The Influence of Voltage Flicker for the Wind Generator upon Distribution System

Similar documents
Impact of Distributed Generation on Voltage Regulation by ULTC Transformer using Various Existing Methods

The Impact of Connecting Distributed Generation to the Distribution System E. V. Mgaya, Z. Müller

Discussion on the Deterministic Approaches for Evaluating the Voltage Deviation due to Distributed Generation

Course ELEC Introduction to electric power and energy systems. Additional exercises with answers December reactive power compensation

Harmonics Issues that Limit Solar Photovoltaic Generation on Distribution Circuits

Connection Impact Assessment Application

Improvement of Power System Distribution Quality Due to Using Dc-Converter Loads and Electric Arc Furnaces. H.A. Khalik, M. A. Aziz, and E. Farouk.

Islanding Detection Method Based On Impedance Measurement

Embedded Generation Connection Application Form

ADVANCED CONTROLS FOR MITIGATION OF FLICKER USING DOUBLY-FED ASYNCHRONOUS WIND TURBINE-GENERATORS

POWER QUALITY SPECIFICATIONS AND GUIDELINES FOR CUSTOMERS ENGINEERING STANDARDS CITY OF LETHBRIDGE ELECTRIC

[Mahagaonkar*, 4.(8): August, 2015] ISSN: (I2OR), Publication Impact Factor: 3.785

LARGE-SCALE WIND POWER INTEGRATION, VOLTAGE STABILITY LIMITS AND MODAL ANALYSIS

POWER CORPORATION. Power Quality. Specifications and Guidelines for Customers. Phone: Fax:

A Power Quality Survey on a 22 kv Electrical Distribution System of a Technical Institution as per Standards

Embedded Generation Connection Application Form

Discussion on the Existing Deterministic Approaches for Evaluating the Voltage Deviation due to Distributed Generation

Embedded Generation Connection Application Form

Study of Centralized Anti-Islanding Method on Large-Scale Photovoltaic Power Plants

HV AC TESTING OF SUPER-LONG CABLES

WIND FARM Flexible AC Transmission Systems

Power Quality Requirements for Connection to the Transmission System

Harmonic Distortion Evaluations

Adaptive Relaying of Radial Distribution system with Distributed Generation

Thyristorised Automatic Power Factor

Connection Impact Assessment Application Form

, ,54 A

IDAHO PURPA GENERATOR INTERCONNECTION REQUEST (Application Form)

Study on Reactive Automatic Compensation System Design

IEEE sion/1547revision_index.html

GENERATOR INTERCONNECTION APPLICATION Category 5 For All Projects with Aggregate Generator Output of More Than 2 MW

METHOD TO DETERMINE CONTRIBUTION OF THE CUSTOMER AND THE POWER SYSTEM TO THE HARMONIC DISTURBANCE

HVDC CAPACITOR COMMUTATED CONVERTERS IN WEAK NETWORKS GUNNAR PERSSON, VICTOR F LESCALE, ALF PERSSON ABB AB, HVDC SWEDEN

2012 Grid of the Future Symposium. Impacts of the Decentralized Photovoltaic Energy Resources on the Grid

IEEE 1547: Standard for Interconnection and Interoperability of Distributed Energy Resources with Associated Electric Power Systems Interfaces

Impact Assessment Generator Form

COMPARATIVE PERFORMANCE OF WIND ENERGY CONVERSION SYSTEM (WECS) WITH PI CONTROLLER USING HEURISTIC OPTIMIZATION ALGORITHMS

Anti-Islanding Protection of Distributed Generation Resources Using Negative Sequence Component of Voltage

Lab 1. Objectives. Single Line Diagram. Methodology. Observations. Jon Jawnsy Yu 26 October 2009

QUESTIONNAIRE for Wind Farm Power Stations only

Hybrid Anti-Islanding Algorithm for Utility Interconnection of Distributed Generation

POWER QUALITY REPORT

MODELING THE EFFECTIVENESS OF POWER ELECTRONICS BASED VOLTAGE REGULATORS ON DISTRIBUTION VOLTAGE DISTURBANCES

Power Conditioning Equipment for Improvement of Power Quality in Distribution Systems M. Weinhold R. Zurowski T. Mangold L. Voss

Enhancement of Voltage Stability & reactive Power Control of Distribution System Using Facts Devices

Voltage Sag and Swell Mitigation Using Dynamic Voltage Restore (DVR)

UProtection Requirements. Ufor a Large scale Wind Park. Shyam Musunuri Siemens Energy

Improvement of Islanding Detector Using Interharmonics Current Injection Method and Its Applications

Numbering System for Protective Devices, Control and Indication Devices for Power Systems

Static Synchronous Compensator (STATCOM) for the improvement of the Electrical System performance with Non Linear load 1

RESEARCH ON CLASSIFICATION OF VOLTAGE SAG SOURCES BASED ON RECORDED EVENTS

Intermittent Renewable Resources (Wind and PV) Distribution Connection Code (DCC) At Medium Voltage (MV)

Power Quality enhancement of a distribution line with DSTATCOM

Form B. Connection Impact Assessment Application Form Distribution System

Influence of Wind Generators in Voltage Dips

POWER QUALITY IMPACTS AND MITIGATION OF DISTRIBUTED SOLAR POWER

HVDC Solutions for Integration of the Renewable Energy Resources

Long lasting transients in power filter circuits

Doãn Văn Đông, College of technology _ Danang University. 2. Local Techniques a. Passive Techniques

ABB DRIVES Technical guide No. 6 Guide to harmonics with AC drives

Emission Limits for Customer Facilities Connected to the Hydro-Québec Transmission System

Compensation of Reactive Power Case Study

ISLANDING DETECTION FOR DISTRIBUTED GENERATION SYSTEM USING VARIOUS METHODS

International Journal of Engineering Research and General Science Volume 5, Issue 2, March-April, 2017 ISSN

MODELING AND SIMULATION OF UNIFIED POWER QUALITY CONDITIONER FOR POWER QUALITY IMPROVEMENT

Level 6 Graduate Diploma in Engineering Electrical Energy Systems

On the Evaluation of Power Quality Indices in Distribution Systems with Dispersed Generation

Project acronym: Multi-island

Investigation of D-Statcom Operation in Electric Distribution System

Study of Effectiveness of Under-excitation Limiter in Dynamic Modeling of Diesel Generators

SYNCHRONOUS MACHINES

THE HISTORY OF FLICKER LIMITS

FUZZY CONTROLLED DSTATCOM FOR HARMONIC COMPENSATION

ECE 528 Understanding Power Quality

Analysis and modeling of thyristor controlled series capacitor for the reduction of voltage sag Manisha Chadar

Improvement of Power Quality using Unified Power Quality Conditioner with Distributed Generation

A STUDY CASE ON HARMONIC DISTORTION CREATED BY WIND TURBINES

Modelling Parameters. Affect on DER Impact Study Results

Islanding and Detection of Distributed Generation Islanding using Negative Sequence Component of Current

A Fuel Cell Fed Single Stage Boost Inverter with Unique Impedance Network

Grid codes and wind farm interconnections CNY Engineering Expo. Syracuse, NY November 13, 2017

Sizing Generators for Leading Power Factor

Technical Report. Zero Reactive Power Passive Current Harmonic Filter (ZRPPCHF) (In House Case Study) Prepared by. Dr. V. R. Kanetkar.

HARMONICS ANALYSIS USING SEQUENTIAL-TIME SIMULATION FOR ADDRESSING SMART GRID CHALLENGES

Comparative performance of wind energy conversion system (WECS) with PI controller using heuristic optimisation algorithms

Laboratory no. 3 FLUORESCENT LAMPS FITTINGS

Active Power Sharing and Frequency Control of Multiple Distributed Generators in A Microgrid

Renewable Interconnection Standard & Experimental Tests. Yahia Baghzouz UNLV Las Vegas, NV, USA

Available online at ScienceDirect. Procedia Technology 21 (2015 ) SMART GRID Technologies, August 6-8, 2015

Power transformers. Shunt reactors Proven history for future success

ISO Rules Part 500 Facilities Division 502 Technical Requirements Section Aggregated Generating Facilities Technical Requirements

INTERIM ARRANGEMENTS FOR GRID TIED DISTRIBUTED ENERGY RESOURCES. Technical Requirements for Grid-Tied DERs

Optimal Reactive Power Dispatch Considering Power Loss of Transformer

Company Directive STANDARD TECHNIQUE: SD7F/2. Determination of Short Circuit Duty for Switchgear on the WPD Distribution System

Power Quality Evaluation of Electrical Distribution Networks

VOLTAGE CRITERIA IN STEEL MILL NETWORKS

POWER FACTOR CORRECTION. HARMONIC FILTERING. MEDIUM AND HIGH VOLTAGE SOLUTIONS.

NORTH CAROLINA INTERCONNECTION REQUEST. Utility: Designated Contact Person: Address: Telephone Number: Address:

A New Approach for Transformer Bushing Monitoring. Emilio Morales Technical Application Specialist Qualitrol

ELEKTROTEHNI KO PODJETJE Leskoπkova cesta 12, 1000 Ljubljana, SLOVENIA

Transcription:

The Influence of Voltage Flicker for the Wind Generator upon Distribution System Jin-Lung Guan, Jyh-Cherng Gu, Ming-Ta Yang, Hsin-Hung Chang, Chun-Wei Huang, and Shao-Yu Huang Digital Open Science Index, Electrical and Computer Engineering waset.org/publication/168 Abstract One of the most important power quality issues is voltage flicker. Nowadays this issue also impacts the power system all over the world. The fact of the matter is that the more and the larger capacity of wind generator has been installed. Under unstable wind power situation, the variation of output current and voltage have caused trouble to voltage flicker. Hence, the major purpose of this study is to analyze the impact of wind generator on voltage flicker of power system. First of all, digital simulation and analysis are carried out based on wind generator operating under various system short circuit capacity, impedance angle, loading, and power factor of load. The simulation results have been confirmed by field measurements. S Keywords Wind Generator, Voltage Flicker, V Value. I. INTRODUCTION INCE the Industrial Revolution in the 18th century, humans have replaced traditional manpower production with machine production, and the demand for various energy sources has increased greatly. As populations increase and the economies develop, global oil reserves will be exhausted in about 50 years at the present consumption rate, and natural gas may be available for about 70 more years. Coal will last longer; however, it can only be used for about 200 more years. Therefore, besides increasing the service efficiency of energy, looking for new renewable energy sources has become an urgent topic. Renewable energy can make up for the insufficiency of energy, as well as slow down environmental pollution. Power generation modes include wind power, water power, solar energy, geothermal heat, methane, tidal and biomass energy. Among these, wind power generation has become technically mature; therefore, wind power generation is the most promising renewable energy source presently being developed. Taiwan is an island with a monsoon period that lasts more than half of each year. The annual average wind speed in many coastal, mountainous and off-island areas is higher than 4m per second; therefore, the wind energy potential is outstanding. According to investigation, the total area of the regions in Taiwan where the annual average wind speed is higher than 4m per second is about 2,000 square kilometers, and the exploitable wind energy potential is estimated at about 3,000 MW. J. L. Guan and H. H. Chang are with the Department of Electrical Engineering, Hwa Hsia Institute of Technology, Taipei, Taiwan, R.O.C. (e-mail: gjl4127@cc.hwh.edu.tw) J. C. Gu, C. W. Huang, and S. Y. Huang are with the National Taiwan University of Science and Technology, Taipei, Taiwan, R.O.C. (e-mail: jcgu@ mouse.ee.ntust.edu. tw) M. T. Yang is with the St. John s University of Science and Technology, Taipei, Taiwan, R.O.C. (e-mail: mtyang@mail.sju.edu.tw) Therefore, the mid-west seashore and off-island regions in Taiwan are suitable for wind power generation. The main reason for voltage flicker is the fast changing load in the power system. However, as the quantity and installed capacity of wind generators increases, the output voltage and output current of wind generators may vary with the wind speed, and the variations in the output voltage may cause voltage flicker. Voltage flicker will affect the luminance of daylight lamps and filament lamps, causing eye discomfort. Long-term continuous flickering will tire the eyes, therefore [1], [2] the most important concern about voltage flicker is its influence on vision. In addition, video size also varies with voltage flicker, and as television screens have white points or white lines, different sophisticated electronics may be influenced by different degrees [3]. In order to know the effect of wind generators on voltage flicker, IEC61400-21 [4] and IEEE 1547 [5] show detailed specifications and restrictions. Taiwan does not have complete specifications for voltage flicker; however, the "Rule of Indoor Wiring Installation" has related regulations. Article 431 specifies that "the voltage flicker value V of sudden changing loads such as arc furnaces at common points shall not exceed 0.45%". The effect of voltage flicker resulting from unstable wind speed becomes severe as the quantity and installed capacity of wind generators increases. In addition, according to actual measurements, the amount voltage flicker varies with the short-circuit capacity, system impedance angle and the quantity of the wind generators. Therefore, this paper studied the influence of wind generators on voltage flicker in the power system, using actual measurements and simulations to discuss the relation of contact capacity, system impedance angle, capacity, and load power factors to voltage flicker when the generators run at different wind speeds. II. ANALYSIS OF THE MEASURED DATA OF WIND FIELD VOLTAGE FLICKER Two commercialized s in Taiwan, represented as A and B were measured. The wind generating set of field A consisted of six generators with a rated capacity of 660 kw, connected to the power grid through a dedicated line. The wind-generating set of field B consisted of two generators with a rated capacity of 1.75 MW for in-plant power supply. The measurement duration was seven days, and the measuring points included the high and low voltage sides of the generators, the point of common coupling (PCC) and the secondary side of the main transformer. The basic data and 989

Digital Open Science Index, Electrical and Computer Engineering waset.org/publication/168 system one-line diagrams of the s are shown in Table I, Figs. 1 and 2. TABLE I THE BASIC DATA OF THE WIND FIELDS Name of Measurement Voltage level Wind generating set duration Field A 11.4kV induction generators 8/24 ~ 8/30 Field B 11.4kV two double-fed induction generators 8/31 ~ 9/7 Fig. 1 One-line diagrams of the A Fig. 2 One-line diagrams of the B As for the selection of measured data, as wind power resources are unstable, this paper selected the data from running generators for analysis. The analysis time is shown in Table II. Although the electrical characteristics of wind generators have no normal distribution mode, consistent and good results can be obtained from statistical induction and an analysis of numerous numerical values, therefore, the 5% inverse cumulative probability value of statistics (i.e. 95% cumulative probability value) of the measured active power (P), reactive power (Q) and voltage flicker ( V ) data (three-phase) of the wind generators was used as the representative value. Considering the probability of noise interference in the measurement, the 97.5% cumulative probability value was defined as the maximum value, and the 2.5% cumulative probability value was the minimum value. Measuring point Field A Field B TABLE II THE ANALYSIS TIME OF THE WIND FIELDS Time Average active power of Sampling time interval a 8/26 00:~01:20 296 kw b 8/28 18:25~22:25 193 kw a 8/31 17:30~20:20 3330 kw b 9/4 :00~18:00 985 kw The average output power for the (a) 296 kw and (b) 193 kw time intervals of A were analyzed, as shown below: In time interval (a), the active power on the low voltage side of generator No. 1 was 46.96~241.88 kw, the reactive power range was 7.41~21.77 kvar, the V range was 0.065~0.123 %, and the representative value was 0.119%. The active power range on the high voltage side of generator No. 1 was 34.88~231.64 kw, the reactive power range was 9.41~26.05 kvar, the V range was 0.04~ 0.051% and the representative value was 0.049%. The active power range of the PCC was 6.16~478.19 kw, the reactive power range was 25.71~56.15 kvar, the V range was 0.048~ 0.059% and the representative value was 0.058%. The active power range on the secondary side of the main transformer was 5950.14~6414.65 kw, the reactive power range was 270.16~444.06 kvar; the V range was 0.024~ 0.035%, and the representative value was 0.033%. In time interval (b), the active power range on the high voltage side of generator No. 1 was -16.07~188.15 kw, the reactive power range was 8~26.2 kvar, the V range was 0.04~ 0.055% and the representative value was 0.051%. The active power range of the PCC was -37~518.2 kw, the reactive power range was 7.9~67.53 kvar, the V range was 0.052~ 0.067% and the representative value was 0.064%. The active power range on the secondary side of the main transformer was 7724~9217 kw, the reactive power range was 31~1813 kvar, the V range was 0.025~0.042%, and the representative value was 0.036%. The average output power for the (a) 3330 kw and (b) 985 kw time intervals of B were analyzed, as shown below: In time interval (a), the active power range of the PCC was 2466.61~3576.19 kw, the reactive power range was 135.03~267.52 kvar, the V range was 0.06~ 0.139% and the representative value was 0.4%. In time interval (b), the active power range of the PCC was 280.38~2074.78 kw, the reactive power range was 6.19~96.41 kvar, the V range was 0.054~ 0.162% and the representative value was 0.117%. According to the V measurement results of the PCC in various s shown in Table III, the generators were not found to significantly influence voltage flicker in the system, conforming to the control value of 0.45% stated by Taiwan Power. According to the V measurement results of various points in A, when the measuring point was close to the secondary side of the main transformer, the voltage flicker was not severe for the large short-circuit capacity and system 990

Digital Open Science Index, Electrical and Computer Engineering waset.org/publication/168 impedance angle; when the measuring point was far from the secondary side of main transformer, the voltage flicker was severe for the small short-circuit capacity and system impedance angle. In addition, according to the measured data of the high voltage side of generator No. 1 and the PCC, the effect on voltage flicker varied with the quantity of connected generators. Name of Field A Field B TABLE III THE MEASUREMENT RESULTS OF VARIOUS WIND FIELDS Average active power of (kw) 296 193 Measuring point P (kw) Q (kvar) V (%) the low voltage side of generator No. 1 236.14 21.11 0.119 the high voltage side of generator No. 1 223.49 25.08 0.049 PCC 459.16 54.95 0.058 the secondary side of the main transformer 6381.4-430.5 0.033 the high voltage side of generator No. 1 165.4 23.67 0.051 PCC 462.50 61 0.064 the secondary side of the main transformer 9186 1772 0.037 3330 3560.4 265.34 0.4 PCC 985 1907.1 82.94 0.117 Generally, the reactive power fluctuation ( Q ) is used for evaluating voltage flicker. As shown in Table IV, the active power fluctuation ( P ) is usually greater than Q when the generator is in operation, therefore, it is necessary to use effective power changing P to evaluate the voltage flicker V ) of the generator. ( Name of Field A Field B TABLE IV THE POWER FLUCTUATION OF VARIOUS WIND FIELDS Average active power of wind field (kw) 296 Measuring point the high voltage side of generator No. 1 P (kw) Q (kvar) V (%) 196.76 16.64 0.049 PCC 372.03 30.44 0.058 the high voltage 193 side of 204.2 18.2 0.0513 generator No. 1 PCC 555.3 59.4 0.064 3330 19.58` 132.49 0.4 PCC 985 1794.38 90.22 0.117 III. SIMULATION ANALYSIS OF VOLTAGE FLICKER OF GENERATORS IN OPERATION Fig. 1 shows the system one-line diagram of A. The primary side short-circuit capacity of the system was 550.58 MVA, the rated capacity of the main transformer was 25 MVA, the rated voltage was 69 kv-11.4 kv, and the percentage impedance value was 8.9%. The dedicated line was a 25 kv 600A XLPE CU 500 MCM cable, the line impedance value was 0.0901+j0.1325 Ω/km, the line load was the average line load for August of every year, and the load power factor was 0.9, as shown in Table V. Generally, Taiwan Power installs a power capacitor in the lines to improve the power factor; for A, the line capacitance was 1800 kvar. TABLE V THE LOAD LINES OF WIND FIELD A Load line active power(kw) reactive power(kvar) power factor(%) (1) 2254 90 90 (2) 119 57 90 (3) 2704 1309 90 (4) 2189 60 90 This paper used Matlab s built-in induction wind generator and double-fed induction wind generator models to simulate the generator. In Matlab, one traditional induction generator with a rated capacity of 2.75 MVA and two double-fed induction wind generators with a rated capacity of 1.5MW were used. The voltage was boosted by the 480V/11.4 kv and 575V/11.4 kv step-up transformers inside the generator, which were connected to the secondary side bus of the main transformer in parallel through a dedicated line. The length of the dedicated line was about 2.7 km. As a traditional induction generator exports effective power to the power grid in parallel operation while consuming the virtual work of the system, the system voltage is disturbed. Therefore, a capacitor is usually installed inside the generator for compensation, with an installed capacity of 750 kvar. The control modes of a double-fed induction wind generator include voltage control and virtual work control modes. The voltage flicker resulting from generator operation varies under different control modes. Therefore, for the two double-fed induction wind generators one set was in the voltage control mode and the other set was in the virtual work mode for analysis in the simulation. The V f was set as 1pu for voltage control, and the virtual work was set as zero for the reactive power control. The system simulation blocks are shown in Figs. 3 and 4. Fig. 3 The system simulation blocks of A 991

Fig. 6 The voltage flicker curve of the induction wind generator under different average wind speed variance ratios Digital Open Science Index, Electrical and Computer Engineering waset.org/publication/168 Fig. 4 The system simulation blocks of A The voltage flicker resulting from generator operation varies at different wind speeds, therefore, this paper used random wind speeds for simulation. The sampling time was the wind speed shifting time interval, as shown in Fig. 5. The random wind speed was expressed as the average wind speed variance ratio. Fig. 5 The wind speed shifting time interval of the sampling time Fig. 6 shows the voltage flicker curve of the induction wind generator under different average wind speed variance ratios corresponding to the short-circuit capacity of the PCC. Fig. 7 shows the voltage flicker curve of the double-fed induction wind generator under different control modes corresponding to the short-circuit capacity of the PCC when the average wind speed variance ratios were 3.77m/s 2 and 1.88m/s 2, respectively. According to Figs. 6 and 7, when the wind speed change was large or the short-circuit capacity was small, the resulting voltage flicker was strong; on the contrary, when the wind speed change was small or the short-circuit capacity was large, the resulting voltage flicker was slight. In the viewpoint of slope, as shown in Fig. 8, when the wind speed changed drastically, the resulting voltage flicker was likely to vary with the short-circuit capacity; when the short-circuit capacity was small, the voltage flicker changed greatly. When the generator is in voltage control mode, the output voltage of the generator is only slightly influenced by the wind speed changes, and voltage flicker is slighter than that in virtual work control mode. Fig. 7 The voltage flicker curve of the double-fed induction wind generator under different control modes Fig. 8 shows the voltage flicker curve of the induction wind generator under different average wind speed variance ratios corresponding to the system impedance angle. Fig. 9 shows the voltage flicker curve of the double-fed induction wind generator under different control modes corresponding to the system impedance angle, when the average wind speed variance ratios were 3.77 and 1.88m/s 2, respectively. According to Figs. 8 and 9, when the wind speed change was large or the system impedance angle was small, the resulting voltage flicker was strong; on the contrary, when the wind speed change was small or the system impedance angle was large, the resulting voltage flicker was slight. In terms of fan control mode, the output voltage of the generator was only slightly influenced by wind speed changes, and the voltage flicker was slighter than that in virtual work control mode. Fig. 8 The voltage flicker curve of the induction wind generator under different average wind speed variance ratios 992

load power factor was low, the resulting voltage flicker was slight. When the generator was in voltage control mode, the output voltage of the generator was only slightly influenced by wind speed changes, and the voltage flicker was slighter than that in virtual work control mode. Digital Open Science Index, Electrical and Computer Engineering waset.org/publication/168 Fig. 9 The voltage flicker curve of the double-fed induction wind generator under different control modes Fig. shows the voltage flicker curve of the induction wind generator under different average wind speed variance ratios of 5.6 and 1.75m/s 2, corresponding to various capacity and load power factors. Figs. 11-13 show the voltage flicker curve of two double-fed induction wind generators with one in voltage control mode and the other in reactive power control mode, under average wind speed variance ratios of 3.77 and 1.88m/s 2, corresponding to various capacity and load power factors. Fig. The voltage flicker curve of the induction wind generator under different average wind speed variance ratios of 5.6 and 1.75m/s 2, corresponding to various capacity and load power factors According to Figs. -13, when the wind speed change was large or the capacity was large, the resulting voltage flicker was strong; on the contrary, when the wind speed change was small or the capacity was small, the resulting voltage flicker was slight. In addition, according to the load power factor, when the capacity was fixed and the load power factor was high, the resulting voltage flicker was strong; on the contrary, when the Fig. 11 The voltage flicker curve of two double-fed induction wind generators with in reactive power control mode, under average wind speed variance ratios of 3.77 and 1.88m/s 2, corresponding to various capacity and load power factors Fig. 12 The voltage flicker curve of two wind generators with in reactive power control mode, under average wind speed variance ratios of 3.77 and 1.88m/s 2, corresponding to various capacity and load power factors 993

REFERENCES [1] G. Manchur and C. C. Erven, Development of A Model for Predicting Flicker from Electric Arc Furnaces, IEEE Trans. on Power Delivery, Vol. 7, No. 1, pp. 416-426, 1992. [2] G. C. Montanari, M. Loggini, A. Cavallini, L. Pitti, and D. Zaninelli, Arc-Furnace Model for Study of Flicekr Compensation in Electrical Networks, IEEE Trans. on Power Delivery, Vol. 9, No. 4, pp. 2026-2036, 1994. [3] J. C. Gu, C. J. Wu, and J. C. chiang, "Effects of High Voltage Side Voltage Flicker Sources on Low Voltage Side Customers," Power Research Institute, Taiwan Power Company, 1994. [4] IEC 61400-21, 2001, Wind turbine generator systems-part 21: measurement and assessment of power quality characteristics of grid connected wind turbines. [5] IEEE Std 1547, Standard for Interconnecting Distributed Resources with Electric Power System, IEEE SCC21, 2003. Digital Open Science Index, Electrical and Computer Engineering waset.org/publication/168 Fig. 13 The voltage flicker curve of two wind generators with in voltage control mode and reactive power control mode, under average wind speed variance ratios of 3.77 and 1.88m/s 2, corresponding to various capacity and load power factors IV. CONCLUSIONS This paper aimed to discuss the effect of wind generators in operation on the amount of voltage flicker in the power system. The effect on voltage flicker was discussed using the power data obtained from actual measurements of s, and these results were verified using a Matlab simulated power system. When a wind generator is in operation, its output power varies with the wind speed, therefore, wind generators are mostly connected to the power grid in parallel at present. The following conclusions were obtained from the research results of this paper: 1) The actual measurement results showed that the voltage flicker values resulting from the operation of wind generators in Taiwan are not severe at the moment, and that they conform to the control value of 0.45% set by the Taiwan Power Company. 2) According to the analysis of the measured data and the simulation results, the voltage flicker value resulting from generator operation varies with the wind speed, contact point short-circuit capacity, system impedance angle, capacity and load power factor. 3) The variance in reactive power is mainly considered in the evaluation of voltage flicker. According to actual measurements and simulation, the reactive power changes only slightly when the generator is in operation, therefore, the voltage flicker should be evaluated according to the variance in effective power. 4) The voltage flicker resulting from generator operation varies with the control mode of a double-fed induction wind generator. When it is in voltage control mode, the output voltage of the generator is influenced only slightly by wind speed changes, and the voltage flicker is slighter than that in virtual work control mode. 994