Instruction Manual T5140 T5141 T5145 T5240 T5241 T5245. Programmable transmitter of CO2 concentration with 4-20 ma output. with 0-10 V output

Similar documents
Programmable transmitter of temperature, relative humidity and other derived humidity values with 0 to 10 V outputs Instruction Manual

Programmable transmitter of temperature, relative humidity and other derived humidity values with 4-20 ma outputs Instruction Manual

Programmable transmitter of temperature, relative humidity and other derived humidity values with 4-20 ma outputs Instruction Manual

Programmable transmitter of temperature, relative humidity and other derived humidity values with 4-20 ma outputs Instruction Manual

Programmable transmitter of temperature, relative humidity and other derived humidity values with 4-20 ma outputs Instruction Manual

Programmable transmitter of temperature, relative humidity and other derived humidity values with 4-20 ma outputs Instruction Manual

T5340, T5341, T5440, T5441 T6340, T6341, T6440, T6441

SELECTION TABLES OF TEMPERATURE,HUMIDITY, PRESSURE CO TRANSMITTERS Txxxx, Pxxxx

SELECTION TABLES OF TEMPERATURE,HUMIDITY, PRESSURE CO TRANSMITTERS Txxxx, Pxxxx

SELECTION TABLES OF TEMPERATURE,HUMIDITY, PRESSURE CO TRANSMITTERS Txxxx, Pxxxx

QPM Series Indoor Air Quality Duct Sensors

CD-Pxx-00-0 Series Duct Mount CO 2 Transmitter

SELECTION TABLES OF TEMPERATURE,HUMIDITY, PRESSURE CO TRANSMITTERS Txxxx, Pxxxx

DP2500 DP0100 DP0250 Differential Pressure Transmitter

Humidity Temperature Sensor TFG80 Duct version with Polyga measuring element

VENTI-LIGHT VLD. Ventilatie Indicator G e b r u i k e r s h a n d l e i d i n g. Ampèrestraat NL-1446 TR PURMEREND

RSMFX-2R MULTIFUNCTIONAL

USER'S GUIDE. Vaisala HUMICAP Humidity and Temperature Transmitters HMD70U/Y U303EN11

M1 Series. Humidity - Temperature Transmitter INSTRUCTION MANUAL

TxBlock-USB Transmitter

DP2500 DP0100 DP0250 Differential Pressure Transmitter

MTV-1-CP 230 VAC POTENTIOMETER WITH MIN & MAX SETTINGS, DRY CONTACT. Mounting and operating instructions

FST Series HUMIDITY-TEMPERATURE TRANSMITTERS INSTRUCTION MANUAL

P5201 Universal Programmable Transmitters with Galvanic Isolation

JUMO Wtrans E01. Measuring probe for humidity, temperature, and CO 2 with wireless data transmission. Brief description. Universal Wtrans receiver

Room air quality sensors

CDG. Carbon Dioxide - User Manual Gas Detector. 1 Intended Use. 2 Functional Description. 3 Installation. 4 Electrical Connection.

Temp. & humidity indicator

Transducer transmitter BILT 4 II 2(1) G. Technical Manual

Endress Hauser. SmarTec M CLD 133 Conductivity Measurement

ENGLISH S-CO2 AMBIENT AIR SENSOR INSTALLATION AND OPERATING INSTRUCTIONS CO 2. TF5701_B_v1_web

Roline L1 Series. Humidity - Temperature Transmitters INSTRUCTION MANUAL

TRANSDUCER of TEMPERATURE and STANDARD SIGNALS P20 type

USER S MANUAL. Rail-mounted temperature transmitter ATL

PLATINUM SENSORS FOR MEASURING TEMPERATURES UP TO 400 C 28.11a

TVA 080 / 100 / 120 / 180 / 200 / 220 Isolation amplifier active

ph or ORP Transmitter

INSTALLATION MANUAL. Model: Smart Analyzer Manufacturer: Smart Impulse. Power meter with consumption breakdown by use 03/12/13

TECHNICAL MANUAL. SERIES AP5202 DC Strain Gage In-Line Amplifier ISO 9001/AS9100

User Manual. PolyGard AT-2000 V3. Infrared Refrigerant Gas Transmitter Serial No. AT March, 2009

TIM-018 Mk2. London Electronics Limited. Triple output loop splitter. Connection details and general information

Type PLC Fitting. Valve for Continuous control. Diaphragm valve. Output

CD770 DIGITAL MULTIMETER INSTRUCTION MANUAL

VFSC9 ELECTRONIC SPEED CONTROLLER. Mounting and operating instructions

SEPARATOR P20G TYPE USER S MANUAL

Digital inductive conductivity transmitter

Operating manual GTL 241 GTL 251. Temperature probe. Please keep the manual for future use.

TLS-A. Laurel Electronics, Inc. Triple output loop splitter. Connection details and general information

STR-LCF. Security Advice Caution. Notes on Disposal. Electronic Fan Coil Thermostat (Flush mounting) Datasheet. Application

RAIL MOUNTED NETWORK METER TYPE N27D USER S MANUAL

MODEL AT-10 ANALOG TRANSMITTER

HD 48V01T... HD 4977T...

USER S MANUAL POWER SUPPLY - ISOLATOR - SIGNAL CONVERTER ZSP 41 POWER SUPPLY - ISOLATOR - SIGNAL CONVERTER SIGNAL MULTIPLIER ZSP 41/2

Type EXT with cable, probe sold

Electromotoric actuators for stroke valves

OPTITEMP TT 20 Technical Datasheet

THM80X Series Industry degree high accuracy Temp. & humidity transmitter

Instruction also available on

User Manual. tsense VAV Disp. CO 2 -, temperature- and relative humidity transmitter

RMO500 M I C R O O H M M E T E R

Worldwide Manufacturer of Gas Detection Solutions. Transmitter EC 23. Operation Manual

QFM21... Duct sensors. Symaro. for relative humidity and temperature

Output Signal Active Note. Output Signal Temperature 22UTH-51 DC V, DC V

1800 Series Attachable Loop-Powered Digital Indicators Operating Manual

OPUS20 Multiple Functions with Internal Sensors

Overview of types. Technical data

Output Signal Active Temperature. Electrical data Power Supply DC V, ±10%, 0.5 W

QAC910. Meteo Sensor. Synco living

DT1100 xx xx xx PS. Isolators, Isolator / Power Supplies. Operating Instructions

I P. /dt. di p V S Applications. Standards 1) IEC : 2007; IEC : ) IEC : 2016; IEC : 2017

GETTING STARTED GUIDE NI AI, ±60 V, 24 Bit, 1 ks/s/ch Simultaneous

I P. /dt. di p V S+ Applications. Standards. 1) IEC ed1.0: 2007; IEC : ed1.0: 2012

User Manual. PolyGard ADTD Infrared Carbon Dioxide Transmitter Serial No. SM03_00X. October, 2011

Bedienungsanleitung Instruction Manual. testo 815 Sound Level Meter

TS-9100 Electronic Sensors and Transducers. Features and Benefits. G Wide range of enclosures and signal outputs

High-precision portable RESISTANCE METER

34134A AC/DC DMM Current Probe. User s Guide. Publication number April 2009

B850 Boiler House Energy Monitor

Conductivity Transmitter

4000RHT DATA SHEET.

GE Sensing. Introduction. Wiring Diagrams (Typical) Field Calibration. Installing the Sensor

Ultrasonic level meters ULM 70

HUMITRAN-RHT & RH RELATIVE HUMIDITY/TEMPERATURE TRANSMITTER RELATIVE HUMIDITY TRANSMITTER

CALYS 50. Field multifunction calibrator for basic use

CALYS 150. Advanced documenting multifunction calibrator thermometer

Electrical data Nominal voltage AC 230 V Nominal voltage frequency

Sarspec, Lda. - Rua Camilo Castelo Branco, 965 PQ Vila Nova de Gaia Phone:

Type Overview. Technical Data. Outdoor Humidity, Temperature Sensor

WIRELESS BASE STATION WIRELESS CONFIGURATION TOOL WIRELESS REPEATER

PolyGard Digital Transmitter DGC DT-02

Installation & Operating Manual. iwap202

OPTITEMP TT 10 C/R Technical Datasheet

E8EB-N0C2B E8EB-N0B2B

Loop Powered Indicator

N24, N25 DIGITAL PANEL METER

Miniature resistance thermometer Model TR33, thread-mounted

User s Guide. Model MA A AC Mini Clamp-on Meter

Electrical data Nominal voltage AC/DC 24 V Nominal voltage frequency

AMM-1022 Digital Multimeter USER`S MANUAL

Product Features Benefits The IMC Group Ltd.

Transcription:

www.cometsystem.com Instruction Manual T5140 T5141 T5145 Programmable transmitter of CO2 concentration with 4-20 ma output T5240 T5241 T5245 Programmable transmitter of CO2 concentration with 0-10 V output

Copyright: COMET System, Ltd. It is prohibited to copy and make any changes in this manual, without explicit agreement of company COMET System, Ltd. All rights reserved. COMET System, Ltd. makes constant development and improvement of their products. Manufacturer reserves the right to make technical changes to the device without previous notice. Misprints reserved. Manufacturer is not responsible for damages caused by using the device in conflict with this manual. To damages caused by using the device in conflict with this manual can not be provide free repairs during the warranty period. Read carefully instruction manual before the first device connection. 2 IE-SNC-T51(2)XX-04

Table of contents GENERAL DESCRIPTION... 4 FACTORY SETTINGS... 5 DEVICE INSTALLATION... 6 MODIFICATION OF DEVICE ADJUSTMENT... 7 INFO MODE... 8 ERROR STATES OF THE DEVICE... 9 TECHNICAL SUPPORT AND SERVICE... 10 TECHNICAL DATA... 11 T5140 AMBIENT AIR CO2 TRANSMITTER... 11 T5240 AMBIENT AIR CO2 TRANSMITTER... 11 T5141 CO2 TRANSMITTER WITH EXTERNAL PROBE... 12 T5241 CO2 TRANSMITTER WITH EXTERNAL PROBE... 12 T5145 CO2 DUCT MOUNT TRANSMITTER... 13 T5245 CO2 DUCT MOUNT TRANSMITTER... 13 GENERAL... 14 OPERATION CONDITIONS... 15 END OF OPERATION... 15 DIMENSIONS... 16 TYPICAL APPLICATION WIRING... 21 OPTIONAL ACCESSORY... 23 IE-SNC-T51(2)XX-04 3

General description The transmitters are designed for measurement of carbon dioxide concentration of air without aggressive ingredients. T5140 T5240 T5141 T5241 T5145 T5245 ambient CO 2 transmitter with 4 20 ma output ambient CO 2 transmitter with 0 10 V output CO 2 transmitter with cable probe with 4 20 ma output CO 2 transmitter with cable probe with 0 10 V output duct mount CO 2 transmitter with 4 20 ma output duct mount CO 2 transmitter with 0 10 V output A multiple point CO2 and temperature adjustment procedure leads to excellent CO2 measurement accuracy over the entire temperature working range; this is a must for process control and outdoor applications. The dual wavelength NDIR CO2 sensing procedure compensates automatically for ageing effects. The CO2 module is highly resistant to pollution and offers maintenance free operation and outstanding long term stability. Measured values can be read in SLOW mode (filtered, averaged) or in FAST mode (current values without averaging). SLOW mode has advantages in applications like climate control because of filtering short time peaks. As an example exhaled air from an employee passing the sensor could affect the climate control negatively with a short response time because the control would trigger a change of the ventilation based on this one-time measurement. On the contrary in FAST mode no software filter is used for calculating the output value. This fact adds a noise of typ. ±30ppm which has to be considered in terms of accuracy. Of principle measurement is the measured value of CO 2 concentration depends on the value of air pressure - altitude at the installation site. For this reason, it is suitable for accurate measurement to set the altitude of the installation site by TSensor software (is available to download free www.cometsystem.com). Measured values are displayed on dual line LCD display. The visual indication of CO 2 concentration is provided by three-color LED. After power up of the device starts internal test. During this time (about 20s) LCD display shows (----) instead of CO 2 concentration value. For setting of all parameters of the transmitter serves the user program TSensor. Cable SP003 (optional accessory) use for connection the device to a personal computer. Device version TxxxxL with watertight male connector instead of a cable gland is designed for easy connection/disconnection of the output cable. Models marked TxxxxZ are non-standard versions of the transmitters. Description is not included in this manual. 4 IE-SNC-T51(2)XX-04

Factory settings If special setting was not required in the order, the device is set from the manufacturer to the following parameters: 4-20 ma output: corresponds 0 to 2000 ppm (T5140 a T5145) corresponds 0 to 10 000 ppm (T5141) 0-10 V output: corresponds 0 to 2000 ppm (T5240 a T5245) corresponds 0 to 10 000 ppm (T5241) measurement mode: display: LED indication: altitude: SLOW switched ON up to 1000 ppm lights green LED from 1000 ppm to 1200 ppm lights yellow LED over 1200 ppm lights red LED 300 m above sea level at the installation site Modification of the setting is possible to do by means of the PC and TSensor program. IE-SNC-T51(2)XX-04 5

Device installation The housing with electronics of the T5140 (T5240) or T5141 (T5241) transmitter is designed for wall mounting with two screws or bolts. The T5145 (T5245) transmitter install by inserting the metal stem into the Pg21 cable gland so that the measured air was fed into the head of device (see picture). To fasten the stem it is also possible to use the flange PP4 or PP90 (see Optional accessory ). The external CO 2 probe unpack and connect to the T5141 (T5241) device. Then place the probe into the measured environment. The connecting terminals are accessible after unscrewing the four screws in the corners of the case and removing the lid. Pass the connecting cable through released gland and connect the wires to terminals (see Typical application wiring ). By jumper J1 select galvanically or non-galvanically isolated output (T5140, T5141 and T5145). Tighten the gland and screw the lid (check the integrity of the seal). The female connector for connecting TxxxxL transmitter connect according to the diagram at Typical application wiring. For device connection it is recommended to use a shielded cable with external diameter 3.5 to 8 mm. Maximum cable length of the current loop is 1200 m, maximum voltage output cable length is 15 m. The cable must be located at indoor rooms and should not be led in parallel along power cabling. Safety distance is up to 0.5 m, otherwise undesirable induction of interference signals can appear. For TxxxxL devices connection it is recommended to use cable with respect to the female connector specification. Do not connect shielding at connector side Warning Installation, commissioning and maintenance may only be carried out by personnel with qualification by applicable regulations and standards. Don t connect transmitter while power supply voltage is on. 6 IE-SNC-T51(2)XX-04

Modification of device adjustment Device adjustment is performed by means of the optional SP003 communication cable, connected to USB port of the PC. It is necessary to have installed configuration program Tsensor on the PC (program is free to download at www.cometsystem.com). During installation please take care about installation of driver for USB communication. unscrew four screws of the device lid and remove the lid. If device is already installed to measuring system, disconnect wires from terminals connect SP003 communication cable to the PC. Installed USB driver detect connected cable and create virtual COM port inside the PC run installed Tsensor program and continue in accordance with his instructions when new setting is saved and finished, disconnect the cable from the device, connect wires into its terminals and place the lid back to the device IE-SNC-T51(2)XX-04 7

Info mode Several settings of installed transmitter are possible to verify without a use of the computer. It is necessary to connect power supply. Unscrew the transmitter lid and shortly press button (the right of the terminal) by means of a tool (e.g. screwdriver). Upper line of the LCD display shows value of CO 2 concentration corresponding to output current 4mA (output voltage 0V) T5140, T5145 T5240, T5245 T5141 T5241 Press button again to get value of CO2 concentration corresponding to output current 20mA (output voltage 10V). T5140, T5145 T5240, T5245 T5141 T5241 Press button again to end info mode and display actual measured values. Warning During info mode no measurement and no output current generation proceed. The transmitter stays at info mode 15 s, and then automatically goes back to measuring cycle. 8 IE-SNC-T51(2)XX-04

Error states of the device Device continuously checks its state during operation. In case error is found LCD displays corresponding error code: Error 0 - first line displays Err0 (output current value is < 3.8 ma). Check sum error of stored setting inside device s memory. This error appears if incorrect writing procedure to device s memory occurred or if damage of calibration data appeared. At this state device does not measure. It is a serious error, contact distributor of the device to fix. Error 2 - there is a reading Err2 on LCD display. The CO 2 concentration measurement error occurred. Error 3 - there is a reading Err3 on LCD display upper line. Error of internal A/D converter appeared (converter does not respond, probably damage of A/D converter). This error does not affect CO 2 concentration measurement. It is a serious error, contact distributor of the device. Error 4 - there is a reading Err4 on LCD display. It is internal device error during initialization of CO 2 sensor. Under this condition device does not measure concentration of CO 2. Value read from device is -9999. CO 2 sensor is probably damaged. It is a serious error, contact distributor of the device. IE-SNC-T51(2)XX-04 9

Technical support and service Technical and service is provided by distributor. For contact see warranty certificate. You can use discussion forum at web address www.forum.cometsystem.cz. 10 IE-SNC-T51(2)XX-04

Technical data T5140 ambient air CO2 transmitter Output: Power: Power consumption: Output in case of error: Concentration of CO 2: Accuracy: 4 to 20 ma 9 to 30 V 1 W during normal operation max. 4 W (for 50 ms with 15 s period) < 3.8 ma or > 24 ma ± (50 ppm + 2 % of measuring value) (at temperature 25 and pressure 1013 hpa) Range: 0 to 2 000 ppm Temp. dependence: typ. 2 ppm / C in the range -20 to 45 C Long term stability: Resolution: Response time: typ. 20 ppm / year 1 ppm t90 < 105 s in SLOW measurement mode t90 < 60 s in FAST measurement mode T5240 ambient air CO2 transmitter Output: Power: Power consumption: Output in case of error: Concentration of CO 2: Accuracy: 0 to 10 V 15 to 30 V 0.5 W during normal operation max. 3 W (for 50 ms with 15 s period) < -0.1 V or > 10.5 V ± (50 ppm + 2 % of measuring value) (at temperature 25 and pressure 1013 hpa) Range: 0 to 2 000 ppm Temp. dependence: typ. 2 ppm / C in the range -20 to 45 C Long term stability: Resolution: Response time: typ. 20 ppm / year 1 ppm t90 < 105 s in SLOW measurement mode t90 < 60 s in FAST measurement mode IE-SNC-T51(2)XX-04 11

T5141 CO2 transmitter with external probe Output: Power: Power consumption: Output in case of error: Concentration of CO 2: Accuracy: 4 to 20 ma 9 to 30 V 1 W during normal operation max. 4 W (for 50 ms with 15 s period) < 3.8 ma or > 24 ma ± (110 ppm + 5 % of measuring value) (at temperature 25 and pressure 1013 hpa) Range: 0 to 10 000 ppm Temp. dependence: ± (1 + CO2 koncentrace [ppm] / 1000) ppm / C (in the range -20 to 45 C) Long term stability: typ. 20 ppm / year Resolution: 1 ppm Response time: t90 < 105 s in SLOW measurement mode t90 < 60 s in FAST measurement mode T5241 CO2 transmitter with external probe Output: Power: Power consumption: Output in case of error: Concentration of CO 2: Accuracy: 0 to 10 V 15 to 30 V 0.5 W during normal operation max. 3 W (for 50 ms with 15 s period) < -0.1 V or > 10.5 V ± (110 ppm + 5 % of measuring value) (at temperature 25 and pressure 1013 hpa) Range: 0 to 10 000 ppm Temp. dependence: ± (1 + CO2 koncentrace [ppm] / 1000) ppm / C (in the range -20 to 45 C) Long term stability: typ. 20 ppm / year Resolution: 1 ppm Response time: t90 < 105 s in SLOW measurement mode t90 < 60 s in FAST measurement mode 12 IE-SNC-T51(2)XX-04

T5145 CO2 duct mount transmitter Output: Power: Power consumption: Output in case of error: Concentration of CO 2: Accuracy: 4 to 20 ma 9 to 30 V 1 W during normal operation max. 4 W (for 50 ms with 15 s period) < 3.8 ma or > 24 ma ± (50 ppm + 2 % of measuring value) (at temperature 25 and pressure 1013 hpa) Range: 0 to 2 000 ppm Temp. dependence: typ. 2 ppm / C in the range -20 to 45 C Long term stability: Resolution: Response time: typ. 20 ppm / year 1 ppm t90 < 105 s in SLOW measurement mode t90 < 60 s in FAST measurement mode T5245 CO2 duct mount transmitter Output: Power: Power consumption: Output in case of error: Concentration of CO 2: Accuracy: 0 to 10 V 15 to 30 V 0.5 W during normal operation max. 3 W (for 50 ms with 15 s period) < -0.1 V or > 10.5 V ± (50 ppm + 2 % of measuring value) (at temperature 25 and pressure 1013 hpa) 0 to 2 000 ppm Range: Temp. dependence: typ. 2 ppm / C in the range -20 to 45 C Long term stability: Resolution: Response time: rozsah: typ. 20 ppm / year 1 ppm t90 < 105 s in SLOW measurement mode 0 až 2 000 ppm IE-SNC-T51(2)XX-04 13

General Protection: IP30 T5140(L), T5240(L) IP65 (device with probe) T5141(L), T5241(L) IP20 T5145(L), T5245(L) Recommended interval of calibration: 5 year Working position: cable gland upwards T5140(L), T5240(L) any position T5141(L), T5241(L) any position *) T5145(L), T5245(L) *) The holes on the stem must be routed in the direction of the air flow, see chapter Device installation. Electromagnetic compatibility: EN 61326-1 Storage temperature range: -40 to +60 C Storage relative humidity range: 5 to +95 C Storage atmospheric pressure range: 700 to 1100 hpa Cable length of probe: 1 m, 2 m or 4 m T5141(L), T5241(L) Weight: approximately T5140(L), T5240(L) T5141(L), T5241(L) 1m probe T5141(L), T5241(L) 2m probe T5141(L), T5241(L) 4m probe T5145(L), T5245(L) Housing material: ABS 150 g 250 g 280 g 340 g 260 g 14 IE-SNC-T51(2)XX-04

Operation conditions Operating temperature range of housing with electronics: -30 to +60 C T5140(L), T5240(L), T5145(L), T5245(L) -30 to +80 C T5141(L), T5241(L) It is recommended to switch off the LCD display at ambient temperatures above 70 C. Operating temperature range of the measuring end of stem: -30 to +60 C T5145(L), T5245(L) Operating temperature range of CO 2 probe: -40 to +60 C T5141(L), T5241(L) Operating relative humidity range: 5 to 95 %RH T5140(L), T5240(L), T5145(L), T5245(L) 0 to 100 %RH (no condensation) T5141(L), T5241(L) Operating pressure range: 850 to 1100 hpa End of operation Dispose of the device according to statutory regulations. IE-SNC-T51(2)XX-04 15

Dimensions T5140 T5240 T5140L T5240L 16 IE-SNC-T51(2)XX-04

T5141 T5241 IE-SNC-T51(2)XX-04 17

T5141L T5241L 18 IE-SNC-T51(2)XX-04

T5145 T5245 IE-SNC-T51(2)XX-04 19

T5145L T5245L 20 IE-SNC-T51(2)XX-04

Typical application wiring Device with 4-20 ma output can be connected to circuitry by means of galvanically isolated or galvanically non-isolated current loop. Output 0-10 V is galvanically non-isolated. Galvanically isolated 4-20 ma output transmitter with cable gland transmitter TxxxxL Loop resistance value Rc = R + resistance of wires shall fulfill the condition Rc[Ω] < 40 x Uss2[V] 360. Galvanically non-isolated 4-20 ma output transmitter with cable gland transmitter TxxxxL Loop resistance value Rc = R + resistance of wires shall fulfill the condition Rc[Ω] < 40 x Uss1[V] 360. IE-SNC-T51(2)XX-04 21

Galvanically non isolated 0-10 V output transmitter with cable gland transmitter TxxxxL R > 20 kω The value of the internal resistance (Ri) of the measuring instrument must be greater than 20 kω. 22 IE-SNC-T51(2)XX-04

Optional accessory Mounting flange PP4 Mounting flange PP90 IE-SNC-T51(2)XX-04 23