Chapter # : 17 Symmetrical Fault Calculations

Similar documents
BE Semester- VI (Electrical Engineering) Question Bank (E 605 ELECTRICAL POWER SYSTEM - II) Y - Y transformer : 300 MVA, 33Y / 220Y kv, X = 15 %

Short Circuit Current Calculations

Cork Institute of Technology. Autumn 2008 Electrical Energy Systems (Time: 3 Hours)

3. (a) List out the advantages and disadvantages of HRC fuse (b) Explain fuse Characteristics in detail. [8+8]

3Ø Short-Circuit Calculations

Three Phase Transformers

Short-Circuit Current Calculations

CONTENTS. 1. Introduction Generating Stations 9 40

Topic 6 Quiz, February 2017 Impedance and Fault Current Calculations For Radial Systems TLC ONLY!!!!! DUE DATE FOR TLC- February 14, 2017

In Class Examples (ICE)

R10. III B.Tech. II Semester Supplementary Examinations, January POWER SYSTEM ANALYSIS (Electrical and Electronics Engineering) Time: 3 Hours

TABLE OF CONTENT

ELG 4125: ELECTRICAL POWER TRANSMISSION AND DISTRIBUTION: TUTORIAL 1: - BY:

Safety through proper system Grounding and Ground Fault Protection

Grounding System Theory and Practice

TRV OVERVIEW FOR REACTANCE LIMITED FAULTS

R10. IV B.Tech I Semester Regular/Supplementary Examinations, Nov/Dec SWITCH GEAR AND PROTECTION. (Electrical and Electronics Engineering)

Three-phase short-circuit current (Isc) calculation at any point within a LV installation using impedance method

Unit 3 Magnetism...21 Introduction The Natural Magnet Magnetic Polarities Magnetic Compass...21

ARC FLASH PPE GUIDELINES FOR INDUSTRIAL POWER SYSTEMS

Preface...x Chapter 1 Electrical Fundamentals

CHAPTER 2 ELECTRICAL POWER SYSTEM OVERCURRENTS

FERRORESONANCE SIMULATION STUDIES USING EMTP

SAMPLE EXAM PROBLEM PROTECTION (6 OF 80 PROBLEMS)

Busbars and lines are important elements

Lecturer: Dr. J B E AL-ATRASH No. of Pages: 4

A DUMMIES GUIDE TO GROUND FAULT PROTECTION

(2) New Standard IEEE P (3) Core : (4) Windings :

Earth Fault Protection

ABB Automation, Inc. Substation Automation & Protection Division Coral Springs, FL Allentown, PA

Short-Circuit Analysis IEC Standard Operation Technology, Inc. Workshop Notes: Short-Circuit IEC

2 Grounding of power supply system neutral

ETAP PowerStation. Electrical Transient Analyzer Program. ETAP PowerStation. Short Circuit Analysis. ANSI Standard 3-Phase Fault Currents

T e l N o : F a x N o : E m a i l : a i s h c m c - m e. c o m w w w. c m c - m e.

3-phase short-circuit current (Isc) at any point within a LV installation

Impact Assessment Generator Form

Electricity Ten Year Statement November Electricity Ten Year Statement November Appendix D

Transient Recovery Voltage (TRV) and Rate of Rise of Recovery Voltage (RRRV) of Line Circuit Breakers in Over Compensated Transmission Lines

EH27401 Communication and Control in Electric Power Systems Lecture 2. Lars Nordström

COURSE PLANNER SUBJECT: ELECTRICAL POWER SYSTEM II

MV network design & devices selection EXERCISE BOOK

PIONEER RESEARCH & DEVELOPMENT GROUP

EDS FAULT LEVELS

Chapter 1 Electrical Theory and Part C Series Parallel and Code Questions Multiwire Branch Circuits Unit 1 Electrician s Math

SCHEME OF COURSE WORK ( ) Electrical & Electronics Engineering. Electrical machines-i, II and power transmission engineering

PSV3St _ Phase-Sequence Voltage Protection Stage1 (PSV3St1) Stage2 (PSV3St2)

SHORT CIRCUIT ANALYSIS OF 220/132 KV SUBSTATION BY USING ETAP

Utility Interconnection and System Protection

POWER SYSTEMS QUALITY Topic 5: Principles for Controlling Harmonics

PROTECTION APPLICATION HANDBOOK

Short Circuit Current and Voltage Stability Analysis of a Realistic Generation System Using Fault Current Limiter and SVC

Notes 1: Introduction to Distribution Systems

Chapter 1. Applied Grounding and Bonding. Applied Grounding and Bonding 9/18/2011. Introduction. Introduction. Paul Dobrowsky Member NEC Panel 5

Rajasthan Technical University, Kota

148 Electric Machines

HARMONICS THE BASICS H A R M O N I C M I T I G A T I O N A N D D I S P L A C E M E N T P O W E R F A C T O R C O R R E C T I O N

Do Capacitor Switching Transients Still Cause Problems?

IMPLEMENTATION OF NETWORK RECONFIGURATION TECHNIQUE FOR LOSS MINIMIZATION ON A 11KV DISTRIBUTION SYSTEM OF MRS SHIMOGA-A CASE STUDY

Welding Transformer: Principle, Requirement and Types

Substation Design Volume VII

86 chapter 2 Transformers

POWER SYSTEM ANALYSIS TADP 641 SETTING EXAMPLE FOR OVERCURRENT RELAYS

A Case Study of Resonance in 11kV Network in the Presence of Series Current Limiting Reactors, VSDs and Power Factor Improvement Capacitors

Transmission Lines and Feeders Protection Pilot wire differential relays (Device 87L) Distance protection

AGN 005 Fault Currents and Short Circuit Decrement Curves

Ground Fault Isolation with Loads Fed from Separately Derived Grounded Sources

EH2741 Communication and Control in Electric Power Systems Lecture 2

Harmonics, its Mitigation & Result of Case study of Spinning Mill

thepower to protect the power to protect i-gard LITERATURE Low and medium voltage

How to maximize reliability using an alternative distribution system for critical loads

a) Determine the smallest, standard-sized circuit breaker that should be used to protect this branch circuit.

Power Factor & Harmonics

Harmonic control devices

Electrical Wiring: Commercial, Seventh Canadian Edition

2.10. Adjustable Frequency Drives. Clean Power Drives. Clean Power Drives

Department of Labor and Industry Electrical Licensing

Harmonic Filters for Power Conversion Equipment (Drives, rectifiers, etc) Effects of Harmonics IEEE Solutions

Power Quality Notes 2-2 (AK)

Transformer Protection

MV Network Operation Issues and Elimination of Phase Voltage Unbalance

EARTH FAULT PROTECTION VIS-A-VIS GENERATOR GROUNDING SYSTEM

Poly Canyon Cogeneration System

INTRODUCTION...xiii Author s Comments...xiii Exam Preparation...xiii Difficult Concepts...xiv Textbook Errors and Corrections...xv Internet...

SHARDA Make Harmonics Filter

The Importance of the Neutral-Grounding Resistor. Presented by: Jeff Glenney, P.Eng. and Don Selkirk, E.I.T.

REV NO EXPERIMENT NO 1 AIM: To perform open and short circuit tests on 1-phase transformer and to calculate efficiency. Apparatus required:

Protection of Electrical Networks. Christophe Prévé

Protection Basics Presented by John S. Levine, P.E. Levine Lectronics and Lectric, Inc GE Consumer & Industrial Multilin

Downloaded From JNTU World. B.Tech II Year II Semester (R09) Supplementary Examinations December/January 2014/2015 GENERATION OF ELECTRIC POWER

S&C Vista Underground Distribution Switchgear Outdoor Distribution

Power System Analysis Prof. A. K. Sinha Department of Electrical Engineering Indian institute of Technology, Kharagpur

ADDENDUM NO. 2 PROJECT: COURTLAND PUMP STATION CONTRACT: IFB NO COM.00030

This document covers common questions concerning the design of an effectively grounded system.

Connection Impact Assessment Application

Harmonic Planning Levels for Australian Distribution Systems

Downloaded From All JNTU World

2/15/2015. Current will always try to return to its source. In order for there to be current, there must be a complete circuit

Chapter G Sizing and protection of conductors

Back to the Basics Event Analysis Using Symmetrical Components

GENERATOR INTERCONNECTION APPLICATION Category 5 For All Projects with Aggregate Generator Output of More Than 2 MW

Transcription:

Chapter # : 17 Symmetrical Fault Calculations Introduction Most of the faults on the power system lead to a short-circuit condition. The short circuit current flows through the equipment, causing considerable damage to the equipment and interruption of service to the consumers. Therefore, the determination of short circuit currents under fault conditions is very important. The choice of apparatus and the design and arrangement of equipments in the power system depends upon short-circuit current considerations. 17.1 Symmetrical Faults on 3-Phase System The fault on the power system which gives rise to symmetrical fault currents (i.e. equal fault currents in the lines with 120 o displacement) is called a symmetrical fault. 11/28/2016 Power System/ Dr. Ramzi A. Abdul-Halem 1

The symmetrical fault occurs when all the three conductors of a 3-phase line are brought together simultaneously into a short circuit condition as shown in Fig. 17.1. Thus referring to Fig. 17.1, fault currents IR, IY and IB will be equal in magnitude with 120 o displacement among them. Because of balanced nature of fault, only one phase need be considered in calculations. The following points may be particularly noted : (i) The symmetrical fault rarely occurs in practice as majority of the faults are of unsymmetrical nature. (ii) The symmetrical fault is the most severe and imposes more heavy duty on the circuit breaker. 11/28/2016 Power System/ Dr. Ramzi A. Abdul-Halem 2

17.2 Limitation of Fault Current When a short circuit occurs at any point in a system, the short-circuit current is limited by the impedance of the system up to the point of fault. Thus referring to Fig. 17.2, if a fault occurs on the feeder at point F, then the short circuit current from the generating station will have a value limited by the impedance of generator and transformer and the impedance of the line between the generator and the point of fault. 11/28/2016 Power System/ Dr. Ramzi A. Abdul-Halem 3

17.3 Percentage Reactance The reactance of generators, transformers, reactors etc. is usually expressed in percentage reactance to permit rapid short circuit calculations. The percentage reactance of a circuit is defined as under : It is the percentage of the total phase-voltage dropped in the circuit when full-load current is flowing i.e., where %X = I X 100...(i) V I = full-load current V = phase voltage X = reactance in ohms per phase Alternatively, percentage reactance (%X) can also be expressed in terms of kva and kv as under : %X = kva X 10 kv 2 where X is the reactance in ohms....(ii) 11/28/2016 Power System/ Dr. Ramzi A. Abdul-Halem 4

If X is the only reactance element in the circuit, then short-circuit current is given by ; I SC = V X = I 100 [By putting the value of X from exp. (i)] % X i.e. short circuit current is obtained by multiplying the full-load current by 100 % X For instance, if the percentage reactance of an element is 20% and the fullload current is 50 A, then short-circuit current will be 50 100/20 = 250 A when only that element is in the circuit. 17.4 Percentage Reactance and Base kva It is clear from exp. (ii) above that percentage reactance of an equipment depends upon its kva rating. 11/28/2016 Power System/ Dr. Ramzi A. Abdul-Halem 5

Generally, the various equipments used in the power system have different kva ratings. Therefore, it is necessary to find the percentage reactances of all the elements on a common kva rating. This common kva rating is known as base kva. The value of this base kva is quite unimportant and may be : (i) equal to that of the largest plant (ii) equal to the total plant capacity (iii) any arbitrary value The conversion can be effected by using the following relation : Base kva % age reactance at base kva = % age reactance at rated kva Rated kva Thus, a 1000 kva transformer with 5% reactance will have a reactance of 10% at 2000 kva base. 11/28/2016 Power System/ Dr. Ramzi A. Abdul-Halem 6

Illustration. The fact that the value of base kva does not affect the short circuit current needs illustration. Consider a 3-phase transmission line operating at 66 kv and connected through a 1000 kva transformer with 5% reactance to a generating station bus-bar. The generator is of 2500 kva with 10% reactance. The single line diagram of the system is shown in Fig. 17.3. Suppose a short-circuit fault between three phases occurs at the high voltage terminals of transformer. It will be shown that whatever value of base kva we may choose, the value of short-circuit current will be the same. 11/28/2016 Power System/ Dr. Ramzi A. Abdul-Halem 7

11/28/2016 Power System/ Dr. Ramzi A. Abdul-Halem 8

17.5 Short-Circuit kva Even if the potential at the point of fault is zero, it is a normal practice to express the short-circuit current in terms of short-circuit kva based on the normal system voltage at the point of fault. The product of normal system voltage and short-circuit current at the point of fault expressed in kva is known as short-circuit kva. Let Since, V = normal phase voltage in volts I = full-load current in amperes at base kva %X = percentage reactance of the system on base kva up to the fault point 11/28/2016 Power System/ Dr. Ramzi A. Abdul-Halem 9

17.6 Reactor Control of Short-Circuit Currents In order to limit the short-circuit currents to a value which the circuit breakers can handle, additional reactances known as reactors are connected in series with the system at suitable points. 17.7 Location of Reactors Short circuit current limiting reactors may be connected (i) in series with each generator (ii) in series with each feeder and (iii) in bus-bars. (1) Generator reactors. When the reactors are connected in series with each generator, they are known as generator reactors (see Fig. 17.4). 11/28/2016 Power System/ Dr. Ramzi A. Abdul-Halem 10

(2) Feeder reactors. When the reactors are connected in series with each feeder, they are known as feeder reactors (see Fig. 17.5). (3) Bus-bar reactors. The above two methods of locating reactors suffer from the disadvantage that there is considerable voltage drop and power loss in the reactors even during normal operation. This disadvantage can be overcome by locating the reactors in the bus-bars. There are two methods for this purpose, namely ; Ring system and Tie-Bar system. 11/28/2016 Power System/ Dr. Ramzi A. Abdul-Halem 11

(i) Ring system. In this system, bus-bar is divided into sections and these sections are connected through reactors as shown in Fig. 17.6. (ii) Tie-Bar system. Fig. 17.7 shows the tie-bar system. 11/28/2016 Power System/ Dr. Ramzi A. Abdul-Halem 12

17.8 Steps for Symmetrical Fault Calculations Three-phase short-circuit faults result in symmetrical fault currents. Therefore, one phase base solution can be consider. The procedure for the solution involves the following steps : (i) Draw a single line diagram of the complete network indicating the rating, voltage and percentage reactance of each element of the network. (ii) Choose a numerically convenient value of base kva and convert all percentage reactances to this base value. (iii) Corresponding to the single line diagram of the network, draw the reactance diagram showing one phase of the system and the neutral. Indicate the % reactances on the base kva in the reactance diagram. The transformer in the system should be represented by a reactance in series. 11/28/2016 Power System/ Dr. Ramzi A. Abdul-Halem 13

(iv) Find the total % reactance of the network up to the point of fault. Let it be X%. (v) Find the full-load current corresponding to the selected base kva and the normal system voltage at the fault point. Let it be I. (vi) Then various short-circuit calculations are : Short-circuit current, ISC = I 100 %X Short-circuit kva = Base kva 100 %X 11/28/2016 Power System/ Dr. Ramzi A. Abdul-Halem 14

11/28/2016 Power System/ Dr. Ramzi A. Abdul-Halem 15

11/28/2016 Power System/ Dr. Ramzi A. Abdul-Halem 16

11/28/2016 Power System/ Dr. Ramzi A. Abdul-Halem 17

11/28/2016 Power System/ Dr. Ramzi A. Abdul-Halem 18

11/28/2016 Power System/ Dr. Ramzi A. Abdul-Halem 19

11/28/2016 Power System/ Dr. Ramzi A. Abdul-Halem 20

PB1 Tutorial Problems PB2 11/28/2016 Power System/ Dr. Ramzi A. Abdul-Halem 21