Lecture 15 EMS Application II Automatic Generation Contol. Davood Babazadeh

Similar documents
EH2741 Communication and Control in Electric Power Systems Lecture 2

Standard BAL-005-0b Automatic Generation Control

EE 742 Chapter 9: Frequency Stability and Control. Fall 2011

Frequency Response Characteristic Survey Training Document

Standard BAL b Automatic Generation Control

Standard BAL b Automatic Generation Control

Load Frequency Control in an Interconnected Hydro Hydro Power System with Superconducting Magnetic Energy Storage Units

EE 742 Power System Components. Y. Baghzouz ECE Department UNLV

Table of Contents Error! Bookmark not defined.

Monitoring and Situational Awareness Conference. Improving EMS Reliability Denver, CO September 18, 2013

Frequency Response Standard Background Document November, 2012

GUIDELINES FOR UTILIZATION OF FREQUENCY AND TIME ERROR DEVICES AND CALIBRATING TIE LINE SIGNAL

Standard BAL b3 Automatic GenerationBalancing Authority Control DRAFT

Agenda Item 3h Attachment 9

NERC Training Document Understand and Calculate Frequency Response

UNIT-II REAL POWER FREQUENCY CONTROL. 1. What is the major control loops used in large generators?

Brianna Swenson Alliant Energy Minnesota Power Systems Conference November 8, 2017

Overview. The Principles of Power System Operation module presents the following topics:

Proposed Language in BAL-003-1/Comments New Standard or Other Action R1. Each Balancing Authority shall This. Attachment A.

Calculating and Using Reporting ACE in a Tie Line Bias Control Program

AUTOMATIC VOLTAGE REGULATOR AND AUTOMATIC LOAD FREQUENCY CONTROL IN TWO-AREA POWER SYSTEM

Area Control Error (ACE) Equation Special Cases

Success Story: Practical Use of Synchrophasor Technology in ISO-NE Operations

Harmonizing the Changing Resource Mix Keeping the Grid Together

Southern Company Interconnection Requirements for Inverter-Based Generation

Keeping it up to Speed Off-Nominal Frequency Operations. CETAC 2018 San Ramon

Implementation Plan Project Balancing Authority Reliability-based Controls - Reserves

Robert W. Cummings - NERC Director of System Analysis and Reliability Initiatives William Herbsleb - Chairman of Frequency Response Standard Drafting

Table 1 - Assignment of BA Obligations... 8

Reliability Guideline: Generating Unit Operations During Complete Loss of Communications

Project Balancing Authority Reliability-based Controls Reliability Standard BAL-005-1

Reliability Guideline: Generating Unit Operations During Complete Loss of Communications

Operationalizing Phasor Technology. Model Validation. Webinar. Ken Martin. March 4, Presented by. Page 0

Procedure for ERO Support of Frequency Response and Frequency Bias Setting Standard. Event Selection Process

Load Frequency and Voltage Control of Two Area Interconnected Power System using PID Controller. Kavita Goswami 1 and Lata Mishra 2

CHAPTER 1 INTRODUCTION

Available Transfer Capability (ATC) EE 521 Analysis of Power Systems Chen-Ching Liu Washington State University

Frequency Response Initiative Report

Standard Development Timeline

WSAT Online Tool for Assessment of Secure Level of Wind Generation on the System

ISO Rules Part 500 Facilities Division 502 Technical Requirements Section Aggregated Generating Facilities Technical Requirements

Using Synchrophasors for Frequency Response Analysis in the Western Interconnection. Bonneville Power Administration -- WECC JSIS Chair

generation greater than 75 MVA (gross aggregate nameplate rating) Generation in the ERCOT Interconnection with the following characteristics:

CHAPTER 4 LOAD FREQUENCY CONTROL OF INTERCONNECTED HYDRO-THERMAL SYSTEM

BAL Standard Project Frequency Response and Frequency Bias Setting Industry Webinar

CHARACTERISTIC NUMBERS OF PRIMARY CONTROL IN THE ISOLATED ESTONIAN POWER SYSTEM

each time the Frequency is above 51Hz. Continuous operation is required

METERING REQUIREMENTS FOR INTERCONNECTION POINTS OF SERVICE

Automatic Generation control of interconnected hydrothermal power plant Using classical and soft computing Technique

Load Frequency Control of Three Different Area Interconnected Power Station using Pi Controller

OPERATING, METERING AND EQUIPMENT PROTECTION REQUIREMENTS FOR PARALLEL OPERATION OF LARGE-SIZE GENERATING FACILITIES GREATER THAN 25,000 KILOWATTS

Testing model data usability Excitation Systems PSS Limiters

NPCC Regional Reliability Reference Directory # 12. Underfrequency Load Shedding Program Requirements

Reliability Guideline Integrating Reporting ACE with the NERC Reliability Standards

Northeast Power Coordinating Council, Inc. Glossary of Terms. Approved by the Reliability Standards Committee

Standard BAL Frequency Response and Frequency Bias Setting

ISO Rules Part 500 Facilities Division 502 Technical Requirements Section SCADA Technical and Operating Requirements

Use of Synchrophasors to Detect Control System and Circuit Breaker Reclosing Issues

Fuel cell power system connection. Dynamics and Control of Distributed Power Systems. DC storage. DC/DC boost converter (1)

A Novel Control Approach for Microgrids Islanded Operation - Load Step Pre-announcement and Bang-Bang Control

Alberta Reliability Standard Frequency Response and Frequency Bias Setting BAL-003-AB-1.1

TECHNICAL SPECIFICATIONS AND OPERATING PROTOCOLS AND PROCEDURES FOR INTERCONNECTION OF LARGE GENERATION FACILITIES. Document 9020

ISO Rules Part 500 Facilities Division 502 Technical Requirements Section SCADA Technical and Operating Requirements

Review of AGC Implementation Issues Before and After Deregulation

Transmission Interconnection Requirements for Inverter-Based Generation

MANITOBA HYDRO TRANSMISSION SYSTEM INTERCONNECTION REQUIREMENTS. April 2009 Version 2

Minutes Frequency Response Initiative Meeting

OPERATING, METERING, AND EQUIPMENT PROTECTION REQUIREMENTS FOR PARALLEL OPERATION OF LARGE-SIZE GENERATING FACILITIES GREATER THAN 2,000 KILOWATTS

Standard Development Timeline

Version 2.6 October Comments to this document can be forwarded to:

Governor with dynamics: Gg(s)= 1 Turbine with dynamics: Gt(s) = 1 Load and machine with dynamics: Gp(s) = 1

We can utilize the power flow control ability of a TCSC to assist the system in the following tasks:

A New Approach Applied to Adaptive Centralized Load Shedding Scheme

A Real-Time Regulator, Turbine and Alternator Test Bench for Ensuring Generators Under Test Contribute to Whole System Stability

Effect of Non-linearities in Fuzzy Based Load Frequency Control

Target Mchunu and Themba Khoza Eskom Transmission Division, System Operator Grid Code Management

AUTOMATIC GENERATION CONTROL OF INTERCONNECTED POWER SYSTEM WITH THE DIVERSE SOURCES USING SUPERCONDUCTING MAGNETIC ENERGY STORAGE (SMES)

Control of Load Frequency of Power System by PID Controller using PSO

ECE 422/522 Power System Operations & Planning/Power Systems Analysis II 5 - Reactive Power and Voltage Control

Automatic Generation Control of Three Area Power Systems Using Ann Controllers

Power System Operation and Control

Recently, the SS38 Working Group on Inter-Area Dynamic Analysis completed two study reports on behalf of the UFLS Regional Standard Drafting Team.

DP&L s Technical Requirements for Interconnection and Parallel Operation of Distributed Generation

Active Power Sharing and Frequency Control of Multiple Distributed Generators in A Microgrid

Load Frequency Control An ELC based approach

Automatic Generation Control of Two Area using Fuzzy Logic Controller

New Redundant Automatic Voltage Regulator (AVR) Solution

CAISO Restricted - Do Not Distribute Outside of RC Project LOI and NDA Entities Page 1 of 24

A Review of Adaptive Under Frequency Load Shedding Scheme on Islanded Distribution System Using MATLAB/SIMULINK

Wind Power Facility Technical Requirements CHANGE HISTORY

Load Frequency Control of Multi-Area Power Systems Using PI, PID, and Fuzzy Logic Controlling Techniques

GRID CONNECTION CODE FOR RENEWABLE POWER PLANTS (RPPs)

Modeling and Simulation of Load Frequency Control for Three Area Power System Using Proportional Integral Derivative (PID) Controller

GLOSSARY OF TERMS FOR PROCESS CONTROL

ATC s Mackinac Back-to-Back HVDC Project: Planning and Operation Considerations for Michigan s Eastern Upper and Northern Lower Peninsulas

Generator Advanced Concepts

The Effect of Fuzzy Logic Controller on Power System Stability; a Comparison between Fuzzy Logic Gain Scheduling PID and Conventional PID Controller

DEVELOPMENT OF SMART UNDERFREQUENCY LOAD SHEDDING SYSTEM

System Protection Schemes in Power Network based on New Principles

Microgrids and Energy Management SURYANARAYANA DOOLLA POWER ENGINEERING LAB DEPARTMENT OF ENERGY SCIENCE AND ENGINEERING INDIAN INSTITUTE OF

Transcription:

Lecture 15 EMS Application II Automatic Generation Contol Davood Babazadeh 2015-12-03

Outline Generation Control - Why - How AGC design - Area Control Error - Parameter Calculation 2

Course road map 3

Recall! SCADA / EMS (Energy Management System) 4

Introduction to Generation Control 5

Load & Generation Balance Match between Electric Load and Generation Frequency is an indication Balanced System, 50/60 Hz Net power surplus, frequency increases Generation Load Net power shortage, frequency decreases ΔP Δf 6

Frequency disturbances NERC technical report, 2011 7

Frequency Control Actions Generation Side Control Demand Side Control Primary Control Governor Δf Power System U pri Generator df dt f UFLS U Sec U UFLS ΔP tie AGC/LFC Secondary Control Δf U CT Operator Connection and Tripping of power Emergency Control 8

Primary Control / Frequency Response Generation is controlled by mechanical output of the prime mover The speed governor senses the change in speed (frequency) Paper # 9 9

Supplementary/Secondary Control Frequency deviation feedback PI or I controller Part of AGC Paper # 9 10

Frequency control time frame Balancing and frequency control occur over a continuum of time using different resources Frequency Response - Governor Regulation - AGC Imbalance / Reserves Emergency Control Time Error Correction NERC technical report, 2011 11

Time Operating Reserves (a), (b) (c) (d) (e) 12

Operating reserves Spinning Reserve - the on-line reserve capacity that is synchronized to the grid system and ready to meet electric demand within 10 minutes of a dispatch instruction by the System Operator. - to maintain system frequency stability during emergency operating conditions and unforeseen load swings. Non-Spinning Reserve - off-line generation capacity that can be ramped to capacity and synchronized to the grid within 10 minutes of a dispatch instruction by the System Operator - and that is capable of maintaining that output for at least two hours. Non-Spinning Reserve is needed to maintain system frequency stability during emergency conditions. 13

Automatic Generation Control 14

Generation Control System The Generation Control system contains real-time processes that regulate the generation of power in accordance with operational and economic constraints maintains system frequency and control area net interchange at their scheduled values. divided into the following sections: - Automatic Generation Control (AGC) - Economic Dispatch (ED) 15

Automatic Generation Control (AGC) The Automatic Generation Control (AGC) regulates the output of electric generating units in order to maintain the power system frequency and/or control area net interchange to their scheduled values. AGC can also regulate the power output of electric generating units to ensure compliance with the current system production schedule. 16

Economic Dispatch (ED) The Economic Dispatch (ED) function calculates the optimum basepoints for in-service economically dispatchable generating units The economically dispatchable generating units are controlled generating units that can be modeled as thermal units or hydro units. 17

Generation Control Functions Automatic Generation Control Economic Dispatch Regulates the generating unit MW outputs Generation Control Applications Provides economic basepoints and participation factors Optional Hydro Calculation function Reserve Monitoring Production Cost Calculation Calculates and monitors system reserves to meet reliability requirements Calculates fuel usage and production costs

Automatic Generation Control Interfaces Unit Economic Basepoints Unit Economic Participation Factors Economic Dispatch Net Scheduled Interchange Interchange Scheduling External Interface External ACE External Unit Data Island Data Estimated Unit & Line MW Automatic Generation Control State Estimator Setpoint/ Pulse Control Commands Unit Connection Status Unit Control Status Unit Output Unit Limits Unit Ramp Rates ACE Calculation Unit Control Mode Unit Basepoint Unit Ramp Schedules System frequency System Time Error Tie Line Flows ABB training course 19

AGC closed Loop Control Calculate the Area Control Error (ACE) Calculate the Desired MW output for each Generating Unit based on Unit Control Mode and Participation Factor Retrieve and Filter Telemetered: Frequency Time Error Generator Data Tie Line Flows Dynamic Schedules Initiate and Monitor Control Actions for each Generating Unit 20

AGC closed Loop Control Calculate the Area Control Error (ACE) Calculate the Desired MW output for each Generating Unit based on Unit Control Mode and Participation Factor Retrieve and Filter Telemetered: Frequency Time Error Generator Data Tie Line Flows Dynamic Schedules Initiate and Monitor Control Actions for each Generating Unit 21

AGC Control Area A coherent area consisting of a group of generators and loads, where all the generators respond to changes in load or speed changes settings, in unison. Frequency is assumed to be same in CA. 22

Area Control Error Demand and generation are constantly changing within all Control Areas. This means Balancing Authorities will usually have some unintentional outflow or inflow at any given instant. This mismatch is represented via a real-time value called Area Control Error (ACE), estimated in MW. 23

AGC Tie-Line A tie-line is a transmission line connecting two different Control Areas All tie-lines in a system must be specified Updated measurements of active power must be available for all tie-lines There may be more than one tie-line connecting two Control Areas Only net interchange is controlled, individual tie-lines are not controlled. 24

Interchange on tie lines Actual Net Interchange (NI A ) - the algebraic sum of tie line flows of a Control Area. NI A1 =I 12 +I 13 Scheduled Net Interchange (NI S ) - the net of all scheduled transactions with other Control areas. Usually, flow into a Control Area is defined as negative. Flow out is positive. 25

ACE Calculation Methods Flat Frequency Control - Calculated based on minus the frequency bias Flat Tie Line Control - Calculated based on the net interchange Tie Line Bias Control - calculated as the net interchange deviation minus the frequency bias 26

Flat Frequency Control ACE is calculated as minus the frequency bias. This term is the balancing authority s obligation to support frequency ACE = - 10B (f a - f s ) f a = Actual frequency (Hz) f s = Scheduled frequency (Hz) B = Balancing authority's frequency bias constant (MW/0.1Hz) 27

Flat Tie Line Control ACE is calculated as the net interchange deviation, that is, the deviation of actual net interchange from the scheduled net interchange. ACE = (NI A - NI S ) I ME NI A = Net Interchange, Actual NI S = Net Interchange, Scheduled I ME = Meter error correction 28

Tie Line Control ACE is calculated as the net interchange deviation, that is, the deviation of actual net interchange from the scheduled net interchange. ACE = (NI A - NI S ) - 10B (f a - f s ) - I ME f a = Actual frequency (Hz) f s = Scheduled frequency (Hz) NI A = Net Interchange, Actual NI S = Net Interchange, Scheduled I ME = Meter error correction 29

Meter error correction The meters that measure instantaneous flow are not always as accurate as the hourly meters on tie lines. check the error between the integrated instantaneous and the hourly meter readings. If there is a metering error, a value should be added to compensate for the estimated error. This value is I ME. This term should normally be very small or zero. 30

ACE example Assume a Balancing Authority with a Bias of -50 MW / 0.1 Hz is purchasing 300 MW. The actual flow into the Balancing Authority is 310 MW. Frequency is 60.01 Hz. Assume no time correction or metering error. Tie Line Control Mode 31

ACE example (Cont ) ACE = (NI A - NI S ) - 10B (f a - f s ) - I ME ACE = (-310 - - 300) 10* (-50) * (60.01 60.00) = (-10) (-5) = -5 MW. The Balancing Authority should be generating 5 MW more to meet its obligation to the Interconnection. Even though it may appear counterintuitive to increase generation when frequency is high, the reason is that this Balancing Area is more energy-deficient at this moment (- 10 MW) than its bias obligation to reduce frequency (-5 MW). 32

Calculated Frequency Bias Constant B D n i 1 1 R i D Area load bias contribution (Mw/01.Hz) due to the almost linear response of the system load to frequency deviation 1/R i frequency bias contribution (Mw/01.Hz) due to n online generating units 33

Load Bias Contribution linear response of the system load to frequency deviation B D n i 1 1 R i D = L damp x L n L damp area load damping factor (1/0.1Hz) L n area total load (MW) 34

Estimation of Speed Droop B D n i 1 1 R i Speed droop of the unit R i = f / P (Hz/MW) f 0 Speed droop design R i f max P 0 35

frequency (Hz) Governor Speed Regulation 52.5 50.0 47.5 0 25 50 75 100 load (MW) initial reset 36

AGC closed Loop Control Calculate the Area Control Error (ACE) Calculate the desired MW output for each Generating Unit based on Unit Control Mode and Participation Factor Retrieve and Filter Telemetered: Frequency Time Error Generator Data Tie Line Flows Dynamic Schedules Initiate and Monitor Control Actions for each Generating Unit 37

Participation Factor ACE is calculated. The contribution of each generator within a Control Area is determined by a participation factor. ACE i = (NI A - NI S ) - 10B (f a - f s ) - I ME P ACE i G k i k n k 1 i k i 1, 0 1 k 38

AGC closed Loop Control Calculate the Area Control Error (ACE) Calculate the desired MW output for each Generating Unit based on Unit Control Mode and Participation Factor Retrieve and Filter Telemetered: Frequency Time Error Generator Data Tie Line Flows Dynamic Schedules Initiate and Monitor Control Actions for each Generating Unit 39

Initiate and Monitor Control Actions Pulse Control - A pulse time corresponding to a MW change is sent out. - A pulse direction (increase/decrease) is also sent - The local control equipment handles the actual pulsing of the unit Set-point Control - An absolute MW value sent out - The local control equipment handles the actual change of unit generation The AGC monitors the unit response 40

AGC closed Loop Control Calculate the Area Control Error (ACE) Calculate the desired MW output for each Generating Unit based on Unit Control Mode and Participation Factor Retrieve and Filter Telemetered: Frequency Time Error Generator Data Tie Line Flows Dynamic Schedules Initiate and Monitor Control Actions for each Generating Unit 41

Telemetered Data Inputs Tie line MW flows Dynamic Schedules System frequency signals System time error Generating unit MW outputs Generating unit breaker or connectivity status Generating unit control status (Local/Remote) Generating unit high and low regulating limits Generating unit raise and lower ramp rates Generating unit MVAR measurement (for SYNC state) 42

Example of Application Outline Tie Line MW Flow Telemetered Data 43

AGC Dashboard Display Use the Dashboard Display to quickly achieve situational awareness of the system. Analog dials indicate Frequency, ACE, etc... Indicators highlight red to show cause of AGC Timeout / Suspend status. Compliance Levels (shown in percent) are also highlighted in color Bar charts indicate available reserves in relation to requirements. 44

AGC in Islanding Situation 45

AGC Operation with Multiple Islands The AGC is designed to work with one island or multiple islands. When islanding occurs or the number of islands changes: - The ACE Calculation Method for all islands is automatically changed to Flat Frequency Control. - The manual schedule status is automatically changed from Automatic to Manual, indicating that the Net Scheduled Interchange received is no longer used by AGC. - The Islanding Data Display is updated with the latest frequency, interchange, and ACE data for each island. - The operator can enter net interchange schedule overrides, change the frequency bias calculation, and change the ACE calculation method for each in-service island as desired. 46

Advanced topics! Control Architecture Centralized Distributed Control Strategies Fuzzy Control Multi-agent ANN Advanced Computations Tie-line loss compensation 47

Summary (AGC) Regulates System Frequency and Area Net Interchange to the Scheduled Values Calculates Area Control Error Calculates Desired MW output of the Generating Units placed under AGC control Performs Closed-Loop Control of the selected Generating Units Reduces excessive duty, unit maintenance and repair cost by monitoring unit response and applying operational constraints Performs Reserve Monitoring 48