Programmable transmitter of temperature, relative humidity and other derived humidity values with 4-20 ma outputs Instruction Manual

Similar documents
Programmable transmitter of temperature, relative humidity and other derived humidity values with 4-20 ma outputs Instruction Manual

Programmable transmitter of temperature, relative humidity and other derived humidity values with 4-20 ma outputs Instruction Manual

Programmable transmitter of temperature, relative humidity and other derived humidity values with 4-20 ma outputs Instruction Manual

Programmable transmitter of temperature, relative humidity and other derived humidity values with 0 to 10 V outputs Instruction Manual

Programmable transmitter of temperature, relative humidity and other derived humidity values with 4-20 ma outputs Instruction Manual

Instruction Manual T5140 T5141 T5145 T5240 T5241 T5245. Programmable transmitter of CO2 concentration with 4-20 ma output. with 0-10 V output

T5340, T5341, T5440, T5441 T6340, T6341, T6440, T6441

SELECTION TABLES OF TEMPERATURE,HUMIDITY, PRESSURE CO TRANSMITTERS Txxxx, Pxxxx

SELECTION TABLES OF TEMPERATURE,HUMIDITY, PRESSURE CO TRANSMITTERS Txxxx, Pxxxx

SELECTION TABLES OF TEMPERATURE,HUMIDITY, PRESSURE CO TRANSMITTERS Txxxx, Pxxxx

JUMO Wtrans E01. Measuring probe for humidity, temperature, and CO 2 with wireless data transmission. Brief description. Universal Wtrans receiver

THM80X Series Industry degree high accuracy Temp. & humidity transmitter

TxBlock-USB Transmitter

Output Signal Active Note. Output Signal Temperature 22UTH-51 DC V, DC V

Type Overview. Technical Data. Outdoor Humidity, Temperature Sensor

PLATINUM SENSORS FOR MEASURING TEMPERATURES UP TO 400 C 28.11a

RSMFX-2R MULTIFUNCTIONAL

M1 Series. Humidity - Temperature Transmitter INSTRUCTION MANUAL

OPTITEMP TT 20 Technical Datasheet

VFSC9 ELECTRONIC SPEED CONTROLLER. Mounting and operating instructions

P5201 Universal Programmable Transmitters with Galvanic Isolation

TRANSDUCER of TEMPERATURE and STANDARD SIGNALS P20 type

Output Signal Active Temperature. Electrical data Power Supply DC V, ±10%, 0.5 W

Roline L1 Series. Humidity - Temperature Transmitters INSTRUCTION MANUAL

B850 Boiler House Energy Monitor

OPTITEMP TT 10 C/R Technical Datasheet

FST Series HUMIDITY-TEMPERATURE TRANSMITTERS INSTRUCTION MANUAL

VOLTAGE. User Guide ACCESSORIES. External Sensor DT140. for MicroLog EC600 and EC V ±0.05V ±3% (before calibration)

CURRENT. User Guide ACCESSORIES. External Sensor DT139. for MicroLog EC600 and EC mA ±0.1mA ±3% (before calibration)

D Series Sensors for Humidity and Temperature Measurement Type DI Room version Optional display Technical data Humidity

ph or ORP Transmitter

SELECTION TABLES OF TEMPERATURE,HUMIDITY, PRESSURE CO TRANSMITTERS Txxxx, Pxxxx

HD 48V01T... HD 4977T...

Resistance thermometer Model TR31, miniature design

USER S MANUAL. Rail-mounted temperature transmitter ATL

Conductivity Transmitter

Miniature resistance thermometer Explosion-protected version Model TR34, thread-mounted

TVA 080 / 100 / 120 / 180 / 200 / 220 Isolation amplifier active

Miniature resistance thermometer Model TR33, thread-mounted

Transducer transmitter BILT 4 II 2(1) G. Technical Manual

Technical Specification Temperature-Humidity-Pressure Sensor

TT2780. Temperature head transmitter For resistance thermometers Pt100, settable using a PC, for installation in a sensor head Form B, BUZ, BUZ-H

Digital flow ELEMENT transmitter for continuous flow measurement

PyroMiniUSB Series Operators Guide

USER S MANUAL POWER SUPPLY - ISOLATOR - SIGNAL CONVERTER ZSP 41 POWER SUPPLY - ISOLATOR - SIGNAL CONVERTER SIGNAL MULTIPLIER ZSP 41/2

MTV-1-CP 230 VAC POTENTIOMETER WITH MIN & MAX SETTINGS, DRY CONTACT. Mounting and operating instructions

Uni-Mux XQL Multi-Channel Data Acquisition Module

Temp. & humidity indicator

MHPS MHPS. Modular pressure transmitter. Technical documentation. Table of content. Characteristics - applications - technical data

Technical Information itemp TMT180

HUMITRAN-RHT & RH RELATIVE HUMIDITY/TEMPERATURE TRANSMITTER RELATIVE HUMIDITY TRANSMITTER

OPERATIONS MANUAL DP-110 IN-DUCT DIGITAL PSYCHROMETER TABLE OF CONTENTS

+GF+ SIGNET Temperature Transmitter Instructions

STR-LCF. Security Advice Caution. Notes on Disposal. Electronic Fan Coil Thermostat (Flush mounting) Datasheet. Application

Technical Information Smartec CLD18

Datasheet Platinum Resistance Pt100 In-head (Push Button) Temperature Transmitter TX203P mA output, default range supplied C

Wireless Room Temperature and Humidity Transmitter (Units without Temperature Setpoint or Override) Installation and Operating Instructions

Technical Information Smartec CLD18

Temperature Measurement

ED701 General Industry Pressure Transmitter

CALYS 150. Advanced documenting multifunction calibrator thermometer

Digital flow transmitter for continuous flow measurement

DP2500 DP0100 DP0250 Differential Pressure Transmitter

Humidity Temperature Sensor TFG80 Duct version with Polyga measuring element

B850 Boiler House Energy Monitor

Product Features Benefits The IMC Group Ltd.

Type PLC Fitting. Valve for Continuous control. Diaphragm valve. Output

Current Loop Interface Module M 2025D

Resistance thermometer Model TR30, compact design

R24 DISPLAY MODULE WITH ACTIVE OUTPUT AND RELAY

DP2500 DP0100 DP0250 Differential Pressure Transmitter

RTD Temperature Sensor omnigrad T -TSM 480, TR 480. Hygienic RTD sensor with Pt 100, class A TSM 480 with electronics programmable via PC

OEM miniature resistance thermometer Models TR31-3 and TR31-K, thread-mounted

Resistance thermometer Model TR30, compact design

Digital flow ELEMENT transmitter for continuous flow measurement

MODEL: R30US4. Remote I/O R30 Series

Ultrasonic level transmitter, non-contact

CALYS 150. Advanced documenting multifunction calibrator thermometer

CALYS 50. Field multifunction calibrator for basic use

Temperature Transmitters - Head Mounted

TECHNICAL MANUAL. SERIES AP5202 DC Strain Gage In-Line Amplifier ISO 9001/AS9100

Temperature Sensor. Temperature Transmitter MPU-LCD with Display Product Information TSM and TSB FOOD SENSORS FOR FOOD AND LIFE SCIENCES.

USER'S GUIDE. Vaisala HUMICAP Humidity and Temperature Transmitters HMD70U/Y U303EN11

ABB conductivity analyzer and probe package

Z170REG-1. Universal converter module with galvanic insulation between 2 analog outputs

SEM210 SEM210X UNIVERSAL TEMPERATURE TRANSMITTER

SuperMini SonicLaser

CALYS 100. Field precision documenting multifunction calibrator

1800 Series Attachable Loop-Powered Digital Indicators Operating Manual

Digital flowmeter for continuous flow measurement

Precision humidity control/sensing

CALYS 75. Field documenting multifunction calibrator

Digital flowmeter for continuous flow measurement

Technical description of the fuel tank sensor "Escort TD-500"

SITRANS T measuring instruments for temperature

Digital temperature transmitter Model T15.H, head mounting version Model T15.R, rail mounting version

Endress Hauser. SmarTec M CLD 133 Conductivity Measurement

The Rosemount 848T Wireless Temperature Transmitter

NA1-PK3 SERIES. Compact Size Picking Sensor. Boasts a compact, pocket lighter size enabling universal installation

QAC910. Meteo Sensor. Synco living

Transcription:

T3110 TRANSMITTER Programmable transmitter of temperature, relative humidity and other derived humidity values with 4-20 ma outputs Instruction Manual

Instruction manual for use of T3110 transmitter Transmitter is designed for measurement of ambient air temperature and relative humidity of air without aggressive ingredients with computing one of the following values: dew point temperature, absolute humidity, specific humidity, mixing ratio and specific enthalpy. Measuring temperature and relative humidity sensors are non-removable instrument parts. Measured and computed values are displayed on dual line LCD display. The first line displays temperature. Value displayed on the second line is selectable among relative humidity and computed value. It is also possible to display both readings with cyclic overwriting in 4 seconds interval. It is possible to switch OFF the LCD at all. Transmitter is connected to circuitry by means of one or two galvanic isolated loops. Each loop has two-wire connection and each loop requires power from evaluation device. It is always necessary to connect current loop I1 for proper transmitter function (from loop I1 part of the transmitter is powered). If current loop I1 is opened or disconnected, then loop I2 and LCD will not work. It is possible to assign measured or computed value to current loop output I1 or output I2 (both two-wire connection). All transmitter setting is performed by means of the PC connected via the optional SP003 communication cable (not included in delivery). Program Tsensor for transmitter setting is available to download free at www.cometsystem.cz. Program enables to assign each current loop output measure value (temperature, relative humidity, computed value) and its range. It is also possible to assign both outputs to the same value (with the same range), if two evaluation devices are necessary to connect. Transmitter setting before operation Transmitter is set from the manufacturer to the following parameters: value at output I1: relative humidity, range 4 20 ma corresponds 0 to 100 % RH value at output I2: temperature, range 4 20 ma corresponds -30 to +80 C display: switched ON value displayed at line 2: relative humidity only Modification of the setting is possible to do by means of the PC using procedure described at the end of this document. Installation of the transmitter Transmitter is designed for wall mounting. There are two mounting holes at the sides of the case. It is NOT recommended to use the device for long time under condensation conditions. It could be the cause of water steam condensation inside the sensor s cover into water phase. This liquid phase stays inside sensor s cover and can t escape from the cover easily. It can dramatically increase response time to relative humidity change. If water condensation occurs for longer time it can cause sensor damage. Similar effect can occur under water aerosol conditions. Don t connect transmitter while power supply voltage is on. Interconnection terminals are accessible after unscrewing four screws and removing the lid. Lace the cable through a gland at the case wall. Connect the cable to terminals with respecting the signal polarity (see figure). Terminals are selfclamping and can be opened by a suitable screwdriver. For the opening, insert the screwdriver to upper terminal hole and lever by him. Do not remember to tighten glands and case lid with inserted packing after cables connecting. It is necessary for warranting of protection IP65. It is recommended to use shielded copper cable (e.g. SYKFY) with outside diameter of the cable must be from 3.5 to 8 mm, maximal length 1200m. The cable must be located at indoor rooms (probe is not protected for outdoor use). The cable should not be led in parallel along power cabling. Safety distance is up to 0.5 m otherwise undesirable induction of interference signals can appear. 2 IE-SNC-T3110-03

Typical application wiring Calculation of minimum power voltage Uss for proper operation: Uss min> Uo min + Imax * Rz, where: Uo min= 9 V Imax... approximately 20 ma Rz... sensing resistor (shunt) Both current loops (I1 and I2) are connected analogically, current loop I1 must be always connected. LCD Info mode Several settings of installed transmitter is possible to verify without a use of the computer. It is necessary to connect at least power of current loop I1. Unscrew the transmitter lid and shortly press button between display and interconnection terminals by means of a tool (e.g. screwdriver). Range and type of value for output 1 (current loop I1 = symbol 1 on display). Type of value, assigned to output 1, is indicated by displayed unit (here %RH = relative humidity). Upper line displays current value corresponding to measured value (lower line). Press button again to get value for upper point (same output, same value) similarly as at previous point. Here 20 ma corresponds to 100 %RH. IE-SNC-T3110-03 3

Press button again to display range and type of value for output 2 (symbol 2 ). Here it is ambient temperature ( C ), when 4 ma corresponds to -30 C. If dew point temperature would be assigned to output 2, displayed symbols are C and DP, for the rest values is shown only number (without corresponding unit). After next press of the button value for upper point appears, here 20 ma corresponds to ambient temperature 80 C. Press button again to end info mode and display actual measured values. Notice: during info mode no measurement and no output current generation proceed. The transmitter stays at info mode 15 s and then automatically goes back to measuring cycle. Technical parameters: Accuracy data shown are for value displayed on LCD display. For value on analog output is valid too, if selected output range is set inside measuring range. Analog outputs: Two galvanic isolated current loops with range from 4 to 20 ma Current output in case of error: <3.8 ma or >24 ma Measuring parameters: Ambient temperature (internal RTD sensor Pt1000/3850ppm): Measuring range: -30 to +80 C Display resolution: 0.1 C Accuracy: ± 0.4 C Relative humidity (RH reading is compensated at the entire temperature range): Measuring range: 0 to 100 %RH (see Installation of the transmitter) Display resolution: 0.1 %RH Accuracy: ± 2.5 %RH from 5 to 95 %RH at 23 C The value computed from ambient temperature and relative humidity: Display resolution: 0,1 C You can choice one of the next value:. Dew point temperature Accuracy: ±1,5 C at ambient temperature T < 25 C and RH >30% Range: -60 to +80 C Absolute humidity Accuracy: ±3g/m 3 at ambient temperature T < 40 C Range: 0 to 400 g/m 3 Specific humidity 1 Accuracy: ±2g/kg at ambient temperature T < 35 C Range: 0 to 550 g/kg 1 This value depends on the atmospheric pressure. For computing is used constant value stored inside device memory. Default value preset by manufacturer is 1013hPa and can be changed by user s software. 4 IE-SNC-T3110-03

Mixing ratio 1 Accuracy: ±2g/kg at ambient temperature T < 35 C Range: 0 to 995 g/kg Specific enthalpy 1 Accuracy: ± 3kJ/kg at ambient temperature T < 25 C Range: 0 to 995 kj/kg 2 Response time with bronze sensor cover (air flow approximately 1 m/s): temperature: t90 < 9 min (temperature step 20 C) relative humidity: t90 < 30 s (humidity step 65 %RH, constant temperature) Recommended interval of calibration: 1 year Measuring interval and LCD display refresh: 0.5 s Communication with computer: via USB port by means of USB communication cable SP003 Power: 9 to 30 V dc, maximum ripple 0.5 % Protection: electronics IP65, sensors are located in bronze cover with IP40 protection Air filter: bronze, filtering ability 0.025 mm Operating conditions: Operating temperature range: -30 to +80 C, over +70 C switch LCD display OFF Operating humidity range: 0 to 100 %RH Outer characteristics in accordance with EN 33-2000-3: normal environment with the specifications: AE1, AN1, BE1 Working position: the stem downwards Electromagnetic compatibility: complies EN 61326-1 Not allowed manipulations: It is not allowed to operate the device under other than specified conditions in technical parameters. Devices are not designed for locations with chemically aggressive environment. Temperature and humidity sensors must not be exposed to direct contact to water or other liquids. It is not allowed to remove the sensor cover to avoid any mechanical damage of the sensors. Storing conditions: temperature -30 to +80 C, humidity 0 to 100 %RH without condensation Dimensions: 89 x 73 x 37 mm, stem length 75 mm Weight: approximately 115 g Material of the case: ABS Procedure of modification of transmitter adjustment: Transmitter adjustment is performed by means of the optional SP003 communication cable, connected to USB port of the PC. It is necessary to have installed driver for USB communication cable and configuration program Tsensor on the PC Connect the SP003 cable to USB port of the PC. Installed driver detects the cable and creates virtual COM port in the PC Run program Tsensor, select English version and select proper communication port (see previous point) 2 This maximum is reached under conditions about 70 C/100%RH or 80 C/70%RH IE-SNC-T3110-03 5

Unscrew four screws of the transmitter lid a remove the lid. If transmitter is already installed to measuring system, disconnect leads from terminals Connect SP003 communication cable to the transmitter connector. Display must light up, or at least must light up all symbols for one second (if LCD was switched OFF by program before). Click on button Connect and perform new transmitter adjustment. Analog output range of the transmitter is possible to set for ambient temperature from 200 to +600 C, for humidity from 0 to 100 %RH, for dew point temperature from -200 to +200 C, for the rest values anything inside its own range. Difference between output range limits must be minimally 30. Click on button Save to store new setting to the transmitter. Click on button Disconnect to let transmitter setting without changes. Disconnect the cable from the transmitter and place the lid back to the transmitter. Error States of the device Device continuously checks its state during operation. In case error is found LCD displays corresponding error code: Error 0 First line displays Err0. Check sum error of stored setting inside device s memory. This error appears if incorrect writing procedure to device s memory occurred or if damage of calibration data appeared. At this state device does not measure and calculate values. It is the serious error, contact distributor of the instrument to fix. Error 1 Measured (calculated) value is over upper limit of allowed full scale range. There is a reading Err1 on LCD display. This state appears in case of: Measured temperature is higher than approximately 600 C (i.e. high non-measurable resistance of temperature sensor, probably opened circuit). Relative humidity is higher than 100%, i.e. damaged humidity sensor, or humidity calculation of humidity is not possible (due to error during temperature measurement) Computed value calculation of the value is not possible (error during measurement of temperature or relative humidity or value is over range) Error 2 There is a reading Err2 on LCD display. Measured (calculated) value is below lower limit of allowed full scale range. This state appears in case of: Measured temperature is lower than approximately -210 C (i.e. low resistance of temperature sensor, probably short circuit). Relative humidity is lower than 0%, i.e. damaged sensor for measurement of relative humidity, or calculation of humidity is not possible (due to error during temperature measurement) Computed value calculation of computed value is not possible (error during measurement of temperature or relative humidity) Error 3 There is a reading Err3 on LCD display upper line. Error of internal A/D converter appeared (converter doe not respond, probably damage of A/D converter). No measurement and calculations of values are proceeded. It is a serious error, contact distributor of the instrument. 6 IE-SNC-T3110-03

End of operation Device itself (after its life) is necessary to liquidate ecologically! Technical support and service Technical support and service is provided by distributor. For contact see warranty certificate. IE-SNC-T3110-03 7

Notes: 8 IE-SNC-T3110-03