CERTIFICATE OF CONFORMANCE This is to confirm that Honeywell Airports Business have verified Tinned Copper Braided Screened Primary Cable supplied by PT Jembo Cable Company Tbk (Indonesia) for airfield lighting applications. Parameter Description Application Airfield Lighting Cable Description Underground Primary Cable for Airport Lighting Circuits Type FAA-L-824 Standards FAA AC 150/5345-7E Type Tinned Copper Wire Braided Working Voltage 5KV Test Voltage 35KV DC (15min) Conductor 7 Stranded Insulation Thickness 2.53 Screen Covering >80 Sheath Thickness 1.68 Overall Dia 13.23 Conductor Resistance 2.9 Ohms/Km @ 20C Min Insulation Resistance 37051 Megohms/Km @ 20*C Screen Resistance 4.55 Ohms/Km @ 20*C Partial Discharge 1.2 pc @4KV Service temp -40*C to +85*C Min Bending Radius 148 a) Round Stranded Tinned Copper Conductor b) Semi Conducting Compound (Extruded) c) XLPE Insulation Construction d) Semi Conducting Tape (Helically Applied) e) Tinned Copper Wire Braided f) Separation Tape g) PE-Outer Sheath (BlacK) Properties Abrasion, Oil, UV & Deicer Resistant Halogen Free Based on technical details provided and independent test reports, these cables are compliant with requirements for usage with Honeywell Single Lamp Control & Monitoring system. This Certificate of Conformity is valid only if the material and performance specification of the supplied cable is as above and per test reports attached. Date: May 30, 2018 Authorized Signatory
Schedule of Technical Data I/N : DTSXC7PE001006MC AIRFIELD LIGHTING PRIMARY CABLE SXC7Pe 1 x 6 ² 5 kv Ref. Spec : FAA Spec for L-824, AC 150/5345-7E Round Stranded Tinned Copper Conductor Extruded Semi-conductive Conductor Screen Tinned Copper Wire Braided Metallic Screen Helically Overlapped Polyester Tape Extruded XLPE Insulation Helically Overlapped Semi-conductive Tape Insulation Screen Extruded PE Outer Sheath ( Black Colour ) Cable Construction 1 Conductor : Round stranded tinned copper wire Number of wire : 7 Appr. Outer Diameter : 3.12 2 Conductor Screen : Extruded Semi-conductive Nom. thickness : 0.3 3 Insulation : Extruded XLPE Min. Average Thickness : 2.3 Min. Point Thickness : 1.97 4 Insulation Screen : Helically Overlapped Semi-conductive Tape 5 Metallic screen : Tinned copper wire braided Covering : 80 6 Core Wrapping : Helically Overlapped Polyester Tape 7 Outer Sheath : Extruded PE ( Black Colour ) Min. Average Thickness : 1.6 Min. Point Thickness : 1.08 Outer Diameter : 12.3 8 Cable Marking : JEMBO CABLE SXC7Pe 1 x 6 ² 5 kv "Year" Minimum bending radius : 148 Electrical Characteristic 1 Max. DC Conductor Resistance at 20 C : 3.08 Ohm/km 2 Max. DC Screen Resistance at 20 C : 5 Ohm/km 3 AC Dielectric Strength at 12.5 kv/ 5 min : No Break Down Shall Occur 4 Min. Insulation resistance : 4000 Meg.Ohm.km 5 Max. Current Rating in Ground at 30ºC : 95 A 6 Short Circuit Current at, 1 sec. : 0.85 ka 0.5 sec. : 1.20 ka 0.3 sec : 1.56 ka 0.1 sec : 2.69 ka Packing 1 Type of Packing : Wooden Drum 2 Standard Length : 1000 m 3 Dimension of Drum : 960 x 570 4 Net Weight : 185 kg 5 Gross Weight : 254 kg
Certificate No. 32122/DBBPAK REPORT OF TESTING @ -i^ - - I -. I I @ ' SUGOFIBMDQ Jl. Arteri Tol Cibitung No. 1, Cibitung Bekasi 17520, Indonesia Phone/Facs: +62 21 88321176/88321166 The sample was submited by client with the following identification: CLIENT JEMBO CABLE COMPANY Tbk, PT. ADDRESS JL. PAJAJARAN KEL GANDASARI, KEC. JATIUWUNG, TANGERANG 15137 - INDONESIA TYPE & SIZE OF CABLE AIRFIELD LIGHTING PRIMARY CABLE SXC7Pe 1x6 25 kv MERK/BRAND REFERENCE STANDARD JEMBO CABLE - ICEAT-27-581/NEMA WC 53-2008 - ASTM D412 - ICEAS-93-639/NEMAWC74 - ICEAT-28-562 - IEC 60092-350 - ASTM D1693 - AC No: 150/5345-7F - ASTM D1505 - IEC 60228 - ASTM D 792 DRUM NUMBER DATE AND PLACE OF 1NTERVENSION TEST REQUIRED SAMPLING PROCEDURE QUALITY RESULT CONCLUSION 090-01 October 3'"- 11th, 2017 at JEMBO CABLE COMPANY Tbk, PT. Jl. Pajajaran Kel. Gandasari, Kec. Jatiuwung, Tangerang 15137 @ Indonesia and October 17-20, 2017 at Sentra Teknologi Polimer (STP) BPPT, Gedung 460 Kawasan Puspitek Serpong, Muncul, Setu, Kota Tangerang Selatan, Banten 15314 Construction and Dimension Test Electrical Test Non Electrical Test Sample were drawn by JEMBO CABLE COMPANY Tbk, PT. The above sample had been tested under our presence for Testing with following results See attached sheets Test results of Airfield Lighting Primary Cable SXC7Pe 1x6 2 5 kv was conformed to the standard requirements The Attachment available is an integral part of this certificate. This test result (s) related to the sample (s) submitted only and the report / certificate cannot be reproduced in any way, except in full context and with the prior approval in writing from Sucofindo Laboratory. This Certificate/report is issued under our General Terms and Conditions, copy of which is available upon request or may be accessed at www.sucofiiido.co.id SBU Laboi CBT200227617-002 Fandi 2692757 SC I-2007A
20C Attachment Page 1 of 10 SUCQFfl^OQ Phone/Facs: +62 21 88321176/88321166 Jl. Arteri Tol Cibitung No. 1, Cibitung Bekasi 17520, Indonesia Email: jiim.cbt@sucofindo.co.id REPORT OF TESTING NO " TEST ITEM UNIT TEST- RESULT STANDARD REQUIREMENT Visual Visual Good Good II 2.1 Construction and Dimension Test Conductor Conductor shape Round stranded Round stranded Number of wire n 7 Min. 7 Outer diameter Avg. 3.12 Approx. 3.12 2.2 Conductor Screen Conductor shield thickness Avg. 0.41 Norn. 0.3 2.3 XLPE Insulation Nominal thickness Avg. 2.53 Nom. 2.3 2.4 Tinned Copper Braided wire earth screen Number of wire 24 24 2.5 Outer Sheath Nominal thickness Avg. 1.68 Nom. 1.6 Outer diameter Avg. 13.23 Approx. 12.5 Ill Electrical Test 3.1 Resistance of conductor at 20 C Q/km 2.90 Max. 3.08 3.2 Rresistance of insulation at 20 C M.Q.km 37 051 Min. 4000 3.3 Partial discharge test at 4 kv pc 1.2 Max. 5 3.4 High voltage test at 12.5 kv for 5 minutes No Breakdown No Breakdown Resistance of tinned copper 3.5 braided wire earth screen at Q/km 4.55 Max. 5 jf 1312618 SCI-2007P
Atachment Page 2 of 10 SUCOFINOO Issuing Office- Phone/Facs: +62 21 88321176/88321166 Jl. Arteri Tol Cibitung No. 1, Cibitung Bekasi 17520, Indonesia REPORT OF TESTING NO TEST ITEM UNIT TEST RESULT STANDARD.REQUIREMENT IV 4.1 4.1.1 Non Electrical Test Mechanical test of XLPE insulation Before ageing Tensile strength MPa 21.83 Min. 12.5 Elongation at break 494.4 Min. 250 4.1.2 After ageing in air oven without conductor Temperature c 121 121 Duration h 168 168 4.1.3 Tensile strength Value after ageing MPa 22.80 Not Applicable Percentage 104.4 Min. 75 4.1.4 Elongation at break Value after ageing 481.4 Not Applicable Percentage 97.37 Min. 75 4.2 4.2.1 Mechanical test of HDPE outer sheath Before ageing Tensile strength MPa 20.10 Min. 17.2 Elongation break 787.4 Min. 350 4.2.2 After ageing in air oven without conductor Temperature Duration c h 100 48 1266386 SCI-2007P
Page 3 of 10 SUCOFINDO Phone/Facs: +62 21 88321176/88321166 Jl. Arteri Tol Cibitung No. 1, Cibitung Bekasi 17520, Indonesia REPORT OF TESTING NO TEST ITEM UNIT TESTRESULT STANDARD;REQUIREMENT 4.2.3 Tensilestrength Valueafterageing MPa 22.29 Percentage 110.8 Min. 75 4.2.4 Elongationatbreak Valueafterageing 801.5 Percentage 101.7 Min. 75 4.3 HeatdistortionofXLPE insulationfor1 hour Diameterofinsulation 8.984 Diameterofinnersemicond @ 3.837 Finaloutsidediameterafter heating 8.865 Temperature C 100 100 1 Load gr 2000 2000 Thicknessbeforeheating 2.574 Thicknessafterheating 2.514 Maximumdistortion 2.3 Max. 30 4.4 Heatdeformationofouter sheathfor1 hour Temperature C 110 110 2 Load gr 2000 2000 Thicknessbeforeheating 1.987 Thicknessafterheating 1.628 Maximumdeformation 18.1 Max.jS^@~^\ UCOBNOO 1266387 SC! -2007 P
Page 4 of 10 BUCOFIIMQQ Phone/Facs:+62 21 88321176/88321166 Jl. ArteriTol Cibitung No. 1. Cibitung Bekasi 17520. Indonesia REPORT OF TESTING NO TEST ITEM UNIT TESTRESULT STANDARDREQUIREMENT 4.5 Hotcreeptestforinsulation Airtemperature C 150 150+2 Timeunderload minutes 15 15 Elongation underload 29.70 Max. 175 Permanentelongation 0.4 Max. 10 4.6EnvironmetalStress Cracking ResistanceTest Testing Duration h 60 60 TestingTemperature C 50 50 Chemical Detergent1-volume Detergent1-volume SampleCondition AfterTesting Defect0/10* Defect0/10* NoDiscoloration NoDiscoloration *)NoDefectOccuredonallsamples(10piece s) OnSampleSurface OnSampleScrape@@1-.. )!
Page 5 of 10!S!30k. SUCOFINDO Issuing Ofice: Phone/Facs: +62 21 88321176/88321166 Jl. Arteri Tol Cibitung No. 1, Cibitung Bekasi 17520, Indonesia ATTACHMENT OF CERTIFICATE @Ill 1266389 SC 1-2007 P
Page 6 of 10 ^flkmhjb* 5UCORNDQ Issuing Office. Phone/Facs: +62 21 88321 176/88321166 Jl. Arteri Tol Cibitung No. I, Cibitung Bekasi 17520, Indonesia ATTACHMENT OF CERTIFICATE CONDUCTOR SCREEN AIRFIELD LIGHTING PRIMARY CABLE SXC7Pe 1x6 2 5 kv HIGH VOLTAGE TEST AIRFIELD LIGHTING PRIMARY CABLE SXC7Pe 1x6 2 5 kv 1266395 SC I-2007P
Page 7 of 10 MimgEgHE SUCOFINDO Phone/Facs: +62 21 86321176/88321166 Jl. Arteri Tol Cibitung No. 1, Cibitung Bekasi 17520. Indonesia ATTACHMENT OF CERTIFICATE PARTIAL DISCHARGE TEST AIRFIELD LIGHTING PRIMARY CABLE SXC7Pe 1x6 2 5 kv RESISTANCE OF TIN COPPER WIRE TEST AIRFIELD LIGHTING PRIMARY CABLE SXC7Pe 1x6 2 5 kv 1266396 SC I -2007 P
Page I of 10 SUCOFINDO Phone/Facs: +6221 88321176/88321166 Jl. Arteri Tol Cibitung No. 1. Cibitung Bekasi 17520, Indonesia ATTACHMENT OF CERTIFICATE HEAT DISTORTION TEST FOR INSULATION AIRFIELD LIGHTING PRIMARY CABLE SXC7Pe 1x6 2 5 kv HEAT DEFORMATION TEST FOR SHEATH AIRFIELD LIGHTING PRIMARY CABLE SXC7Pe 1x6 2 5 kv 1266397 SC I-2007P
Page! of 10 SUCOFBNQO Phone/Facs: +62 2 1 88321176/88321 166 Jl. Arteri Tol Cibitung No. I. Cibitung Bekasi 17520, Indonesia ATTACHMENT OF CERTIFICATE HOT CREEP TEST FOR INSULATION AIRFIELD LIGHTING PRIMARY CABLE SXC7Pe 1x6 2 5 kv AGEING TEST AIRFIELD LIGHTING PRIMARY CABLE SXC7Pe 1x6 2 5 kv
To Certificate No 32122/DBBPAK Page 10 of 10 wesssr SUCOFINDO Phone/Facs +62 21 88321176/88321166 Jl Arten Tol Cibitung No. 1. Cibitung Bekasi 17520, Indonesia Email' jum.cbt@sucofindo.co id ATTACHMENT OF CERTIFICATE TENSILE TEST AIRFIELD LIGHTING PRIMARY CABLE SXC7Pe 1x6 25 kv CRACKING TEST AIRFIELD LIGHTING PRIMARY CABLE SXC7Pe 1x6 2 5 kv 1266399 S C I - 2 00 7 P