized Polycarbonate film capacitors MKC 344

FGJTCFWP"KPUVKVWVG"QH"VGEJPQNQI[" FGRCTVOGPV"QH"GNGEVTKECN"GPIKPGGTKPI" VGG"246"JKIJ"XQNVCIG"GPIKPGGTKPI

By Gill ( ) PDF created with FinePrint pdffactory trial version

CONSULTANT PROCEDURES & DESIGN GUIDELINES Liquid-Filled Utility Transformers UNIVERSITY OF MISSOURI

Tertiary Winding Design in wye-wye Connected Transformers Restricted Siemens Energy 2013 All rights reserved.

Transcription:

Special tests (Credit: http://www.breakbulk.com/wp-content/uploads/2015/02/20141117160247x.jpg) Transformers handling and transport Damages that may arise and how to find them Table of contents summary Damages that may arise during handling and transport of transformers and how special tests are used to find them are the focus of this article. Abstract In this article we analyze damages that transformers may suffer during handling and transportation, which we consider that may be the most harmful to the equipment, the type of damages and their causes and what special tests shall be performed during Factory Acceptance Tests (FAT) and Site Acceptance Tests (SAT) to help find what non-visible damages could have occurred. Keywords: impact; vibrations; IEC Standards; distortion; bushings. 1

1. Introduction Severe damages in transformers may be caused when they are subjected to sea transportation, namely with troubled sea, and road transportation, if the road is very rough. Although it is known that transportation under these conditions will cause vibrations and small shocks in packages and equipment, it is also known that if packaging and fixing are not suitable the amplitude of those vibrations and shocks can cause non-visible damages, which can lead to a failure of the equipment. For additional information, refer to IEEE C57.150, Guide for the Transportation of Transformers and Reactors Rated 10000 kva or Higher and Guide on transformer transportation, CIGRÉ, Working Group A2.42, Technical Brochure N º 673, 2017. It must be emphasized that although this paper does not intend to be an in-depth document because these problems are generally known, that is unfortunately true that is still happening that transformers arrive to site with visible and/or concealed damages due to improper packing, handling and transportation procedures. For this reason it cannot be highlighted enough to draw the attention of manufacturers, logistics and transportation companies, contractors and owners for this issue and the respective consequences. To prevent such situations of destruction, it is necessary, during FAT to perform certain special tests (such as defined in IEC Standards 60076-1 Power transformers Part 1: General, IEEE C57.12.90, Test Code for Liquid-Immersed Distribution, Power, and Regulating Transformers, IEEE C57.152, Guide for Diagnostic Field Testing of Fluid-Filled Power Transformers, Regulators, and Reactors and IEC 60137, Insulated bushings for alternating voltages above 1 000 V), and repeated them during SAT whenever the conditions of handling and transportation indicates any potential damage. Recommended special tests for this purpose include the following: Measurement of frequency response analysis (SFRA see point 3) Measurement of tan δ (dielectric losses) of the bushings (see point 3) Determination of capacitances windings-to-earth and between windings Measurement of DC insulation resistances between windings and winding to earth Measurement of DC insulation resistances core to earth and core frame to earth Single phase excitation current tests Magnetic balancing tests Both results must be compared and conclusions must be drawn about the eventual damages of the transformers. Although IEC and IEEE standards are referred, the basis of this article is IEC standards, since they are international standards used worldwide, while IEEE standards are USA standards, used only in a few countries when compared with IEC standards. 2

2. Problems and damages Transformers with high rated power and for voltages above 123 kv usually are transported without the oil, the tank being filled with nitrogen or dry air, and without the bushings, the conservator, and cooling equipment. Mechanical shocks above design limits or about 3g (g is the gravidity acceleration (9.8 m/s 2 ); 3g is the force equivalent to 3 times the gravidity acceleration in transformers may cause visible and/or concealed damages, such as: Visible damages include, but are not limited to, scratches in the surface protective coating and finishing of the tank, whether they are just hot-dip galvanization or painting (that sooner or later will lead to corrosion) see Figure 1 leaks of nitrogen and external cracks and chips, and even contamination, in the bushings. Figure 1 Scratches in the surface protective coating of a transformer tank Common concealed damages inside the transformer, which can negatively impact the reliability of the transformer and which consequences may appear only after an indefinite time upon energizing, are: Geometrical distortion of winding/core. Due to active part movement, the insulation between the turns can be abraded, causing a short circuit and damage to the windings later during operation. Loss of coil clamping pressure. Mechanical vibrations may cause the windings to lose their clamping pressure, eventually leading to collapse of the windings during electric faults. Contamination of the oil (resulting from the degradation of windings insulation). Safe clearance between the tank and the active part may be compromised. Unintentional grounding of core or core frame that can cause gassing during operation But apart from physical damages, incorrect packing and transportation procedures can also cause other type of damages, namely contamination of oil or of the windings insulation with water, moisture, dust and other contaminants. These contaminations will result in premature ageing of insulation materials, this meaning that their dielectric strength will be reduced with the corresponding decrease of useful life of the transformer and/or severe failures. In order to investigate if transformers were subjected to excessive mechanical impacts, it is recommended to use impact (or shock) recorders, like the one shown in Figure 2, during transformers transportation to evaluate the magnitude of those mechanical shocks. 3

Figure 2 Impact shock recorder 3. Tests to be performed to find mechanical damages (according with IEC standard 60076-1) IEC standard 60076-1 defines special tests, which can be used to find eventual damages due to excessive mechanical impacts, whether mechanical or any kind of contamination. These tests are the following: Measurement of frequency response analysis (SFRA) Measurement of tan δ (dielectric losses) of the bushings Determination of capacitances windings-to-earth and between windings Determination of DC insulation resistances between windings and winding to earth Testing procedures and acceptance criteria are defined in the referred standard. To evaluate the possibility of internal cracks or contamination in transformer bushing it must be performed the tan δ test, which represents the dielectric losses of the insulation material, also known by dissipation factor. However, in an ideal insulator the current that passes through it is totally capacitive (I C ), but real insulators do not have 100% purity, this meaning that the current through the insulator as also a resistive component (I R ), and we say that insulator has losses that are represented by tan δ, being δ the angle shown in Figure 3. Resistive current results from impurities or damages in the insulator and dielectric strength is inversely proportional to this current. 4

From the figure above we can conclude that: Figure 3 Angle of losses and currents of an insulator (1) Hence, if I R increases the losses will increase this meaning that the dielectric strength of the insulator decreases. To find possible damages in the core or in the windings of the transformer caused by an impact greater than what is acceptable a SFRA test (Sweep Frequency Response Analysis) must be performed. In colloquial language we can say that SFRA is the DNA (deoxyribonucleic acid) or the finger print of the transformer. Each winding and the core presents a unique frequency response and when sweep frequencies are applied to the transformer a particular signature is produced. It is important to understand that transformers with the same voltage ratio and rated power, constructed the same way and using the same materials in the core, windings and insulation will have similar and very close signature to sweep frequencies, but not identical, a fact that is considered important. The test is performed applying to the transformer frequencies in the range of ± 5 Hz to ± 2 MHz being the connections for this test represented in Figure 4. 5

Figure 4 SFRA test Applied frequencies between ± 5 Hz and ± 5 khz indicate the impact of the core, as well as its magnetization and the residual flux. In the range of ± 5 khz to 500 khz are shown the effect of the relation between the windings and their relative radial and geometrical movements. For frequencies above 500 khz it is indicated the impact of axial movements of the windings and of the internal connections circuits. However it must be not that according to the reference standard used in this paper, test procedure shall be agreed between manufacturer and purchaser. Measurement tests of capacitances windings-to-earth and between windings and DC insulation resistances between windings and winding to earth give important information about possible damages in the windings if the transformer was subjected to excessive mechanical impacts. Measurement of capacitances windings-to-earth and between windings is used to determine the dissipation factor of the insulation material of the windings. Similar to what referred above an increase of that factor represents a decrease of dielectric strength of the mentioned insulation material. DC insulation resistance tests are used to measure the insulation resistance of between windings and from each individual winding to earth, usually calculated from the measured applied voltage and measured leakage current, at ambient temperature and converted to 75 C. The calculated values are then compared to minimum insulation resistance (normally expressed in MΩ) specified in the standard, according to primary and secondary voltages of the transformer and the connection diagram of the windings (star or delta). 6

4. Other tests Other tests, different from those referred above, may be also be used to investigate eventual damages in a transformer due to incorrect handling and transportation procedures, particularly when the special tests considered in IEC standard 60076-1 were not performed during FAT. However, it must be noted that these tests are based on standards that may be not used by all entities involved in the transformer installation (namely owner, manufacturer and contractor) and that may not be as accurate and reliable as the ones specified by IEC and that were prior discussed. Measurement of DC insulation resistances core to earth and core frame to earth test (not defined in IEC standard 60076-1, either type, routine or special) is similar to measurement of DC insulation resistances between windings and winding to earth and may be used to investigate if any damage occurred, basically if the core is grounded due to excessive mechanical impacts. According to IEEE C57.12.90 this test is considered to be a routine test for transformers up to 69 kv and a special test for voltages above. Measurement of single-phase excitation current test is usually performed during manufacturing stage and normally it is used to as a base for diagnosis of secondary windings faults (short-circuits and open circuits), eventual core earthing and other fabrication defects. However, in what concerns faults in windings and core, whenever more accurate tests, namely SFRA test, were not performed, this test may also be used to find eventual problems on those components. Basic principle of this test is to apply a low voltage V 1 (usually 400/230 V) on the primary terminal of the transformer; a small current will flow through the core the magnetizing current (I mag ), which is the current required to magnetize the core of the transformer a force a magnetic flux to circulate in the core, the magnetizing flux (Φ mag ). If the secondary is open only a small current is necessary for the magnetic flux enters the winding and induces a voltage in secondary, that we will call V 2. This small current is the excitation current (I exc ) of the transformer. Comparing the off-load excitation currents measured at FAT and SAT, if the difference between them is bigger than the tolerance defined in the standards there is a strong probability that a defect had occur in the windings (primary and/or secondary). Figure 5 shows a simplified diagram of what was explained. Figure 5 Simplified diagram of single-phase excitation current test To identify if the defect is in the secondary winding, theoretical principle below described is used. If a load, requiring a current I L is applied in the secondary that load has a reluctance that oppose to movement of magnetic flux in the core. Hence, the current in the primary will increase I L to overcome that reluctance. This situation is shown in Figure 6. 7

Figure 6 Currents in the transformer with a load in the secondary When the transformer has no load in the secondary and there is a short-circuit between turns of the secondary winding or this winding as a fault to the ground, by applying a low voltage in the primary, the transformer acts as if a load is connect. Hence the measured excitation current is higher than it should be. If the pattern of the excitation current is not regular this may a problem in the core or that there are masked problems, but which are not possible to identify. Both measurement of DC insulation resistances core to earth and core frame to earth and measurement of single-phase excitation current tests must be performed in accordance with IEEE standard C57.12.00, General Requirements for Liquid-Immersed Distribution, Power, and Regulating Transformers. Magnetic balance test is also usually performed in MV/MV and MV/LV transformers, and not generally used in large HV/HV transformers (HV: high voltage; MV: medium voltage; LV: low voltage), during manufacturing stage, or at site as precommissioning test, to evaluate any defects in the turns of the windings (faults in the insulation of turns, de-shaping of the windings, etc.) or in the core (loosen bolts and nuts, failure in the staking of laminated sheets, external loops around the core, abnormal magnetizing current caused by faults in the turns of the windings, etc.). Common procedure of this test is to apply a low voltage (400-231 V, 50 Hz or 60 Hz) between two phases (let us say between phase A and phase B V AB ) and measure voltages between phases B and C (V BC ) and phases A and C (V AC ) and to compare the results. Under normal circumstances, without any defect in the transformer, it should be verified: V AB = V BC + V AC (2) If there is a problem in the transformer, then, probably: V AB V BC + V AC (3) The disadvantage of this test is that the results obtained are merely indicative and by themselves do not assure that there is a defect in the transformer, and additional tests must be performed to ensure that a real problem exists. Conclusion 8

Handling and transportation may pose the risk of internal damages in transformers and components and the contamination of insulating agents. To evaluate those possible injuries it is recommended to use an impact recorder and to perform the tests discussed above performed during FAT and SAT and to compare both results. Based on results of these tests, decisions can be made to perform additional tests and/or an internal inspection, at site or at factory, depending of possible damages, as a part of prior to energize the transformer. Bibliography [1] IEC Standard 60076-1 Power transformers Part 1: General [2] IEC Standard 60137 Insulated bushings for alternating voltages above 1 000 V) [3] Reykherdt, Dr Andrey A., Condition Monitoring of Power Transformers, Select Solutions [4] IEEE C57.150 Guide for the Transportation of Transformers and Reactors Rated 10000 kva or Higher [5] IEEE C57.152 Guide for Diagnostic Field Testing of Fluid-Filled Power Transformers, Regulators, and Reactors [6] IEEE C57.12.90, Test Code for Liquid-Immersed Distribution, Power, and Regulating Transformers [7] IEEE C57.12.00, General Requirements for Liquid-Immersed Distribution, Power, and Regulating Transformers [8] Guide on transformer transportation, CIGRÉ, Working Group A2.42, Technical Brochure N º 673, 2017 [9] Bolotinha, Manuel, Basics of HV, MV and LV Installations, Editora Ómega (www.editoraomega.com), January 2017 Author Manuel Bolotinha completed his University Degree in Electrical Engineering (Power Systems) in 1974 at Instituto Superior Técnico Lisbon University, where he was an Assistant Professor. His career includes the design, site supervision e contract management of electrical installations works (High, Medium and Low Voltage) in Portugal, Africa, Asia and South America. He is a Senior Fellow of the Portuguese Engineers Association (Ordem dos Engenheiros), a Fellow of IEEE and a certified Professional Instructor, conducting training courses, whose course Books he is the author, in Portugal, Africa and the Middle East He is also author of several technical articles and books. 9