Conzerv EM6400NG series Multi-function power & energy meters Technical datasheet
PB115131 Introducing EM6400NG, next generation power meters of iconic EM6400 series with innovative Accurate measurements of THD and individual harmonics (complying with IEC61557-12) helps in EM6400NG series multi-function power meter Model reference Commercial reference Applications Cost management: Electrical installation remote monitoring Panel instrumentation Energy management Network management: THD and individual harmonics up to 15th order for Volts and Amps, per-phase Min/Max values of instantaneous parameters with timestamp Main characteristics EM6400NG POP EM6400NG POP EM6400NG RS485 EM6400NG RS485 EM6400NG RS485 METSEEM6400NGPOCL1 METSEEM6400NGPOCL5 METSEEM6400NGRSCL1 METSEEM6400NGRSCL5 METSEEM6400NGRSCL2 v 5 A, I-nominal v (W, VA, VAR, Amps) with 2 PLSED310111EN - 05/2015
PB115132 General Basic metering with THD, Individual Harmonics, RTC, and min/max readings Instantaneous RMS values Current Average line current of 3-phase, per-phase, and calculated neutral current Voltage Average voltage of L-L, L-N parameters, and per-phase EM6400NG series multi-function power meter - front Real, reactive, and apparent power Total and per-phase value Displacement power factor Average and per-phase signed, four quadrant True power factor Average and per-phase signed, four quadrant Energy values stored in non-volatile memory Accumulated Active, Reactive and Apparent Energy, Received and Delivered registers Demand values Current average Present, Last, Predicted, Peak, and Peak Date Time Active power Reactive power Apparent power Present, Last, Predicted, Peak, and Peak Date Time Present, Last, Predicted, Peak, and Peak Date Time Present, Last, Predicted, Peak, and Peak Date Time Demand sync methods Demand calculation mode Thermal, Timed, Command Sync, and Clocked Sync Display Auto range Communication Native Plug and Play support for Schneider Electric energy management system software - StruxureWare Power Monitoring Expert, StruxureWare PowerSCADA Expert along with ION Setup programming support PLSED310111EN - 05/2015 3
PB115133 Electrical characteristics Type of measurement Measurement accuracy True RMS, 64 samples per cycle EM6400NG series multi-function power meter - rear Current, Phase Voltage L-N, L-L Power Real Energy Reactive Energy IEC 62053-23 Class 2 THD and Individual Harmonic, V & A Input-voltage VT primary U nominal Measured V with full range Permanent overload Impedance 15th 277 V L-N/480V L-L 35 to 600 V AC L-L 750 V AC L-L Input-current CT ratings Measured Amps with over Withstand Impedance VA Burden AC control power Operating range Burden Ride-through time DC control power Operating range Burden Ride-through time Real time clock Ride-through time Displays update Instantaneous Demand Harmonics Secondary 1 A or 5 A I-nominal 5 ma to 6 A Continuous 12 A, 50 A at 10 sec/hr < 6 VA at 277 V L-N < 2 W at 277 V DC 3 years 1 s 15 s 5 s 1ph, 2w, LN 1ph, 2w, LL 1ph, 3w, LL with N (2phase) 3ph, 3w, Delta, Ungrounded 3ph, 3w, Delta, Corner Grounded 3ph, 3w, Wye, Ungrounded 3ph, 3w, Wye Grounded 3ph, 3w, Wye, Resistance Grounded 3ph, 4w, Open Delta, Center-Tapped 3ph, 4w, Delta, Center-Tapped 3ph, 4w, Wye, Ungrounded 3ph, 4w, Wye Grounded 3ph, 4w, Wye, Resistance Grounded Through communication only 4 PLSED310111EN - 05/2015
PB115134 92.0 +0.8 (3.62) +0.03 92.0 +0.8 (3.62) +0.03 <6.4 (< 0.25) Mechanical characteristics Weight IP degree of protection Material Dimensions W x H x D Mounting position Panel thickness Environmental characteristics Operating temperature Storage temperature Humidity rating Pollution degree 2 Altitude Product life Vertical 2000 m (6561 ft) Category III > 7 years Electromagnetic compatiility (as per IEC 62052-11) Electrostatic discharge IEC 61000-4-2 IEC 61000-4-3 Immunity to fast transients IEC 61000-4-4 Immunity to impulse waves IEC 61000-4-5 Conducted immunity IEC 61000-4-6 IEC 61000-4-8 Immunity to voltage dips IEC 61000-4-11 Emission Safety Europe US and Canada Measurement category (Voltage and Current inputs) Overvoltage category (Control power) Dielectric Protective Class Communication CE, as per IEC 61010-1 Ed-3 for 600V AC CAT III up to 480 V L-L CAT II up to 600 V L-L CAT III up to 300 V L-N As per IEC/UL 61010-1 Ed-3 C-Tick (RCM) RS485 port Pulse Output (POP) Isolation Protection features Display language Human machine interface Display type Keypad CAL LED Indicator Max 40 V DC, 20 ma 20 ms ON time (kwh, kvah, or kvarh) Password protected for set-up parameters English Printed installation guide (QSG) with meter and user guide in soft format 4 digits per row 2 columns of LEDs at either side of the LED panel to indicate the parameters under measurement pulse) Tested as per IEC 61326-1 standard PLSED310111EN - 05/2015 5
Feature set summary Parameter EM6400NG POP EM6400NG RS485 Accuracy Class for Wh Sampling rate per cycle 64 64 per-phase, average and calculated neutral current V L-N, V L-L - per-phase and average Power True True Displacement per-phase and total 3-ph Demand parameters (W, VA, VAR, Amps) Date and timestamp for peak demand Current (no timestamp) Current, Voltage (4 Quadrant) Delivered (Import), Received (Export) Delivered, Received Delivered, Received Total, Net, Last cleared Power On hours, Load Run hours and Power Outage - Voltage L-N or L-L, Amps per phase Individual Harmonics - up to 15th Min/Max with Real time clock - Communication POP Through communication only 6 PLSED310111EN - 05/2015
Dimensions and connections EM6400NG multi-function meter mechanical dimensions PB115136 PB115135 90.44 (3.56) mm (in) 77.01 (3.0) 62.76 (2.47) 89.81 (3.53) EM6400NG multi-function meter display overview Conzerv EM6400NG 96.0 (3.78) Conzerv EM6400NG Phase measurements Demand measurements RTC Negative indicator Navigation key Energy readings Navigation key OK 96.0 (3.78) VL-N, VL-L, I, kva, kw, kvar, PF, VTHD, ITHD DM, PrsDM, PrdDM, MD Date and time To navigate down Apparent energy, Active energy, and Reactive energy To navigate up Enter key 90.42 (3.56) 110.1 (4.33) Energy pulsing LED (Red), Hearteat / communications LED (Green) x 1000 indicator System measurements Vavg, kva, F, Iavg, kw, In, PFavg, kvar, Iun Retainer clip Input current terminals A1(S1, S2), A2 (S1, S2), A3 (S1, S2) RS-485 communications/ POP terminals D1+, D0- Protective cover Auxiliary power supply (control power) terminals Input voltage terminals L+, N- V1, V2, V3, VN PLSED310111EN - 05/2015 7
Schneider Electric Industries SAS 35, Rue Joseph Monier, CS 30323 2015 - Schneider Electric - All rights reserved PLSED310111EN 05-2015