1 2 3 4 P Digital panelmeter with microprocessor based technology 5 digit PU5 Universal measuring input free configurable Measuring inputs: voltage, current, shunt, thermocouple, resistance, resistor thermocouple Resolution 24 bit Measuring rate up to 50 measuring cycles/s Tara key [ ] (function optionally) Min/max memory 30 points linearization 4 free scalable setpoints/hysteresis/delay time Optical setpoint indication Serial interfaces RS232/RS485/CANopen Protection IP54 standard / IP65 option status 11/11/03 - panelmeteranalog_gb.doc page 37 PU5
Digital panelmeter Universal panelmeter Voltage, current, shunt, thermocouple Resistance, resistor thermocouple 1 2 3 4 P + - + - N L + - 24VDC or 115V AC or 230V AC Power 230V AC Power 115V AC Power 24V DC (galv. insulated) ORDER NUMBER OF TYPE (without options) PU 5.000X.1540B PU 5.000X.1440B PU 5.000X.1740B S1 S2 S3 S4 Interface 21 22 23 24 25 26 27 28 29 30 31 32 41 42 43 Relay PU5 Kl. 1 KL. 2 Kl. 3 Kl. 4 Kl. 5 Kl. 6 Kl. 7 0...10 V + U U 0...5 V -0,5...2,5 V + U U -0,5...1,25 V ± 500 mv ± 300 mv ± 150 mv ± 75 mv ± 35 mv ± 15 mv 0/4...20mA + I I 0...5 ma 0...2 ma PTxxx 2-wire + Force + Force + Sense Sense term 3 term 4 PTxxx 3-wire + Force Force + Sense Sense term 3 PTxxx 4-wire + Force Force + Sense Sense Thermocouples + Signal Signal Resistance 2-wire + Force term 3 + Force term 4 + Sense Sense Resistance 3-wire Resistance 4-wire + Force term 3 Force + Sense Sense + Force Force + Sense Sense status 11/11/03 - panelmeteranalog_gb.doc page 38 PU5
OPTIONS PU5... Additional price LED green x X Protection IP65 frontside x X Plug in terminal x X (The sensor is galv. insulated from the measuring input) 24VDC/50mA (power 230/115VAC) x X 10VDC/20mA (power 230/115VAC) x X 24VDC/50mA (power 24 V/DC galv.insulated) x X 10VDC/20mA (power 24 V/DC galv.insulated) x X (The analog is galv. insulated from the measuring input) 0-10VDC / 12 bit (power 230/115VAC) x X 0-20mA/load 500Ω (power 230/115VAC) x X 4-20mA/load 500Ω (power 230/115VAC) x X 0-10VDC / 12 bit (power 24 V/DC galv.insulated) x X 0-20mA/load 500Ω (power 24 V/DC galv.insulated) x X 4-20mA/load 500Ω (power 24 V/DC galv.insulated) x X Interface RS232 without galv. insulation x X Interface RS232 mit galv. insulation (power 230/115VAC) x X Interface RS485 mit galv. insulation (power 230/115VAC) x X Interface RS232 mit galv. insulation (power 24 V/DC galv.insulated) x X Interface RS485 mit galv. insulation (power 24 V/DC galv.insulated) x X 2 Relays (changing contacts) x X 4 Relays (changing contacts) x X Tare funktion S252 (special software with min/max indication and tare function) x X Other voltages on demand Other sensor volages on demand Higher resolution on demand Technical data Housing Dimensions 96 x 48 x 134 mm (BxHxT) including screw terminal 96 x 48 x 148 mm (BxHxT) including plug in terminal Assembly cut out 92,0 +0,8 x 45,0 +0,6 mm Fastening Snap in screw element Wall thickness 0...50 mm Material PC/ABS-Blend, black, UL94V-0 Protection Standard IP54 (front), IP00 (rearside) Weight Appr. 450 g Connection Screw- /screw-plug in terminal; wire cross section up to 2,5 mm 2 Display Character high 14 mm Segment colour red Display range -9999...99999 Setpoints One LED per setpoint Overflow Horizontal bars at top Underflow Horizontal bars at the bottom Input Measuring range R I Measuring error Digit T U= 20...40 C [%] MB Measuring range / 1...10 V 150 kω 0,01 ± 1 Input resistance / 1...5 V 150 kω 0,02 ± 1 Measuring error 0/4...20 ma 50 Ω 0,02 ± 1 at measuring time = 1 s 0...5 ma 50 Ω 0,02 ± 1 0...2 ma 50 Ω 0,02 ± 1 500...2500 mv 1 MΩ 0,03 ± 1 500...1250 mv 1 MΩ 0,03 ± 1 ± 500 mv 1 MΩ 0,03 ± 1 ± 300 mv 1 MΩ 0,03 ± 1 ± 150 mv 1 MΩ 0,03 ± 1 ± 75 mv 1 MΩ 0,04 ± 1 ± 35 mv 1 MΩ 0,06 ± 1 ± 15 mv 1 MΩ 0,06 ± 1 PTxxxx (2/3/4-wire) 1 MΩ 0,04 ± 1-200,0-850,0 C Thermocouple Typ L ( 200...900 C) 1 MΩ 0,06 ± 1K Typ J ( 210...1200 C) 1 MΩ 0,05 ± 1K Typ K ( 250...1271 C) 1 MΩ 0,05 ± 1K Typ B (100...1810 C) 1 MΩ 0,10 ± 1K status 11/11/03 - panelmeteranalog_gb.doc page 39
Technical data Input Measuring range R I Measuring error Digit T U= 20...40 C [%] MB Typ S (0...1767 C) 1 MΩ 0,06 ± 1K Typ N ( 250...1300 C) 1 MΩ 0,06 ± 1K Typ E ( 260...1000 C) 1 MΩ 0,06 ± 1K Typ R (0...1767 C) 1 MΩ 0,07 ± 1K Typ T ( 240...400 C) 1 MΩ 0,07 ± 1K Resistance 1 MΩ 0,04 ± 1 100Ω 2/3/4-wire Resistance 1 MΩ 0,04 ± 1 1kΩ 2/3/4-wire Resistance 1 MΩ 0,04 ± 1 10kΩ 2/3/4-wire Temperature drift with T U < 20 C resp. > 40 C All measuring inputs 50 ppm/k Measuring time Current, voltage 0,02...10,00 s PTxxxx 2/4-wire 0,04...10,00 s PTxxxx 3-wire 0,06...10,00 s Thermocouple 0,04...10,00 s Resistance 2/4-wire 0,04...10,00 s Resistance 3-wire 0,06...10,00 s Measuring principle Sigma/Delta The maximum permitted value on the input clips is 120% of the nominal value. Output Relays (galv. separated) Error Internal resistance (galv. separated) Interface Protocol RS232 (optional galv. separated) RS232 (optional galv. separated) Lead length RS485 (optional galv. separated) Lead length Change over contact 230V/AC 5A resp. 30V/DC 2A (cos ϕ=1) Separation in accordance with DIN EN 50178 Specifications in accordance with DIN EN 60255 0...10 V (12-bit) load 1 kω 0...20 ma (12-bit) load 500 Ω 4...20 ma (12-bit) load 500 Ω 0,1 % within range T U= 20...40 C, outside 50 ppm/k 100 Ω 10V/DC 20 ma 24V/DC 50 ma Manufacturer specific ASCII 9600 baud, no parity, 8 databits, 1 stopbit 9600 baud, no parity, 8 data bits, 1 stopbit max. 3 m 9600 baud, no parity, 8 databits, 1 stopbit max. 1000 m Mains unit Power 230 V/AC / 50/60 Hz / ±10 % and 115 V/AC / 50/60 Hz / ±10 % (galv. separated) 24 V/DC / ±10 % Power consumption Memory Data life max. 8 VA Parameter memory EEPROM >100 years Ambient conditions Working temperture 0...60 C Storing temperture -20...80 C Climatic resistance rel. humidity 75 % in the annual mean without formation of condensation EMV DIN 61326 CE-sign Conformity to 89/336/EWG Safety standard DIN 61010 status 11/11/03 - panelmeteranalog_gb.doc page 40
Technical data Housing: 141mm 111 Upper terminal Lower terminal 48 seal Snap in screw element Eject gap 96 Display and control elements 5 134mm with screw terminal 148mm with plug in terminal Assembly cut out +0,8 mm 92,0 mm -0,0 mm 45,0 mm +0,6 mm -0,0 mm status 11/11/03 - panelmeteranalog_gb.doc page 41
Connecting examples Measurement a current signal from a 2-line transmitter using the sensor ; voltage 230V/AC Input signal 230VAC Power + - + - N L + -? B1 U Measurement of a voltage signal (5V or 10V) from a 3-wire transmitter using the sensor ; voltage 24 V/DC 24VDC Power + - + - + - + -? B1 U Measurement of a voltage signal 2,5V) from a 3-wire transmitter using the sensor ; voltage 230V/AC sensor 230VAC Power + - + - N L + -? B1 U Measurement of a resistance thermometer (e.g. PT100) or resistance in the 2-wire technology; voltage 230 V/AC 230VAC Power + - + - N L status 11/11/03 - panelmeteranalog_gb.doc page 42
Connecting examples Measurement of a resistance thermometer (e.g. PT100) or resistance in the 3-wire technology; voltage 24 V/DC 24VDC ( ) + - + - + - Measurement of a resistance thermometer (e.g. PT100) or resistance in the 4-wire technology; voltage 230 V/AC Measurement of a thermocouple; connection of the analog ; connection of the digital input to the sensor ; voltage 230 V/AC Terminal assignment for interface RS232 41 42 43 RS485 41 42 43 GND TxD RxD GND (RS) Data B(+) Data A (-) 230VAC + - + - N L 230VAC + - + - N L + - + - + S1 status 11/11/03 - panelmeteranalog_gb.doc page 43
Ordering code PU5, PZ5 Digital panelmeter with microprocessor P U 5 0 0 0 X 1 5 4 0 B Basic model (processor) Internal index Base Setpoints Universal measuring device U 0 No setpoint 2 inputs Z 2 2 Relay s 4 4 Relay s Number of digits 5 digits 5 Mechanical options 1 IP65, foil keyboard, screw terminal 4 IP54, foil keboard, screw terminal Interface 7 IP65, foil keyboard, plug in terminal No interface 0 9 IP54, foil keyboard, plug in terminal CAN (galv. insulated) 1 RS232 2 RS232 (galv. insulated) 3 Power RS485 (galv. insulated) 4 4 115 V/AC RS485 5 5 230V/AC 7 24VDC(galv. insulated) No sensor 0 Size of housing 10V/20mA 2 1 24V/50mA 3 Measuring input Outputs X Universal input No 0 1 Direct voltage, direct current 0-10V 1 0-20mA 2 4-20mA 3 status 11/11/03 - panelmeteranalog_gb.doc page 44
Fastening clips ORDER NUMBER OF TYPE ZU-KK1 Fixing clasps ZU-KS1 Blind covers with fastening clamps GH009-06 status 11/11/03 - panelmeteranalog_gb.doc page 85 ZU
Dimension strips Montwill digital panelmeter are equipped with an insertable dimensionstrip. Each dimensionstrip is bilateral printed with three different dimensions plus one blank dimension. The table below shows the available dimensionstrips which are attached to every panel meter. (free of charge) ORDER NUMBER GH009-48-xx l/min l/h l/s 01 h mg mg/l 22 bar psi mbar 02 kg kg/h Kp 23 mnn N bar abs 03 ppm vpm % Vol 24 dan Nm kn 04 Pak/min Tak/min Stck/min 25 Ω PS mm/min 05 NO NO 2 NO x 26 C F Grad 06 ma A ka 27 min -1 1/min U/min 07 W kw m/min 28 t t/h Gramm 08 upm rpm yd/min 29 ph kpa MPa 09 Hz khz cm/min 30 O 2 CO CO 2 10 Pa hpa Hübe/min 31 mv V kv 11 %Nm %dan Hübe 32 VA kva K 12 ms/cm us/cm cm 3 33 Fl/h FL/min Tabl/h 13 N/m 2 N/mm 2 %rh 34 ft/min tr/min rpm 14 ~ = g/m 3 35 Var Mvar km/h 15 ml ml/min Ncm 36 m 3 /h l m 3 /min 16 MW Mp MN 37 gal/h gal/min mmws 17 ml/m 3 inch mws 38 m cm mm 18 m/h m 3 m/s 19 mm/s s min 20 % %rel F 21 (For substitute deliveries) status 11/11/03 - panelmeteranalog_gb.doc page 86 ZU