Grounding System Theory and Practice

Similar documents
A DUMMIES GUIDE TO GROUND FAULT PROTECTION

2 Grounding of power supply system neutral

Upgrading Your Electrical Distribution System To Resistance Grounding

Our Brands. Where we are?

Section 6: System Grounding Bill Brown, P.E., Square D Engineering Services

CHAPTER 15 GROUNDING REQUIREMENTS FOR ELECTRICAL EQUIPMENT

Summary of the Impacts of Grounding on System Protection

Webinar: An Effective Arc Flash Safety Program

thepower to protect the power to protect i-gard LITERATURE Low and medium voltage

Ground Fault Currents in Unit Generator-Transformer at Various NGR and Transformer Configurations

Overview of Grounding for Industrial and Commercial Power Systems Presented By Robert Schuerger, P.E.

Topic 6 Quiz, February 2017 Impedance and Fault Current Calculations For Radial Systems TLC ONLY!!!!! DUE DATE FOR TLC- February 14, 2017

FERRORESONANCE SIMULATION STUDIES USING EMTP

EPG. by Chris C. Kleronomos

MV Network Operation Issues and Elimination of Phase Voltage Unbalance

R10. IV B.Tech I Semester Regular/Supplementary Examinations, Nov/Dec SWITCH GEAR AND PROTECTION. (Electrical and Electronics Engineering)

Safety through proper system Grounding and Ground Fault Protection

CONTENTS. 1. Introduction Generating Stations 9 40

Coil Products Beginnings 1960 State of the Art. Customer partnership around the globe. Continuous innovation since 1900

Effective System Grounding

SUBJECT CODE : EE6702 SUBJECT NAME: Protection & switchgear STAFF NAME : Ms.J.C.Vinitha

Busbars and lines are important elements

ENERGY SAVING WITH OPTIMIZATION OF VOLTAGE AND CURRENT QUALITY

The Importance of the Neutral-Grounding Resistor. Presented by: Jeff Glenney, P.Eng. and Don Selkirk, E.I.T.

CHAPTER 2 ELECTRICAL POWER SYSTEM OVERCURRENTS

FGJTCFWP"KPUVKVWVG"QH"VGEJPQNQI[" FGRCTVOGPV"QH"GNGEVTKECN"GPIKPGGTKPI" VGG"246"JKIJ"XQNVCIG"GPIKPGGTKPI

Utility System Lightning Protection

ELECTRICAL POWER ENGINEERING

HPS Universal BUCK-BOOST TRANSFORMERS

The InterNational Electrical Testing Association Journal. BY STEVE TURNER, Beckwith Electric Company, Inc.

Earth Fault Protection

Do Capacitor Switching Transients Still Cause Problems?

TN, TT & IT Earthing Arrangements

Level 6 Graduate Diploma in Engineering Electrical Energy Systems

Optimal neutral ground resistor rating of the medium voltage systems in power generating stations

Grounding for Power Quality

Short-Circuit Analysis IEC Standard Operation Technology, Inc. Workshop Notes: Short-Circuit IEC

Design and Simulation of Passive Filter

SAFETY ASPECTS AND NOVEL TECHNICAL SOLUTIONS FOR EARTH FAULT MANAGEMENT IN MV ELECTRICITY DISTRIBUTION NETWORKS

2. Current interruption transients

Shortcomings of the Low impedance Restricted Earth Fault function as applied to an Auto Transformer. Anura Perera, Paul Keller

Tab 2 Voltage Stresses Switching Transients

Protecting Large Machines for Arcing Faults

TECHNICAL INFORMATION

Look over Chapter 31 sections 1-4, 6, 8, 9, 10, 11 Examples 1-8. Look over Chapter 21 sections Examples PHYS 2212 PHYS 1112

Transformer Protection

(2) New Standard IEEE P (3) Core : (4) Windings :

GENERATOR INTERCONNECTION APPLICATION Category 5 For All Projects with Aggregate Generator Output of More Than 2 MW

10. DISTURBANCE VOLTAGE WITHSTAND CAPABILITY

Numbering System for Protective Devices, Control and Indication Devices for Power Systems

3. (a) List out the advantages and disadvantages of HRC fuse (b) Explain fuse Characteristics in detail. [8+8]

ELEC Transmission i and

COPYRIGHTED MATERIAL. Index

Unit 3 Magnetism...21 Introduction The Natural Magnet Magnetic Polarities Magnetic Compass...21

1% Switchgear and Substations

Preface...x Chapter 1 Electrical Fundamentals

Ground Fault Isolation with Loads Fed from Separately Derived Grounded Sources

, ,54 A

GOOD GROUNDING PRACTICES. A Brief Introduction to the Basics of Electrical Grounding for Power Systems

UProtection Requirements. Ufor a Large scale Wind Park. Shyam Musunuri Siemens Energy

Although shunt capacitors

Methods of secondary short circuit current control in single phase transformers

Transient Recovery Voltage (TRV) and Rate of Rise of Recovery Voltage (RRRV) of Line Circuit Breakers in Over Compensated Transmission Lines

Chapter # : 17 Symmetrical Fault Calculations

TECHNICAL BULLETIN 004a Ferroresonance

State of North Dakota Engineering data submittal Page 1 For interconnection of distributed generation to Otter Tail Power Company

Rayleigh Pulse Forming Network. Part II Assessment of sensitivity

System grounding of wind farm medium voltage cable grids

Lecture Outline Chapter 24. Physics, 4 th Edition James S. Walker. Copyright 2010 Pearson Education, Inc.

Electrical Theory. Power Principles and Phase Angle. PJM State & Member Training Dept. PJM /22/2018

By Gill ( ) PDF created with FinePrint pdffactory trial version

USING OVER-DAMPING METHOD TO SUPPRESS THE FERRO-RESONANCE OF POTENTIAL TRANSFORMER

HVDC High Voltage Direct Current

Industrial and Commercial Power Systems Topic 7 EARTHING

Effects of Harmonic Distortion I

Module 2 : Current and Voltage Transformers. Lecture 8 : Introduction to VT. Objectives. 8.1 Voltage Transformers 8.1.1Role of Tuning Reactor

SAMPLE EXAM PROBLEM PROTECTION (6 OF 80 PROBLEMS)

Grounding Recommendations for On Site Power Systems

Partial Discharge, Survey or Monitor?

VALIDATION THROUGH REAL TIME SIMULATION OF A CONTROL AND PROTECTION SYSTEM APPLIED TO A RESONANT EARTHED NEUTRAL NETWORK

EARTH FAULT PROTECTION VIS-A-VIS GENERATOR GROUNDING SYSTEM

Protection Basics Presented by John S. Levine, P.E. Levine Lectronics and Lectric, Inc GE Consumer & Industrial Multilin

Neutral Reactor Optimization in order to Reduce Arc Extinction Time during Three-Phase Tripping

RESONANT TRANSFORMER

G. KOEPPL Koeppl Power Experts Switzerland

A Study on Ferroresonance Mitigation Techniques for Power Transformer

Radar. Radio. Electronics. Television. .104f 4E011 UNITED ELECTRONICS LABORATORIES LOUISVILLE

Specialists in HV and MV test and diagnostics. Testing in Substations

SECTION 3 BASIC AUTOMATIC CONTROLS UNIT 12 BASIC ELECTRICITY AND MAGNETISM. Unit Objectives. Unit Objectives 2/29/2012

Končar TMS - Bushing monitoring

ENGINEERING DATA SUBMITTAL For the Interconnection of Generation System

Chapter 30 Inductance, Electromagnetic. Copyright 2009 Pearson Education, Inc.

BE Semester- VI (Electrical Engineering) Question Bank (E 605 ELECTRICAL POWER SYSTEM - II) Y - Y transformer : 300 MVA, 33Y / 220Y kv, X = 15 %

EVALUATION OF DIFFERENT SOLUTIONS OF FAULTED PHASE EARTHING TECHNIQUE FOR AN EARTH FAULT CURRENT LIMITATION

Delayed Current Zero Crossing Phenomena during Switching of Shunt-Compensated Lines

INTERNATIONAL JOURNAL OF ELECTRICAL ENGINEERING & TECHNOLOGY (IJEET)

Electrical Engineering. Power Systems. Comprehensive Theory with Solved Examples and Practice Questions. Publications

System Protection and Control Subcommittee

Ferroresonance Experience in UK: Simulations and Measurements

ANALYSIS OF FAULTS INTERRUPTED BY GENERATOR

Transcription:

Grounding System Theory and Practice Course No. E-3046 Credit: 3 PDH

Grounding System Theory and Practice Velimir Lackovic, Electrical Engineer System grounding has been used since electrical power systems began. However, many companies and industrial plants have used system grounding methods differently. The problem of whether a system neutral should be grounded, and how it should be grounded, has many times been misunderstood completely. Therefore, grounding of many systems has been based upon past experience rather than engineering analysis. This course provides applicable information for grounding, such as definitions, reasons for having a system ground, the most desirable grounding method, and so on, and how to measure ground resistance in order to maintain the grounding system. The definition of grounding is commonly used for both, system grounding and equipment grounding. The National Electrical Code (NEC) defines system ground as a connection to ground from one of the current-carrying conductors of an electrical power system or of an interior wiring system, whereas an equipment ground is defined as a connection to ground from one or more of the noncurrent-carrying metal parts of a wiring system or equipment connected to the system. Following definitions describe power system grounding. - System neutral ground: A connection to ground from the neutral point or points of a circuit, transformer, motor, generator, or system. - Grounded system: A system of conductors in which at least one conductor or point is intentionally grounded. - Ungrounded system: A system of conductors in which there is no intentional connection to ground. - Solidly grounded: A system in which there is no intentional impedance in ground connection; in such a system the line to ground fault currents may equal three-phase fault current. - Resistance grounded: A system grounded through a resistance the value of which can be such as to provide either a low- or high-resistance ground system. The low-resistance ground system can have from 25 to several thousand amperes depending upon the value of the resistance. The high- resistance ground system usually has a value less than 25 A but greater than the value given by XCO/3, where XCO is the charging capacitance of the system. - Reactance grounded: A system grounded through a reactance. - Resonant grounded: The system grounding reactance value is such that the rated frequency fault current flowing through it is substantially equal to the current flowing between the conductors and the earth (charging current of the system). - Ground-fault neutralizer: A grounding device that provides an inductive component of current in a ground fault that is substantially equal to, and therefore neutralizes, the rated frequency capacitive component of the ground fault current. 1 Grounding System Theory and Practice PDHengineer.com

Selection of Grounding Method The selection of a method for power system grounding is very difficult because a large number of factors must be considered before a power system grounding method can be chosen. The following discussion outlines some problems with various grounding methods and explains how and why grounding systems are applied. Ungrounded Systems Early electrical systems were almost universally operated ungrounded. On small systems an insulation failure on one phase did not cause an outage. The failure could probably be found and repaired at a convenient time without a forced outage. This worked well as long as the systems were small. However, as systems increased in size and voltage rating, an increasing number of insulation failures produced multiple failures and major faults. At first, the reasons for these failures were not understood, and considerable work was done to find why they occurred. Figure 1 below shows a typical ungrounded neutral system. Figure 1. Ungrounded neutral system Actually, it is a capacitive grounded neutral system, the capacitance being the conductor capacitance to ground. In normal operation, the capacitive current of all three lines is leading the respective line to neutral voltages by 90, and the vector sum of all three currents is zero. Figure 2 shows what happens when the system of Figure 1 is accidentally grounded. Figure 2. Fault on ungrounded neutral system 2 Grounding System Theory and Practice PDHengineer.com

The charging current of the faulted phase goes to zero because its voltage to ground is zero. The voltages of the unfaulted phases increase to full line-to-line value with respect to ground, and their charging currents increase proportionally. In addition, because of the 30 shift of the line voltages with respect to ground, the charging currents shift accordingly, and the sum of the charging currents in the unfaulted phases is three times the normal value and appears in the ground, returning to the system through the fault. If the fault can be interrupted, it will most likely be done at a current zero. However, since the current leads by 90 in the capacitive circuit, current zero occurs at the instant of a voltage maximum; thus, if the fault momentarily clears, a high voltage immediately appears across the fault, and restrike of the fault will probably occur. In the momentary interval of time that the fault has been cleared the excessive voltage charge of the capacitors on the unfaulted lines has been trapped as a direct current (DC) charge. When the arc restrikes again: the capacitors are again recharged by a line-to-ground voltage added to the trapped charge. Thus, a restrike after another current zero clearing is more inevitable, adding another charge. The phenomenon thus probably becomes an oscillating and self-perpetuating build-up in voltage, which eventually will lead to an insulation failure on another phase and a major two-phase fault. While the first failure may have been a tree branch in the line, the second failure may occur at some other location entirely, perhaps involving expensive equipment insulation, such as a transformer. Thus, the principal advantage claimed for the ungrounded system actually caused troubles that resulted in its abandonment. These troubles coupled with other factors led to the adoption of grounded neutral systems in some form. Some of the other factors were as follows: - Because of greater danger to personnel, code authorities frowned on ungrounded systems. - Equipment costs were generally lower for equipment rated for grounded neutral systems because of the reduction in insulation permissible; because graded insulation could be used, single-bushing, single-phase transformers could be used. - At the higher voltages being used today (69 kv and above), material savings in transformer costs can be realized by employing reduced basic insulation level (BIL). These savings are in addition to the modest savings above, and may amount to substantial savings in the cost of transformers in the various voltage classes with reduced insulation. The requirements for safely reducing insulation level demand that system neutrals be grounded. Thus, these savings are not available on the ungrounded system. Solidly Grounded Systems The simplest and most effective method of grounding is to solidly connect the neutrals of any wye-connected transformers or generators to ground. This method has two major advantages: It is simple and inexpensive in that it requires no extra equipment. It minimizes the magnitude of the overvoltage that will appear on the unfaulted phases during a ground fault, resulting in a reduction in the stress on insulation as compared with other methods. This is the reason that solidly grounded neutrals are a necessity where reduced BIL insulation is to be used. In spite of the advantages of the solidly grounded system, there are associated disadvantages such that other grounding methods are often used. These disadvantages all stem 3 Grounding System Theory and Practice PDHengineer.com

from the fact that a solidly grounded system produces the greatest magnitude of ground fault current when a fault to ground occurs. It is realized that with a grounded neutral system perhaps 95% or more of all faults start as a single phase to ground fault. If the amount of ground current that flows can be controlled and the fault cleared promptly, the amount of damage at the fault will be reduced and the fault probably restricted so as not to involve more than one phase. This may result in preventing bum downs, reduction in the cost of making repairs, and reduction in the frequency or extent of maintenance on the breakers that interrupt the fault. In the case of machines or transformers, the difference in repair cost may be that of replacing a few damaged coils as compared with completely replacing the machine or transformer, which may be necessary where oil fires and explosion follow the transformer fault, or where heavy fault currents melt down coils and burn and weld together expensive areas of laminated electrical steel in the transformer core or machine stator iron. Since the damage done is approximately proportional to I 2 t, it is obvious that much more can be done in the reduction of current than by reduction in time. Under certain conditions, single phase to ground faults can give rise to short-circuit currents 50% in excess of three-phase short-circuit current. Thus, breakers whose ratings make them entirely capable of interrupting. Three phase faults may be in severe difficulty handling a single phase to ground fault. In view of this, the potential savings in damage and repair costs or avoiding the cost of having to install larger breakers may justify avoiding the simple and inexpensive solidly grounded system in favour of a more complex and expensive system that will provide control of the amount of fault current. Reactance and Resistance Grounded Systems Reactors are commonly employed as neutral impedance for ground current limitation when the amount of current reduction is small. This is because reactors of low ohmic value to handle large quantities of current can be built quite inexpensively as compared with a resistor for the same current limitation. Reactors to provide current limitation to values less than approximately 30% 50% of value are not practical. This is true partly because the high ohmic values necessary to provide the higher current limitation makes them more expensive than resistors, and partly because high values of reactance grounding approach the conditions of ungrounded systems and give rise to high transient voltages. Resistors are generally used where it is desired to limit fault currents to moderate to small values. The directly connected resistor is not practical for extremes of current limitation. Reactors are used where a small reduction of current is required, because a resistor large enough to handle the large quantities of current remaining would have to have resistor grids of tremendous cross section or many parallel grid paths, and as a result would be very expensive. On the other hand, if extreme limitation of ground current by resistors is desired, the resistor again becomes excessively expensive. This is because there are maximum values of resistance that it is practical to build into a resistor unit before the cross-sectional area of the resistance conductor becomes so small as to make it too susceptible to mechanical failure from shock, rust, corrosion, and the like. Thus, to get very high values of resistance, the resistor must be made up by connecting a tremendous number of moderate resistance units in series and it becomes expensive and bulky. 4 Grounding System Theory and Practice PDHengineer.com

A variation of the directly connected resistor is used, where it is desirable and practical to limit ground fault currents to extremely low values, to avoid the expense and difficulties of the very high value resistance. A distribution transformer is connected between the neutral to be grounded and ground. A resistor is then connected across the secondary of the transformer, as shown in Figure 3. Figure 3. Impedances in the resistor grounded system The actual 0.25 Ω resistor in the transformer secondary is stepped up in value as it appears to the generator neutral by the square of the transformer ratio of 13,200/240 or 3024 times. Thus, the 1/4 Ω secondary resistor appears as a 756 Ω resistor in the generator neutral. This limits the ground fault current to a maximum of 11.5 A. This represents only a small percent of current on the basis of machine full-load current and of the maximum three-phase fault current available. This is representative of the extreme of current limitation. It accomplishes the ultimate in the reduction of fault damage. Further reduction of fault current would be dangerous, because if it were attempted, the capacitance of the generator and step-up transformer windings and the generator lead bus duct would predominate over the higher values of resistance, and the system would approach the characteristics of the original ungrounded system of Figure 1 with its dangers of arcing grounds. Resonant Grounding One of the earliest methods of attempting to eliminate the faults of the ungrounded system and still retain the claimed advantages for it was by means of resonant grounding using the Peterson coil. This method attempted to eliminate the fault current that could cause the arcing ground condition. Figure 4 shows the system of Figures 1 and.2 with the Peterson coil applied. 5 Grounding System Theory and Practice PDHengineer.com